5.performance of Transmission Lines-1
5.performance of Transmission Lines-1
V R I R cos ɸ R
ȠT = x 100 (5.1)
V S I S cos ɸS
V R I R cos ɸR
Or Ƞ T = x 100 (5.2)
V R I R cos ɸR +line losses
2
Where V R , I R and cos ɸR are the receiving-end voltage, current and power factor (all phase values) while V S , I S
and cos ɸS are the sending-end voltage, current and power factor (all phase values).
OD V R cos ɸR + IR
(ii) Sending end p.f., cos ɸ S = =
OC Vs
3
Line losses = I²R
Power sent out = V R I R cos ɸ R + I²R
Power delivered
%age Transmission efficiency = x 100
Power sent out
V R I R cos ɸR
= x 100
V R I R cos ɸ R + I ² R
An approximate expression for the sending end voltage V s can be obtained as follows. Draw perpendicular from
B and C on OA produced as shown in Fig. 5.1. Then OC is nearly equal to OF
i.e.,
4
(i) The approximate formula for V s (=V R + IR cos ɸ R + I X L sin ɸ R) gives fairly correct results for lagging power
factors. However, appreciable error is caused for leading power factors. Therefore, approximate expression for
V s should be used for lagging p.f. only.
(ii) The solution in complex notation is in more presentable form.
Mixed Sending - and Receiving – end Conditions
Sometimes the mixed conditions arise for example when the sending-end voltage and the receiving-end power
and power factor are given and the sending-end power and power factor and receiving-end voltage are to be
determined. In such circumstances the solution becomes more complicated. Such problems can be dealt with as
follows:
We know that, Power delivered,
P = V R I cos ɸR watts (5)
Reactive volt-amperes delivered,
Q = V R I sin ɸ R (5.1)
Sending-end voltage,
V s = ( V R cos ɸR + IR )2 +(V R sin ɸR + IX )²
√
Or V 2s = V 2R cos ² ɸR + 2V RIR cos ɸR + I ² R ² + V 2R sin ² ɸ R + 2V RIX sin ɸ R + I ² X ²
P
Substituting V R I cos ɸ R = P, V R I sin ɸR = Q and I = from Eqs. (5), (5.1) and (5) respectively in above
V R cos ɸR
eq. (5.2) we have
2 2 ( R2 + X 2 ) P ²
V = V + 2(PR + QX) +
s R
V 2R cos ² ɸR
2 2 4 2 ( R2 + X 2 ) P ²
Or V - V = V + 2V (PR + QX) +
s R R R
cos ² ɸ R
4 2 2 ( R2 + X 2 ) P ²
Or V -VR R [V s −2(PR+ QX ) ] +
cos ² ɸ R
=0
Or V 4R - AV 2R + B = 0
( R2 + X 2 ) P ²
Where A = V 2s −2(PR+QX ) and B =
cos ² ɸ R
5
A ± √ ( A2 −4 B)
Or VR=
√ 2
(5.3)
From the above expression two values for V R will be obtained depending on whether the +ive or –ive sign is
used. The solution giving the higher value of V R and consequently higher transmission efficiency is one
required in practice, and therefore the +ive is usually taken.
After determining the value of V R , other quantities can be evaluated.
Example 1
A single-phase line is transmitting 1,100kW power to a factory at 11kV and at 0.8pf lagging. It has a total
resistance of 2Ω and a loop reactance of 3Ω. Determine (i) the voltage at the sending end, (ii) percentage
regulation and (iii) transmission efficiency
Solution
P x 1000 1100 x 1000
Load current, I = = = 125A
V R cos ɸR 11,000 x 0.8
V R I R cos ɸR
= x 100
V R I R cos ɸ R + I ² R
1100
= x 100 = 97.24%
1100+31.25
Example 2
A short three-phase transmission line of parameters R = 0.4Ω and X = 0.4Ω is delivering 2,000kVA to a load at
a pf of 0.8 lagging at the receiving end of the line. If the load voltage is 3,000V, determine the voltage
regulation and efficiency of the line.
Solution
6
3,000
Phase voltage at sending end, V R = = 1732V
√3
= V R + I (R cos ɸ R + X sin ɸ R)
V s−V R 1947.5−1732
Percentage regulation = x 100 = x 100 = 12.44%
VR 1732
3 I ² R 3 x ( 384.9 )2 x 0.4
Total line losses = = = 177.8kW
1000 1000
Output Power
Transmission efficiency, Ƞ T x 100
Output Power+line losses
1600
= x 100 = 90%
1600+177.8
7
Fig. 5.3 Fig. 5.4
Effect of Load p.f. on Regulation and Efficiency
The regulation and efficiency of a transmission line depend to a considerable extent upon the power factor of
the load.
1. Effect on regulation. The expression for voltage regulation of a short transmission line is given by :
I R cos ɸ R + I X L sin ɸ R
%age Voltage regulation = x 100 (for lagging p.f.)
VR
P
∴I=
V R cos ɸR
P
I=
3V R cos ɸ R
It is clear that in each case, for a given amount of power to be transmitted (P) and receiving end voltage (V R),
the load current I is inversely proportional to the load p.f. cos ɸR. Consequently, with the decrease in load p.f.,
the load current and hence the line losses are increased. This leads to the conclusion that transmission efficiency
of a line decreases with the decrease in load p.f. and vice-versa.
8
Example 3
What is the maximum length in km for a 1-phase transmission line having copper conductor of 0·775 cm² cross-
section over which 200 kW at unity power factor and at 3300V are to be delivered? The efficiency of
transmission is 90%. Take specific resistance as 1.725 μ Ω cm.
Solution
Receiving end power = 200 kW = 200000 W
200 000
∴ Sending end power = = 222222 W
0.9
200 x 10³
Line current, I = = 60.6A
3300 x 1
Line losses = 2 I² R
or 22222 = 2 (60·6)² × R
22222
∴ R= = 3.025Ω
2 x (60 · 6)²
Now, R = ρ l/a
Ra 3.025 x 0.775
∴l= = = 1.36 x 106 cm = 13.6km.
ρ 1.725 x 10−6
Example 4
Estimate the distance over which a load of 15000 kW at a p.f. 0·8 lagging can be delivered by a 3-phase
transmission line having conductors each of resistance 1 Ω per kilometer. The voltage at the receiving end is to
be 132 kV and the loss in the transmission is to be 5%.
Solution.
Power delivered 15000 x 103
Line current, I = = = 82A
√ 3 x line voltage x power factor √ 3 x 132 x 10 3 x 0.8
9
Line losses = 3 I²R
750× 10³
∴ R=¿ = 37.18Ω
3 ×(82)²
Resistance of each conductor per km is 1 Ω (given).
∴ Length of line = 37·18 km
Example 5
An 11 kV, 3-phase transmission line has a resistance of 1·5 Ω and reactance of 4 Ω per phase. Calculate the
percentage regulation and efficiency of the line when a total load of 5000 kVA at 0.8 lagging power factor is
supplied at 11 kV at the distant end.
Solution.
Resistance of each conductor, R = 1·5 Ω
11 x 10³
Receiving end voltage/phase, V R = = 6351V
√3
Using the approximate expression for V S (sending end voltage per phase), we get,
V S = V R + I R cos ɸR + I X L sin ɸ R
10
Output power 4000
Transmission efficiency = × 100 = × 100 = 92·8%
Input Power 4310
5.5 Medium Transmission Lines
In short transmission line calculations, the effects of the line capacitance are neglected because such lines have
smaller lengths and transmit power at relatively low voltages (< 20 kV). However, as the length and voltage of
the line increase, the capacitance gradually becomes of greater importance.
Since medium transmission lines have sufficient length (50-150 km) and usually operate at voltages greater than
20 kV, the effects of capacitance cannot be neglected. Therefore, in order to obtain reasonable accuracy in
medium transmission line calculations, the line capacitance must be taken into consideration.
The capacitance is uniformly distributed over the entire length of the line. However, in order to make the
calculations simple, the line capacitance is assumed to be lumped or concentrated in the form of capacitors
shunted across the line at one or more points. Such a treatment of localizing the line capacitance gives
reasonably accurate results. The most commonly used methods (known as localized capacitance methods) for
the solution of medium transmissions lines are:
(i) End condenser method (ii) Nominal T method (iii) Nominal π method.
Although the above methods are used for obtaining the performance calculations of medium lines, they can also
be used for short lines if their line capacitance is given in a particular problem.
End Condenser Method
In this method, the capacitance of the line is lumped or concentrated at the receiving or load end as shown in
Fig. 5.5. This method of localizing the line capacitance at the load end overestimates the effects of capacitance.
In Fig. 5.5, one phase of the 3-phase transmission line is shown as it is more convenient to work in phase
instead of line-to-line values.
Let I R = load current per phase
R = resistance per phase
X L = inductive reactance per phase
C = capacitance per phase
cos ɸR = receiving end power factor (lagging)
V S = sending end voltage per phase
The phasor diagram for the circuit is shown in Fig 5.6. Taking the receiving end voltage V R as the reference
phasor, we have, V R = V R + j 0
I R = I R (cos ɸR − j sin ɸ R)
Load current, ⃗
11
IC = j ⃗
Capacitive current, ⃗ VRωC=j2πfC⃗
VR
IS = ⃗
⃗ IR + ⃗
IC
= I R (cos ɸR − j sin ɸ R) + j 2 π f CV R
= I R cos ɸR + j (- I R sin ɸ R + 2 π f CV R )
I S ⃗Z = ⃗
Voltage drop/phase = ⃗ I S (R + j X L)
V S= ⃗
Sending end voltage, ⃗ VR+⃗
I S ⃗Z = ⃗
VR+ ⃗
I S (R + j X L)
V s−V R
% regulation = x 100
VR
V R I R cos ɸR
= x 100
V R I R cos ɸ R + I 2S R
Limitations. Although end condenser method for the solution of medium lines is simple to work out
calculations, yet it has the following drawbacks:
(i) There is a considerable error (about 10%) in calculations because the distributed capacitance has been
assumed to be lumped or concentrated.
(ii) This method overestimates the effects of line capacitance.
Nominal T Method
In this method, the whole line capacitance is assumed to be concentrated at the middle point of the line and half
the line resistance and reactance are lumped on its either side as shown in Fig. 5.7. Therefore, in this
arrangement, full charging current flows over half the line. In Fig. 5.7, one phase of 3- phase transmission line
is shown as it is advantageous to work in phase instead of line-to-line values.
12
Fig.5.7
Let I R = load current per phase; R = resistance per phase
X L = inductive reactance per phase; C = capacitance per phase
cos ɸR = receiving end power factor (lagging) ; V s = sending end voltage/phase
V 1 = voltage across capacitor C
The phasor diagram for the circuit is shown in Fig. 5.8. Taking the receiving end voltage V
⃗R as the reference
phasor, we have,
Voltage across C, V1 = ⃗
⃗ VR+⃗
I R ⃗Z / 2
R X
(
= V R +¿ I R (cos ɸR − j sin ɸ R)
2
+j L
2 )
Capacitive current, IC = = j ω C ⃗
⃗ V1 = j 2 π f C ⃗
V1
13
Z
⃗ X
Sending end voltage, VS = ⃗
⃗ V1 + ⃗
IS = ⃗ IS R + j L
V1 + ⃗ ( )
2 2 2
Nominal π Method
In this method, capacitance of each conductor (i.e., line to neutral) is divided into two halves; one half being
lumped at the sending end and the other half at the receiving end as shown in Fig. 5.9. It is obvious that
capacitance at the sending end has no effect on the line drop. However, it’s charging current must be added to
line current in order to obtain the total sending end current.
Line current, IL = ⃗
⃗ IR + ⃗
IC1
VS = ⃗
Sending end voltage, ⃗ VR+⃗
I L ⃗Z = ⃗
VR+⃗
I L ( R + j X L)
14
Fig. 5.10
IS = ⃗
∴ Sending end current, ⃗ IL + ⃗
IC2
Fig. 5.11
Fig. 5.11 shows the equivalent circuit of a 3-phase long transmission line on a phase-neutral basis. The whole
1
line length is divided into n sections, each section having line constants th of those for the whole line. The
n
following points may by noted:
(i) The line constants are uniformly distributed over the entire length of line as is actually the case.
(ii) The resistance and inductive reactance are the series elements.
(iii) The leakage susceptance (B) and leakage conductance (G) are shunt elements. The leakage susceptance is
due to the fact that capacitance exists between line and neutral. The leakage conductance takes into account the
energy losses occurring through leakage over the insulators or due to corona effect between conductors.
Admittance = √ G ²+B ² .
(iv) The leakage current through shunt admittance is maximum at the sending end of the line and decreases
continuously as the receiving end of the circuit is approached at which point its value is zero.
15
5.6.1 Analysis of Long Transmission Line (Rigorous method)
Fig. 5.12 shows one phase and neutral connection of a 3-phase line with impedance and shunt admittance of the
line uniformly distributed.
Fig. 5.12
Consider a small element in the line of length dx situated at a distance x from the receiving end.
dV
Or =Iz (i)
dx
Now, the current entering the element is I + dI whereas the current leaving the element is I. The difference in
the currents flows through shunt admittance of the element i.e.,
dI = Current through shunt admittance of element = V y dx
dI
or =Vy (ii)
dx
d ²V dI dI
dx ²
= z
dx
= z (V y) [ ∴
dx
=V y ¿ exp .(ii) ]
d ²V
Or =yzV (iii)
dx ²
16
V = k 1 cosh ( x √ y z ) + k 2 sinh ( x √ y z ) (iv)
dV
But =Iz [from exp. (i)]
dx
∴ I z = k 1 √ y z sinh ( x √ y z ) + k 2 √ z y cosh ( x √ y z )
y
Or I=
√ [ k sinh ( x √ y z )+ k 2 cosh ( x √ y z ) ]
z 1
(v)
Equations (iv) and (v) give the expressions for V and I in the form of unknown constants k 1 and k 2. The values
of k 1 and k 2 can be found by applying end conditions as under:
At x = 0, V = V R and I = I R
Putting these values in eq. (iv), we have,
V R = k 1 cosh 0 + k 2 sinh 0 = k 1 + 0
∴ V R= k 1
y k sinh 0+ k cosh 0 y
IR =
√ z
[ 1 2 ]=
√ z
[ 0 + k2 ]
z I
∴ k2 =
y √R
z I
V = V R cosh ( x √ y z ) +
√ y
R sinh ( x √ y z )
y V
And I=
√
z
R sinh ( x √ y z ) + I R cosh ( x √ y z )
The sending end voltage (V S ) and sending end current ( I S) are obtained by putting x = l in the above equations
i.e.,
V S = V Rcosh ( l √ y z ) + z I R sinh ( l √ y z )
y √ 17
y V
IS =
z √ R sinh ( l √ y z ) + I R cosh ( l √ y z )
Now, l √ y z = √ l y . l z = √ Y Z
y yl Y
And
√ √ √
z
=
zl
=
Z
Z
V S = V Rcosh √ Y Z + I R
√ Y
sinh √ Y Z
I S = V R Y sinh √ Y Z + I R cosh √ Y Z
Z√
It is helpful to expand hyperbolic sine and cosine in terms of their power series.
Z Y Z²Y ²
cosh √ Y Z = 1+ ( 2
+
24
+… .. )
sinh √ Y Z = ¿
Example 6
A 3-φ transmission line 200 km long has the following constants:
Resistance/phase/km = 0·16 Ω
Reactance/phase/km = 0·25 Ω
Shunt admittance/phase/km = 1·5 × 10−6 S
Calculate by rigorous method the sending end voltage and current when the line is delivering a load of 20 MW
at 0·8 p.f. lagging. The receiving end voltage is kept constant at 110 kV.
Solution
Total resistance/phase, R = 0·16 × 200 = 32 Ω
Total reactance/phase, X L = 0·25 × 200 = 50 Ω
Total shunt admittance/phase, Y = j 1·5 × 10−6 × 200 = 0·0003 ∠ 90º
Series Impedance/phase, Z = R + j X L = 32 + j 50 = 59·4 ∠ 58º
The sending end voltage V S per phase is given by:
Z
V S = V Rcosh √ Y Z + I R
√ Y
sinh √ Z Y
Z Y = 0.0178 ¿ 148˚
18
Z²Y² = 0·00032 ∠ 296º
Z 59 · 4 ∠ 58 ˚
√ √
Y
=
0.0003< 90 °
= 445 ¿−¿ 16˚
Y 0.0003< 90 °
√ √
Z
=
59 · 4 ∠ 58 ˚
= 0.00224 ¿ 16˚
Z Y Z ²Y ²
∴ cosh √ Y Z = 1+ + approximately
2 24
0.0178 0.00032
=1+ ¿ 148˚ + ¿ 296˚
2 24
Sinh √ Y Z = √ Y Z + ¿ ¿ approximately
0.0024<222 °
= 0 133 ¿ 74˚ +
6
20 x 10 6
Receiving end current, I R = = 131A
√ 3 x 110 x 103 x 0.8
19
= 63000 ∠ 0·26º + 7724 ∠ 58º6′
I S = V R Y sinh √ Y Z + I R cosh √ Y Z
√Z
IS = ⃗
⃗ VR+⃗
C ⃗ IR
D ⃗
20
solving a transmission line. Once the values of these constants are known, performance calculations of the line
can be easily worked out. The following points may be kept in mind:
(i) The constants ⃗ A ,⃗B ,⃗
C and ⃗ D are generally complex numbers.
(ii) The constants A and D are dimensionless whereas the dimensions of B and C are ohms and siemen
⃗ ⃗
respectively.
(iii) For a given transmisson line,
⃗A=⃗ D
(iv) For a given transmission line,
⃗A⃗D−⃗ B⃗C=1
5.7.1 Determination of Generalized Constants for Transmission Lines
As stated previously, the sending end voltage (⃗ V S ) and sending end current (⃗
I S) of a transmission line can be
expressed as:
VS = ⃗
⃗ VR+⃗
A ⃗ B ⃗IR (i)
IS = ⃗
⃗ C ⃗VR+⃗ D ⃗IR (ii)
The values of these constants for different types of transmission lines shall be determined.
(i) Short lines. In short transmission lines, the effect of line capacitance is neglected. Therefore, the line is
considered to have series impedance. Fig. 5.13 shows the circuit of a 3-phase transmission line on a single
phase basis.
And VS = ⃗
⃗ VR+⃗ I R ⃗Z (iv)
Comparing these with eqs. (i) and (ii), we have,
A = 1;
⃗ B = ⃗Z , ⃗
⃗ C=0 D=1
and ⃗
Incidentally; A=⃗
⃗ D
And A⃗
⃗ D−⃗ B⃗C = 1 × 1 − ⃗Z × 0 = 1
(ii) Medium lines – Nominal T method. In this method, the whole line to neutral capacitance is assumed to be
concentrated at the middle point of the line and half the line resistance and reactance are lumped on either side
as shown in Fig. 5.14.
21
Fig. 5.14 Medium Lines
Here, VS = ⃗
⃗ V1 IS ⃗
+⃗ Z /2 (v)
And V1 = ⃗
⃗ VR+⃗
IR ⃗
Z /2
Now, IC = ⃗
⃗ IS - ⃗
IR
V 1 Y⃗
=⃗ where Y = shunt admittance
IRZ
⃗
Y ⃗
=⃗ (
V R+
2 )
I⃗ Z
∴ IS = ⃗
⃗ IR + ⃗
Y⃗ Y R
VR+⃗
2
Y⃗
⃗ Z
Y⃗
⃗ VR +⃗ I R 1+ ( 2 ) (vi)
I ⃗
⃗ Z ⃗
I ⃗
Z
VS = ⃗
⃗ VR+ R + S
2 2
Substituting the value of I S, we get,
Y⃗
⃗ Z ⃗ Y⃗ ⃗
Z² ⃗
V S = 1+
⃗
(2
VR + ⃗ )
Z+
4 (
IR ) (vii)
Comparing eqs. (vii) and (vi) with those of (i) and (ii), we have,
Y⃗
⃗ Z ⃗ ⃗ Y⃗
⃗ Z ⃗ ⃗
⃗A=⃗ D=1+
2
; B = Z 1+
2( ; C=Y )
YZ YZ
Incidentally: A⃗
⃗ D-⃗
B⃗C = 1+
2 (
² - Z 1+
2
Y ) ( )
22
Y ²Z ² Z ²Y ²
=1+ +YZ -ZY- =1
4 4
(iii) Medium lines—Nominal π method. In this method, line-to-neutral capacitance is divided into two halves;
one half being concentrated at the load end and the other half at the sending end as shown in Fig. 5.15.
Y = j ω C = shunt admittance
⃗
IS = ⃗
⃗ IL + ⃗
IC2
Or IS = ⃗
⃗ IL + ⃗
VS ⃗
Y /2 viii
Also IL = ⃗
⃗ IR + ⃗
IC1 = ⃗
IR + ⃗
VR⃗
Y /2 ix
Now VS = ⃗
⃗ VR+⃗
I L ⃗Z = ⃗
V R + (⃗
I R +⃗
V R⃗
Y /2 ) ⃗Z (Putting the value of ⃗
IL )
Y⃗
⃗ Z
∴ VS = ⃗
⃗ V R 1+( 2 )
I R ⃗Z
+⃗ x
Also IS = ⃗
⃗ IL + ⃗VS ⃗ I R +⃗
Y /2 = ( ⃗ V R⃗
Y /2 ) + ⃗
VS ⃗ IL )
Y /2 (Putting the value of ⃗
V S from eq. (x), we get,
Putting the value of ⃗
Y Y
⃗ ⃗ Y⃗ ⃗
Z ⃗⃗
IS = ⃗
⃗ IR + ⃗
VR +
2 2
V R 1+
⃗
{ (
2
+I R Z) }
Y ⃗
⃗ V ⃗Y ⃗
V ⃗
Y ²⃗
Z ⃗ Y⃗
IR ⃗
Z
IR + ⃗
=⃗ VR + R + R +
2 2 4 2
Y⃗
⃗ Z Y⃗
⃗ Z
=⃗ (
I R 1+
2
+⃗ )
V R Y⃗ 1+ (4 ) xi
Comparing equations (x) and (xi) with those of (i) and (ii), we get,
23
Y⃗
⃗ Z ⃗ ⃗ ⃗ ⃗ Y⃗
⃗ Z
D = 1+
A=⃗
⃗
(
2 )
; B = Z ; C = Y 1+
4 ( )
YZ 2 YZ
Also ⃗A⃗D-⃗ B⃗C = 1+( 2 )
- Z Y 1+( 4 )
Y ²Z ² Y ²Z ²
=1+ +YZ–ZY- =1
4 4
(iv) Long lines—Rigorous method. By rigorous method, the sending end voltage and current of a long
transmission line are given by:
V S = V Rcosh √ Y Z + I R Z sinh √ Y Z
√Y
I S = V R Y sinh √ Y Z + I R cosh √ Y Z
√
Z
Comparing these equations with those of (i) and (ii), we get,
Z ⃗ = Y sinh √ Y Z
A=⃗
⃗ D = cosh √ Y Z ; ⃗
B=
Y √
sinh √ Y Z ; C
Z √
Incidentally
Z Y
A⃗
⃗ D-⃗
B⃗C = cosh √ Y Z x cosh √ Y Z -
√ Y
sinh √ Y Z x
Z √
sinh √ Y Z
= cosh² √ Y Z - sinh² √ Y Z = 1
24
Fig. 5.16 Element of transmission line
Due to the surge, the voltage build-up in the line travels along the line and would cause damage to the
transformer and other terminal equipment.
Let e = instantaneous voltage (varies with both distance and time)
i = instantaneous current (varies with both distance and time)
r = resistance of line per unit length
l = inductance of line per unit length
c = capacitance of line per unit length
g = conductance of line per unit length
The voltage drop across PQ and the corresponding current through it are given by the following equations.
de di
v=- . dx = r dx i + l dx
dx dt
di de
i=- . dx = g dx e + c dx
dx dt
Eliminating dx gives us the partial differential equations
de di
- =ri+l xii
dx dt
di de
- =ge+c xiii
dx dt
Differentiating equation (xii) with respect to x, and equation (xiii) with respect to t, and eliminating i, we have
d ²e d ²e de
=l.c + (c . r + l . g) + g . r e
dx ² dt ² dt
25
d ²e d ²e
=l.c
dx ² dt ²
It is usual to substitute l.c = 1/a2, where a has the dimension of velocity. In this case the equation becomes
d ²e d ²e
a² =
dx ² dt ²
The solution to this second order partial differential equation can be written in the form of two arbitrary
functions.
Consider the function e = f(x - at). For this
d ²e d ²e
a² = a² f” (x – at), also = f"(x - a t) . (- a )²
dx ² dt ²
It is thus seen that this function satisfies the partial differential equation. Similarly, consider the function e = F(x
+ at) . For this
d ²e d ²e
a² = a² f” (x + at), also = f"(x + a t) . ( a )²
dx ² dt ²
This too is seen to satisfy the partial differential equation. Thus the general solution to the partial differential
equation is
where f and F are two arbitrary functions of (x-at) and (x+at). These two functions can be shown to be forward
and reverse traveling, as follows.
Consider a point x 1 at an instant t 1 on a transmission line.
e 1 = f( x 1 - a t 1)
At any time t afterwards (i.e. at time t + t 1), the value of this same function at the position x would be given by
26
Now a.t is the distance traveled by a wave traveling with velocity a in the forward direction in a time t. Thus it
is seen that the voltage at a distance a.t in the forward direction is always equal to the value at the earlier
position at the earlier time for any value of time. Thus the function f(x-at) represents a forward wave.
Similarly, it can be seen that the function F(x+at) represents a reverse wave. The effect of resistance and
conductance, which have been neglected, would be so as to modify the shape of the wave, and also to cause
attenuation. These are generally quite small, and the wave travels with little modification.
de de
l =- = - f ' (x – at)
dt dt
1 1 c
∴i=
al
f(x – at) = . e =
al l
.e
√
1 1
i.e. e =
√ c √
. i = Z 0 . i where Z 0 =
c
Z 0 is known as the surge (or characteristic) impedance of the transmission line. The surge current i traveling
along the line is always accompanied by a surge voltage e = Z 0 i traveling in the same direction. For a reverse
wave, it can be similarly shown that the surge current i is associated with a surge voltage e = - Z 0 i.
For a transmission line, with conductors of radius r and conductor spacing d, it can be shown that the
inductance per unit length of the line is given by
μ0 d
l= log e H/m
2π r
2 π ε0 εr
c= d F/m
log e
r
for air ε r = 1
1
∴ 1. c = μ0 ε 0 =
a²
1
But = velocity of light
√ μ 0 ε0
27
Therefore the velocity of propagation of the wave a is equal to the velocity of light. [Note: If the resistance of
the line was not neglected, the velocity of propagation of the wave would be found to be slightly less than that
of light (about 5 to 10%)].
For a cable, the dielectric material has a relative permittivityε r different from unity. In this case, the above
derivation would give the velocity of propagation in a cable as
For commercial cables, ε r lies between about 2.5 and 4.0, so that the velocity of propagation in a cable is about
half to two-third that of light. The surge impedance of a power transmission line can be calculated as follows.
2
d
√c
ε0 √(
Z 0 = 1 = μ 0 log e r
2 )
Substituting the velocity of light as 3 x 108 m/s and simplifying gives
d
Z 0 = 60 log e ( ) Ω
r
For an overhead line, for practical values of conductor radius r and spacing d, the surge impedance Z 0 is of the
order of 300 to 600 Ω. For a cable, the corresponding surge impedance would be given by the expression which
has values in the region of 50 to 60 Ω.
d
Z 0 = 60 / √ε r . log e ( ) Ω
r
5.10 Energy stored in surge
The energy stored in a traveling wave is the sum of the energies stored in the voltage wave and in the current
wave.
1 1
Energy = c e² + 1 i²
2 2
l 1 1
e=
√ c
i, i.e. c e² = 1 i² , i.e c e² = 1 i²
2 2
∴ total energy = c e²
But for a surge, e = Zo i. It is seen that half the energy of the surge is stored in the electrostatic field and half in
the electromagnetic field.
1. SKIN EFFECT
28
The phenomena arising due to unequal distribution of current over the entire cross section of the conductor
being used for long distance power transmission is referred as the skin effect in transmission lines. Such a
phenomena does not have much role to play in case of a very short line, but with increase in the effective length
of the conductors, skin effect increases considerably. So the modifications in line calculation need to be done
accordingly. The distribution of current over the entire cross section of the conductor is quite uniform in case of
a dc system. But what we are using in the present era of power system engineering is predominantly an
alternating current system, where the current tends to flow with higher density through the surface of the
conductors (i.e skin of the conductor), leaving the core deprived of necessary number of electrons. In fact there
even arises a condition when absolutely no current flows through the core, and concentrating the entire amount
on the surface region, thus resulting in an increase in the effective resistance of the conductor. This particular
trend of an ac transmission system to take the surface path for the flow of current depriving the core is referred
to as the skin effect in transmission lines.
Why skin effect occurs in transmission lines?
Having understood the phenomena of skin effect let us now see why this arises in case of an a.c. system. To
have a clear understanding of that look into the cross sectional view of the conductor during the flow of
alternating current given in Fig. 5.17 below.
2. FERRANTI EFFECT
In general practice we know, that for all electrical systems current flows from the region of higher potential to
the region of lower potential, to compensate for the potential difference that exists in the system. In all practical
cases the sending end voltage is higher than the receiving end, so current flows from the source or the supply
end to the load. But Sir S.Z. Ferranti, in the year 1890, came up with an astonishing theory about medium or
long distance transmission lines suggesting that in case of light loading or no load operation of transmission
system, the receiving end voltage often increases beyond the sending end voltage, leading to a phenomenon
known as Ferranti effect in power system.
Why Ferranti effect occurs in a transmission line?
A long transmission line can be considered to compose a considerably high amount of capacitance and
inductance distributed across the entire length of the line. Ferranti Effect occurs when current drawn by the
distributed capacitance of the line itself is greater than the current associated with the load at the receiving end
of the line (during light or no load). This capacitor charging current leads to voltage drop across the line
inductance of the transmission system which is in phase with the sending end voltages. This voltage drop keeps
on increasing additively as we move towards the load end of the line and subsequently the receiving end voltage
tends to get larger than applied voltage leading to the phenomena called Ferranti effect in power system. It is
illustrated with the help of a phasor diagram below.
Thus both the capacitance and inductance effect of transmission line are equally responsible for this particular
phenomena to occur, and hence Ferranti effect is negligible in case of a short transmission lines as the
inductance of such a line is practically considered to be nearing zero. In general for a 300 Km line operating at a
frequency of 50 Hz, the no load receiving end voltage has been found to be 5% higher than the sending end
voltage.
Now for analysis of Ferranti effect let us consider the phasor diagram shown above.
Here Vr is considered to be the reference phasor, represented by OA.
Thus Vr = Vr (1 + j0)
= Vr + IcR + jIcX
30
= Vr+ Ic (R + jX)
Since, in case of a long transmission line the capacitance is distributed throughout its length, the average current
flowing is,
IcX = 1/2Vrω l c0 X ω L0 l
From the above equation it is absolutely evident, that the rise in voltage at the receiving end is directly
proportional to the square of the line length, and hence in case of a long transmission line it keeps increasing
with length and even goes beyond the applied sending end voltage at times, leading to the phenomena called
Ferranti effect in power system.
3. CORONA
Electric-power transmission practically deals in the bulk transfer of electrical energy, from generating stations
situated many kilometers away from the main consumption centers or the cities. For this reason the long
distance transmission cables are of utmost necessity for effective power transfer, which in-evidently results in
huge losses across the system.
Minimizing those has been a major challenge for power engineers of late and to do that one should have a clear
understanding of the type and nature of losses. One of them being the corona effect in power system, which
has a predominant role in reducing the efficiency of EHV(extra high voltage lines).
What is corona effect in power system and why it occurs?
For corona effect to occur effectively, two factors here are of prime importance as mentioned below:-
31
1) Alternating potential difference must be supplied across the line.
2) The spacing of the conductors, must be large enough compared to the line diameter.
4. PROXIMITY EFFECT
Proximity means nearness in space or time, so as the name suggests, proximity effect in transmission lines
indicates the effect in one conductor for other neighboring conductors. When the alternating current is flowing
through a conductor, alternating magnetic flux is generated surrounding the conductor. This magnetic flux
associates with the neighboring wires and generates a circulating current (it can be termed as ‘eddy current’
also). This circulating current increases the resistance of the conductor and push away the flowing current
through the conductor, which causes the crowding effect. When the gaps between two wires are greater the
proximity effect is less and it rises when the gap reduces. The flux due to central conductor links with right side
conductor. In a two wire system more lines of flux link elements farther apart than the elements nearest to each
other. Therefore, the inductance of the elements farther apart is more as compared to the elements near to each
other and hence the current density is less in the elements farther apart than the current density in the element
near to each other. As a result the effective resistance of the conductor is increased due to non uniform
distribution of current. This phenomenon is actually referred as proximity effect. This effect is pronounced in
the case of cables where the distance between the conductors is small whereas proximity effect in transmission
lines in the case of overhead system, with usual spacing is negligibly small.
Where, cosθ is the power factor of the system. Hence, if this power factor has got less valve, the corresponding
current (I) increases for same active power P. As the current of the system increases, the ohmic loss of the
system increases. Ohmic loss means, generated electrical power is lost as unwanted heat originated in the
system. The cross section of the conducting parts of the system may also have to be increased for carrying extra
34
ampere burden, which is also not economical in the commercial point of view. Another major disadvantage is
poor voltage regulation of the system, which mainly caused due to poor power factor.
The equipments used to compensate reactive power. There are mainly two equipments used for this purpose.
(1) Synchronous condensers
(2) Static capacitors or Capacitor Bank
Synchronous condensers can produce reactive power and the production of reactive power can be regulated.
Due to this regulating advantage, the synchronous condensers are very suitable for correcting power factor of
the system, but this equipment is quite expensive compared to static capacitors. That is why synchronous
condensers, are justified to use only for voltage regulation of very high voltage transmission system. The
regulation in static capacitors can also be achieved to some extend by split the total capacitor bank in 3 sectors
of ratio 1: 2:2. This division enables the capacitor to run in 1, 2, 1+2=3, 2+2=4, 1+2+2=5 steps. If still further
steps are required, the division may be made in the ratio 1:2:3 or 1:2:4. These divisions make the static
capacitor bank more expensive but still the cost is much lower them synchronous condensers. It is found that
maximum benefit from compensating equipments can be achieved when they are connected to the individual
load side. This is practically and economically possible only by using small rated capacitors with individual
load not by using synchronous condensers.
35
Fig. 5.20 Series and Shunt Capacitor Bank
These categories are mainly based on the methods of connecting capacitor bank with the system. Among these
two categories, shunt capacitors are more commonly used in the power system of all voltage levels. There are
some specific advantages of using shunt capacitors such as,
a) It reduces line current of the system.
b) It improves voltage level of the load.
c) It also reduces system Losses.
d) It improves power factor of the source current.
e) It reduces load of the alternator.
f) It reduces capital investment per mega watt of the Load.
All the above mentioned benefits come from the fact, that the effect of capacitor reduces reactive current
flowing through the whole system. Shunt capacitor draws almost fixed amount of leading current which is
superimposed on the load current and consequently reduces reactive components of the load and hence
improves the power factor of the system. series capacitor on the other hand has no control over flow of current.
As these are connected in series with load, the load current always passes through the series capacitor bank.
Actually, the capacitive reactance of series capacitor neutralizes the inductive reactance of the line hence,
reduces, effective reactance of the line. Thereby, voltage regulation of the system is improved. But series
capacitor bank has a major disadvantage. During faulty condition, the voltage across the capacitor maybe raised
up to 15 times more than its rated value. Thus series capacitor must have sophisticated and elaborate protective
equipments. Because of this, use of-series capacitor is confined in the extra high voltage system only.
36