Tumble Dryer Micro-Programming - Operation Manual
Tumble Dryer Micro-Programming - Operation Manual
Programming
OPL Micro Control
Refer to Page 7 for Model Identification
TMB2586N_SVG
Original Instructions
Keep These Instructions for Future Reference.
CAUTION: Read the instructions before using the machine.
(If this machine changes ownership, this manual must accompany machine.)
Introduction........................................................................................... 7
Model Identification........................................................................................7
Preliminary Information.......................................................................10
About the Control......................................................................................... 10
Power Failure Recovery................................................................................ 10
Restore to Factory Defaults............................................................................10
Control Identification............................................................................11
Operational Keypad.......................................................................................11
Operation Modes.......................................................................................... 12
General Modes of Operation.......................................................................12
Power-up Mode.........................................................................................12
System Check Mode.................................................................................. 12
Start Mode................................................................................................12
Run Mode.................................................................................................12
Rapid Advance Mode................................................................................ 13
Pause Mode.............................................................................................. 13
Error Mode............................................................................................... 13
Cool Down Mode...................................................................................... 13
End of Cycle Mode....................................................................................13
Extended Tumble Mode............................................................................. 13
Reversing Mode (reversing models only).....................................................13
Programming Control...........................................................................17
What Can Be Programmed?........................................................................... 17
How to Program a Cycle................................................................................17
Programmable Options Available................................................................... 17
Manual Reset........................................................................................28
How to Enter Manual Reset........................................................................... 28
Custom Save......................................................................................... 29
Error Codes..........................................................................................41
Cycle Charts......................................................................................... 45
Moisture Sensing Machine Cycles.................................................................. 45
Non-Moisture Sensing Machine Cycles...........................................................46
Introduction
Model Identification
Information in this manual is applicable to these models. Refer
to the machine serial plate for the model number.
E - Electric
L - L.P. Gas
M - Medium Electric
N - Natural Gas
S - Steam
Preliminary Information
About the Control Clean Lint Screen Reminder = Off
Display Limit Cycles = Disabled
This control is an advanced, programmable computer that lets the
owner control most machine features by pressing a sequence of Manual Diagnostics = Enabled
keypads. *Reverse Cylinder Rotate Time = 30 (seconds)
The control allows the owner to program custom cycles, run di- *Reverse Cylinder Stop Time = 6 (seconds) (25-F75 models), 10
agnostic cycles, and retrieve audit and error information. (seconds) (120-200 models)
Tumble Dryers shipped from the factory have default cycles and *Advanced Reversing = Disabled
other settings built in. The owner can change the default cycle or
any cycle. **Advanced Options for Moisture Dry = Disabled
IMPORTANT: It is extremely important that the tumble **Display Moisture Sensor Error = Enabled
dryer has a positive ground and that all mechanical
and electrical connections are made before applying *Only available on units equipped with reversing feature.
power to or operating the tumble dryer. **Only available on units equipped with moisture sensing fea-
ture.
Power Failure Recovery
Refer to Factory Defaults, Menu section for information on Re-
If a cycle is in progress when the power fails, and if the power storing Factory Defaults.
outage lasts five or more seconds, the cycle is lost and cannot be
resumed when power recovers. If the power outage lasts less than
five seconds, the control will resume the cycle when the power
recovers.
Ignition Retries = 3
Temperature Units = Fahrenheit (°F)
High (H) Temperature = 190 (°F)
Medium (M) Temperature = 160 (°F)
Low (L) Temperature = 140 (°F)
Very Low (VL) Temperature = 120 (°F)
Cool Down Temperature = 100 (°F)
Cool Down Time = 2 (minutes)
Rapid Advance = Enabled
Multi-Step Cycles = Disabled
Daylight Saving = Enabled
Key Pad Audio = Enabled
End of Cycle Audio = Enabled (5 seconds)
End of Cycle External Signal = Disabled
Control Identification
Operational Keypad NOTE: The reversing feature is not available on all
models.
The control includes five keypads. These functions are available
to the operator and are intended to control and manage operation
of the tumble dryer.
TMB2586N_SVG
Keypad Description
UP ARROW Press to scroll through menu options and edit parameter values.
DOWN ARROW Press to scroll through menu options and edit parameter values.
BACK ARROW Press to go to the list of parameters without saving the value when adjusting the value
of a programming parameter. Also, press to go to the previous menu when the control
displays a parameter, return to Idle Mode when the control displays the main menu or
clear an error message from the display.
STOP Press to pause a cycle while in Run Mode or abort a cycle if the control is in Pause
Mode.
START Press to start the selected cycle, select an option when in the menu or save a value
when editing a parameter.
PROGRAM LED will light up if the control is in Manual Programming Mode or if a cycle is being
modified.
ENERGY SAVER LED will light up when a Moisture Dry or Auto Dry cycle is running.
HEATING LED will light up when the machine is in the heat portion of the cycle.
Table 1
Operation Modes Press Stop keypad to stop cycle and enter Pause Mode. Control
enters Pause Mode if loading or lint door opens. Press Start to
General Modes of Operation Rapid Advance.
The control enters this mode at power-up. When power is applied Display 1 NNN SS Cycle Time Remaining in
to the tumble dryer, the control becomes active and will display Minutes and Seconds
its software version as SHHH (HHH is the version number) for one
second. If the control was not powered down during a running Display 2 CHH Sy or Cycle Number (HH) and
cycle, it will enter the Idle Mode. After the control completes op- CHHSCd Step Number (Y) or Cycle
eration in the Power-up Mode it will enter Idle Mode. Number (HH) and Step
Cooldown
System Check Mode
Display 3 A HHHF or A Actual Temperature
The front end control enters this mode after Power-Up Mode.
System Check Mode acts as an extension to Power-Up Mode and HHHC
during this mode, the control will check if the correct drive mo- Display 4 P HHHF or P Programmed Temperature
tor, fan motor and ignition control (for gas machines only) are HHHC
connected to the machine. If the motor type checks have success-
fully been completed or if the door is not closed prior to the five Display 5 SAvE Custom Save Mode Dis-
(5) second timer expiring, the front end control will continue to play
the next mode. The mode that is entered after System Check
Mode completes is determined in Power-Up Mode. If the door Table 2
was not closed and the motor type check was not completed, this
check will be done the next time the motor drive contactor is ena- Moisture
bled. If the test detects an incorrect drive motor, fan motor or ig- Dry Cycle 6 Digit
nition control, a Board ID Error will be set Display Display Description
Start Mode
Display 1 rnC HH Actual Moisture Level
The control enters this mode when it is ready to start or resume a
cycle. The display will show CyC-XX where XX is the cycle Display 2 CHH Sy or Cycle Number (HH) and
number. CHHSCd Step Number (Y) or Cycle
Number (HH) and Step
If there is no input from the operator for 4.25 minutes (i.e., key- Cooldown
pad presses, opening or closing the loading door), the display will
turn off. Operator input (i.e., keypad presses opening or closing Display 3 A HHHF or A Actual Temperature
the loading door) will turn on the display. HHHC
After pressing the START (enter) keypad if the door is closed, the Display 4 P HHHF or P Programmed Temperature
cycle will begin. The cycle time in minutes will be displayed. HHHC
Run Mode Display 5 PnCHH Programmed Moisture
Level
The Control enters Run Mode during a cycle. Loading and lint
doors are closed during Run Mode. Display 6 SAvE Custom Save Mode Dis-
While in Run Mode, any programmed value can be changed for play
the currently running cycle. Press the Up or Down keypads to
Display 7 HH HH Time Remaining Display
scroll through the displays. Press the Back keypad to select a pa-
(Time past target and cool-
rameter and press Up or Down to change the value. Once the cy-
down only)
cle is complete, the control will go back to the original program-
med parameters. Refer to the Tables below for each cycle type’s Table 3
displays.
Error Mode
Auto Dry
Cycle 6 Digit This mode will be entered to display all fatal machine errors.
Display Display Description
Cool Down Mode
Display 1 NNN SS Elapsed Time in Minutes The control enters the Cool Down Mode after the heat step of the
and Seconds cycle is completed or fatal error occurs. The control turns the
heater off and for steam heated units turns the damper motor on.
Display 2 CHH Sy or Cycle Number (HH) and
The cool down step will end once the cool down temperature has
CHHSCd Step Number (Y) or Cycle
been reached or the programmed cool down time expires, which
Number (HH) and Step
ever happens first.
Cooldown
End of Cycle Mode
Display 3 A HHHF or A Actual Temperature
HHHC The control enters End of Cycle Mode after the cool down seg-
ment is finished. The display will toggle between LoAd and
Display 4 P HHHF or P Programmed Temperature
rEAdy for one second each until End of Cycle Mode is exited. If
HHHC the door has not been opened or a keypad has not been pressed
Display 5 P HH Programmed Target Level after two minutes, the machine will enter Extended Tumble
Mode. This mode is exited when the door is opened or Stop key-
Table 4 pad is pressed. The control will then return to Idle Mode.
If the Rapid Advance Option is enabled, the user can advance a The Extended Tumble Mode has two portions. The Anti-Wrinkle
running machine cycle by pressing the Start keypad. In a Time Tumble is entered two minutes after the cycle has ended if the
Dry cycle, pressing the Start keypad will decrease the remaining door is not opened. The cylinder will tumble for 30 seconds every
time by one minute. Pressing and holding the Start keypad will two minutes for up to one hour. Once Anti-Wrinkle Tumble is
decrease the remaining time by four minutes per second until the complete, Extended Tumble Mode is entered after 20 minutes.
end of the cycle.
If the door hasn’t been opened and no keys have been pressed
In the Auto-Dry and Moisture Dry cycles, pressing the Start key- one hour after the Anti-Wrinkle Tumble has ended, the control in-
pad will advance the cycle to the cooldown step. crements the Anti-Wrinkle Time Exceeded audit counter and en-
In the Cool Down step, pressing the Start keypad will decrease ters Delayed Tumble. The cylinder will tumble for two minutes
the remaining time by one minute. every 60 minutes for up to 18 hours.
When the cycle is completed, the audit counter, Total Rapid Ad- Reversing Mode (reversing models only)
vance Cycles, is incremented rather than the Total Machine Cy-
cles audit counter. Models equipped with the reversing feature will rotate in the for-
ward direction, pause, rotate in the reverse direction and then
Pause Mode pause for programmable times and steps of the cycle. Factory de-
fault reversing rotate time is 30 seconds and reversing stop time
If Stop keypad is pressed or the loading or lint door is opened is 6 seconds for all cycles with reversing enabled.
while in Run Mode, control enters Pause Mode.
If the door was opened to enter Pause Mode, the control will
show CLOSE, door until the door is closed or Pause Mode is ex-
ited. If the door is closed, the control will show PUSH for one
second followed by StArt for one second as well as flash the
Start keypad LED one second on/one second off.
If the Stop keypad was pressed to enter Pause Mode and the load-
ing door is closed, the control will show PAUSE until Pause
Mode is exited.
Any time PAUSE is shown on the control, the Start keypad LED
will flash one second on/one second off to prompt the user to re-
start the cycle.
To Start a Cycle
1. Press the Up or Down keypad to change cycles.
2. Press Start to start selected cycle.
NOTE: If loading door is open when the Start keypad is
pressed, display will show CLOSE, door If lint door is
open when the start keypad is pressed, display will
show CLOSE, Lint, door.
rApCyC
Press the Start ( / )
Total Rapid
Press the keypad to read audit.
Advance Cycles
Start ( / ) keypad.
Er CyC
Press the Start ( / )
Total Cycles
keypad to read audit.
Stopped by an Error
HtECyC
Press the Start ( / )
Total Cycles
Stopped by Max keypad to read audit.
Heat Time
rESEt Press the Start ( / )
Manual Reset keypad to reset control.
AntiCt
Press the Start ( / )
Total Time
keypad to read audit.
Anti-wrinkle Exceeded
diAg Press the Start ( / ) keypad to
Diagnostic enter Diagnostic Tests. Refer to
Tests Diagnostic Tests flowchart. End2OP
Press the Start ( / )
Average Time From End
keypad to read audit.
of Cycle to Door Open
End2St
Press the Start ( / )
Average Time From End
keypad to read audit.
of Cycle to Run Mode
TMB1792R_SVG
Figure 1
Programming Control
What Can Be Programmed? How to Program a Cycle
This feature allows the owner to program cycle parameters and 1. Press the Up or Down keypad to scroll through the option list.
other features by using the keypads. The control must have the 2. Press Start to select an option to program.
Manual Programming Mode enabled, which is the factory de-
3. Press the Up or Down keypad to change the value of that op-
fault. This mode can only be turned OFF and ON by using an ex-
tion.
ternal device. Refer to this section when programming the con-
trol. 4. Press Start to save the change.
NOTE: Press the Back keypad to leave the option
For an overview of the programming organization, refer to the
without saving any change.
flowcharts on the following pages.
5. After pressing Start , control will go to the next option in the
For more advanced users, a quick reference list of the options list.
available through the programming mode is located below.
6. Press Back keypad to go to Idle Mode.
NOTE: The codes in the Option Display column of the
Programmable Options List are what will show in the Programmable Options Available
display when that option is selected.
4 tENP- Temperature - -
a tENP 1 High Temperature 190°F 160°-190°F [71°-88°C](35, T45, 55, 50, 75, 120,
[88°C] 170, 200 Pound Models), 155°-190°F [68°-88°C](25,
30, T30 Pound Models)
Table continues...
b tENP 2 Medium Temperature 160°F 140°-160°F [60°-71°C](50, 75, 120, 170, 200 Pound
[71°C] Models), 135°-160°F [57°-71°C](25, 30, T30 Pound
Models),145°-165°F [63°-74°C](35, T45, 55 Pound
Models)
c tENP 3 Low Temperature 140°F 120°-140°F [49°-60°C](50, 75, 120, 170, 200 Pound
[60°C] Models), 105°-145°F [41°-63°C](25, 30, T30 Pound
Models),125°-155°F [52°-68°C](35, T45, 55 Pound
Models)
Table continues...
2 CHHtyP Cycle HH Type - tinE (Time Dry), Auto (Auto Dry), noiSt (Moisture
Dry)
Table continues...
Prog
To enter a programming
Manual Programming
option, press the Start ( / )
keypad. To exit, press
Press the the Back () keypad.
Start ( / ) keypad
aud 2
End of Cycle
Error- E LNit
Error Limit Cycle
Displays Display
E Nois
Moisture Sensor
Error Display
E ffLN
False Flame
Error Display
CLrErr
Allow
Error Clearing
Cd- Cd 1
Cool Cool Down
Down Temperature
Cd 2
Cool Down
Time (minutes)
continued TMB1793R-a_SVG
Figure 2
continued
To enter a programming
option, press the Start ( / )
keypad. To exit, press
the Back () keypad.
tENp 1
tENp-
High
Temperature
Temperature
tENp 2
Medium
Temperature
Press the Up ()
or the Down ()
keypad to scroll
through the
tENp 3
programmable Low
options. Temperature
tp f C
Temperature
Fahrenheit/Celcius tENp 4
Very Low
Temperature
aIg
Auto Ignite
Retry
rtC-
rtC 1
Real Time
Minutes
Clock
rtC 2
Hours
rtC 3
Day
rtC 4
Date
rtC 5
Month
rtC 6
Year
continued TMB1793R-b_SVG
Figure 3
dLs 2
Start Month
dLs 4
Start Week of Month
dLs 5
Start Hour
dLs 6
End Month
dLs 7
End Day of Week
dLs 8
End Week of Month
dLs 9
End Hour
continued TMB1793R-c_SVG
Figure 4
To enter a programming
continued option, press the Start ( / )
keypad. To exit, press
the Back () keypad.
CyCLE- CyCHH-
Cycle Cycle HH CHHEn
Programming (HH represents Cycle HH Enable Disable
cycle number)
on
Enable
oFF
Disable
CHHtyP
Cycle HH Type
tinE
Time Dry
Auto
Press the Up ()
or the Down () Auto Dry
keypad to scroll
through the
programmable options. noiSt
Moisture Dry
CHHnt
Cycle HH Material Type
0
Cotton
CHHtPt
Cycle HH 1
Time Past Target Blend
2
Bedding
3
Delicate
4
Synthetic
continued
5
continued Wool
TMB1793R-d_SVG
Figure 5
To enter a programming
option, press the Start ( / )
continued continued
keypad. To exit, press
the Back () keypad.
CHHS1-
Step 1
CHHS11
Step 1
Enable/Disable
CHHCd-
Cool Down
CHHS12
Step 1
CHHCd1 Time
Cool Down
Temperature CHHS13
Step 1
CHHCd2 Temperature
Cool Down Time
CHHS14
Step 1 Auto Dry
CHHCd3 Target Level
Cool Down
Step Reversing
Enable/Disable CHHS15
Step 1 Moisture
Dry Target Level
CHHr-
Reversing CHHS16
Step 1 Reversing
Enable/Disable
CHH r1
Cycle Reversing
Enable/Disable
CHH r2
Cycle Reversing
Rotate Time
CHH r3
Cycle Reversing
Stop Time
continued continued
TMB1815R_SVG
Figure 6
To enter a programming
continued option, press the Start ( / )
keypad. To exit, press
Press the Up ()
or the Down () the Back () keypad.
keypad to scroll
through the rEv- rEv 1
programmable Reversing Rotate Time
options. Parameters (seconds)
rEv 2
raPdEn Stop Time
Manual Rapid Advance (seconds)
diAgEn
Manual Diagnostics
ft En
Factory Test Cycle
Ht dP
Heating Indicator
Decimal Point
Lint
Lint Screen Reminder
PWrSvE
Display Power Save
NdryOP
Advanced Moisture
Dry Options
ESi9 2
ESi9 1
ESi9- External Signal
External Signal
External Signal End of Cycle Duration
End of Cycle
(seconds)
TMB1816R_SVG
Figure 7
Display Description
Table 5
2. Once the desired option appears in the display, press the Start
keypad once to start the audit count.
3. Press the Start keypad again. The control will go to the next
audit option in the Audit Options List.
4. To select other audit options, repeat steps 1 – 3.
Manual Reset
This feature allows the owner to reset the machine control’s pro-
gramming data to the factory default settings by pressing a se-
quence of keypads on the control. For an explanation of the Fac-
tory Default Settings, refer to Programming Control.
Table 6
Custom Save
This feature allows the owner to save a current cycle. For time
dry cycles, the custom save will reprogram the cycle time to the
time that has elapsed in the current cycle. For moisture dry cy-
cles, the custom save feature will save the current moisture level
as the target moisture level for the current cycle.
1. While a cycle is running, press the Back and Start keypads.
2. Display will change to SAUE and Start keypad will flash.
3. Press the Start keypad.
Table 7 continues...
Table 7
d 1
diAg Control Software Version Number
Diagnostic Tests
d 2
Input/Output Board Software Number
d 3
Drive Software Version Number
d 4
Fan Software Version Number
d 5
Ignition Control Software Version Number
d 8
Service Door Opening Test d 34
ICM Alarm Status
d 14
Dryer On Temperature Test d 35
ICM Reset Test
d 15
Door Switch Input Test
Cabinet Limit Thermostat
d 16
Lint Door Switch Test
Stove Limit Thermostat 1
d 19 d 36
Temperature Sensor Display Test Heat Interlock Test
(Heater/Temp Sensor only) Stove Limit Thermostat 2
d 20
12.5VDC Voltage Test Manual Reset Limit
Thermostat
d 21
24VDC Voltage Test
d 28
AC Mains Voltage Test d 37
Air Flow Switch Test
d 29
Machine Configuration Display #1 Test d 38
Fan Motor Test
d 30
Machine Configuration Display #2 Test d 39
Damper Motor Test
d 31
Machine Configuration Display #3 Test d 40
Drive Motor Test
d 32 d 41
Machine Configuration Display #4 Test Moisture Sensor Test (Shorted)
d 33 d 42
Machine Configuration Display #5 Test Moisture Sensor Test (Resistance)
TMB1794R_SVG
Figure 8
Control Software Version Number Test This option tests the service door switch. To start test, control
must be in the Testing Mode. Refer to How To Enter Testing Fea-
This option displays the control software version number. To start ture at the beginning of this section.
test, control must be in the Testing Mode. Refer to How To Enter
To enter, press the START (enter) keypad. The display will show
Testing Feature at the beginning of this section.
S oP when the service door switch is open and S CL when the
To enter, press the START (enter) keypad. The display will show service door switch is closed.
S XXX where XXX is the software version number.
The service door switch has to be closed for at least one second
To exit the test, press the Back keypad. The control will return to and opened for at least a half a second to make a valid count.
the Testing Mode. This test will add counts to the service door opening counter for
the audit and save the date/time for each opening of the test.
Input/Output Board Software Version Number Test
To exit the test, press the Back keypad. The control will return to
This option displays the input/output board software version the Testing Mode.
number. To start test, control must be in the Testing Mode. Refer
to How To Enter Testing Feature at the beginning of this section. Dryer On Temperature Test
To enter, press the START (enter) keypad. The display will show This option tests the temperature inside the cylinder while run-
ob XX where XX is the software version number. ning a cycle. To start test, control must be in the Testing Mode.
Refer to How To Enter Testing Feature at the beginning of this
To exit the test, press the Back keypad. The control will return to
section.
the Testing Mode.
To enter, press the START (enter) keypad when the Start LED is
Drive Software Version Number Test flashing. The machine will run until it has reached the selected
This option displays the current drive software version number. cycle temperature. The display will show XXXF for degrees in
To start test, control must be in the Testing Mode. Refer to How Fahrenheit or XXXC for degrees in Celsius. The XXX will show
To Enter Testing Feature at the beginning of this section. the degrees. During cool down, the control will display the time
remaining as NN (minutes) or NN SS (minutes and seconds).
To enter, press the START (enter) keypad. The display will show
dbXX.XX where XX.XX is the software version number. To exit the test, open the door. The control will then return to the
testing mode.
To exit the test, press the Back keypad. The control will return to
the Testing Mode. Door Switch Input Test
Fan Software Version Number Test This option tests the door switch. To start test, control must be in
the Ready Mode or Starting Mode. Refer to How To Enter Testing
This option displays the current fan software version number. To Feature at the beginning of this section.
start test, control must be in the Testing Mode. Refer to How To
Enter Testing Feature at the beginning of this section. To enter, press the START (enter) keypad. The display will show
dr oP if loading door is open or dr CL if loading door is
To enter, press the START (enter) keypad. The display will show closed.
FbXX.XX where XX.XX is the software version number.
To exit the test, press the Back keypad. The control will return to
To exit the test, press the Back keypad. The control will return to the Testing Mode.
the Testing Mode.
Lint Door Switch Test
Ignition Control Software Version Number Test
(gas models only) This option tests the lint door switch. To start test, control must
be in the Testing Mode. Refer to How To Enter Testing Feature at
This option displays the current ignition control software version the beginning of this section.
number. To start test, control must be in the Testing Mode. Refer
to How To Enter Testing Feature at the beginning of this section. To enter, press the START (enter) keypad. The display will show
LintoP when the lint door switch is open and LintCL when
To enter, press the START (enter) keypad. The display will show the lint door switch is closed.
iC XX where XX is the software version number.
The lint door switch has to be closed or open for at least one sec-
To exit the test, press the Back keypad. The control will return to ond for the control to register the switch as closed or open.
the Testing Mode.
NOTE: Loading door must be closed while testing lint
door.
To exit the test, press the Back keypad. The control will return to drops are connected, or serial card reader or network board are
the Testing Mode. connected.
Temperature Sensor Display Test Refer to Table 8 for test information.
This option displays the temperature sensed at the thermistor in To exit the test, press the Back keypad. The control will return to
1°F increments. To start test, control must be in the Testing the Testing Mode.
Mode. Refer to How To Enter Testing Feature at the beginning of
this section. COMM COMM
BOARD "A" BOARD "B"
To enter, press the START (enter) keypad. The display will show CONFIGVAL- HEADER HEADER
XXXF or XXXC. The F will show Fahrenheit, the C will show Cel- UE PRESENT PRESENT
sius and the XXX will show degrees. If control senses a shorted
thermistor, the display will show SHort. If the control senses an
0 NO NO
open thermistor, the display will show oPEn.
To exit the test, press the Back keypad. The control will return to 8 YES NO
the Testing Mode.
16 NO YES
12.5VDC Voltage Test
24 YES YES
This test displays the value of the 12.5VDC supply. To start test,
control must be in the Testing Mode. Refer to How To Enter Test- Table 8
ing Feature at the beginning of this section.
Machine Configuration Display #2 Test
To enter, press the START (enter) keypad. The display will show
XX.XX where XX.XX is the voltage. This option shows the machine configuration values for the ma-
chine type. To start test, control must be in the Testing Mode. Re-
To exit the test, press the Back keypad. The control will return to fer to How To Enter Testing Feature at the beginning of this sec-
the Testing Mode. tion.
24VDC Voltage Test To enter, press the START (enter) keypad. The display will show
B XXX, with XXX the number corresponding to the machine ca-
This test displays the value of the 24VDC supply. To start test,
pacity. Refer to Table 9 .
control must be in the Testing Mode. Refer to How To Enter Test-
ing Feature at the beginning of this section. To exit the test, press the Back keypad. The control will return to
the Testing Mode.
To enter, press the START (enter) keypad. The display will show
XX.XX where XX.XX is the voltage.
Value Description
To exit the test, press the Back keypad. The control will return to
the Testing Mode. 0 Invalid
AC Mains Voltage Test
1 25 Pound Tumble Dryer
This test displays the value of the curent AC Mains Voltage. To
start test, control must be in the Testing Mode. Refer to How To 2 30 Pound Tumble Dryer
Enter Testing Feature at the beginning of this section.
3 35 Pound Tumble Dryer
To enter, press the START (enter) keypad. The display will show
XXX.X where XXX is the voltage. 4 T30 Pound Stack Tumble Dryer
To exit the test, press the Back keypad. The control will return to 5 T45 Pound Stack Tumble Dryer
the Testing Mode.
6 50 Pound Tumble Dryer
Machine Configuration Display #1 Test
7 55 Pound Tumble Dryer
This option shows whether communication interfaces are con-
nected. To start test, control must be in the Testing Mode. Refer 9 75 Pound Tumble Dryer
to How To Enter Testing Feature at the beginning of this section.
To enter, press the START (enter) keypad. The display will show 10 F75 Pound Tumble Dryer
A XXX, with XXX a number corresponding to whether or not coin
Table 9 continues...
This option shows the machine configuration values for the ma- 31 200 Pound Tumble Dryer
chine capacity. To start test, control must be in the Testing Mode.
Refer to How To Enter Testing Feature at the beginning of this Table 10
section.
Machine Configuration Display #4 Test
To enter, press the START (enter) keypad. The display will show
C XXX, with XXX representing the machine capacity. Refer to Ta- This option shows which dipswitches are set on the control. To
ble 10 . start test, control must be in the Testing Mode. Refer to How To
Enter Testing Feature at the beginning of this section.
To exit the test, press the Back keypad. The control will return to
the Testing Mode. To enter, press the START (enter) keypad. The display will show
D XXX, with XXX representing the machine capacity. Refer to Ta-
Value Description ble 11 .
120VAC Sup-
0 Invalid Config Value Heat Type ply
1 Tumble Dryer Single Pocket
0 Non-CE Gas 120VAC
2 Stack Tumble Dryer 1 Non-CE Gas 240VAC
3 Stack Tumble Dryer - Lower Pocket 4 Non-CE Gas 120VAC
Table 10 continues...
If supply voltage is 100-127VAC per phase, the voltage configu- START (enter). When this test is started, the ICM reset will be-
ration should be 120VAC. come active. If the reset signal is active for a long enough period
of time (3.5 seconds) the ICM Lockout input will become inac-
If supply voltage is 200-240VAC per phase, the voltage configu-
tive (3.5 seconds) and then stop the ICM Reset Test.
ration should be 240VAC.
To exit the test, press the Back keypad. The control will return to Heater Interlock Test
the Testing Mode. While this test is running, the control will show the status of the
Machine Configuration Display #5 Test following inputs for two seconds each. The control will continue
scrolling through the input status displays until the test is aborted.
This option shows the machine configuration values for the volt-
To start test, the control must be in the Testing Mode. Refer to
age. To start test, control must be in the Testing Mode. Refer to
How To Enter Testing Feature at the beginning of this section.
How To Enter Testing Feature at the beginning of this section.
To enter, press Start. Refer to four sections below for more details
To enter, press the START (enter) keypad. The display will show
on individual statuses.
E HHH, with HHH representing the voltage. Refer to Table 12 .
NOTE: These switches are tested in sequence. If one
Adjust Fan 480V Motor switch is sensed open, the rest will be open as well.
Speed for Drives (1 for
Config Value Heat Type Yes, 0 for No) To exit the test, press the Back keypad. The control will return to
the Testing Mode.
2 Gas/Steam 0 Cabinet Limit Thermostat
3 Gas/Steam 1 The display will show CAb oP if sensed open for at least 1.5
4 Electric 0 seconds and CAb CL if sensed closed for at least one second.
6 Eco Gas 0 The display will show SL1 oP if sensed open for at least 1.6
seconds and SL1 CL if sensed closed for at least one second.
7 Eco Gas 1
Stove Limit Thermostat 2
8 Eco Electric 0
The display will show SL2 oP if sensed open for at least 1.7
9 Eco Electric 1
seconds and SL2 CL if sensed closed for at least one second.
10 Low kW Electric 0 Manual Reset Limit Thermostat
11 Low kW Electric 1
The display will show NrL oP if the switch is sensed open for at
Table 12 least 3.0 seconds and NrL CL if the switch is sensed closed for
at least one second.
To exit the test, press the Back keypad. The control will return to
Airflow Switch Test
the Testing Mode.
ICM Alarm Status (gas models only) This option shows the current state of the airflow switch. To start
test, control must be in the Testing Mode. Refer to How To Enter
This option shows the status of the ICM (Ignition Control Mod- Testing Feature at the beginning of this section.
ule) Alarm. To start test, control must be in the Testing Mode.
To enter, press the Start keypad. The display will show AF oP or
Refer to How To Enter Testing Feature at the beginning of this
AF CL, with AF oP being open and AF CL being closed.
section.
Switch has to be closed for at least one second or open for at least
To enter, press the Start keypad. The display will show iAL on
one second for a valid change.
if the alarm is active for at least one second or iALoFF if the
alarm is not active for one second. To exit the test, press the Back keypad. The control will return to
the Testing Mode.
To exit the test, press the Back keypad. The control will return to
the Testing Mode. Fan Motor Test
ICM Reset Test (gas models only) This option shows the fan motor running. To start test, control
must be in the Testing Mode. Refer to How To Enter Testing Fea-
The ICM Reset Test can be used to clear/reset an active alarm. ture at the beginning of this section.
When the test is entered, the display will show rESEt . Press
To enter, press the Start keypad. The display will show PAUSE to trol ran the whole test reading the expected moisture sensor level
indicate the fan motor is going to run. When test is running, Fan and without an intermittent signal or high resistance, PASS will
is displayed. be shown. If either the loading or lint doors are opened during the
test, the control will reset the test step and allow it to be run
NOTE: This test does not count towards the total ma-
again. When the test is complete and result is displayed, the con-
chine run time operation.
trol sounds a 5 second audio signal. Press a key to advance to the
To exit the test, press the Back keypad. The control will return to next test step. If the Up or Down keypad is pressed while the test
the Testing Mode. is in progress the control will toggle between displays HH, rnC
HH and SnrHHH. If the display is left on rnC HH or SnrHHH for
Damper Motor Test (steam models only)
5 seconds the control will revert to showing rnC 1.
This option shows the damper motor running. To start test, con- Moisture Sensor Test (Resistance Test Jumper)
trol must be in the Testing Mode. Refer to How To Enter Testing
Feature at the beginning of this section. This step is skipped if the control is not configured for Moisture
To enter, press the Start keypad. The display will show PAUSE to Sensing. When entering this test, the control will show rnC 2
indicate the damper motor is going to run. When test is running, while flashing the Start key LED one second on/one second off,
allowing the user to place the 510k Ohm resistor between the cyl-
damper is displayed.
inder and the baffle (black jumper) which simulates an expected
NOTE: This test does not count towards the total ma- moisture sensor level. When the Start keypad is pressed, this step
chine run time operation. energizes the Fan Motor Contactor and Forward Motor Contactor
To exit the test, press the Back keypad. The control will return to and the control will show HH. The moisture sensor test is 30 sec-
the Testing Mode. onds. During this 30 second period, the control is continually
monitoring the moisture sensor input for the expected moisture
Drive Motor Test sensor level. If an intermittent signal or unexpected resistance is
sensed before the time expires, the test is terminated and the con-
NOTE: For nonreversing models, the display will show trol will show OPEn , indicating that the test has failed. At this
Frd indefinitely. time, the user has the option to press the Back keypad to return
This option shows the drive motor running. The test will turn the and run the test again. If the control ran the test reading the ex-
cylinder forward for 30 seconds, pause for 6 seconds, rotate in pected moisture sensor level and without an inttermittent signal
the reverse direction for 30 seconds and pause for 6 seconds. or unexpected resistance, PASS will be shown. If either the load-
ing or lint doors are opened during the test, the control will reset
To start test, control must be in the Testing Mode. Refer to How the test step and allow it to be run again. When the test is com-
To Enter Testing Feature at the beginning of this section. plete and result is displayed, the control sounds a 5 second audio
To enter, press the Start keypad. The display will show Frd when signal. Press a key to advance to the next test step. If the Up or
spinning in forward direction, PAUSE when the cylinder is Down keypad is pressed while the test is in progress the control
paused and rEv when spinning in the reverse direction. will toggle between HH, rnC HH and SnrHHH. If the display is
left on rnC HH or SnrHHH for 5 seconds the control will revert
NOTE: This test does not count towards the total ma- to showing rnC 2.
chine run time operation.
To exit the test, press the Back keypad. The control will return to
Factory Test Cycle
the Testing Mode. To Enter Factory Test Cycle
Moisture Sensor Test (Shorted Test Jumper) 1. Be certain control is in Start Mode, and service door or coin
This step is skipped if the control is not configured for Moisture vault is open.
Sensing. When entering this test, the control will show rnC 1 2. While pressing and holding the Down keypad with one hand,
while flashing the Start LED one second on/one second off, al- press the Back keypad with the other hand.
lowing the user to short the cylinder to the baffle (orange jump- 3. When the control enters the Factory Test Cycle, it will first
er). When the Start key is pressed, this test step energizes the Fan display td for product type (tumble dryer).
Motor Contactor and Forward Motor Contactor and the control
4. The control will advance through the sequence of test steps
will show HH. The moisture sensor test is 30 seconds. During this whenever the START (enter) keypad is pressed, with the ex-
30 second period, the control is continually monitoring the mois- ception of the Keypad Test. Refer to Table 13 for all tests in
ture sensor input for the expected short circuit. If an intermittent the Factory Test Cycle.
signal or high resistance is sensed before the 30 seconds expire,
the test is terminated and the control will show OPEn , indicat-
To Exit Factory Test Cycle
ing that the test has failed. At this time the user has the option to
press the Back keypad to return and run the test again. If the con- The control must be powered down to end the test.
dbXX Drive Software Version Number XX is the drive software version number.
FbXX Fan Drive Software Version Num- XX is the fan drive software version number.
ber
icXX (skipped if electric ICM Software Version XX is the ICM software version number.
or steam machine)
AX Control Type X is the feature level of the control.
XX DipSwitch Configuration XX is the machine type. 00 is 120V and 01 is 240V.
XXX Machine Size XXX is the configured machine size. tXXis for stack machines and
FXX is for fast dry.
Pad or PAXX Keypad Test When a key is pressed, the control will display the number assigned
to the keypad. As each keypad is pressed, its corresponding LED
will be lit and remain on for the duration of the test. When all key-
pads have been pressed, the control will advance to Show Entire Dis-
play Mode test cycle.
All LEDs and display Show Entire Display Mode This mode will light all display elements and sound the audio.
segments will light
S oP or S CL Service Door Switch Test oP signifies the service door switch is open or CL signifies the serv-
ice door switch is closed.
droP or drCL Loading Door Test oP signifies the loading door is open or CL signifies the loading door
is closed.
LtoP or LtCL Lint Door Test oP signifies the lint door is open or CL signifies the lint door is
closed.
XXXF or XXXC Thermistor Temperature Test The temperature will be displayed in either Fahrenheit or Celsius,
depending on machine’s configuration. If control senses a shorted
thermistor, SH will be displayed. If control senses an open thermis-
tor, oP will be displayed.
Table 13 continues...
rnC 1 Moisture Sensor Test (Shorted) This step is skipped if the control is not configured for Moisture
Sensing. When entering this test, the control will show rnC 1 while
flashing the Start LED one second on/one second off, allowing the
user to short the cylinder to the baffle (orange jumper). When the
Start key is pressed, this test step energizes the Fan Motor Contactor
and Forward Motor Contactor and the control will show HH. The
moisture sensor test is 30 seconds. During this 30 second period, the
control is continually monitoring the moisture sensor input for the
expected short circuit. If an intermittent signal or high resistance is
sensed before the 30 seconds expire, the test is terminated and the
control will show OPEn , indicating that the test has failed. At this
time the user has the option to press the Back keypad to return and
run the test again. If the control ran the whole test reading the ex-
pected moisture sensor level and without an intermittent signal or
high resistance, PASS will be shown. If either the loading or lint
doors are opened during the test, the control will reset the test step
and allow it to be run again. When the test is complete and result is
displayed, the control sounds a 5 second audio signal. Press a key to
advance to the next test step. If the Up or Down keypad is pressed
while the test is in progress the control will toggle between displays
HH, rnC HH and SnrHHH. If the display is left on rnC HH or
SnrHHH for 5 seconds the control will revert to showing rnC 1.
rnC 2 Moisture Sensor Test (Resistance) This step is skipped if the control is not configured for Moisture
Sensing. When entering this test, the control will show rnC 2 while
flashing the Start key LED one second on/one second off, allowing
the user to place the 510k Ohm resistor between the cylinder and the
baffle (black jumper) which simulates an expected moisture sensor
level. When the Start keypad is pressed, this step energizes the Fan
Motor Contactor and Forward Motor Contactor and the control will
show HH. The moisture sensor test is 30 seconds. During this 30 sec-
ond period, the control is continually monitoring the moisture sensor
input for the expected moisture sensor level. If an intermittent signal
or unexpected resistance is sensed before the time expires, the test is
terminated and the control will show OPEn , indicating that the test
has failed. At this time, the user has the option to press the Back key-
pad to return and run the test again. If the control ran the test reading
the expected moisture sensor level and without an inttermittent sig-
nal or unexpected resistance, PASS will be shown. If either the
loading or lint doors are opened during the test, the control will reset
the test step and allow it to be run again. When the test is complete
and result is displayed, the control sounds a 5 second audio signal.
Press a key to advance to the next test step. If the Up or Down key-
pad is pressed while the test is in progress the control will toggle be-
tween HH, rnC HH and SnrHHH. If the display is left on rnC HH
or SnrHHH for 5 seconds the control will revert to showing rnC 2.
Table 13 continues...
10 10 Minute Test Cycle Determines if dryer can function in a cycle for 10 minutes. LED dis-
play will flash one second on and one second off. If the door is
opened while the START LED is flashing, the control will display
door until the door is closed. While this 10 Minute Test Cycle is
running, the START pad may be used to decrement the remaining
cycle time. If power to the control is turned off before this test cycle
has ended, the cycle is cleared. When the control is powered back
up, it will be reset to Ready Mode.
Pd Power Down This is the final step of the Factory Test Cycle and when displayed it
signifies the test has been completed.
Table 13
Error Codes
Following is a list of possible error codes for an electronic con-
trol. Errors beginning with EC refer to card reader errors. All oth-
er errors refer to machine errors.
ALArN Break-In Alarm Error Check the service door or coin vault switches.
E AF Airflow Switch Bounces Inspect lint screen, ductwork and make-up air. Cycle power to machine
(power down, then power up).
E Co SCI Communications Error Communication failure. Power down, power up, check connections and
try again. If error persists, replace control or output board.
E dS Brownout/Voltage Configuration Unexpected supply voltage. Check wiring at input of machine to make
sure the correct input voltage is supplied to the machine. Check the har-
ness connections between the user control and the output board. If the
user control was replaced, set dipswitch #1 to the same setting as the
previous control. If reworking the machine to use a different supply
voltage, the dip switch #1 setting may need to be changed. If the dip
switch #1 setting is changed, power down, power up and try again.
E HEAt Machine Did Not Reach Expected The ignition control has power, but a flame was not sensed after the
Temperature programmed amount of retries. Be sure that gas and gas valve are
turned on. If problem persists, troubleshoot the ignition circuit. (Igniter,
Cable, Ignition Control Module.) For electric machines, check wiring
to auxiliary switch on electric contactors and make sure contactors
work properly.
E id Board ID Error Incorrect replacement control. Replace user control or output board
with correct part. The board ID error will also be set if the wrong drive
motor, fan motor or ignition control are connected. The display will
show drivE, Fan or iCN. Check machine configurations and connect
correct drive motor, fan motor or ignition control.
E nr Drive/Output Board Not Ready Hardware failure. Replace output board.
E oP Open Thermistor Error Remove any lint build-up around thermistor. Check wire connections.
If problem persists, replace control or thermistor.
E SH Shorted Thermistor Error Remove any lint build-up around thermistor. If problem persists, re-
place control or thermistor.
EAF1 Airflow Switch Failed to Open Inspect lint screen and ductwork. Wipe clean and completely dry off
the airflow switch vane as well as the mating material. Once error is
cleared, control will go back to previous mode of operation.
EAF2 Airflow Switch Failed to Close If machine is newly installed, make sure shipping tie has been removed
from airflow switch. Inspect lint screen and ductwork. Cycle power to
machine (power down, then power up).
ECAb Cabinet Limit Cycle Remove any lint build-up around thermostat. If problem persists, re-
place control or thermostat. Check thermistor function. Error can also
be caused by running no load or a small load.
Table 14 continues...
ECodrv, ECoFAn Drive and Fan Communication Er- Communication failure. Power down for at least 1 minute, power up,
ror check connections between I/O board and Drive/Fan and try again. If
error persists, replace tumbler I/O board or motor with which the error
occurred (Fan or Drive).
ECoiCN ICM Communication Error Communication failure. Power down, power up, check connections and
try again. If error persists, replace tumbler I/O board or ignition con-
trol.
Ed 04 Drive Motor Stall Error Check that cylinder turns freely, make sure machine is not overloaded.
Error can be cleared by any key press.
Ed 05 Drive Motor Coherence Check Er- Can be caused by an unbalanced load. Try to redistribute the load and
ror lengthen the reversing pause time if reversing is enabled. Error can be
cleared by any key press.
Ed 11 Drive Motor Overload Error Check that cylinder turns freely, make sure machine is not overloaded.
Error can be cleared by any key press.
Ed 13 Drive Motor Hall Sensor Failure Power down machine to clear error.
EFAn02, Ed 02 Fan and Drive Motor High DC Voltage to Fan/Drive is too high. Unpower machine to clear error.
Bus Error Check voltage input and check wiring to machine. Replace fan/drive
motor if error persists.
EFAn04 Fan Motor Stall Error Check that blower wheel spins freely. Error can be cleared by any key
press.
EFAn05 Fan Motor Coherence Check Error Check that blower wheel spins freely. Error can be cleared by any key
press.
EFAn06, Ed 06 Fan and Drive Motor IPM Over- IPM temperature is detected too high. Check that heat sink on the fan/
temp Error drive is clear of lint or any other obstruction and check that cylinder
spins freely when empty. Replace fan/drive motor if error persists.
EFAn08, Ed 08 Fan and Drive Motor Current Lim- Check that cylinder/fan turns freely, make sure machine is not over-
it Error loaded. Replace fan/drive motor if error persists.
EFAn09, Ed 09 Fan and Drive Motor 460V Drive Check that cylinder/fan turns freely, make sure machine is not over-
Overcurrent loaded. Replace fan/drive motor if error persists.
EFan10, Ed 10 Fan and Drive Motor Low DC Bus Voltage to Fan/Drive is too low. For 120V machines, make sure wire
Error harness jumper is connected which connects pins 1 and 2 of the 5-pin
connector on the motor. Check voltage input and check wiring to ma-
chine. Replace fan/drive motor if error persists.
EFAn12, Ed 12 Fan and Drive Motor Microcon- Try to power down and power up the machine to clear the error. If error
troller Fault persists replace fan/drive motor.
EFLt01 Optional Heat Output Shorted Check wiring to valve/motor connected to output, replace valve/motor.
EFLt02 Motor Relay Enable Output Short- Check motor power relay connected between, if error persists replace
ed relay.
EFLt03 Spare Relay Enable Ouptut Short- Check relay powered by KM2 output, if error persists replace relay.
ed
Table 14 continues...
EFLt04 Auxiliary Relay 1 Ouput Shorted Check relay powered by Aux 1 output, if error persists replace relay.
Error
EFLt05 Run Relay Output Shorted Error Check Relay powered by the Run output, if error persists replace relay.
EFLt06 Gas Valve 1 Output Shorted Error Check gas valve 1, if error persists replace valve.
EFLt07 Gas Valve 2 Output Shorted Error Check gas valve 2, if error persists replace valve.
EiCN ICM Lockout Alarm Active Check that the gas is turned on and that the ignition circuit functions.
Also check that the gas valve is operational.
EiCN01 False Flame Error Press any key, open the loading door or cycle power to machine.
EiCN02 ICM Alarm Reset Shorted Error Check wiring between the I/O board and the ignition control. Power
down and power up machine to clear the error.
EiCN03 ICM Hardware Failure Error Ignition control has detected a hardware fault. Power down and power
machine to clear error. Replace ignition control if error persists.
Eio 06 I/O Board 24VDC Supply Over Check machine input voltage. Power down and power up the machine
Voltage Error to clear error. If error persists replace I/O board.
Eio 07 I/O Board 24VDC Supply Under Check machine input voltage, clear any debris or lint from the I/O
Voltage Error board. Power down and power up the machine to clear error. If error
persists replace I/O board.
Eio 08 Heat Output Shorted Error Power down machine to clear error, power up machine, try heating
again. If error persists, replace I/O board.
Eio 15 Mosfet Enabled Shorted Error Power down machine to clear error, power up machine, try running a
cycle. If error persists, replace I/O board.
ENoiSt Moisture Sensor Error Make sure cylinder is empty and check slip ring connection on back of
machine.
ENrL Manual Reset Limit Error Inspect tumble dryers venting/ventwork to ensure that the ventwork is
adequate and that there are no blockages. Be sure to clean and inspect
lint screen. Remove any lint buildup around the thermostat. Check ther-
mistor and cabinet limit function. Limit needs to be manually reset and
machine needs to be powered down to clear the error. If problem per-
sists, replace thermostat.
EnXX Machine ID Chip Error Communication failure. Power down, power up and try again. If error
persists, check connection between user control and Machine ID chip,
or try replacing the user control or the Machine ID chip.
ESL1 Stove Limit 1 Cycle Inspect tumble dryers venting/ventwork to ensure that the ventwork is
adequate and that there are no blockages. Be sure to clean and inspect
lint screen. Remove any lint buildup around the thermostat. Check
make-up air and gas pressure. If problem persists, replace thermostat.
ESL2 Stove Limit 2 Cycle Inspect tumble dryers venting/ventwork to ensure that the ventwork is
adequate and that there are no blockages. Be sure to clean and inspect
lint screen. Remove any lint buildup around the thermostat. Check
make-up air and gas pressure. If problem persists, replace thermostat.
Table 14
Cycle Charts
Moisture Sensing Machine Cycles
Cycle No. Cycle Name Cycle Type Material Type Reversing Temperature Target
Moisture
or Time
10 Napkins Synthetic Iron Moisture Dry Synthetic OFF 140°F [60°C] 20%
11 Napkins Blend Iron Moisture Dry Blend OFF 160°F [71°C] 20%
12 Napkins Cotton Iron Moisture Dry Cotton OFF 190°F [88°C] 20%
Table continues...