How To Wire A Proximity Sensor To A PLC
How To Wire A Proximity Sensor To A PLC
---
Your Keyword Go
Pepperl+Fuchs Blog
^
How to Wire a Proximity Sensor to a PLC
Posted by
Sam Horn on Tue, Sep 18, 2018
Tweet Share
Power supply
The power supply provides power to the CPU, I/O modules, and signal devices.
CPU (sometimes called a processor or controller)
A CPU (central processing unit) is essentially the brains of the operation.
The CPU takes data from the I/O system and processes it according to what the programmer specifies.
I/O system
I/O modules (sometimes referred to as I/O cards) can accept input signals, deliver output signals, or both
Input modules can accept digital or analog signals
Signal devices
Signal devices can be push buttons, sensors, or switches. In this case, we will talk about sensors">
Connecting a proximity sensor to a PLC can be a daunting task at first glance. For one thing, there is no
universal way to connect proximity sensors. The process varies depending on the sensor and input
module used in the configuration.
The Basics
The first step is understanding how PLC networks are set up. The four major components of a network
include the following:
1. Power supply
The power supply provides power to the CPU, I/O modules, and signal devices.
2. CPU (sometimes called a processor or controller)
A CPU (central processing unit) is essentially the brains of the operation.
The CPU takes data from the I/O system and processes it according to what the programmer
specifies.
3. I/O system
I/O modules (sometimes referred to as I/O cards) can accept input signals, deliver output
signals, or both
Input modules can accept digital or analog signals
Menu
---
4. Signal devices
Signal devices can be push buttons, sensors, or switches. In this case, we will talk about
Your Keyword sensors. Go
Sensors are wired to I/O modules, and I/O modules are wired back to the CPU. It is important to read the
wiring diagram of an input module to understand its operation. The module’s operating voltage, input type,
and terminal layout are a few of the parameters used to wire up the network. Terms like load, sinking,
sourcing, positive or common, PNP, NPN, 2-, 3-, and 4-wire will be used throughout this discussion. To get
familiar with some of these terms, read our blog post How to Read a Sensor Connection Diagram.
Input/Output Type
A sourcing (PNP) sensor must run into a sinking input card, while a sinking (NPN) sensor must run into a
sourcing input card. This is true because the network can be modeled as a simple circuit, and in order to
complete the circuit, current must flow in a complete loop. Some modules can accept both PNP and NPN
inputs and are noted on the module’s wiring diagram.
The term common refers to a (+/-) reference polarity of a PNP or NPN configuration. A common wire is
used to reduce the number of terminal connections made between sensors and a PLC. This wire is noted
on the I/O module’s wiring diagram.
PNP sensor outputs switch in a positive (+) fashion. This means that multiple sensors can be connected
to an input card with all sensor negative wires to one common (-) wire.
NPN sensor outputs switch in a negative (-) fashion. This means that multiple sensors can be connected
Menu
---
to an input card with all sensor positive wires to one common (+) wire.
Hardwire Connections
Your Keyword Go
Input cards do not know the difference between 2-, 3-, or 4-wire sensors, but input cards for 2-wire sensors
must be rated to accept the sensor’s voltage drop and off-state current level (noted on datasheets.)
Sensors with 3 and 4 wires have dedicated output wires. These output wires are run straight to a module’s
input.
Normally open or normally closed sensor logic does not affect physical connections between a sensor
and a PLC.
Internal Loads
Sourcing cards have an internal resistive load connected between V+ and its inputs. Sinking cards have an
internal resistive load connected between its inputs and V- (also called ground or 0 VDC.) Why is this true?
A PNP (sourcing) sensor switches to (+), while the sinking card already has a connection to DC ground. An
NPN (sinking) sensor switches to (-), while the sourcing card already has a connection to V+.
System Layout
Output type
PNP or NPN
Output signal
Digital or analog; if analog, is it an analog voltage or analog current signal?
A digital sensor output must run into a digital input card, and an analog sensor output must run into
an analog input card
Connection type
2-, 3-, or 4-wire
Menu
---
The input card’s datasheet shows the following:
Your Keyword
Sinking or sourcing Go
In a PNP configuration, the sensor output is internally connected to the positive voltage polarity. To make a
complete circuit, the load (PLC input) must be externally connected to a negative (common) voltage
polarity. In an NPN configuration, the sensor output is internally connected to the negative voltage polarity.
To make a complete circuit, the load must be externally wired to a positive (common) voltage polarity:
How the sensor is connected to a power source depends on whether the sensor has a PNP or NPN output
type. A PNP sensor is typically referred to as a sourcing sensor, which means the sensor can be thought of
as sourcing (or giving) signal input power to the I/O card. An NPN sensor is typically referred to as a
sinking sensor, which means the sensor can be thought of as sinking (or receiving) signal input power
from the I/O card.
Recall that a sourcing (PNP) sensor sends power and signal to a sinking module, while a sinking (NPN)
sensor receives power and signal from a sourcing module. PNP sensors switch to (+), while NPN sensors
switch to (-).
Sinking input cards have a load internally connected between its inputs and a DC ground terminal. To
complete the circuit, the PNP sensor switches to (+). Sourcing input cards have a load internally
connected between its inputs and a +VDC terminal. To complete the circuit, the NPN sensor switches to
(-).
Pulling It All Together
Menu
---
Step 1: Identify the Network Parameters
Output type
Your Keyword Go
Output signal
Connection type
Sinking/sourcing
I/O connection
Power operation
Step 2: Connect Sensor Output(s) to PLC Input(s)
2-wire configurations
PNP sensor (load externally wired to negative terminal)
Sensor (-) wire is run straight to PLC input
NPN sensor (load externally wired to positive terminal)
Sensor (+) wire is run straight to PLC input
3-wire configurations
PNP sensor
Sensor output wire is run straight to PLC input
NPN sensor
Sensor output wire is run straight to PLC input
4-wire configurations
PNP sensor
Sensor output wires are run to separate PLC inputs
NPN sensor
Sensor output wires are run to separate PLC inputs
Step 3: Connect Sensor and Input Module to Power
2-wire configurations
PNP sensor
Sensor (-) wire is run straight to PLC input
Sensor (+) wire is run to +VDC
NPN sensor
Sensor (+) wire is run straight to PLC input
Sensor (-) wire is run to 0 VDC (negative terminal) on the power supply
3-wire configurations
PNP sensor
Sensor (+) wire is run to +VDC power supply
Sensor (-) wire is run to common (0 VDC) on the input card
NPN sensor
Sensor (+) wire is run to +VDC on the input card
Sensor (-) wire is run to common (0 VDC) power supply
Your Keyword Go
Thinking of the circuit in terms of current flow, red arrows on the diagram above depict the direction of
current flow to show that current flows out of the power source at the positive terminal and into the
sensor. When the PNP sensor detects a target, it will switch to positive and close the circuit to send a
signal through the output wire into the input card. The input card is sinking, which means its internal load
is connected between its input terminals and ground. It must complete the circuit by connecting a
common (-) polarity wire to the negative terminal of the power source.
An Allen-Bradley ControlLogix 1746-IV16 Input Module is used in this example. From the catalog found on
Rockwell Automation’s website, it can be seen that this is a Digital Sourcing Input module. Only sinking
(NPN) sensors can be connected to this module. How does this circuit operate?
Current flows out of the positive terminal of the power supply into the input module. In this case, the input
module is sourcing power to the sensor. Current flows out of the input module from the V+ terminal (where
the input card’s internal load is connected between V+ and its input terminals) into the sensor to power
the sensor. The NPN sensor switches to (-) and sinks power back to the power supply to complete the
circuit.
Menu
---
Your Keyword Go
In industry, most PLC manufacturers do not model PLC Networks in terms of current. For simplicity of this
discussion, the setup is modeled as a circuit with current flow to help distinguish PNP- and NPN-type
circuits.
2-wire DC PNP, 2-wire DC NPN, 3-wire DC PNP, and 3-wire DC NPN cases have been covered in this
discussion. Connecting a 4-wire DC sensor is the same as a 3-wire sensor, but each output wire is
connected to a different input on the input card. Examples used in this discussion are common setups in
modern industry but vary depending on the application.
Topics:
PLC,
proximity sensors
Your Keyword Go
Subscribe
Recent Posts
SIL 3 Current Drivers for Intrinsically Safe Signals – Minimal Hardware Costs and Improved Test Intervals
PS1000 Industrial Power Supplies in Redundant Architectures up to Zone 2/Div. 2
Setup, Installation and Commissioning of the 5500-MAN Manifold Valve System for Fully Automatic
Pressurized Enclosure Systems
How RFID with IO-Link Eases Machine Access
Which Applications Can Be Solved with the VOS Vision Tool Set?
Circuit Fault Detection without Additional Wiring
Hardware and Software Features of the R2000 Series 2-D Laser Scanner
Configuring the 7500 Series Purge and Pressurization System
How to Prevent Dust Explosions Using Pressurization
Viator® USB HART Interface Troubleshooting with ViatorCheckBT
Posts by Topic
Photoelectric Sensors (67)
Menu
---
Inductive Sensors (61)
Ask an Expert (57)
Ultrasonic
Your KeywordSensors (52) Go
AS-Interface (46)
see all
Follow Me
Phone: 330-425-3555
Home
Industrial Sensors
Explosion Protection
Products
Markets+Applications
Contact Us
About Us
Careers
What's New?
amplify
Menu
---
Select Country
Sitemap
Your Keyword Go
Privacy Policy
Legal Notice
Pepperl+Fuchs is a leading developer and manufacturer of electronic sensors and components for the global automation market.
Continuous innovation, enduring quality, and steady growth guarantees continued success, since more than 60 years. Pepperl+Fuchs
employs 5,600 people worldwide and has manufacturing facilities in Germany, USA, Singapore, Hungary, Indonesia and Vietnam, most of
them ISO 9001 certified.