The document is a preventive maintenance report for servers, storage, and networking equipment at a data center. It documents the maintenance performed, including checking hardware status, applying any necessary firmware updates, and replacing parts. Photos show the equipment was found to be in normal working condition. The estimated maintenance time was 45 minutes per server.

Uploaded by

Aimanullah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
463 views

Contoh Preventive Maintenance

The document is a preventive maintenance report for servers, storage, and networking equipment at a data center. It documents the maintenance performed, including checking hardware status, applying any necessary firmware updates, and replacing parts. Photos show the equipment was found to be in normal working condition. The estimated maintenance time was 45 minutes per server.

Uploaded by

Aimanullah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 35

Preventive Maintenance 8 Report

Provided by

PT SMARTINDO INTEGRASI SYSTEM


Document Matrix Control

Document Tittle : Preventive Maintenance Report


Version : 8.0
Creation Date: 17 December 2020
Document Author(S) : M. Syahid
Status : Complete
8.0 Initial Release

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 2
Table Content
TABLE CONTENT 1

1. INTRODUCTION 2

1.1 BACKGROUND.....................................................................................................................................2
1.2 PURPOSE..........................................................................................................................................2

2. HARDWARE LIST 2

3. MAINTENANCE SERVER RESULT PICTURE 3

3.1 SERVER POWEREDGE R740 BZJ99V2..........................................................................................3


3.2 SERVER POWEREDGE R740 BR999V2.........................................................................................6
3.3 SERVER POWEREDGE R740 BZJG9V2.........................................................................................9
3.4 SERVER POWEREDGE R740 BZHB9V2.......................................................................................12
3.5 SERVER POWEREDGE R740 BZGC9V2........................................................................................15

4. MAINTENANCE STORAGE RESULT PICTURE 18

4.1 STORAGE SC5020 FK7F9V2.......................................................................................................18

5. MAINTENANCE BROCADE RESULT PICTURE20

5.1 BROCADE 6505 FKS0T72............................................................................................................20


5.2 BROCADE 6505 JTS0T72.............................................................................................................22

6. MAINTENANCE ML3 RESULT PICTURE 24

6.1 DELLEMC ML3 DK54FN2..............................................................................................................24


6.1.1 Summary.................................................................................................................................24

7. SUMMARY 26

7.1 CHECKING HEALTH STATUS...........................................................................................................26


7.2 CORECTIVE.....................................................................................................................................26
7.3 PARTS REPLACEMENT....................................................................................................................26
7.4 REPAIR............................................................................................................................................27
7.5 WARRANTY.....................................................................................................................................27
7.6 Firmware Version............................................................................................................................32

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 1
1. Introduction
1.1 Background
PT. Smartindo Integrasi System ditunjuk melakukan Preventive Maintenance di
PT. Madhani Talatah Nusantara. Preventive maintenance akan dilakukan
setiap 2 bulan sekali di Data Center.

1.2 Purpose
Tujuan dokumen ini dibuat untuk memastikan kondisi device Server
PowerEdge R740, Storage SC5020, Brocade 6505, DellEMC ML3. Dengan
melampirkan kondisi komponen hardware berupa batteries, CPU processor,
Fans, Network Device, Power Supplies, Memory dan Hard Disk yang diambil
dari management device.

2. Hardware List
No Hardware Model Service Tag
1 Server DellEMC PowerEdge R740 BZJ99V2
2 Server DellEMC PowerEdge R740 BR999V2

3 Server DellEMC PowerEdge R740 BZJG9V2

4 Server DellEMC PowerEdge R740 BZHB9V2

5 Server DellEMC PowerEdge R740 BZGC9V2

6 Storage DellEMC Storage SC5020 FK7F9V2

7 Brocade Brocade 6505 FKS0T72

8 Brocade Brocade 6505 JTS0T72

9 Tape Library DellEMC ML3 DK54FN2

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 2
3. Maintenance Server Result Picture
3.1 Server PowerEdge R740 BZJ99V2
3.1.1 Summary
Service
Server Name Model IP Address Operating System
Tag
Dell
 VMware Host 01 PowerEdge BZJ99V2 VMWare ESXi 6.7.0 Build 10764712
R740
Current Lastest Estimated Time
Components Name Importance
Version Version (Minutes)
BIOS 2.5.4 2.10.0 Urgent 15
4.10.10.1
iDRAC9 with Lifecycle Controller 4.40.00.00 Recommend 15
0
NIC Card 14.10.05 15.15.06 Recommend 15
Total Estimated Time 45 Minutes
HARDWARE STATUS
CPU

MEMORY

POWER SUPPLY

PCI DEVICE

NETWORK - ETHERNET

Fan

TEMPERATURE

VOLTAGE

3.1.2 System Identity

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 3
3.1.3 VMware vSphere Performance

3.1.4 CPU

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 4
3.1.5 Memory

3.1.6 Disk

CPU & Memory performance pada host ini dalam keadaan normal seperti pada
screenshot di atas.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 5
3.2 Server PowerEdge R740 BR999V2
3.2.1 Summary
Service
Server Name Model IP Address Operating System
Tag
Dell
 VMware Host 02 PowerEdge BR999V2 VMWare ESXi 6.7.0 Build 10764712
R740
Current Lastest Estimated Time
Components Name Importance
Version Version (Minutes)
BIOS 2.5.4 2.10.0 Urgent 15
iDRAC9 with Lifecycle
4.10.10.10 4.40.00.00 Recommend 15
Controller
NIC Card 14.10.05 15.15.06 Recommend 15
Total Estimated Time 45 Minutes
HARDWARE STATUS
CPU

MEMORY

POWER SUPPLY

PCI DEVICE

NETWORK - ETHERNET

Fan

TEMPERATURE

VOLTAGE

3.2.2 System Identity

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 6
3.2.3 VMware vSphere Performance

3.2.4 CPU

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 7
3.2.5 Memory

3.2.6 Disk

CPU & Memory performance pada host ini dalam keadaan normal seperti pada
screenshot di atas.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 8
3.3 Server PowerEdge R740 BZJG9V2
3.3.1 Summary
Service
Server Name Model IP Address Operating System
Tag
Dell
 VMware Host 03 PowerEdge BZJG9V2 VMWare ESXi 6.7.0 Build 10764712
R740
Current Lastest Estimated Time
Components Name Importance
Version Version (Minutes)
BIOS 2.5.4 2.10.0 Urgent 15
iDRAC9 with Lifecycle Controller 4.10.10.10 4.40.00.00 Recommend 15
NIC Card 14.10.05 15.15.06 Recommend 15
Total Estimated Time 45 Minutes
HARDWARE STATUS
CPU

MEMORY

POWER SUPPLY

PCI DEVICE

NETWORK - ETHERNET

FAN

TEMPERATURE

VOLTAGE

3.3.2 System Identity

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 9
3.3.3 VMware vSphere Performance

3.3.4 CPU

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 10
3.3.5 Memory

3.3.6 Disk

CPU & Memory performance pada host ini dalam keadaan normal seperti pada
screenshot di atas.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 11
3.4 Server PowerEdge R740 BZHB9V2
3.4.1 Summary
Service
Server Name Model IP Address Operating System
Tag
Dell
 VMware Host 04 PowerEdge BZHB9V2 VMWare ESXi 6.7.0 Build 10764712
R740
Current Lastest Estimated Time
Components Name Importance
Version Version (Minutes)
BIOS 2.5.4 2.10.0 Urgent 15
iDRAC9 with Lifecycle Controller 4.10.10.10 4.40.00.00 Recommend 15
NIC Card 14.10.05 15.15.06 Recommend 15
Total Estimated Time 45 Minutes
HARDWARE STATUS
CPU

MEMORY

POWER SUPPLY

PCI DEVICE

NETWORK - ETHERNET

Fan

TEMPERATURE

VOLTAGE

3.4.2 System Identity

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 12
3.4.3 VMware vSphere Performance

3.4.4 CPU

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 13
3.4.5 Memory

3.4.6 Disk

CPU & Memory performance pada host ini dalam keadaan normal seperti pada
screenshot di atas.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 14
3.5 Server PowerEdge R740 BZGC9V2
3.5.1 Summary
Service
Server Name Model IP Address Operating System
Tag
Dell
 VMware Host 05 PowerEdge BZGC9V2 VMWare ESXi 6.7.0 Build 10764712
R740
Current Lastest Estimated Time
Components Name Importance
Version Version (Minutes)
BIOS 2.5.4 2.10.0 Urgent 15
iDRAC9 with Lifecycle Controller 4.10.10.10 4.40.00.00 Recommend 15
NIC Card 14.10.05 15.15.06 Recommend 15
Total Estimated Time 45 Minutes
HARDWARE STATUS
CPU

MEMORY

POWER SUPPLY

PCI DEVICE

NETWORK - ETHERNET

Fan

TEMPERATURE

VOLTAGE

3.5.2 System Identity

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 15
3.5.3 VMware vSphere Performance

3.5.4 CPU

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 16
3.5.5 Memory

3.5.6 Disk

CPU & Memory performance pada host ini dalam keadaan normal seperti pada
screenshot di atas.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 17
4. Maintenance Storage Result Picture
4.1 Storage SC5020 FK7F9V2
4.1.1 Summary
Storage Service
Model IP Address Operating System
Name Tag
  Storage SC5020 FK7F9V2
HARDWARE STATUS
Temperature

Cooling FANS

POWER SUPPLIES

CONTROLLERS

DISK

INTERFACES

4.1.2 Status Summary

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 18
Madhani -Preventive Maintenance Report
Smartindo Maintenance Service Hal 19
5. Maintenance Brocade Result Picture
5.1 Brocade 6505 FKS0T72
5.1.1 Summary
Name Model Service Tag IP Address Operating System
  Brocade 6505 FKS0T72
HARDWARE STATUS
Temperature

Cooling FANS

POWER SUPPLIES

5.1.2 Switch View

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 20
5.1.3 Port Admin

5.1.4 Name Server

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 21
5.2 Brocade 6505 JTS0T72
5.2.1 Summary

Name Model Service Tag IP Address Operating System


  Brocade 6505 JTS0T72
HARDWARE STATUS
Temperature

Cooling FANS

POWER SUPPLIES

5.2.2 Switch View

5.2.2 Port Admin

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 22
5.2.3 Name Server

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 23
6. Maintenance ML3 Result Picture
6.1 DellEMC ML3 DK54FN2
6.1.1 Summary
Name Model Service Tag IP Address Operating System
  DellEMC ML3 DK54FN2
HARDWARE STATUS
POWERED

TEMPERATURE

COLLING FAN STATUS

CONTROLLERS

6.1.2 Driver

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 24
6.1.3 Cartridge

6.1.4 Library

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 25
7. Summary
7.1 Checking Health Status
Berdasarkan hasil dari server management iDRAC, kami telah memeriksa
perangkat keras komponen Server seperti power thermal / temperature,
batteries, fans, memory, power supplies, network card, processor dalam
kondisi baik. Dan untuk hard disk berada dalam kondisi baik untuk server.

7.2 Corective
No. Tanggal Permasalahan Penyelesaian Status
Email Datastore Alert Dilakukan penambahan capacity
(Datastore usage on pada Datastore
1 Maret 2020 disk) Solved

Fan high performance * Restart server host 3 * Reset


2 05-Mar-20 100% host 3 iDRAC * Update Frmware iDRAC Solved
pada semua Host
Disk Tier Low RAID 6- We have sync the time on both
10 has substituted controllers & no more error on the
3 11-Mar-20 page allocation witch time difference on both controller. Solved
different disk

Storage tidak dapat Update SCOS 7.4.x terdapat fix


diakses, BBU_FRU berikut :
BBU Battery is low, dan - SCOS-49124 Intermittent
Controller 361243 is erroneous battery failures might
4 12-Jun-20 down occur Solved
- SCOS-55136 a controller might
reset because of a cache-to-flash
restore error.
Link Reset on Port Replace HBA fc Slot 1 dan Slot 7
S0,P8(12) vc_no=0
5 19-Aug-20 crd(s)lost=12 auto Solved
trigger.

7.3 Parts Replacement


Berdasarkan hasil pemeriksaan terdapat kerusakan pada HBA FC slot 1 dan
slot 7 pada host 5 terditeksi hanya 8Gbps seharusnya 16Gbps.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 26
7.4 Repair
Pada tanggal 9 September 2020 sudah dilakukan pergantian part pada HBA
FC slot 1 dan slot 7, dan saat ini FC sudah terditeksi kembali menjadi 16Gbps.

7.5 Warranty
List of Extended Warranty
Service
No Model Start Date End Date SLA Support
Tag
1 BZJ99V2 DellEMC PowerEdge R740 February 08, 2019 February 10, 2022 4-hour Onsite Service
BR999V2 DellEMC PowerEdge R740
2 February 08, 2019 February 10, 2022 4-hour Onsite Service
BZJG9V2 DellEMC PowerEdge R740
3 February 08, 2019 February 10, 2022 4-hour Onsite Service
BZHB9V2 DellEMC PowerEdge R740
4 February 08, 2019 February 10, 2022 4-hour Onsite Service
BZGC9V2 DellEMC PowerEdge R740
5 February 08, 2019 February 10, 2022 4-hour Onsite Service
FK7F9V2 DellEMC Storage SC5020
6 February 20, 2019 February 22, 2022 4-hour Onsite Service
FKS0T72 Brocade 6505
7 February 22, 2019 February 24, 2022 4-hour Onsite Service
JTS0T72 Brocade 6505
8 February 22, 2019 February 24, 2022 4-hour Onsite Service
DK54FN2 DellEMC ML3
9 February 08, 2019 February 10, 2022 4-hour Onsite Service

Detail Report
7.5.1. Service Tag : BZJ99V2
End Date : February 10, 2022

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 27
7.5.2. Service Tag : BR99V2
End Date : February 10, 2022

7.5.3.Service Tag : BZJG9V2


End Date : February 10, 2022

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 28
7.5.4. Service Tag : BZJGV2
End Date : February 10, 2022

7.5.5.Service Tag : BZGC9V2


End Date : February 10, 2022

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 29
7.5.6.Service Tag : FK7F9V2
End Date : February 22, 2022

7.5.7.Service Tag : FKS0T72


End Date : February 24, 2022

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 30
7.5.8.Service Tag : JTS0T72
End Date : February 24, 2022

7.5.9.Service Tag : DK54FN2


End Date : February 10, 2022

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 31
7.6 Firmware Version
Berdasarkan hasil dari management iDRAC Server PowerEdge R740, Storage
SC5020, Brocade 6505, DellEMC ML3. Berikut versi firmware latest yang telah
di released dari Dell Support Website.

Estimated
Service Components Current Update
Device Importance Downtime Time
Tag Name Version Version
(Minutes)
No
iDRAC 4.10.10.10 4.40.00.00 Recommend 15
Downtime
DellEMC
No
PowerEdge BZJ99V2 NIC 14.10.05 15.15.06 Recommend 15
Downtime
R740
No
BIOS 2.5.4 2.10.0 Urgent 15
Downtime
No
iDRAC 4.10.10.10 4.40.00.00 Recommend 15
Downtime
DellEMC
No
PowerEdge BR999V2 NIC 14.10.05 15.15.06 Recommend 15
Downtime
R740
No
BIOS 2.5.4 2.10.0 Urgent 15
Downtime
No
iDRAC 4.10.10.10 4.40.00.00 Recommend 15
Downtime
DellEMC
No
PowerEdge BZJG9V2 NIC 14.10.05 15.15.06 Recommend 15
Downtime
R740
No
BIOS 2.5.4 2.10.0 Urgent 15
Downtime
No
iDRAC 4.10.10.10 4.40.00.00 Recommend 15
Downtime
DellEMC
No
PowerEdge BZHB9V2 NIC 14.10.05 15.15.06 Recommend 15
Downtime
R740
No
BIOS 2.5.4 2.10.0 Urgent 15
Downtime
No
iDRAC 4.10.10.10 4.40.00.00 Recommend 15
Downtime
DellEMC
No
PowerEdge BZGC9V2 NIC 14.10.05 15.15.06 Recommend 15
Downtime
R740
No
BIOS 2.5.4 2.10.0 Urgent 15
Downtime
225
Total Estimated Time
Minutes

7.6.1 Dell PowerEdge R740 BIOS New Version


No Hardware Model Service Tag
1 Server DellEMC PowerEdge R740 BZJ99V2
DellEMC PowerEdge R740 BR999V2
2 Server
DellEMC PowerEdge R740 BZJG9V2
3 Server
DellEMC PowerEdge R740 BZHB9V2
4 Server
DellEMC PowerEdge R740 BZGC9V2
5 Server

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 32
Semua PowerEdge R740 BIOS firmware saat ini adalah V 2.5.4 dan versi terbaru
dari Dell saat ini adalah V. 2.10

7.6.2 Dell PowerEdge R740 IDRAC Firmware New Version

No Hardware Model Service Tag


1 Server DellEMC PowerEdge R740 BZJ99V2
DellEMC PowerEdge R740 BR999V2
2 Server
DellEMC PowerEdge R740 BZJG9V2
3 Server
DellEMC PowerEdge R740 BZHB9V2
4 Server
DellEMC PowerEdge R740 BZGC9V2
5 Server

Semua PowerEdge R740 iDRAC firmware saat ini V. 4.10.10.10. dan versi terbaru
dari dell saat ini adalah 4.40.00.00.

Madhani -Preventive Maintenance Report


Smartindo Maintenance Service Hal 33