0% found this document useful (0 votes)
447 views68 pages

Victrix Tera 28 1 - 32 1 - 38 1: IE Instructions and Warnings

This document provides instructions for installing, using, and maintaining a boiler. It includes information on installation requirements, boiler components, startup procedures, control panel operation, troubleshooting tips, and maintenance instructions. Safety symbols and warnings are also explained.

Uploaded by

Gigi Duru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
447 views68 pages

Victrix Tera 28 1 - 32 1 - 38 1: IE Instructions and Warnings

This document provides instructions for installing, using, and maintaining a boiler. It includes information on installation requirements, boiler components, startup procedures, control panel operation, troubleshooting tips, and maintenance instructions. Safety symbols and warnings are also explained.

Uploaded by

Gigi Duru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 68

Instructions and warnings

Installer
IE VICTRIX TERA
User 28 1 - 32 1 - 38 1
Maintenance technician
*1.040295ENG*
CONTENTS

Dear Customer,.................................................................................. 4 2.4 Using the boiler................................................................... 36


General warnings.............................................................................. 4 2.5 Fault and anomaly signals................................................. 37
Safety symbols used........................................................................... 5 2.6 Information Menu.............................................................. 39
Personal protective equipment........................................................ 5 2.7 Boiler shutdown.................................................................. 40
2.8 Restore central heating system pressure.......................... 40
1 Boiler installation................................................................. 6 2.9 Draining the system........................................................... 40
1.1 Installation recommendations............................................ 6 2.10 Draining the domestic hot water circuit.......................... 40
1.2 Main dimensions.................................................................. 9 2.11 Antifreeze protection......................................................... 40
1.3 Minimum installation distances......................................... 9 2.12 Cleaning the case................................................................ 40
1.4 Antifreeze protection......................................................... 10 2.13 Decommissioning............................................................... 40
1.5 Installation inside the recessed frame (Optional).......... 11 2.14 Gas system not used for periods over 12 months........... 40
1.6 Boiler connection unit....................................................... 12
1.7 Gas connection................................................................... 12 3 Instructions for maintenance and initial check.............. 41
1.8 Hydraulic connection......................................................... 13 3.1 General warnings................................................................ 41
1.9 Electrical connection.......................................................... 14 3.2 Initial check......................................................................... 41
1.10 Remote controls and room chrono-thermostats 3.3 Yearly appliance check and maintenance........................ 42
(Optional)............................................................................ 14 3.4 Boiler Hydraulic diagram.................................................. 43
1.11 External temperature probe (Optional)........................... 15 3.5 Wiring diagram................................................................... 44
1.12 Immergas flue systems....................................................... 16 3.6 Possible problems and their causes.................................. 45
1.13 Tables of resistance factors and equivalent lengths 3.7 Converting the boiler to other types of gas..................... 45
“GREEN SERIES”................................................................ 17 3.8 Calibration of fan speed..................................................... 46
1.14 Outdoor installation in partially protected area............. 19 3.9 Adjustment of the air-gas ratio......................................... 46
1.15 Internal installation using a recessed frame 3.10 Checks following conversion to another type of gas...... 46
with direct air intake.......................................................... 21 3.11 Programming the P.C.B..................................................... 47
1.16 Concentric horizontal kit installation.............................. 21 3.12 Password-protected special functions.............................. 51
1.17 Concentric vertical Kit installation.................................. 22 3.13 Screed heater function....................................................... 51
1.18 Separator kit installation.................................................... 24 3.14 Automatic vent function (dl)............................................ 51
1.19 Adaptor C9 kit installation................................................ 25 3.15 Flue installation (Fu).......................................................... 51
1.20 Ducting of flues or technical slots.................................... 27 3.16 Maintenance function (MA)............................................. 52
1.21 Configuration type B, open chamber and fan 3.17 "Chimney sweep” function................................................ 52
assisted for indoors............................................................. 27 3.18 Solar panels coupling function......................................... 52
1.22 Flue exhaust to flue/chimney............................................ 27 3.19 Pump anti-block function................................................. 52
1.23 Flues, chimneys, chimney pots and terminals................ 28 3.20 3-way anti-block system.................................................... 52
1.24 Water treatment system filling.......................................... 28 3.21 Radiators antifreeze function............................................ 52
1.25 System filling....................................................................... 29 3.22 Casing removal................................................................... 53
1.26 Filling the condensate drain trap...................................... 29
1.27 Gas system start-up............................................................ 29 4 Technical data..................................................................... 55
1.28 Boiler start-up (Ignition)................................................... 29 4.1 Variable heat output........................................................... 55
1.29 Circulation pump................................................................ 29 4.2 Combustion parameters.................................................... 56
1.30 Circulation pump 4.3 Technical data..................................................................... 57
with new wave 3 electronics.............................................. 31 4.4 Key for Data nameplate..................................................... 58
1.31 Boiler components.............................................................. 32 4.5 Technical parameters for combination boilers (in
1.32 Kits available on request.................................................... 32 compliance with Regulation 813/2013)........................... 59
4.6 Product fiche (in compliance with Regulation
2 Instructions for use and maintenance.............................. 33 811/2013)............................................................................. 61
2.1 General warnings................................................................ 33 4.7 Parameters for filling in the package fiche...................... 63
2.2 Cleaning and maintenance................................................ 35
2.3 Control panel....................................................................... 35
Dear Customer,
Congratulations for having chosen a top-quality Immergas product, able to assure well-being and safety for a long period of time. As an
Immergas Customer, you can also count on an Authorised After-Sales centre, prepared and updated to guarantee constant efficiency of
your boiler. Read the following pages carefully: you will be able to draw useful tips on the proper use of the device, compliance with which
will confirm your satisfaction with the Immergas product.
For any assistance and scheduled maintenance please contact Authorised After-Sales centres: they have original spare parts and are
specifically trained by the manufacturer.

GENERAL WARNINGS
This book contains important information for the:
Installer (section 1);
User (section 2);
Maintenance Technician (section 3).
• The user must carefully read the instructions in the specific section (section 2).
• The user must limit operations on the appliance only to those explicitly allowed in the specific section.
• The appliance must be installed by qualified and professionally trained personnel.
• The instruction booklet is an integral and essential part of the product and must be given to the new user in the case of transfer
or succession of ownership.
• It must be stored with care and consulted carefully, as all of the warnings provide important safety indications for installation,
use and maintenance stages.
• In compliance with legislation in force, the systems must be designed by qualified professionals, within the dimensional limits
established by the Law. Installation and maintenance must be performed in compliance with the regulations in force, according
to the manufacturer's instructions and by professionally qualified staff, intended as staff with specific technical skills in the system
sector, as envisioned by the Law.
• Improper installation or assembly of the Immergas appliance and/or components, accessories, kits and devices can cause unexpected
problems for people, animals and objects. Read the instructions provided with the product carefully to ensure proper installation.
• This instructions manual provides technical information for installing Immergas products. As for the other issues related to the
installation of products (e.g. safety at the workplace, environmental protection, accident prevention), it is necessary to comply
with the provisions of the standards in force and the principles of good practice.
• All Immergas products are protected with suitable transport packaging.
• The material must be stored in a dry place protected from the weather.
• Damaged products must not be installed.
• Maintenance must be carried out by skilled technical staff that represents a guarantee of qualifications and professionalism.
• The appliance must only be destined for the use for which it has been expressly declared. Any other use will be considered improper
and therefore potentially dangerous.
• If errors occur during installation, operation and maintenance, due to non-compliance with technical laws in force, standards or
instructions contained in this book (or however supplied by the manufacturer), the manufacturer is excluded from any contractual
and extra-contractual liability for any damage and the appliance warranty is invalidated.

The company IMMERGAS S.p.A., with registered office in via Cisa Ligure 95 42041 Brescello (RE), declares that the design, manu-
facturing and after-sales assistance processes comply with the requirements of standard UNI EN ISO 9001:2015.
For further details on the product CE marking, request a copy of the Declaration of Conformity from the manufacturer, specifying the
appliance model and the language of the country.

The manufacturer declines all liability due to printing or transcription errors, reserving the right to make any modifications to its
technical and commercial documents without forewarning.
SAFETY SYMBOLS USED.

GENERIC HAZARD
Strictly follow all of the indications next to the pictogram. Failure to follow the indications can generate hazard situa-
tions resulting in possible harm to the health of the operator and user in general.

ELECTRICAL HAZARD
Strictly follow all of the indications next to the pictogram. The symbol indicates the appliance’s electrical components
or, in this manual, identifies actions that can cause an electrical hazard.

MOVING PARTS
The symbol indicates the appliance’s moving components that can cause hazards.

HOT SURFACES
The symbol indicates the appliance’s very hot components that can cause burns.

SHARP SURFACES
The symbol indicates the appliance’s components or parts that can cause cuts if touched.

EARTH TERMINAL CONNECTION


The symbol identifies the appliance’s earth terminal connection point.

READ AND UNDERSTAND THE INSTRUCTIONS


Read and understand the appliance’s instructions before performing any operation, carefully following the indications
provided.

INFORMATION
Indicates useful tips or additional information.

The user must not dispose of the appliance at the end of its service life as municipal waste, but send it to appro-
priate collection centres.

PERSONAL PROTECTIVE EQUIPMENT.

SAFETY GLOVES

SAFETY GOGGLES

SAFETY FOOTWEAR
1 BOILER INSTALLATION.

1.1 INSTALLATION RECOMMENDATIONS.

ATTENTION:
INSTALLER

operators who install and service the


appliance must wear the personal
protective equipment required by ap-
plicable law.
OK
1

The Victrix Tera boiler has been designed for wall ATTENTION:
mounted installation only; for central heating and
check the environmental operating
production of domestic hot water for domestic use
and similar purposes. conditions of all parts relevant to in-
The place of installation of the appliance and relative stallation, referring to the values shown in the
Immergas accessories must have suitable features technical data table in this booklet.
USER

(technical and structural), such as to allow for (always in safe,


efficient and comfortable conditions):
- installation (according to the provisions of technical legisla- ATTENTION:
tion and technical regulations); Installation of the Victrix Tera boiler
- maintenance operations (including scheduled, periodic, when powered by LPG must comply
routine and special maintenance);
with the rules regarding gases with a greater
- removal (outdoors in the place for loading and transporting
the appliances and components) as well as their eventual density than air (remember, as an example,
replacement with appliances and/or equivalent components. that it is prohibited to install plants powered
MAINTENANCE TECHNICIAN

The wall surface must be smooth, without any protrusions or with the above-mentioned gas in rooms where
recesses enabling access to the rear part. They are not designed the floor is at a lower quota than the country
to be installed on plinths or floors (Fig. 1).
By varying the type of installation the classification of the boiler level).
also varies, precisely:
- Type B23 or B53 boiler if installed using the relevant terminal ATTENTION:
for air intake directly from the room in which the boiler has if installing a kit or servicing the ap-
been installed.
pliance, always empty the system’s
- Type C boiler if installed using concentric pipes or other types
of pipes envisioned for the sealed chamber boiler for intake
domestic hot water circuit first so as not to
of air and expulsion of flue gas. compromise the appliance’s electrical safety
Only professionally qualified companies are authorised to (Par. 2.10).
install Immergas gas appliances.
Installation must be carried out according to regulation stand-
ards, current legislation and in compliance with local technical
regulations and the required technical procedures.

ATTENTION:
It is not permitted to install boilers that
are removed and decommissioned from
other systems. The manufacturer declines all
liability for damage caused by boilers removed
from other systems or for any non-conformi-
ties of such equipment.

6
Before installing the appliance, ensure it has been Installation Standards:
delivered in perfect condition; if in doubt, contact
the supplier immediately. Packing materials (staples, - this boiler can be installed out-
nails, plastic bags, polystyrene foam, etc.) constitute a doors in a partially protected area.
hazard and must be kept out of the reach of children. A partially protected area is one in which

INSTALLER
If the appliance is installed inside or between cabinets, ensure the boiler is not exposed to the direct ac-
sufficient space for normal servicing; therefore it is advisable to
leave clearance of at least 3 cm between the boiler casing and
tion of the weather (rain, snow, hail, etc.).
the vertical sides of the cabinet. Leave adequate space above the This type of installation is only possible
boiler for possible water and flue removal connections (Fig. 3). when permitted by the laws in force in the
appliance's country of destination.
It is just as important that the intake grids and exhaust
terminals are not obstructed. - Installation of gas appliances, flue exhaust
It is recommended to check that no flue gas recircula- pipes and combustion air intake pipes is
tion is found in the air sample points (0.5% maximum forbidden in places with a fire risk (for ex-
permitted CO2).
ample: garages, closed parking stalls), and
Keep all flammable objects away from the appliance (paper, in potentially dangerous places.
rags, plastic, polystyrene, etc.).
The minimum distance for exhaust pipes from flammable
- Installation on the vertical projection

USER
materials must be at least 25 cm.
Do not place household appliances underneath the boiler as of cooking hobs is forbidden.
they could be damaged if the safety valve intervenes, if the - Installation is forbidden in places/
drain trap is blocked, or if there are leaks from the hydraulic
connections; otherwise, the manufacturer cannot be held re- rooms that constitute public areas of apart-
sponsible for any damage caused to the household appliances. ment buildings, internal stairways or other
For the aforementioned reasons, we recommend not placing escape routes (e.g. floor landings, entrance
furnishings, furniture, etc. under the boiler. halls, etc.).
In the event of malfunctions, faults or incorrect operation, turn - Installation is also forbidden in places/

MAINTENANCE TECHNICIAN
the appliance off immediately and contact an authorised com-
pany (e.g. the Authorised Technical Assistance centre, which rooms that constitute public areas of apart-
has specifically trained staff and original spare parts). Do not ment buildings such as cellars, entrance
attempt to modify or repair the appliance alone. halls, attics, lofts, etc., unless otherwise
Any modification to the appliance that is not explicitly indicated
in this section of the booklet is forbidden. provided for by local regulations in force.
- These boilers are not suitable for installation
on walls made of combustible material.

N.B.: installing the wall recessed frame kit must guar-


antee the boiler stable, efficient support. The recessed
frame kit ensures appropriate support only if installed
correctly (according to the rules of good practice),
following the instructions on its instructions leaflet.
The recessed frame for the boiler is not a supporting
structure and must not replace the wall removed. It is necessary
to position the boiler inside the wall. For safety reasons against
any leaks it is necessary to plaster the boiler housing in the brick
wall.

7
N.B.: wall mounting of the boiler must guarantee This means that the drain trap is filled with
stable and efficient support for the boiler. The
plugs (standard supply) are only to be used to fix
condensate to the correct level preventing the
the boiler to the wall; they only ensure adequate passage of flue gas.
support if inserted correctly (according to technical
INSTALLER

standards) in walls made of solid or semi-hollow ATTENTION:


brick or block. In the case of walls made of hollow bricks or - Type B open chamber boilers must not
blocks, partitions with limited static properties, or in any case
walls other than those indicated, a static test must be carried be installed in places where commer-
out on the mounting system. cial, artisan or industrial activities take place,
which use products that may develop volatile
These boilers are used to heat water to below boiling vapours or substances (e.g. acid vapours,
temperature in atmospheric pressure.
They must be connected to a central heating system glues, paints, solvents, combustibles, etc.),
and domestic hot water circuit suited to their perfor- as well as dusts (e.g. dust deriving from the
mance and capacity. working of wood, coal fines, cement, etc.),
which may be harmful for the components
Risk of damage due to corrosion caused by unsuitable of the appliance and jeopardise operation.
combustion air and environment.
Spray, solvents, chlorine-based detergents, paints, glue, - Unless otherwise provided for by local reg-
USER

ammonium compounds, powders and similar cause ulations in force, configurations B23 and B53:
product and flue duct corrosion. the boilers must not be installed in bedrooms,
- Check that combustion air power supply is free from bathrooms or bedsits. They must neither be
chlorine, sulphur, powders, etc.
installed in rooms containing solid fuel heat
- Make sure that no chemical substances are stored in the place
of installation. generators nor in rooms communicating with
- If you want to install the product in beauty salons, paint said rooms.
workshops, carpenter’s shop, cleaning companies or - The installation rooms must be permanently
similar, choose a separate installation area that ensures
MAINTENANCE TECHNICIAN

combustion air supply that is free from chemical substances.


ventilated, in compliance with the local reg-
- Make sure the combustion air is not fed from chimneys that ulations in force (at least 6 cm2 for every kW
were used with gas boilers or other heating devices. In fact, these of installed heat input, except in the event of
may cause an accumulation of soot in the chimney. any increases needed for electro-mechanical
vacuum cleaners or other devices that could
Risk of material damage after using sprays and liquids put the installation room under vacuum).
to search for leaks
Leak sprays and liquids clog the reference hole (P1-Fig.
- Installation of appliances in B 23 and B 53
40) of the gas valve, damaging it irreparably. configuration is recommended in non-resi-
During installation and maintenance, do not use spray dential premises and which are permanently
or liquids in the upper area of the gas valve (side referring to the ventilated.
electric connections)

ATTENTION:
Filling the condensate drain trap. Failure to comply with the above implies
On first lighting of the boiler, flue gas may personal responsibility and invalidates
come out from the condensate drain; af- the warranty.
ter a few minutes’ operation, check that this no
longer occurs.

8
1.2 MAIN DIMENSIONS.

INSTALLER
Key:
V - Electrical connection
G - Gas supply
AC - Domestic hot water outlet
ACV - Solar valve kit DHW inlet (optional)
AF - Domestic hot water inlet
SC - Condensate drain (minimum internal diameter Ø 13 mm)
M - System flow
R - System return

Height Width Depth


(mm) (mm) (mm)
748 440 256

CONNECTIONS
WATER

USER
GAS DOMESTIC SYSTEM
CW
G AC AF R M
3/4” 1/2” 1/2” 3/4” 3/4”

MAINTENANCE TECHNICIAN
1.3 MINIMUM INSTALLATION DISTANCES.

Key:
A - 450 mm
B - 350 mm
C - 30 mm
D - 30 mm
E - 350 mm

9
1.4 ANTIFREEZE PROTECTION. N.B.: if the boiler is installed in places where the
Minimum temperature –5 °C. temperature drops below 0°C, the domestic hot
The boiler comes standard with an antifreeze function water and central heating attachment pipes must
that activates the pump and burner when the system be insulated.
water temperature drops below 4°C. Note: the antifreeze systems described in this chap-
INSTALLER

In these conditions the boiler is protected against freez- ter are only to protect the boiler. The presence of
ing down to a temperature of -5°C. these functions and devices does not exclude the possibility
of parts of the system or domestic hot water circuit outside
Minimum temperature –15 °C. the boiler from freezing.
If the boiler is installed in a place where the temperature drops
below -5°C, the appliance may freeze.
To prevent the risk of freezing follow the instructions below:
- protect the central heating circuit from freezing by inserting
a good-quality antifreeze liquid, which is specially suited for
central heating systems and which is manufacturer guaranteed
against damage to the heat exchanger or other components.
The antifreeze liquid must not be harmful to one's health. The
instructions of the manufacturer of the liquid must be strictly
followed regarding the necessary percentage with respect to
the minimum temperature provided for.
USER

N.B.: the excessive use of glycol could jeopardise the proper


functioning of the appliance.
- An aqueous solution must be made with potential pollution
class of water 2 (EN 1717:2002).
- The central heating circuit of Immergas boilers are made from
materials that resist wear caused by ethylene and propylene
glycol based antifreeze liquids (if the mixtures are prepared
perfectly).
- For life and possible disposal, follow the manufacturer's in-
MAINTENANCE TECHNICIAN

structions of liquid.
- Protect the domestic hot water circuit against freezing by
using an accessory that is supplied on request (anti-freeze
kit) comprising two electric heating elements, the relevant
cables and a control thermostat (carefully read and follow the
installation instructions contained in the accessory kit pack).
In these conditions the boiler is protected against freezing to
temperature of -15°C.
Boiler antifreeze protection (both -5°C and -15°C) is thus
ensured only if:
- the boiler is correctly connected to gas and electricity power
supply circuits;
- the boiler is powered constantly;
- the boiler is not in “off ” mode;
- the boiler is not in anomaly conditions (Paragraph 2.5);
- the essential components of the boiler and/or antifreeze kit
are not faulty.
The warranty does not cover damage due to interruption of the
electrical power supply and failure to comply with that stated
on the previous page.

10
1.5 INSTALLATION INSIDE THE RECESSED FRAME
(OPTIONAL).
The boiler is designed for installation inside the Immergas re-
cessed frame (supplied as optional). The necessary parts for this
type of installation (brackets) must also be purchased separately

INSTALLER
as optional kit.
To install proceed as follows: 2 1
- Install the bracket (2) inside the recessed frame fixing it with the
screws (3) in the pre-drilled holes (Fig. 4).
- Hang the boiler (4) to the bracket (2) (Fig. 5). 3
- Block the boiler (4) by mounting the brackets (5) and fixing them 3
with their screws (6) (Fig. 6).
The brackets (5) used to centre the boiler on the frame and hold 4
it in place stop against the frame (1) so do not require fixing to
the frame itself.

USER
2 1

MAINTENANCE TECHNICIAN
2

5
1
6

4 5

6
6

11
1.6 BOILER CONNECTION UNIT.
The connection unit consisting of all the necessary parts to per- According to local regulations in force,
form the hydraulic and gas system connections of the appliance make sure that a gas cock is installed
comes as optional kit, perform the connections respecting the upstream of each connection between
arrangement of Fig. 7 based on the type of installation to be made.
the appliance and the gas system. This cock,
INSTALLER

if supplied by the appliance’s manufacturer,


1.7 GAS CONNECTION.
can be directly connected to the appliance
Our boilers are designed to operate with methane gas (G20) and
L.P.G. Supply pipes must be the same as or larger than the 3/4”G (i.e. downstream from the pipes connecting
boiler fitting. the system to the appliance), according to the
manufacturer’s instructions.
ATTENTION:
The Immergas connection unit, supplied as
Before connecting the gas line, carefully
an optional kit, also includes the gas cock,
clean inside all the fuel feed system pipes
whose installation instructions are provided
to remove any residue that could impair boiler
in the kit.
efficiency. Also make sure the gas corresponds
In any case, make sure the gas cock is connect-
to that for which the boiler is prepared (see
ed properly.
boiler data nameplate). If different, the boiler
must be converted for operation with the other
USER

The gas supply pipe must be suitably dimensioned according to


type of gas (see converting appliance for other current regulations in order to guarantee correct gas flow rate to
gas types). It is also important to check the dy- the burner even in conditions of maximum generator output and
namic pressure of the mains (methane or LPG) to guarantee appliance efficiency (technical specifications). The
coupling system must conform to standards in force (EN 1775).
used to supply the boiler, which must comply
with EN 437 and its attachment, as insufficient ATTENTION:
levels may reduce generator output and cause the appliance is designed to operate with
discomfort to the user. fuel gas free from impurities; otherwise
MAINTENANCE TECHNICIAN

Ensure correct gas cock connection. it is advisable to fit special filters upstream of
the appliance to restore the purity of the fuel.

AC
V SC
AF
3
2
Key:
V - Electrical connection
G G - Gas supply
AC - Domestic hot water outlet
1
AF - Domestic hot water inlet
R SC - Condensate drain
M
(minimum internal diameter Ø 13 mm)
M - System flow
R - System return
1 - System filling valve
2 - System draining valve
3 - 3 bar safety valve drain fitting signal
7

12
Storage tanks (in case of supply from LPG depot).
- New LPG storage tanks may contain residual inert gases (nitro- ATTENTION:
gen) that degrade the mixture delivered to the appliance casing the manufacturer declines all liability
functioning anomalies.
in the event of damage caused by the
- Due to the composition of the LPG mixture, layering of the
installation of an automatic filling system.

INSTALLER
mixture components may occur during the period of storage in
the tanks. This can cause a variation in the calorific value of the
In order to meet the system requirements established by EN 1717
mixture delivered to the appliance, with subsequent change in
in terms of pollution of drinking water, we recommend installing
its performance.
the IMMERGAS anti-backflow kit to be used upstream of the cold
water inlet connection of the boiler. We also recommend using a
1.8 HYDRAULIC CONNECTION. category 1, 2 or 3 heat transfer fluid (ex: water + glycol) in the boil-
In order not to void the condensation module war- er's primary circuit (CH circuit), as defined in standard EN 1717.
ranty, before making the boiler connections, carefully To preserve the duration of appliance efficiency fea-
clean the heating system (pipes, radiators, etc.) with tures, in the presence of water whose features can
special pickling or descaling products to remove lead to the deposit of lime scale, installation of the
any deposits that could compromise correct boiler “polyphosphate dispenser” kit is recommended .
operation.
3 bar safety valve.
A treatment of the heating and water system water is required, Safety valve (Part. 3 Fig. 7) discharge must always be conveyed
in compliance with the technical standards in force, in order to through a draining funnel. Consequently, in the event of valve

USER
protect the system and the appliance from deposits (e.g. scale), intervention, the discharged liquid will end up in the sewer system.
slurry or other hazardous deposits. In order not to void the heat
Condensate drain.
exchanger warranty, you are required to comply with what has
To drain the condensate produced by the appliance, it is necessary
been prescribed in (Par. 1.24).
to connect to the drainage system by means of acid condensate
Hydraulic connections must be made in a rational way using the resistant pipes, with an internal Ø of at least 13 mm. The system
couplings on the boiler template. connecting the appliance to the drainage system must be carried
out in such a way as to prevent occlusion and freezing of the liquid
contained in it. Before appliance ignition, ensure that the con-
densate can be correctly removed. After first ignition, check that

MAINTENANCE TECHNICIAN
the drain trap is filled with condensate (Para. 1.26). Also, comply
with national and local regulations on discharging waste waters.
In the event condensate is not discharged into the wastewater
drainage system, a condensate neutraliser must be installed to
ensure compliance with the parameters established by the legis-
lation in force.

13
1.9 ELECTRICAL CONNECTION. To protect from possible dispersions of DC voltage, it is necessary
The appliance has an IPX5D protection degree; electrical safety of to provide a type A differential safety device.
the appliance is achieved only when it is connected properly to an If the power cable is damaged, contact a qualified company (e.g.
efficient earthing system, as specified by current safety standards. the Authorised After-Sales Technical Assistance Service) for its
replacement to avoid a hazard.
ATTENTION:
INSTALLER

The power cable must be laid as shown (Fig. 7).


the manufacturer declines any respon-
If the network fuse on the P.C.B. needs replacing, this must also
sibility for damage or physical injury
be done by qualified personnel: use a 3.15 A fast fuse.
caused by failure to connect the boiler
For the main power supply to the appliance, never use adapters,
to an efficient earthing system or failure multiple sockets or extension leads.
to comply with the reference standards. Installation with system operating at direct low temperature.
• Open the control panel connections compartment (Fig. 8). The boiler can directly supply a low-temperature system by setting
the flow temperature adjustment range “t0” and “t1” (Par. 3.11).
To carry out electrical connections, all you have to do is open the In this situation it is good practice to insert a relevant safety kit
connections compartment as follows: (optional) made up from a thermostat (with adjustable tempera-
- Disassemble the cover (Fig. 54). ture). The thermostat must be positioned on the system flow pipe
- Disassemble the cover (b) as follows: at a distance of at least 2 metres from the boiler.
1. Loosen the screw (a).
2. Press the two hooks on the connections compartment
1.10 REMOTE CONTROLS AND ROOM CHRONO-
USER

cover.
THERMOSTATS (OPTIONAL).
3. Remove the cover (b) from the control panel (c).
The boiler is prepared for the application of room chrono-ther-
- At this point, it is possible to access the terminal board (d).
mostats or remote controls, which are available as optional kits
Also ensure that the electrical installation corresponds to maxi- (Fig. 9).
mum absorbed power specifications, as shown on the boiler data
nameplate. Boilers are supplied with a special “X” type power All Immergas chrono-thermostats are connected with 2 wires
cable without plug. only. Carefully read the user and assembly instructions contained
in the accessory kit.
ATTENTION:
ATTENTION:
the power supply cable must be connect-
MAINTENANCE TECHNICIAN

disconnect power to the appliance be-


ed to a 230V ±10% / 50Hz mains supply
fore any electrical connection.
respecting L-N polarity and earth con-
nection ; this network must also have
a multi-pole circuit breaker with class III
overvoltage category in compliance with
installation regulations.

1
3
d
a b
8 9

14
• On/Off Immergas digital chrono-thermostat. Comando Amico Remoto Remote Control V2 or On/Off
The chrono-thermostat allows: chrono-thermostat electrical connections (Optional). The op-
- set two room temperature values: one for day (comfort tem- erations described below must be performed after having removed
perature) and one for night (reduced temperature); the voltage from the appliance. Any thermostat or On/Off environ-
- set a weekly programme with four daily switch on and switch ment chrono-thermostat must be connected to clamps 44/40 and

INSTALLER
off times; 41 eliminating jumper X40 (Fig. 39). Make sure that the On/Off
- select the required operating mode from the various possible thermostat contact is “dry”, i.e. independent of the mains voltage,
alternatives: otherwise the P.C.B. would be damaged. Any Comando Amico
• manual mode (with adjustable temperature); Remoto remote control V2 must be connected to terminals 44/40
• automatic mode (with set programme); and 41, eliminating jumper X40 on the P.C.B. ( Fig. 39). The boiler
• forced automatic mode (momentarily changing the temperature can only be connected to one remote control.
of the automatic programme).
The chrono-thermostat is powered by two 1.5V LR 6 type alkaline If the Comando Amico Remoto remote control V2 or
batteries; any other On/Off chrono-thermostat is used arrange
two separate lines in compliance with current regu-
• Comando Amico Remoto Remote Control Device V2 (CARV2) lations regarding electrical systems. No boiler pipes
with climate chrono-thermostat function. must ever be used to earth the electric system or telephone
In addition to the functions described in the previous point, lines. Ensure elimination of this risk before making the boiler
the CARV2 panel enables the user to control all the important electrical connections.
information regarding operation of the appliance and the heating
system with the opportunity to easily intervene on the previously
set parameters, without having to go to where the appliance is 1.11 EXTERNAL TEMPERATURE PROBE (OPTIONAL).

USER
installed. The panel is provided with self-diagnosis to display The boiler is designed for the application of the external tempera-
any boiler functioning anomalies. The climate chrono-thermo- ture probe (Fig. 10), which is available as an optional kit. Refer to
stat incorporated into the remote panel enables the system flow the relative instruction sheet for positioning of the external probe.
temperature to be adjusted to the actual needs of the room being The probe can be connected directly to the boiler electrical
heated, in order to obtain the desired room temperature with system and allows the max. system flow temperature to be au-
extreme precision and therefore with evident saving in running tomatically decreased when the external temperature increases,
costs. The CARV2 is fed directly by the boiler by means of the in order to adjust the heat supplied to the system according to
same 2 wires used for the transmission of data between the boiler the change in external temperature. The external probe always
and device. operates when connected, regardless of the presence or type of

MAINTENANCE TECHNICIAN
room chrono-thermostat used and can work in combination with
Immergas chrono-thermostats. The correlation between system
flow temperature and external temperature is determined by the
position of the central heating selector switch on the boiler control
panel (or on the CARV2 control panel if connected to the boiler)
according to the curves shown in the diagram (Fig. 11). The elec-
tric connection of the external probe must be made on clamps 38
and 39 on the terminal board in the boiler control panel (Fig. 39).

EXTERNAL PROBE
Correction law of the flow temperature depending on the external temperature and
user adjustment of the central heating temperature.
45
Position of the central heating
temperature user adjustment
58

31

10 11

15
1.12 IMMERGAS FLUE SYSTEMS.
Immergas supplies various solutions separately from the boilers (A)
regarding the installation of air intake terminals and flue exhaust,
which are fundamental for boiler operation.

ATTENTION:
INSTALLER

the boiler must be installed exclusive-


ly with an original Immergas “Green
Range” inspectionable air intake system and
flue gas extraction system made of plastic,
(B)
with the exception of the C6 configuration, as 12
required by the regulations in force and by the
• Positioning the gaskets (black) for “green range” flue systems.
product’s approval. Position the gasket correctly (for bends and extensions) (Fig. 12):
This flue can be identified by an identification - gasket (A) with notches, to use for bends;
mark and special distinctive marking bearing - gasket (B) without notches, to use for extensions.
the note "only for condensation boilers". N.B.: if necessary, to ease the push-fitting, spread the elements
with commonly-used talc.
The plastic pipes cannot be installed outdoors, • Coupling extension pipes and concentric elbows.
for tracts longer than 40 cm, without suitable
USER

To install snap-fit extensions with other elements of the flue


protection from UV rays and other atmos- extraction elements assembly, follows: Fit the concentric pipe
pheric agents. or elbow with the male side (smooth) on the female side (with
lip seal) to the end stop on the previously installed element in
order to ensure sealing efficiency of the coupling.
• Resistance factors and equivalent lengths.
N.B.:if the exhaust terminal and/or extension concentric pipe
Each flue component has a Resistance Factor based on exper-
needs shortening, consider that the internal duct must always
imental tests and specified in the table below. The Resistance
protrude by 5 mm with respect to the external duct.
Factor for individual components is independent from the type
of boiler on which it is installed and has a dimensionless size. It N.B.: for safety purposes, do not obstruct the boiler intake/
MAINTENANCE TECHNICIAN

is however, conditioned by the temperature of the fluids that pass exhaust terminal, even temporarily.
through the pipe and therefore, varies according to applications The various parts of the flue system must be checked
for air intake or flue exhaust. Each single component has a resist- to ensure that they have been laid in such a way as
ance corresponding to a certain length in metres of pipe of the to prevent the coupled parts from detaching, in par-
same diameter; the so-called equivalent length, can be obtained ticular, the flue exhaust duct in the Ø80 separator kit
from the ratio between the relative Resistance Factors. configuration. Should the aforesaid condition not be
All boilers have an experimentally obtainable maximum Re- adequately guaranteed, it will be necessary to use the
sistance Factor equal to 100. special clamp ring nut clip kit.
The maximum Resistance Factor allowed corresponds to the
resistance encountered with the maximum allowed pipe length N.B.: when installing horizontal pipes, a minimum inclination of
for each type of Terminal Kit. This information allows calcula- 3% towards the boiler must be maintained, and a section clamp
tions to be made to verify the possibility of setting up various with plug must be installed every 3 metres.
flue configurations. • Installation inside the recessed frame. In this mode, install the
Note: to dimension the flue ducting using commercial compo- flue according to your needs using the appropriate pre-sections
nents, refer to the table of combustion parameters (Paragraph 4.2). in the frame to exit from its clearances.

16
1.13 TABLES OF RESISTANCE FACTORS AND EQUIVALENT LENGTHS “GREEN SERIES”.

Resistance Length
TYPE OF DUCT Resistance in m of concentric pipe
(R) Ø 80/125

INSTALLER
Concentric pipe 80/125 Ø m 1 2.1 1

Ø 80/125 90° concentric bend 3.0 1.4

Ø 80/125 45° concentric bend 2.1 1

Terminal complete with concentric horizontal intake-exhaust


2.8 1.3
Ø 80/125

Terminal complete with concentric vertical intake-exhaust


3.6 1.7
Ø 80/125

90° concentric bend Ø 80/125 with inspection 3.4 1.6

USER
Stub pipe with inspection Ø 80/125 3.4 1.6

MAINTENANCE TECHNICIAN

17
Length Length
Resistance Length Length
in metres of in metres of
TYPE OF DUCT Factor in metres in metres
concentric pipe Ø concentric pipe
(R) of a Ø 80 pipe of a Ø 60 pipe
60/100 Ø 80/125
INSTALLER

Concentric pipe Intake and Intake m 7.3


m1 Exhaust m 1.9 m 3.0
Ø 60/100 m 1 Exhaust 6.4 Exhaust m 5.3
Ø 60/100 90° concentric Intake and Intake m 9.4
m 1.3 Exhaust m 2.5 m 3.9
bend Exhaust 8.2 Exhaust m 6.8
Ø 60/100 45° concentric Intake and Intake m 7.3
m1 Exhaust m 1.9 m 3.0
bend Exhaust 6.4 Exhaust m 5.3
Terminal complete with con- Intake m 17.2
Intake and
centric horizontal intake-ex- m 2.3 Exhaust m 4.5 m 7.1
Exhaust 15 Exhaust m 12.5
haust Ø 60/100
Intake terminal - Intake m 11.5
Intake and
horizontal concentric exhaust m 1.5 Exhaust m 3.0 4.7 m
Exhaust 10 Exhaust m 8.3
Ø 60/100
Complete intake terminal - Intake m 18.7
Intake and
vertical concentric exhaust m 2.5 Exhaust m 4.9 m 7.7
Exhaust 16.3 Exhaust m 13.6
Ø 60/100
USER

Concentric vertical Intake m 10.3


Intake and
intake-exhaust terminal 1.4 m Exhaust m 2.7 m 4.3
Exhaust 9 Exhaust m 7.5
Ø 60/100

Intake 0.87 m 0.1 Intake m 1.0 m 0.4


Pipe Ø 80 m 1 Exhaust m 0.4
Exhaust 1.2 m 0.2 Exhaust m 1.0 m 0.5
Complete terminal
Intake 3 m 0.5 Intake m 3.4 Exhaust m 0.9 1.4 m
intake Ø 80 m 1

Intake terminal Ø 80 Intake 2.2 m 0.35 Intake m 2.5 m1


Exhaust m 0.6
MAINTENANCE TECHNICIAN

Exhaust terminal Ø 80 m 0.9


Exhaust 1.9 m 0.3 Exhaust m 1.6
Intake 1.9 m 0.3 Intake m 2.2 m 0.9
Ø 80 90° bend Exhaust m 0.8
Exhaust 2.6 m 0.4 Exhaust m 2.1 m 1.2

Intake 1.2 m 0.2 Intake m 1.4 m 0.5


Ø 80 45° bend Exhaust m 0.5
Exhaust 1.6 m 0.25 Exhaust m 1.3 0.7
Pipe Ø 60 m 1 Intake m 3.8
Exhaust 3.3 m 0.5 Exhaust m 1.0 m 1.5
for ducting Exhaust m 2.7
Ø 60 90° bend Intake m 4.0
for ducting Exhaust 3.5 m 0.55 Exhaust m 1.1 m 1.6
Exhaust m 2.9

Intake and Intake m 3.0


Reduction Ø 80/60 m 0.4 Exhaust m 0.8 m 1.2
Exhaust 2.6 Exhaust m 2.1
Intake m 14
Terminal complete with ver-
Exhaust 12.2 m 1.9 Exhaust m 3.7 m 5.8
tical exhaust Ø 60 for ducting
Exhaust m 10.1

18
1.14 OUTDOOR INSTALLATION IN PARTIALLY Engage the 90° Ø 80 bend with the male end (smooth) in the
PROTECTED AREA. female end (with lip seal) of the Ø 80 flange unit to the end stop.
Introduce the gasket, making it run along the bend. Fix it using
A partially protected area is one in which the appliance
the metal sheet plate and tighten by means of the clips present in
is not exposed to the direct action of the weather (rain,
the kit, making sure to block the 4 gasket flaps. Fit the male end
snow, hail, etc.).

INSTALLER
(smooth) of the exhaust pipe into the female end of the 90° Ø 80
bend, making sure that the relevant wall sealing plate is already
This type of installation is only possible fitted; this will ensure hold and joining of the elements making
when permitted by the laws in force in up the kit.
the appliance's country of destination. Max. length of exhaust pipe.
The exhaust pipe (both vertical or horizontal) can be extended to
If the appliance is installed in a place where the a max. length of 30 linear metres.
ambient temperature drops below -5 °C, use the op- Coupling of extension pipes.
tional antifreeze kit, checking the ambient operating To install push-fitting extensions with other elements of the
temperature range shown in the technical data table flue, proceed as follows: Fit the pipe or elbow with the male side
in this instruction booklet. (smooth) in the female side (with lip seal) to the end stop on the
previously installed element. This will ensure sealing efficiency
Configuration type B, open chamber and fan assisted of the coupling.
(B23 or B53). Configuration without cover kit in a partially protected location
Using the special cover kit one can achieve direct air intake (Fig. (type C boiler).
13) and flue exhaust in a single chimney or directly outside. In this

USER
By leaving the side plugs fitted it is possible to install the appliance
configuration it is possible to install the boiler in a partially pro- externally without the cover kit. Installation takes place using the
tected place. In this configuration the boiler is classified as type B. Ø60/100 and Ø 80/125 concentric intake/ exhaust kits. Refer to
With this configuration: the paragraph on indoor installation. In this configuration the
- air intake takes place directly from the environment in which top cover kit guarantees additional protection for the boiler. It is
the appliance is installed (external); recommended but not compulsory. The Ø 80/80 separating device
- the flue exhaust must be connected to its own single chimney cannot be used in this configuration (coupled with the cover kit).
(B23) or ducted directly outside via a vertical terminal for direct
exhaust (B53) or via an Immergas ducting system (B53).
The technical regulations in force must be respected.

MAINTENANCE TECHNICIAN
Cover kit assembly (Fig. 14).
Remove the two plugs from the lateral intake holes. Now cover
the left intake hole using the relevant plate, fixing it onto the right
side using the 2 previously-removed screws. Install the Ø 80 outlet
flange on the central hole of the boiler, taking care to insert the
gasket supplied with the kit and tighten by means of the screws
provided. Install the upper cover, fixing it using the 4 screws
present in the kit, positioning the relevant gaskets.

ATTENTION:
the diaphragm in the Victrix Tera 28
model in the kit, must necessarily be
inserted in the Ø 80 flange, ensuring it stops.

19
INSTALLER

13
USER
MAINTENANCE TECHNICIAN

The cover kit includes:


N° 1 Thermoformed cover
N°1 Gasket clamping plate
N°1 Gasket
N°1 Gasket tightening clip
N°1 Intake hole covering plate
N°1 Diaphragm (for Victrix Tera 28 only)

The terminal kit includes:


N° 1 Gasket
N° 1 Exhaust flange Ø 80
N° 1 Ø 80 90° bend
N° 1 Exhaust pipe Ø 80
N° 1 Wall sealing plate

14 15

20
1.15 INTERNAL INSTALLATION USING A RECESSED self-threading screws. Fit the male side (smooth) to the bends in
FRAME WITH DIRECT AIR INTAKE. the female side of the flanges.
• Configuration type B, open chamber and fan assisted. The intake bend must face the rear side of the boiler.
Using a kit separator, one can achieve direct air intake (Fig.  17)
and flue exhaust in a single chimney or directly outside. In this Fit the exhaust pipe with the male side (smooth) to the female
side of the bend up to the end stop, making sure that the internal

INSTALLER
configuration the boiler is classified as type B23.
wall sealing plate has been fitted and connecting the required flue
With this configuration: according to personal requirements.
- air intake takes place directly from the environment in which
the appliance is installed (the recessed frame is ventilated), and Max. length of exhaust pipe.
only functions in permanently ventilated rooms; The exhaust pipe (both vertical or horizontal) can be extended to
a max. length of 30 linear metres.
- the flue exhaust must be connected to its own individual chimney
or channelled directly into the external atmosphere.
The technical regulations in force must be respected. 1.16 CONCENTRIC HORIZONTAL KIT INSTALLATION.
Separator kit installation (Fig. 16) • Type C configuration, sealed chamber and fan assisted.
Install the discharge flange on the central hole of the boiler, posi- The position of the terminal (in terms of distances from openings,
tioning the relative gasket with the circular projections downwards overlooking buildings, floor, etc.) must be in compliance with the
in contact with the boiler flange, and tighten using the hex screws regulations in force.
with flat tip contained in the kit. Remove the flat flange present This terminal is connected directly to the outside of the building
in the lateral hole with respect to the central one (according to for air intake and flue exhaust. The horizontal kit can be installed
needs) and replace it with the intake flange, positioning its gas- with the rear, right side, left side or front outlet. For installation

USER
ket already present in the boiler and tighten using the supplied with frontal outlet, one must use the fixing plate and a concentric
bend coupling in order to ensure sufficient space to carry out the
tests required by law upon commissioning.
• External grid.
Both the Ø 60/100 and Ø 80/125 intake/exhaust terminal, if prop-
erly installed, is pleasant to look at on the outside of the building.
Make sure that the external silicone wall sealing plate is properly
inserted in the wall.

MAINTENANCE TECHNICIAN
ATTENTION:
for correct functioning of the system
the terminal with grid must be in-
stalled correctly ensuring that, the "high"
indication present on the terminal is respect-
ed on installation.

16

17

21
Horizontal intake-exhaust kit Ø 60/100. Kit assembly (Fig. 18). • Extensions for Ø 80/125 horizontal kit (Fig. 21).
Install the bend with flange (2) on the central hole of the boiler, The kit with this configuration can be extended up to a max.
positioning gasket (1) with the circular projections downwards in length of 32 m, including the terminal with grid and excluding the
contact with the boiler flange, and tighten using the screws present concentric bend leaving the boiler. If additional components are
in the kit. Fit the Ø 60/100 (3) concentric terminal pipe with the assembled, the length equivalent to the maximum allowed must be
INSTALLER

male side (smooth) to the female side of the bend (2) up to the subtracted. In this case the special extensions must be requested.
end stop; making sure that the internal and external wall sealing
plate have been fitted, this will ensure sealing and joining of the
elements making up the kit. 1.17 CONCENTRIC VERTICAL KIT INSTALLATION.
• Type C configuration, sealed chamber and fan assisted.
• Extensions for Ø 60/100 horizontal kit (Fig. 19). Concentric vertical intake and exhaust kit. This vertical terminal
The kit with this configuration can be extended up to a max. is connected directly to the outside of the building for air intake
horizontal length of 12.9 m including the terminal with grid and and flue exhaust.
excluding the concentric bend leaving the boiler. This configu- N.B.: the vertical kit with aluminium tile enables installation on
ration corresponds to a resistance factor of 100. In this case the terraces and roofs with a maximum slope of 45% (approx 25°) and
special extensions must be requested. the height between the terminal cap and half-shell (374 mm for
Immergas also provides a Ø 60/100 simplified terminal, which in Ø 60/100 and 260 mm for Ø 80/125) must always be observed.
combination with its extension kits allows you to reach a maxi-
mum extension of 11.9 metres.

Horizontal intake-exhaust kit Ø 80/125. Kit assembly (Fig. 20).


USER

To install the kit Ø 80/125 one must use the flanged adapter kit
in order to install the flue system Ø 80/125. Install the flanged
adaptor (2) on the central hole of the boiler, positioning gasket
(1) with the circular projections downwards in contact with the
boiler flange, and tighten using the screws contained in the kit.
Engage the bend (3) with the male side (smooth) to the end stop
on the adapter (1). Fit the Ø 80/125 (5) concentric terminal pipe
with the male side (smooth) to the female side of the bend (4)
(with lip seals) up to the end stop; making sure that the internal
(6) and external wall sealing plate (7) have been fitted, this will
MAINTENANCE TECHNICIAN

ensure sealing and joining of the elements making up the kit.

C13 C13
Max. 12900 mm
2
1 3
4
5
The kit includes:
N° 1 - Gasket (1)
N° 1 - Concentric bend Ø 60/100 (2) Max. 12790 mm
N° 1 - Int./exhaust concentric terminal Ø 60/100 (3)
N° 1 - Internal wall sealing plate (4)
N° 1 - External wall sealing plate (5) 18 19

C13 C13

3
Max. 32000 mm
2 4
5
6
1
The adaptor kit includes: The Kit Ø 80/125 includes:
N° 1 - Gasket (1) N° 1 - Ø 80/125 87° concentric bend (3)
N° 1 - Adapter N° 1 - Int./exhaust concentric
Ø 80/125 (2) terminal Ø 80/125 (4) Max. 31956 mm
N° 1 - Internal wall sealing plate (5)
N° 1 - External wall sealing plate (6)
The remaining kit components must
not be used
20 21

22
Vertical kit with aluminium tile Ø 60/100. Kit assembly Vertical kit with aluminium tile Ø 80/125. Kit assembly
(Fig. 22). (Fig. 24).
Install the concentric flange (2) on the central hole of the boiler, To install the kit Ø 80/125 one must use the flanged adapter kit
positioning gasket (1) with the circular projections downwards in order to install the flue system Ø 80/125. Install the flanged
in contact with the boiler flange, and tighten using the screws adaptor (2) on the central hole of the boiler, positioning gasket

INSTALLER
contained in the kit. (1) with the circular projections downwards in contact with the
Installation of the fake aluminium tile: replace the tiles with the boiler flange, and tighten using the screws contained in the kit.
aluminium sheet (4), shaping it to ensure that rainwater runs off. Installation of the fake aluminium tile: replace the tiles with the
Position the fixed half-shell (6) on the aluminium tile and insert aluminium sheet (4), shaping it to ensure that rainwater runs off.
the intake-exhaust pipe (5). Fit the Ø 60/100 concentric terminal Position the fixed half-shell (5) on the aluminium tile and insert
pipe with the male side (5) (smooth) into the flange (2) up to the the intake-exhaust pipe (7). Fit the Ø 80/125 concentric terminal
end stop; making sure that the wall sealing plate has been fitted pipe with the male end (smooth) to the female end of the adapter
(3), this will ensure sealing and joining of the elements making (1) (with lip gasket) up to the stop; making sure that the wall seal-
up the kit. ing plate (3) has been fitted, this will ensure sealing and joining
of the elements making up the kit.
N.B.: when the boiler is installed in areas where very rigid temper-
atures can be reached, a special antifreeze kit is available that can be • Extensions for vertical kit Ø 80/125 (Fig. 25).
installed as an alternative to the standard kit. The kit with this configuration can be extended up to a max. length
of 32 m including the terminal. If additional components are
• Extensions for vertical kit Ø 60/100 (Fig. 23). assembled, the length equivalent to the maximum allowed must
The kit with this configuration can be extended to a max. straight be subtracted. In this case specific extensions must be requested.
vertical length of 14.4 m, including the terminal. This configura-

USER
tion corresponds to a resistance factor of 100. In this case specific
extensions must be requested.

C33 C33

The Kit includes:


N° 1 - Gasket (1)
5 N° 1 - Female concentric flange (2)
Max. 14400 mm)

7 N° 1 - Wall sealing plate (3)

MAINTENANCE TECHNICIAN
4 6
N° 1 - Aluminium tile (4)

Max. 4
N° 1 - Int./exhaust concentric pipe
Ø 60/100 (5)

5
N° 1 - Fixed half-shell (6)

%
N° 1 - Mobile half-shell (7)

1
22 23

C33 C33

The adaptor kit includes:


7 N° 1 - Gasket (1)
N° 1 - Adapter
6 Ø 80/125 (2)
Max. 32000 mm

5 The Kit Ø 80/125 includes:


N° 1 - Wall sealing plate (3)
Max.

4 N° 1 - Aluminium tile (4)


45

N° 1 - Fixed half-shell (5)


%

N° 1 - Mobile half-shell (6)


N° 1 - No.80/125 - Int./exhaust
3 concentric pipe (7)
The remaining kit components
2 must not be used

1
24 25

23
1.18 SEPARATOR KIT INSTALLATION. • Installation clearances (Fig. 27).
• Type C configuration, sealed chamber and fan assisted. The minimum installation clearance measurements of the Ø 80/80
Separator kit Ø 80/80. separator terminal kit have been stated in some limit conditions.
This kit allows air to come in from outside the building and the
• Extensions for separator kit Ø 80/80.
exhaust to exit from the chimney, flue or intubated duct through
The maximum vertical straight length (without bends) that can
INSTALLER

divided flue exhaust and air intake pipes. Combustion products


be used for Ø 80 intake and exhaust pipes is 41 metres, regardless
are expelled from pipe (S) (strictly in plastic, so as to resist acid
from whether they are used for intake or exhaust. The maximum
condensate). Air is taken in through duct (A) for combustion
horizontal straight length (with bend in suction and in exhaust)
(this is also in plastic). The intake pipe (A) can be installed either
that can be used for Ø 80 intake and exhaust pipes is 36 metres,
on the right or left hand side of the central exhaust pipe (S). Both
regardless from whether they are used for intake or exhaust. Please
ducts can be routed in any direction.
note the type of installation C43 must be done with a natural
• Assembly of separator kit Ø 80/80 (Fig. 26). draught flue.
Install flange (4) on the central hole of the boiler, positioning
N.B.: to favour the removal of possible condensate forming in the
gasket (1) with the circular projections downwards in contact
exhaust pipe, tilt the pipes towards the boiler with a minimum
with the boiler flange, and tighten using the hex screws with flat
slope of 1.5% (Fig. 28).
tip contained in the kit. Remove the flat flange present in the lat-
eral hole with respect to the central one (according to needs) and
replace it with the flange (3), positioning the gasket (2) already
present in the boiler and tighten using the supplied self-threading
screws. Fit the male side (smooth) to the bends (5) in the female
side of the flanges (3 and 4). Fit the intake terminal (6) with the
USER

male side (smooth) in the female side of the bend (5) up to the
end stop, ensuring that the internal and external wall sealing plates
are fitted. Fit the exhaust pipe (9) with the male end (smooth) to
the female end of the bend (5) up to the end stop; making sure
that the internal wall sealing plate has been fitted, this will ensure
sealing and joining of the elements making up the kit.

C53* - C83 C43


5 5 6
7
MAINTENANCE TECHNICIAN

8
7 S
9

4 A
3
1 2
The kit includes: N° 2 - Ø 80 90° bend (5)
N° 1 - Exhaust gasket (1) N° 1 - Intake terminal Ø 80 (6)
N° 1 - Flange gasket (2) N° 2 - Internal wall sealing plates (7)
N° 1 - Female intake flange (3) N° 1 - External wall sealing plate (8)
N° 1 - Female exhaust flange (4) N° 1 - Exhaust pipe Ø 80 (9)
* to complete C53 configuration, also provide for a “green range” roof discharge terminal.
The configuration on walls opposite the building is not allowed.
26 27

C83

80 mm

Minimum gradient 1.5 %

28

24
1.19 ADAPTOR C9 KIT INSTALLATION. Kit Assembly.
This kit allows an Immergas boiler to be installed in "C93" config- - Mount the components of kit "C9" on the door (A) of the ducting
uration, with combustion air intake directly from the shaft where system (Fig. 30).
the flue gas exhaust is, obtained by means of a ducting system. - (Version Ø 125 only) mount the flanged adaptor (11) interposing
the concentric gasket (10) on the boiler, fitting it with the screws
System composition.

INSTALLER
(12).
The system must be combined with the following components
- Mount the ducting system as described in the relative instruc-
(sold separately) to be functional and complete:
tions sheet.
- kit C93 Ø 100 or Ø125 version;
- Calculate the distances between the boiler drain and the bend
- ducting kit Ø60 and Ø80 rigid and Ø50 and Ø80 flexible;
of the ducting system.
- flue exhaust kit Ø 60/100 or Ø 80/125 configured according to
- Prepare the boiler flue system, making sure that the internal pipe
the installation and type of boiler.
of the concentric kit is fitted up to the end stop in the ducting
system curve (Quota "X" Fig. 31), whereas the external pipe must
reach the end stop of the adapter (1).
N.B.: to encourage the removal of possible condensate forming
in the exhaust pipe, tilt the pipes towards the boiler with a min-
imum slope of 1.5%.
- Mount the cover (A) complete with adaptor (1) and caps (6) on
the wall and assemble the flue system to the ducting system.
N.B.: (version Ø 125 only) before assembly check the gaskets are
in the right position. In the event component lubrication (already

USER
A A
carried out by the manufacturer) is not sufficient, remove the
B C
residual lubricant using a dry cloth, then to ease fitting coat the
parts with common or industrial talc.
Ducting
Ø 60 Rigid and Once all components have been assembled properly, the exhaust
Ø 50 Flexible SHAFT SHAFT fumes will be expelled via the ducting system; the combustion
(A) mm (B) mm (C) mm air for normal boiler operation will be aspirated directly by the
66 106 126 shaft (Fig. 31).
Ducting

MAINTENANCE TECHNICIAN
Ø 80 Rigid SHAFT SHAFT
(A) mm (B) mm (C) mm
86 126 146

Ducting
Ø 80 Flexible SHAFT SHAFT
(A) mm (B) mm (C) mm
90 130 150
29

Installation drawings key:


Kit composition:
Unique identification of the component
Ref. Qty Description 1 in the kit
1 1 Door adaptor Ø 100 or Ø 125 Identification of the component not
2 1 Door gasket made of neoprene A supplied in this kit
3 4 Screws 4.2 x 9 AF 2
1
4 1 Hex headed screw M6 x 20 3
5 1 Flat nylon washer M6
6 2 Door hole closure metal-sheet plate plug
7 1 Plug gasket made of neoprene A
8 1 Toothed washer M6 12
9 1 Nut M6 3
10 1 (kit 80/125) Concentric gasket Ø 60-100
8 9
11 1 (kit 80/125) Flanged adapter Ø 80-125 3 6
12 4 (kit 80/125) Hex headed screws M4 x 16 slotted
12 7
- 1 (kit 80/125) Bag of lubricating talc 6
5
4
Supplied separately: 11
10
Ref. Qty Description
A 1 Ducting kit door
30

25
Technical data.
- The dimensions of the shafts must ensure a minimum gap be-
tween the outer wall of the smoke duct and the inner wall of the
shaft: 30 mm for circular section shafts and 20 mm in the event
of a square section shaft (Fig. 29).
INSTALLER

- Maximum 2 changes of direction are allowed on the vertical


section of the flue system with a maximum clearance angle of
30° with respect to the vertical.
- The maximum vertical extension using a Ø 60 ducting system is
13 m, the maximum extension includes 1 bend Ø 60/10 at 90°,
1 m of horizontal pipe 60/100, 1 90° ducted bend Ø 60 and the
roof terminal for ducting.
- To determine the C93 flue system in configurations other than
that described (Fig. 31) one must consider that 1 metre of ducted
pipe according to the indications described has a resistance factor
equal to 4.9.
- The maximum vertical extension using a Ø 80 ducting system
is 28 m, the maximum extension includes 1 adapter 60/100 to
80/125, 1 87° bend Ø 80/125, 1 m of horizontal pipe 80/125, 1
90° ducted bend Ø 80 and the roof terminal for ducting.
- To determine the C93 flue system in configurations other than
USER

that described (Fig. 31) one must consider the following head
losses:
- 1 m of concentric pipe Ø 80/125 = 1 m of ducted pipe;
- 1 87° bend = 1.4 m of ducted pipe;
Consequently one must subtract the equivalent length of the part
added to the 28 m available.
MAINTENANCE TECHNICIAN

C93

31

26
1.20 DUCTING OF FLUES OR TECHNICAL SLOTS. - The maximum length specified by the manufacturer must be
Ducting is an operation through which by the introduction respected; in this regard:
of one or more relevant pipes, a system is realised for the - The max. possible length of the Ø 60 flexible ducting vertical
evacuation of the combustion products of a gas appliance section is equal to 22 m. This length is obtained considering the
made up from the coupling of an existing or new ducting pipe complete Ø 80 exhaust terminal, 1m of Ø 80 pipe in exhaust,

INSTALLER
with a chimney, flue or technical slot (also in new buildings) two 90° Ø 80 bends at boiler outlet.
(Fig. 32). Ducting requires the use of ducts declared to be suitable - The max. possible length of the Ø 80 flexible ducting vertical
for the purpose by the manufacturer, following the (installation section is equal to 30 m. This length is obtained considering the
and user) instructions, provided by the manufacturer and the Ø80 complete exhaust terminal, 1m of Ø 80 pipe in exhaust, two
requirements of the standards in force. 90° Ø 80 bends at boiler outlet for connecting to the ducting
Immergas ducting system. system and two direction changes of the flexible hose inside
The Ø 60 rigid, Ø 80 flexible and Ø80 rigid “Green Range” ducting the chimney/technical slot.
systems must only be used for domestic use and with Immergas - The max. possible length of the Ø 80 flexible ducting vertical
condensing boilers. section is equal to 30 m. This length is obtained considering the
In any case, ducting operations must respect the provisions complete Ø 80 exhaust terminal, 1m of Ø 80 pipe in exhaust,
contained in the standard and in current technical regulations; two 90° Ø 80 bends at boiler outlet.
in particular, the declaration of conformity must be compiled You can also install an additional Ø50 flexible ducting system
at the end of work and on commissioning of the ducted system. the specifications of which are found on the relevant instructions
The instructions in the project or technical report must likewise sheet inside the kit.
be followed, in cases provided for by the standard and current
technical regulations. To guarantee reliability and operation over

USER
time of the ducting system, make sure: 1.21 CONFIGURATION TYPE B, OPEN CHAMBER AND
- it is used in average atmospheric and environmental conditions, FAN ASSISTED FOR INDOORS.
according to current regulations (absence of flue gas, dusts or The appliance can be installed inside buildings in B23 or B53 mode;
gases that can alter the normal thermophysical or chemical con- in this case, all technical rules and national and local regulations
ditions; existence of temperatures coming within the standard in force, must be complied with.
range of daily variation, etc.). For installation the cover kit must be used, referred to in (Par. 1.14).
- Installation and maintenance must be performed according to 1.22 FLUE EXHAUST TO FLUE/CHIMNEY.
the indications supplied by the manufacturer included with the Flue exhaust does not necessarily have to be connected to a branched
“green range” ducting system chosen and in compliance with

MAINTENANCE TECHNICIAN
type traditional flue for type B appliances with natural draught (CCR).
the regulations in force. The flue exhaust, for boiler clots installed in C configuration, can
be connected to a special LAS type multiple flue. For B23 con-
figurations, exhaust is only allowed into individual chimney or
directly into the external atmosphere via a relevant terminal, unless
otherwise provided for by local regulations in force. The multiple
flues and the combined flues must also only be connected to type C
appliances of the same type (condensation), having nominal heat
inputs that do not differ by more than 30% less with respect to the
maximum that can be attached and powered by the same fuel. The
C53 thermo-fluid dynamic features (flue flow rate, % of carbon dioxide,
% humidity etc.) of the appliances attached to the same multiple
flues or combined flues, must not differ by more than 10% with
respect to the average boiler attached. Multiple and combine flues
must be specially designed according to the calculation method
and requirements of the standards, by professionally qualified
technical personnel. Chimney or flue sections for connection of
the flue exhaust pipe must comply with requisites of technical
standards in force. It is possible to replace a type C conventional
device with one provided with condensation only, if the derogation
conditions established by the regulations in force have been verified.

32

27
1.23 FLUES, CHIMNEYS, CHIMNEY POTS AND
1.24 WATER TREATMENT SYSTEM FILLING.
TERMINALS.
As already mentioned in the previous paragraphs, a
The flues, chimneys and chimney caps for the evacuation of com-
treatment of the thermal and domestic system water
bustion products must be in compliance with applicable standards.
is required, in compliance with the local standards
Chimneys and roof-installed exhaust terminals must comply with
in force.
INSTALLER

the outlet height and with the distance from technical volumes
set forth by the technical standards in force. The parameters that influence the duration and proper oper-
ation of the heat exchanger are the water's PH, total hardness,
Positioning the wall flue exhaust terminals. conductivity, and oxygen, together with the system's processing
The exhaust terminals must: residues (any welding residues), any oil present and corrosion
- be installed on external perimeter walls of the building; products that can, in turn, cause damage to the heat exchanger.
- be positioned according to the minimum distances specified in
To prevent damage, it is recommended to:
current technical standards.
- before installation on new systems as well as old ones, clean
Combustion products exhaust of natural draught or fan assisted the system with clean water to eliminate solid residues con-
appliances in open-top closed environments. tained therein.
In spaces closed on all sides with open tops (ventilation pits, - Clean the system with a chemical treatment:
courtyards etc.), direct combustion product exhaust is allowed for - Clean the new system with a suitable cleaning device (for
natural draught or fan assisted gas appliances with a heat input example Sentinel X300, Fernox Cleaner F3 or Jenaqua
range from 4 to 35 kW, provided the conditions as per the current 300) combined with thorough washing.
technical standards are respected.
- Clean the old system with a suitable cleaning device (for
example Sentinel X400 or X800, Fernox Cleaner F3 or
USER

Jenaqua 400) combined with thorough washing.


- Check the maximum total hardness and quantity of filling
water referring to the graphics (Fig. 33); if the contents and
hardness of the water are below the indicated curve, no spe-
cific treatment is required; otherwise, to limit the content of
calcium carbonate, you must provide for water-filling treat-
ment.
- Should you be required to provide for water treatment, this
should be carried out by completely desalinating the filling
MAINTENANCE TECHNICIAN

water. As opposed to the complete softening process, desal-


inating the water completely not only removes hardening
agents (Ca, Mg), but also eliminates all other minerals to
reduce water-filling conductivity up to 10 microsiemens/
cm. Given its low conductivity, desalinated water does not
only prevent the formation of lime scale, but also serves as
protection against corrosion.
- Insert a suitable inhibitor / passivator (for example Sentinel
X100, Fernox Protector F1, or Jenaqua 100); if required, also
insert appropriate antifreeze (such as for example Sentinel
X500, Fernox Alphi 11 or Jenaqua 500).
- Check electrical conduction of the water, which should be
higher than 2000 µs/cm in the case of treated water and lower
than 600 µs/cm in the case of non-treated water.
System water litres

- To prevent corrosion, the water system's pH should be be-


tween 7.5 and 9.5, measured at a temperature between 20-
25°C.
- Check the maximum content of chlorides, which should be
less than 250 mg/l.
N.B.: for quantities and methods of use of water-treatment
Water total hardness °F products, refer to the instructions provided by their man-
ufacturer.
N.B.: the graph refers to the entire life cycle of
the system. Therefore, also consider scheduled
and unscheduled maintenance, which involves
emptying and filling the said system.

33

28
1.25 SYSTEM FILLING. 1.29 CIRCULATION PUMP.
Once the boiler is connected, proceed with system filling via the The boilers are supplied with a variable speed circulator pump.
filling cock (Part. 26 Fig. 36). Filling is performed at low speed to In the central heating mode, the following operating modes are
ensure release of air bubbles in the water via the boiler and central available and can be selected from the “P.C.B. programming”
heating system vents. menu.

INSTALLER
The boiler has a built-in automatic vent valve on the pump. Check if the N.B.: the ∆T(A3) can be controlled compatibly with the charac-
cap is loose. Then open the radiator vent valves. teristics of the central heating system and of the boiler.
Close radiator vent valves when only water escapes from them. •Proportional head (A3 = 0): the circulator speed varies according
Close the filling valve when the boiler pressure gauge indicates to the power emitted by the burner, the greater the power the
approx. 1.2 bar. greater the speed.
N.B.: during these operations, enable the automatic vent functions • ∆T Constant (A3 = 5 - 25 K): the pump speed varies to maintain
on the boiler (active on first ignition). the ∆T constant between the system flow and return according
to set value K (A3 = 15 Default).
1.26 FILLING THE CONDENSATE DRAIN TRAP. • Fixed: by setting parameters “A1” and “A2” at the same value
On first lighting of the boiler, flue gas may come out the conden- (5/6 - 9), the pump operates at constant speed. For the boiler
sate drain; after a few minutes’ operation check that this no longer to work properly, it is not allowed to drop below the minimum
occurs. This means that the drain trap is filled with condensate to value indicated above.
the correct level preventing the passage of flue gas. In domestic hot water mode, the circulator pump always runs at
full speed.
1.27 GAS SYSTEM START-UP.

USER
To start up the system, refer to the technical standard in force. Pump release. If, after a prolonged period of inactivity, the circu-
lation pump is blocked, turn the motor shaft using a screwdriver.
In particular, for new gas systems: Take great care during this operation to avoid damage to the motor.
- open windows and doors;
Bypass Regulation (Part. 23 Fig.36). The boiler leaves the factory
- avoid presence of sparks or naked flames; with the bypass open.
- bleed all air from the pipelines; If necessary, the bypass can be regulated to system requirements
- check that the internal system is properly sealed according to from minimum (bypass closed) to maximum (bypass open). Ad-
the specifications set forth by technical regulations in force. just using a flat-head screwdriver. Turning clockwise opens the
bypass and anticlockwise closes it.

MAINTENANCE TECHNICIAN
1.28 BOILER START-UP (IGNITION). N.B.: the bypass ensures minimum circulation of the water in the
To commission the boiler (the operations listed below must only be boiler and correct operation of the appliance if the systems are
performed by qualified personnel and in the presence of staff only): divided into more than one zone.
- check that the internal system is properly sealed according to
the regulations in force;
- ensure that the type of gas used corresponds to the boiler settings
(the type of gas appears on the display on first electrical power
supply, or by checking the relative parameter “G”);
- check connection to a 230V-50Hz power mains, correct L-N
polarity and the earthing connection;
- check that there are no external factors that may cause the
formation of fuel pockets;
- switch the boiler on and ensure correct ignition;
- make sure that the gas flow rate and relevant pressure values
comply with those given in the manual (Par. 4.1 - 4.4);
- ensure that the safety device intervenes in the event of gas supply
failure and check the relative intervention time;
- check the intervention of the main switch located upstream from
the boiler and in the boiler;
- check that the intake and/or exhaust terminals (if fitted) are not
blocked.
- Carry out the flue test.
The system must not be started up if even only one of the checks
should be negative.

29
Head available to the system.

Victrix Tera 28 1
INSTALLER

Speed 9

Circulator pump absorbed power (W)


A
Head (kPa)

Speed 9 D
C

Spe
ed B
6
USER

Flow rate (l/h)


A+B = Head available with bypass closed
B = Head available with bypass open
C+D = Power absorbed by the pump with by-pass open (dotted area)
D = Power absorbed by the pump with bypass closed (dotted area) 34
MAINTENANCE TECHNICIAN

Victrix Tera 32 1

Speed
9
A

Circulator pump absorbed power (W)


Head (kPa)

Speed
9

Spe B
ed
5

Flow rate (l/h)


A+B = Head available with bypass closed
B = Head available with bypass open
C+D = Power absorbed by the pump with by-pass open (dotted area)
D = Power absorbed by the pump with bypass closed (dotted area) 35

30
Victrix Tera 38 1

Speed
A 9

INSTALLER
C

Circulator pump absorbed power (W)


Head (kPa)

Speed
9

D
B
Spe
ed
5

USER
Flow rate (l/h)
A+B = Head available with bypass closed
B = Head available with bypass open
C+D = Power absorbed by the pump with by-pass open (dotted area)
D = Power absorbed by the pump with bypass closed (dotted area) 36

1.30 CIRCULATION PUMP If the pump detects an alarm, the LED switches from green to red;

MAINTENANCE TECHNICIAN
WITH NEW WAVE 3 ELECTRONICS. this can mean one of the following failures:
The boilers are supplied with a variable speed circulator pump. - low supply voltage;
In the central heating mode, the following operating modes are - rotor seized;
available and can be selected from the “P.C.B. programming” - electrical error.
menu. To see in detail the meaning of the red LED, please refer to the rele-
vant paragraph (Possible problems and their causes).
N.B.: the ∆T(A3) can be controlled compatibly with the charac-
teristics of the central heating system and of the boiler. The LED, in addition to being green or red, can also re-
main off.
•Proportional head (A3 = 0): the circulator speed varies according It is normal for the LED to be off when the pump is not
to the power emitted by the burner, the greater the power the powered, whereas with the pump powered, the LED
greater the speed.
must be lit: if switched off, it means there is a fault.
• ∆T Constant (A3 = 5 - 25 K): the pump speed varies to maintain
the ∆T constant between the system flow and return according Pump release. If, after a prolonged period of inactivity, the circu-
to set value K (A3 = 15 Default). lation pump is blocked, turn the motor shaft using a screwdriver.
• Fixed: by setting parameters “A1” and “A2” at the same value Take great care during this operation to avoid damage to the motor.
(5/6 - 9), the pump operates at constant speed. For the boiler
Bypass Regulation (Part. 23 Fig.36). The boiler leaves the factory
to work properly, it is not allowed to drop below the minimum
with the bypass open.
value indicated above.
In domestic hot water mode, the circulator pump always runs at If necessary, the bypass can be regulated to system requirements
full speed. from minimum (bypass closed) to maximum (bypass open). Ad-
just using a flat-head screwdriver. Turning clockwise opens the
Pump LED. bypass and anticlockwise closes it.
The LED flashes green when the pump is powered and the pwm N.B.: the bypass ensures minimum circulation of the water in the
control signal is connected. boiler and correct operation of the appliance if the systems are
The LED lights up steady green when the pump is pow- divided into more than one zone.
ered and the signal cable disconnected. In these condi-
tions the pump works at maximum and without control.

31
1.31 BOILER COMPONENTS.

37
INSTALLER
USER
MAINTENANCE TECHNICIAN

Key: 9 - Gas nozzle 18 - Return probe


1 - System expansion vessel 10 - Gas valve 19 - System pressure switch
2 - Burner 11 - DHW heat exchanger 20 - Air vent valve
3 - Ignition/detection electrode 12 - System draining valve 21 - Boiler pump
4 - Air intake pipe 13 - DHW probe 22 - 3 bar safety valve
5 - Flow probe 14 - Sample points (air A) - (flue gases F) 23 - Bypass
6 - Fan 15 - Flue probe 24 - 3-way valve (motorised)
7 - Condensate drain trap 16 - Condensation module 25 - Valve drain fitting signal
8 - D.H.W. flow switch 17 - Venturi 26 - System filling valve

1.32 KITS AVAILABLE ON REQUEST. N.B.: this is a type of chemical conditioning treatment for do-
• System shut-off valve kits with or without inspection filter mestic hot water, if provided for by current regulations.
(on request). The boiler is designed for installation of system • Cover kit (on request). If installed outdoors in a partially pro-
interception cocks to be placed on flow and return pipes of the tected place with direct air intake, it is compulsory to mount the
connection assembly. This kit is particularly useful for mainte- appropriate top protective cover for the correct functioning of
nance as it allows the boiler to be drained separately without the boiler and to protect it from adverse weather conditions.
having to empty the entire system. Moreover, the version with
• Cycloidal filter kit (on request). The magnetic cycloidal filter is
filter preserves the operating features of the boiler thanks to its
able to detect the ferrous residues present in the system's water.
inspectionable filter.
Thanks to the two cocks in the kit, it facilitates maintenance by
• Polyphosphate dispenser kit (on request). The polyphosphate cleaning the filter without having to empty the circuit.
dispenser reduces the formation of lime-scale and preserves the
The above-mentioned kits are supplied complete with instructions
original heat exchange and domestic hot water production condi-
for assembly and use.
tions. The boiler is prepared for application of the polyphosphate
dispenser kit.

32
2 INSTRUCTIONS

MAINTENANCE.
FOR USE AND
• Do not open or tamper with the ap-
pliance.
2.1 GENERAL WARNINGS.
• Do not take apart or tamper with the
ATTENTION:

INSTALLER
intake and exhaust pipes.
• Never expose the wall-mounted boiler • Only use the user interface devices listed in
to direct vapours from a cooking sur- this section of the booklet.
face.
• Do not climb on the appliance, do not use
• The device can be used by children at least 8 the appliance as a supporting surface.
years old as well as by persons with reduced
physical, sensory or mental capabilities, or ATTENTION:
lack of experience or required knowledge, The use of components involving use of
provided that they are under surveillance, electrical power requires some funda-
or after they have been instructed relating mental rules to be observed such as:
to the safe use and have understood the po- - do not touch the appliance with wet or moist
tential dangers. Children must not play with parts of the body; do not touch it when bare-
the appliance. Cleaning and maintenance foot;

USER
destined to be performed by the user can not
- never pull electrical cables or leave the ap-
be carried out by unsupervised children.
pliance exposed to atmospheric agents (rain,
• For safety purposes, check that the air in- sunlight, etc.);
take/flue exhaust terminals (if fitted) are not
- the appliance power cable must not be re-
blocked.
placed by the user;
• If temporary shutdown of the boiler is re-
- in the event of damage to the cable, switch
quired, proceed as follows:

MAINTENANCE TECHNICIAN
off the appliance and contact exclusively
a) drain the heating system if antifreeze is qualified staff for replacement;
not used;
- if the appliance is not to be used for a certain
b) shut-off all electrical, water and gas sup- period, disconnect the main power switch.
plies.
• In the case of work or maintenance to ATTENTION:
structures located in the vicinity of ducting water at a temperature of more than
or devices for flue extraction and relative 50 °C can cause serious burns. Always
accessories, switch off the appliance and check the water temperature before any use.
on completion of operations ensure that a
qualified technician checks efficiency of the The temperatures indicated by the display have a
ducting or other devices. tolerance of +/- 3°C due to environmental conditions
that cannot be blamed on the boiler.
• Never clean the appliance or connected parts
with easily flammable substances.
• Never leave containers or flammable sub-
stances in the same environment as the
appliance.

33
ATTENTION: ATTENTION:
if you smell gas in the building: if you smell burning or see smoke com-
- close the gas meter interception device ing out of the appliance, switch it off,
or the main interception device; disconnect power, close the main gas cock,
INSTALLER

- if possible, close the gas interception cock on open the windows and call an authorised
the product; company (e.g. Authorised After-Sales Service).
- if possible, open doors and windows wide and
create an air current; ATTENTION:
- do not use open flames (e.g. lighters, matches); At the end of its service life, the appli-
- do not smoke; ance must not be disposed of like nor-
- do not use electrical switches, plugs, door mal household waste nor abandoned
bells, telephones or intercom devices in the in the environment, but must be removed by a
building; professionally authorised company as required
by current legislation. Contact the manufac-
- call an authorised company (e.g. Authorised
turer for disposal instructions.
After-Sales Service).
USER
MAINTENANCE TECHNICIAN

34
2.2 CLEANING AND MAINTENANCE.

To preserve the boiler's integrity and keep the safety


features, performance and reliability, which distin-
guish it, unchanged over time, you must execute

INSTALLER
maintenance operations on a yearly basis in compli-
ance with what is stated in the relative point at “annual
check and maintenance of the appliance” within the
limits established by the Law.

2.3 CONTROL PANEL.

USER
MAINTENANCE TECHNICIAN
Key: 11 - Flame presence symbol and relative output scale
1 - Off/Stand-by/Summer/Winter button 12 - Operation with external temperature probe active
2 - Information buttons (optional)
3 - Reset Button 13 - Solar function active
4 - Key used to decrease the 14 - Central heating room mode function active
DHW temperature 15 - Central heating temperature level indicator
5 - Key used to increase the 16 - Boiler in Stand-by mode
DHW temperature 17 - Operation in winter mode
6 - Button to increase the system water flow temperature 18 - Operation in summer mode
7 - Button to decrease the system water flow temperature 19 - Temperature indicator, boiler info and error codes
8 - Boiler manometer 20 - Not used on this model
9 - DHW production phase operating mode active 21 - Blocked boiler, it needs to be unblocked by pressing the
10 - Boiler connected to remote control V2 (optional) or to “RESET” button
other external devices 22 - D.H.W. temperature level indicator

37

35
2.4 USING THE BOILER. During a withdrawal, if the outlet water is hot enough or if there
Before ignition make sure the heating system is filled with water is “Solar ignition delay” time, the boiler does not switch on, the
and that the manometer (8) indicates a pressure of 1 - 1.2 bar. D.H.W. withdrawal symbol ( ) appears on the display along
- Open the gas cock upstream from the boiler. with the flashing solar function symbol ( ).
- Press the button “ “ repeatedly to cyclically switch from When the water supplied by the solar system is at a temperature
INSTALLER

lower than what is set, or if the “Solar ignition delay” time has
“stand-by” ( ) to “summer” ( ) and “winter” ( ) mode.
elapsed, the boiler switches on. At this point, the solar function
• Summer ( ): in this mode the boiler functions only to produce symbol remains permanently on.
the DHW, the temperature is set via the buttons “ “ and the • Operation with optional external probe ( ). In the case of a
relative temperature is shown on the display via the indicator system with optional external probe, the boiler flow temperature
(19). Moreover, the temperature level that can be selected is for central heating is managed by the external probe depending
shown on the indicator (22). on the external temperature measured (Par. 1.11). The flow tem-
• Winter ( ): in this mode the boiler works both for producing perature can be modified by selecting the functioning curve via
domestic hot water and for central heating. The DHW tem- the buttons “ “ (or on the CARV2 control panel, if connected
perature is always regulated via the buttons “ “, the central to the boiler) selecting a value from “0 to 9”.
heating temperature is regulated via the buttons “ “ and the
relative temperature is shown on the display via the indicator With external probe present, the relative symbol (12) will appear
(19). Moreover, the temperature level that can be selected is on the display. In the central heating mode, if the temperature
shown on the indicator (15). of the water contained in the system is sufficient to heat the
radiators, the boiler can only function with the activation of the
From this moment the boiler functions automatically. With no pump.
demand for heat (central heating or domestic hot water pro-
USER

duction) the boiler goes to “standby” function, equivalent to • “Stand-by” mode. Press button “ “ repeatedly until the
the boiler being powered without presence of flame. Each time symbol ( ) appears. The boiler remains off from this moment,
the burner ignites, the relative flame present symbol is displayed though the antifreeze, pump anti-block and 3-way function and
(11) with relative output scale. signalling of any anomalies are guaranteed.
• “Off ” mode. By holding the button “ ” down for 8 sec-
• Operation with Comando Amico RemotoV2 (CARV2) (Option-
onds, the display switches-off and the boiler is off completely.
al). If the CARV2 is connected, the ( ) symbol will appear on
The safety functions are not guaranteed in this mode.
the display. The boiler regulation parameters can be set via the
CARV2 control panel and the reset button (3) remains active on ATTENTION:
the boiler control panel, along with the switch-off button (1)
in “Stand-by” and “Off ” mode, the boil-
MAINTENANCE TECHNICIAN

(“off ” mode only) and the display where the functioning state
is shown. er is to be considered still live.
N.B.: if the boiler is put into “off ” mode, the “ERR>CM” con-
nection error symbol will appear on the CARV2. The CAR V2 is • Display operation. The display lights up while the control panel
however powered constantly so as not to lose memorised pro- is being used; after a set inactivity period, the brightness drops
grams. until only the active symbols are displayed. The lighting mode can
be varied via parameter “t8” in the P.C.B. programming menu.
• Solar operating mode ( ). This function is activated automat-
ically id the boiler detects a probe on the DHW inlet (optional)
or if the “Solar ignition delay” parameter is more than 0 seconds.

36
2.5 FAULT AND ANOMALY SIGNALS.
The Victrix Tera boiler reports any anomalies via a code shown on
the boiler display (19) according to the following table:

Error

INSTALLER
Anomaly signalled Cause Boiler status / Solution
Code
In the event of request of room central heating or domes-
tic hot water production, the boiler does not switch on
01 No ignition block within the preset time. Upon appliance commissioning Press the Reset button (1)
or after extended downtime, it may be necessary to
eliminate the block.
Safety thermostat During normal operation, if a fault causes excessive over-
02 Press the Reset button (1)
block (overheating) heating internally, the boiler goes into overheating block.
Flue safety thermostat During normal operation, if a fault causes excessive flue
03 Press the Reset button (1)
block gas overheating, the boiler blocks
The P.C.B. detects a fault on the gas valve supply. Check
Contacts resistance
04 its connection. (the anomaly is detected and displayed Press the Reset button (1)
block
only in the event of a request).
05 Flow probe anomaly The board detects an anomaly on the flow NTC probe. The boiler does not start (1)
The board detects an anomaly on the domestic hot water
Domestic hot water In this case the boiler continues to produce domestic hot
06 NTC probe. In this case the antifreeze function is also
probe anomaly water but not with optimal performance (1)

USER
inhibited
Attention: the fault may be reset up to 5 times con-
secutively, after which the function in inhibited for at
Maximum N° of
08 Number of allowed resets already performed. least one hour. One attempt is gained every hour for a
resets.
maximum of 5 attempts. By switching the appliance on
and off again, the 5 attempts are re-acquired.
Sufficient water pressure inside the central heating Check on the boiler pressure gauge that the system
Insufficient system
10 circuit to guarantee the correct operation of the boiler pressure is between 1-1.2 bar and restore the correct
pressure
is not detected. pressure if necessary.
If normal conditions are restored the boiler restarts
If the board detects an anomaly or incongruity on the

MAINTENANCE TECHNICIAN
15 Configuration error without having to be reset. Check that the boiler is con-
electric wiring, the boiler will not start.
figured correctly (1)
16 Fan anomaly This occurs if the fan has a mechanical or electrical fault.
Press the Reset button (1)
This occurs in the event of a leak on the detection circuit
20 Parasite flame block Press the Reset button (1)
or anomaly in the flame control unit.
23 Return probe anomaly The board detects an anomaly on the return NTC probe The boiler does not start (1)
Push button control If normal conditions are restored the boiler restarts
24 The board detects an anomaly on the pushbutton panel.
panel anomaly without having to be reset (1).
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Technical After-Sales Service)
(2) The anomaly can only be verified in the list of errors in the “Information” menu

37
Error
Anomaly signalled Cause Boiler status / Solution
Code
This occurs if there is overheating in the boiler due to
insufficient water circulating in the primary circuit; the
causes can be:
INSTALLER

Insufficient
27 - low system circulation; check that no shut-off devices Press the Reset button (1).
circulation
are closed on the heating circuit and that the system is
free of air (deaerated);
- pump blocked; free the pump.
29 Flue probe anomaly The board detects an anomaly on the flue probe The boiler does not start (1)
Disconnect and reconnect the power to the boiler. If the
This occurs if an incompatible remote control is con- Remote Control is still not detected on re-starting, the
Loss of remote control
31 nected, or if communication between the boiler and the boiler will switch to local operating mode, i.e. using the
communication
remote control is lost controls on the control panel. In this case the "Central
Heating" (1) function cannot be activated.
Low power supply This occurs when the power supply voltage is lower If normal conditions are restored the boiler restarts
37
voltage than the allowed limits for the correct boiler operation. without having to be reset (1)
This occurs when the boiler is ignited correctly and the
burner flame switches off unexpectedly; a new attempt If normal conditions are restored the boiler restarts
38 Loss of flame signal
at ignition is performed and if normal conditions are without having to be reset (1) (2)
restored, the boiler does not have to be reset.
USER

Block due to loss of This occurs if the ''Flame signal loss'' error occurs many Press the Reset button, before restarting, the boiler will
43
flame signal times in a row within a preset period (38). run a post-ventilation cycle. (1)

The power of the burner is limited to prevent damage


to the condensation module and once the right ΔT is
The boiler detects a sudden, unexpected increase in the restored, the boiler resumes regular operation. Make sure
45 High ΔT
ΔT between the flow probe and the system return probe. there is water circulating in the boiler, that the pump is
configured according to system requirements and that
the return probe works properly. (1) (2)
Burner power Should flue high temperature be detected, the boiler
47 (1)
limitation reduces power supplied so as not to damage it.
MAINTENANCE TECHNICIAN

If there is no communication between the boiler and


CAR Wireless
Wireless version CAR, an anomaly is signalled. From Check operation of the Wireless CAR, check the battery
51 communication
this moment, it is only possible to control the system by charge (refer to the relative instructions booklet).
failure
means of the control panel of the boiler itself.

Anomaly pump The pump is stopped due to one of the following causes: Try to unblock the pump as described in the relative
60 section. If normal conditions are restored the boiler
blocked - Impeller blocked, electrical fault restarts without having to be reset (1)
Vent the pump and the central heating circuit. If normal
Air in circulator
61 Air is detected inside the pump; the pump cannot work conditions are restored the boiler restarts without having
pump
to be reset (1)
Return/flow probe In case of an incorrect boiler wiring connection the
70 The boiler does not start (1)
exchange error is detected
Return and/or flow Possible failure of one or both system return and flow
75 The boiler does not start (1)
probe malfunction probes
Return and/or flow
A malfunction of one or both system return and flow
76 probes temperature The boiler does not start (1)
probes is detected
drift
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Technical After-Sales Service)
(2) The anomaly can only be verified in the list of errors in the “Information” menu

38
2.6 INFORMATION MENU.
By pressing the button “ “, the “Information menu” is activated
for at least 1 second, displaying some boiler operating parameters.
To scroll through the various parameters, press the buttons “DHW
regulation” “ “.

INSTALLER
With the menu active on the indicator (19) the parameter via the
letter “d” plus the number of the parameter that is being displayed
will alternately show.
To view the parameter value, select it by pressing the button
.
Press “ ” or wait 15 minutes to go back to the previous
screen or exit the menu.

Parameter ID Description
d 0.0 Not used
d 0.1 Displays the flame signal (uA)

USER
d 0.2 Displays the primary heat exchanger output instant heating flow temperature
d 0.3 Displays the instant output temperature from the DHW exchanger
d 0.4 Displays the values set for central heating set
d 0.5 Displays the values set for DHW set
Displays the external environment temperature (if optional external probe present)
d 0.6
If the temperature is below zero, the value is displayed flashing.
d 0.7 Displays the temperature of the inlet DHW (with optional DHW inlet probe present)
d 0.8 Displays the system return water temperature
Displays the list of the last eight anomalies.
d 0.9

MAINTENANCE TECHNICIAN
(to scroll the list press the “central heating temperature regulation” buttons (6 and 7))
Anomaly list reset. Once “d 1.0” is displayed, press the Reset button for at least 3 seconds; deletion is confirmed via the “88”
d 1.0
symbols flashing for two seconds
d 1.1 Not used
d 1.2 Displays the pump operating speed
d 1.3 Not used
d 1.4 Displays the pump flow rate (lh/100)
d 1.5 Displays the fan operating speed (rpm/100)
d 1.6 Displays the temperature read on the flue probe
d 1.7 Displays the calculated flow temperature
d 1.8 At the end of the screed heater function, displays for how many hours the flow temperature remained at “Top set”
d 1.9 Toggles between the safety software version and the functional software version
d 2.0 Displays the flow temperature of zone two (optional)
d 2.1 Displays the flow temperature of zone three (optional)
d 2.2 Not used

39
2.7 BOILER SHUTDOWN. 2.11 ANTIFREEZE PROTECTION.
Switch the boiler off by putting it in “off ” mode, disconnect the The boiler has an antifreeze function that switches the burner on
omnipolar switch outside of the boiler and close the gas cock automatically when the temperature drops below 4°C (standard
upstream from the appliance. Never leave the boiler switched on protection to minimum temperature of -5°C). All information
if left unused for prolonged periods. relative to the antifreeze protection is stated in (Par. 1.4). In order
INSTALLER

to guarantee the integrity of the appliance and the domestic hot


2.8 RESTORE CENTRAL HEATING SYSTEM water heating system in zones where the temperature drops below
PRESSURE. zero, we recommend the central heating system is protected using
Periodically check the system water pressure. The boiler pressure anti-freeze liquid and installation of the Immergas Antifreeze Kit
gauge should read a value of between 1 and 1.2 bar. in the boiler. In the case of prolonged inactivity (second case), we
If pressure falls below 1 bar (with the circuit cold), restore normal also recommend that:
pressure via the cock located at the bottom of the boiler (Part. 1 - disconnect the electric power supply;
Fig. 7). - the central heating circuit and boiler domestic hot water circuit
N.B.: close the valve after the operation. must be drained. In systems that are drained frequently, filling
If pressure values reach around 3 bar the safety valve may be must be carried out with suitably treated water to eliminate
activated. hardness that can cause lime-scale.
In this case, remove water from a radiator air vent valve until a pressure
of 1 bar is achieved, or ask for assistance from professionally qualified 2.12 CLEANING THE CASE.
personnel. Use damp cloths and neutral detergent to clean the boiler casing.
In the event of frequent pressure drops, contact qualified staff for Never use abrasive or powder detergents.
assistance to eliminate the possible system leakage.
USER

2.13 DECOMMISSIONING.
2.9 DRAINING THE SYSTEM. In the event of permanent shutdown of the boiler, contact profes-
To drain the boiler, use the special draining valve (Part. 2 Fig. 7). sional staff for the procedures and ensure that the electrical, water
Before draining, ensure that the filling cock is closed. and gas supply lines are shut off and disconnected.

ATTENTION: 2.14 GAS SYSTEM NOT USED FOR PERIODS OVER 12


if glycol was input in the system’s circuit, MONTHS.
The current regulation provides that gas systems not used for
make sure it is discharged into the waste
over 12 months must be checked prior to being used again, as per
water system, pursuant to regulation EN 1717
MAINTENANCE TECHNICIAN

regulations in force, by professionally qualified staff.


If the inspection is successful, the boiler can be recommissioned
according to the instructions specified in point 3 herein.
2.10 DRAINING THE DOMESTIC HOT WATER
CIRCUIT.
To do this, always close the domestic cold water inlet upstream
of the appliance.
Open any domestic hot water tap to discharge the pressure from
the circuit.

40
3 INSTRUCTIONS
FOR
MAINTENANCE AND
3.2 INITIAL CHECK.
To commission the boiler:
INITIAL CHECK. - make sure that the type of gas used corresponds to
boiler settings;

INSTALLER
- check connection to a 230V-50Hz power mains,
3.1 GENERAL WARNINGS. correct L-N polarity and the earthing connection;
ATTENTION: - make sure the central heating system is filled with water and
that the pressure gauge indicates a pressure of 1-1.2 bar;
operators who install and service the - switch the boiler on and ensure correct ignition;
appliance must wear the personal pro- - check the proper calibration of the number of fan revolutions;
tective equipment (PPE) required by - check the CO2 flow rate in the flue:
applicable law. - maximum
Note: the list of possible PPE is not - intermediate
- minimum
complete as they are indicated by the
- ensure that the safety device intervenes in the event of gas
employer. supply failure and check the relative intervention time;
- check activation of the main switch located upstream of the
ATTENTION: boiler;
- check that the intake and/or exhaust terminals are not
before performing any maintenance

USER
blocked;
operation, make sure: - ensure activation of all adjustment devices;
- you have disconnected the power to - seal the gas flow rate regulation devices (if settings are mod-
ified);
the appliance;
- ensure production of domestic hot water;
- you have closed the gas cock; - check tightness of water circuits;
- you have discharged the pressure from - check ventilation and/or aeration of the installation room
where provided.
the system and domestic hot water
Even if just one single safety check provides a negative result,

MAINTENANCE TECHNICIAN
circuit. do not commission the system

Risk of material damage after using sprays and liq-


uids to search for leaks.
Leak sprays and liquids clog the reference hole P1 (Fig.
40) of the gas valve, damaging it irreparably.
During installation and maintenance, do not use spray
or liquids in the upper area of the gas valve (side referring to the
electric connections)

Supply of spare parts.


The device’s warranty shall be rendered null and void
if unapproved or unsuitable parts are used for main-
tenance or repairs. These will also compromise the
product’s compliance, and the said product may no
longer be valid and fail to meet the current regulations.
With regard to the above, only use Immergas original spare parts
when replacing parts.

If additional documentation needs to be consulted for


extraordinary maintenance, contact the Authorised
After-Sales Service.

41
3.3 YEARLY APPLIANCE CHECK AND - Check the CO2 by using the chimney sweep func-
MAINTENANCE. tion at the three reference heat outputs, using the
The following checks and maintenance should be parameters in the table below. Should values out of
performed at least once a year to ensure operation, the indicated tolerance range be detected, check the
integrity of the ignition / detection electrode and, if
INSTALLER

safety and efficiency of the appliance over time.


required, change it, also changing the relative gasket.
- Clean the flue side of the heat exchanger.
At this point, activate the “complete calibration”
- Clean the main burner. function.
- Check the correct positioning, integrity and cleanliness of the - Check correct operation of control and adjustment devices
detection and ignition electrode; remove any oxide present. of the appliance. and in particular:
- If deposits are detected in the combustion chamber they must - system regulation probes intervention;
be removed and the heat exchanger coils must be cleaned
- domestic hot water control thermostat intervention.
using nylon or broomcorn brushes; it is forbidden to use
brushes made of metal or other materials that may damage - Check tightness of gas circuit and the internal system.
the combustion chamber. It is also forbidden to use alkaline - Check the intervention of the device against no gas ionisation
or acid detergents. flame control. Intervention time must be less than 10 seconds.
- Check the integrity of the insulating panels inside the com-
bustion chamber and if damaged replace them.
Victrix Tera 28 1
- Visually check for water leaks or oxidation from/on fittings
CO2 at maximum output CO2 at minimum output
and traces of condensate residues inside the sealed chamber.
G 20 9.70% + 0.50 / - 0.20 8.80% + 0.20 / - 0.30
- Check the contents of the condensate drain trap.
USER

- Check that there are no material residues in the condensate G 31 11.40% + 0.10 / - 0.30 10.60% + 0.30 / - 0.10
drain siphon clogging the condensate passage; also check that
Victrix Tera 32 1
the entire condensate drainage circuit is clear and efficient.
CO2 at maximum output CO2 at minimum output
In the event of obstructions (dirt, sediment, etc.) with con-
sequent leakage of condensate in the combustion chamber, G 20 9.50 (± 0.20) 8.60% + 0.20 / - 0.30
one must replace the insulating panels. G 31 11.20% + 0.20 / - 0.40 10.00% + 0.40 / - 0.20
- Check that the burner and gas manifold seal gaskets are intact
and perfectly efficient, otherwise replace them. In any case the Victrix Tera 38 1
gaskets must be replaced at least every two years, regardless CO2 at maximum output CO2 at minimum output
MAINTENANCE TECHNICIAN

of their state of wear. G 20 9,20% + 0,40 / - 0,20 8,50% + 0,10 / - 0,30


- Check that the burner is intact, that it has no deformations or G 31 10,10% ± 0,20 9,40% ± 0,20
cuts and that it is properly fixed to the combustion chamber
lid; otherwise it must be replaced.
- Visually check that the drain of the water safety valve is not In addition to yearly maintenance, one must also
clogged. check the energy efficiency of the thermal system,
with frequency and procedures that comply with the
- Check that, after discharging system pressure and bringing it
indications of the technical regulations in force.
to zero (read on boiler pressure gauge), the expansion vessel
pressure is at 1.0 bar.
- Check that the system static pressure (with system cold and
after refilling the system by means of the filling valve) is be-
tween 1 and 1.2 bar.
- Visually check that the safety and control devices have not
been tampered with and/or shorted, in particular:
- Check the condition and integrity of the electrical system and
in particular:
- the power cables must be inside the cable fixings;
- there must be no traces of blackening or burning.
- Check correct lighting and functioning.

42
3.4 BOILER HYDRAULIC DIAGRAM.

INSTALLER
USER
MAINTENANCE TECHNICIAN
Key:
18 - Burner
1 - Gas valve
19 - Return probe
2 - D.H.W. flow switch
20 - Fan
3 - Gas nozzle
21 - Air vent valve
4 - Flow limiter
22 - Boiler pump
5 - DHW probe
23 - Absolute pressure switch
6 - Condensate drain trap
24 - 3-way valve (motorised)
7 - System filling valve
25 - Bypass
8 - DHW heat exchanger
26 - System draining valve
9 - System expansion vessel
27 - 3 bar safety valve
10 - Positive (+) pressure point
28 - 3 bar safety valve drain fitting signal
11 - Venturi
12 - Flow probe G - Gas supply
13 - Ignition/detection electrodes AC - Domestic hot water outlet
14 - Air intake pipe AF - Domestic hot water inlet
15 - Flue probe SC - Condensate drain
16 - Flue sample point M - System flow
17 - Air sample point R - System return
38

43
3.5 WIRING DIAGRAM.
INSTALLER

Power supply
230 Vac
50Hz
USER

IMG BUS
(optional)
CAR v2
Key: (optional)

B1 - Flow probe
B2 - DHW probe Colour code key:
B4 - External probe (optional) BK - Black
MAINTENANCE TECHNICIAN

B5 - Return probe BL - Blue


B9 - DHW inlet probe (optional) BR - Brown
B10 - Flue probe G - Green
CARV2 - Comando Amico RemotoV2 remote control GY - Grey
(optional) OR - Orange
E3 - Ignition and detection electrode P - Purple
M1 - Boiler pump PK - Pink
M20 - Fan R - Red
M30 - Three-way motor stepper W - White
S4 - D.H.W. flow switch Y - Yellow
S5 - System pressure switch Y/G - Yellow/Green
S20 - Room thermostat (optional)
T2 - Ignition transformer
X40 - Room thermostat jumper
Y1 - Gas valve
39

Comando Amico Remoto remote controlV2.


The boiler is prepared for the application of the Comando Amico
Remoto remote control V2 (CARV2), which must be connected to
clamps 44/40 and 41 of the terminal board (located in the boiler
control panel) respecting the polarity and eliminating jumper X40.
Room thermostat.
The boiler is prepared for the application of the room thermo-
stat (S20), which must be connected to clamps 44/40 - 41 of the
terminal board (located in the boiler control panel) eliminating
jumper X40.

44
3.6 POSSIBLE PROBLEMS AND THEIR CAUSES. - Poor production of D.H.W. If a drop in performance is detected
during supply of D.H.W., it is possible that the condensation
Maintenance interventions must be carried out by module or D.H.W. heat exchanger is clogged. In this case, contact
an authorised company (e.g. Authorised After-Sales Authorised After-Sales Assistance Service that has procedures
Technical Assistance Service). to clean the module or D.H.W. heat exchanger.

INSTALLER
- Smell of gas. Caused by leakage from gas circuit pipelines. Check - Red pump LED.
tightness of gas intake circuit. There can be three possible causes for this anomaly:
- Repeated ignition blocks. It can be caused by no gas, check the - Low power supply voltage. When the minimum voltage is
presence of pressure in the network and that the gas adduction reached after about 2 seconds, the LED switches from green
cock is open. Incorrect adjustment of the gas valve, check the to red and the pump stops. Wait for the power supply voltage
correct calibration of the gas valve. to rise; when the pump restarts, the LED will turn green again
- Irregular combustion or noisiness. It may be caused by: a with a delay of about one second.
dirty burner, incorrect combustion parameters, intake-exhaust Note: obviously the flow rate decreases as the supply voltage
terminal not correctly installed. Clean the above components decreases.
and ensure correct installation of the terminal, check correct - Rotor seized. Powering the pump with the rotor seized, after
setting of the gas valve (Off-Set setting) and correct percentage about 4 seconds the LED switches from green to red. Carefully
of CO2 in flue gas. act on the screw in the middle of the head to manually release
- Non-optimal ignition of first ignitions of the burner. Even the crankshaft; circulation starts up immediately after the rotor
if the burner is perfectly calibrated, first ignition of the burner is released and the LED switches from red to green after about
(after calibration) can be sub-optimal; the system automatically 10 seconds.

USER
regulates ignition until it finds optimal ignition of the said burner. - Electrical error. Pump, wiring or P.C.B. fault. Check the indi-
- Frequent interventions of the safety thermostat function cated components.
(delegated to flow probe and system return probe). It can de-
pend on the lack of water in the boiler, little water circulation in 3.7 CONVERTING THE BOILER TO OTHER
the system or blocked pump. Check on the pressure gauge that TYPES OF GAS.
the system pressure is within established limits. Check that the If the device must be adapted to a different type of gas
radiator valves are not closed and also the functionality of the than what is specified on the plate, you must request
pump. an Immergas kit with frequency and mode compliant
- Drain trap clogged. This may be caused by dirt or combustion with what is specified in the technical legislation in

MAINTENANCE TECHNICIAN
products deposited inside. Check, by means of the condensate force.
drain cap, that there are no residues of material blocking the flow The gas conversion operation must be carried out by an
of condensate. authorised company (e.g. Authorised After-Sales Technical
- Heat exchanger blocked. This may be caused by the drain trap Assistance Service).
being blocked. Check, by means of the condensate drain cap, that To convert to another type of gas the following operations are
there are no residues of material blocking the flow of condensate. required:
- Noise due to air in the system. Check opening of the special air - disconnect power to the appliance;
vent valve cap (Part. 20 Fig. 36). Make sure the system pressure - replace the nozzle positioned above the gas valve (Part.9Fig.
and expansion tank factory-set pressure values are within the 36) taking care to disconnect the appliance during this oper-
set limits; The factory-set pressure values of the expansion vessel ation;
must be 1.0 bar, the value of system pressure must be between - re-power the appliance;
1 and 1.2 bar. - calibrate fan speed (Par. 3.8);
- Noise due to air inside the condensation module. Use the manual - adjust the correct air/gas ratio (Par. 3.9);
air vent valve (Part. 20 Fig. 36) to eliminate any air present in the
condensation module. When the operation has been performed, - seal the gas flow rate regulation devices (if settings are mod-
close the manual air vent valve. ified);
- after completing the conversion, apply the sticker, contained
in the conversion kit, on the data plate in the area relating to
the type of gas.
These adjustments must be made with reference to the type of
gas used, following that given in the table (Par. 4.2).

45
3.8 CALIBRATION OF FAN SPEED. Calibration of the CO2 at minimum output
Enter the chimney sweep mode without withdrawing DHW and
ATTENTION: set the output to minimum (0%). To have an exact value of CO2
verification and calibration are neces- the technician must insert the sampling probe to the bottom of
the sample point, then check that the CO2 value is that specified
sary, in the case of transformation to
INSTALLER

in the table, otherwise adjust the screw (Part. 3 Fig. 40) (Off-Set
other types of gas, in the extraordinary main- adjuster). To increase the CO2 value, turn the adjustment screw
tenance phase with replacement of the PCB, (3) in a clockwise direction and vice versa to decrease it.
air/gas circuit components or in the case of Calibration of the CO2 at maximum output
installations with flue extraction systems, with When you finish the minimum CO2 adjustment, while maintain-
ing the chimney sweep function active, set the output to maximum
horizontal concentric pipe measuring more (99%). To have an exact value of CO2 the technician must insert
than 1 metre. the sampling probe to the bottom of the sample point, then check
that the CO2 value is that specified in the table, otherwise adjust
The boiler heat output is correlated to the length of the air intake the screw (Part. 12 Fig. 40) (gas flow rate regulator).
and flue exhaust pipes. This decreases with the increase of pipe To increase the CO2 value, turn the adjustment screw (12) in a
length. The boiler leaves the factory adjusted for minimum pipe clockwise direction and vice versa to decrease it.
length (1m coaxial). At every adjustment variation on the screw 12 it is necessary to
- activate flue test (Parag. 3.15); wait for the boiler to stabilise itself at the value set (about 30 sec.).
- detect the flue signal ∆P (Ref. 16 and 17 Fig. 38);
3.10 CHECKS FOLLOWING CONVERSION TO
- compare the signal ∆P and, if necessary, correct the S1 operating
USER

ANOTHER TYPE OF GAS.


parameters with the following table:
After making sure that conversion was carried out with a nozzle
Victrix Tera 28 1 Victrix Tera 32 1 of suitable diameter for the type of gas used and the settings are
∆P > 200 Pa ∆P > 200 Pa made at the correct pressure, check that the burner flame is not
G20 S1 = 126 (6300 rpm) G20 S1 = 134 (6700 rpm) too high or low and is stable (does not detach from burner);
G31 S1 = 121 (6050 rpm) G31 S1 = 127 (6350 rpm)
Maintenance interventions must be carried out by
Victrix Tera 38 1 an authorised company (e.g. Authorised After-Sales
Technical Assistance Service).
∆P > 200 Pa
MAINTENANCE TECHNICIAN

G20 S1 = 128 (6350 rpm)


G31 S1 = 130 (6400 rpm)

3.9 ADJUSTMENT OF THE AIR-GAS RATIO.

ATTENTION:
the verification operations of the CO2
must be carried out with the casing
mounted, while the gas valve calibration op-
erations must be carried out with the casing
open and removing the voltage from the boiler.

42 Gas Valve
Key:
1 - Gas valve inlet pressure point
P3
2 - Gas valve outlet pressure point
2 3 - Off/Set adjustment screw
12 - Outlet gas flow rate adjuster
+

P1 +

12
1
3

40

46
3.11 PROGRAMMING THE P.C.B. Pressing the mode of op-
The boiler is prepared for possible programming of several op- eration button “ ”
eration parameters. By modifying these parameters as described displays the value of the
below, the boiler can be adapted according to specific needs. selected parameter and by
To access the programming phase, press and hold the buttons pressing the buttons to

INSTALLER
“ ” and “ ” for more than 5 seconds, the display shows adjust the central heating
two dashes “--” flashing and you must enter the password to access temperature “ ” you
the programming menus. 44 can adjust its value.
To enter the first digit, use
the buttons to adjust the
Press the mode of opera-
DHW “ ”; to enter tion button “ ”  for
the second digit, use the more than 1 second to
buttons to adjust the cen- store the parameter value;
tral heating temperature confirmation is given by
“ ”. the word “ ” which ap-
41 To confirm the password pears for 2 seconds.
( ) and access the menu, 45
press the operating mode
button “ ”.
If you want to exit a pa-

USER
Once in the menu, you can rameter without changing
cyclically scroll the four its value, press the button
submenus (P, t, A, S) by “ ”.
pressing the DHW but- Wait for 15 minutes or
tons “ ”, to access the press the “ ” but-
menu press the button ton to exit programming
“ ”. 46 mode.
42

MAINTENANCE TECHNICIAN
The first digit of the central
indicator (19) shows the
family of the parameter,
while the second digit
shows its number.

43

Programming phase sequence.

Menu ←
P0 - P5 (without
“P”
← t0 - t9 ← Value memorising)
+ > 5’’ “t” “ ”
A0 - A6 parameter
“A” → →
S0 - S2 > 1’’
“S”
(Memorise)

47

47
Id Custom-
Parameter Description Range Default
Parameter ised value
Max DHW Defines the maximum heat output percentage of the boiler during
P0 0 - 100 % 100 %
output the D.H.W. phase compared to the maximum heat output available
P1 Min CH output Defines in percentage the minimum output in central heating mode 0 - P2 0%
INSTALLER

Victrix Tera 28 1
G20 = 85
G31 = 82
Victrix Tera 32 1
Defines the maximum heat output percentage of the boiler during the
P2 Max CH output 0 - 100 % G20 = 85
central heating mode compared to the maximum heat output available
G31 = 85
Victrix Tera 38 1
G20 = 80
G31 = 81
P3 - Not available for this model - -
The pump can function in two ways.
- 0 intermittent: in winter "mode" the circulator is managed by the
Pump room thermostat or by the remote control
P4 0-1 0
functioning
- 1 continuous: in "winter" mode the circulator is always powered and
is therefore always in operation
External probe If the reading of the external probe is not correct it is possible to correct
P5 -9 - 9 K 0
correction it in order to compensate any environmental factors.
USER

P6 - Not available for this model - -


P7 - Not available for this model - -

Cus-
Id
Parameter Description Range Default tomised
Parameter
value
Central heating set
t0 point minimum Defines the minimum flow temperature. 20 - 50 °C 25
temperature
Central heating set
MAINTENANCE TECHNICIAN

t1 point maximum Defines the maximum flow temperature. (t0+5) - 85 °C 85


temperature
The boiler is set to switch-on immediately after a request for DHW.
In the case of coupling with a solar storage tank positioned upstream
from the boiler, it is possible to compensate the distance between the
t2 Solar delay timing 0 - 30 seconds 2
storage tank and the boiler in order to allow the water to reach the
boiler. Set the time necessary to verify that the water is hot enough
(see par. Solar panels coupling)
In winter mode the boiler, at the end of a domestic hot water request,
Domestic hot is ready to switch to central heating mode if there is an active request.
0 - 100 seconds
t3 water priority Timing sets a time period in which the boiler waits before changing 2
(step 10 sec)
timing the operating mode, in order to quickly and comfortably satisfy an
additional request for domestic hot water.
Central heating The boiler has an electronic timer, which prevents the burner from 0 - 600 seconds
t4 18
ignitions timer igniting too often in central heating mode (step 10 sec)
Central heating In central heating mode, the boiler performs an ignition ramp in order 0 = 840 seconds
t5 18
ramp timer to reach the maximum output set (step 10 sec)

48
CH ignition delay The boiler is set to switch-on immediately after a request. In the event
0 - 600 seconds
t6 from TA and CR of particular systems (e.g. area systems with motorised thermostatic 0
(step 10 sec)
request valves etc.) it may be necessary to delay ignition
Establishes the display lighting mode.
- 0: the display lights up during use and lowers after 15 seconds of

INSTALLER
t7 Display lighting inactivity. In the case of anomaly the display flashes. 0-2 0
- 1: display lighting off.
- 2: the display is always lit up.
Establishes what the indicator displays 19 (Fig. 37).
"Summer" mode:
- 0: the indicator is always off.
- 1: circulator active, it displays the flow temperature,
t8 Display pump off the indicator is off 0-1 1
"Winter" mode:
- 0: it always displays the value set on the central heating selector
- 1: circulator active, it displays the flow temperature,
pump off always displays the value set on the CH selector
Flow off
Increases the flow off temperature at ignition only in the first 60 sec-
t9 temperature 0 - 15 0
onds. After the flame is detected, the temperature is increased by t9
increase

Cus-

USER
Id
Parameter Description Range Default tomised
Parameter
value
Defines the type of hydraulics in the boiler
A0 Hydraulic model 0-1 0
(0 = instant; 1 = storage tank)
Maximum pump Defines the maximum operating speed of the circulator
A1 A2 - 9 9
speed (If A1 = A2 circulator operating at set speed)
Victrix Tera 28 1
6
Minimum pump Victrix Tera 32 1
A2 Defines the minimum operating speed of the circulator 1 - A1

MAINTENANCE TECHNICIAN
speed 5
Victrix Tera 38 1
5
Sets the pump operating mode
Pump operating - DELTA T = 0: proportional head (see parag. 1.29 - 1.30)
A3 0 - 25 15
mode
- DELTA T = 5 - 25 K: ∆T constant (see Parag. 1.29 - 1.30)
Establishes the temperature to be added to the DHW set-point to cal-
Storage tank flow
A4 culate the flow set to heat the storage tank (only useful with a coupled 5 - 50 °C 25
offset
storage tank and parameter A0=1).
Temperature value to be subtracted from the DHW set-point to cal-
Storage tank
A5 culate the boiler ignition to heat the storage tank (only useful with a 0 - 15 °C 3
activation offset
coupled storage tank and parameter A0=1).
Establishes the switch-off method in DHW mode.
- 0 Fixed: the switch-off temperature is fixed at the maximum value
A6 DHW thermostat regardless of the value set on the control panel. 0-1 0
- 1 Correlated: the boiler switches off according to the temperature
set.

49
Victrix Tera 28 1
Cus-
Id
Parameter Description Range Default tomised
Parameter
value
DHW minimum no. of Defines the operating speed of the fan at minimum DHW 20 - 60 27 (G20)
S0
INSTALLER

fan revs output (x 50 =RPM) 26 (G31)


DHW maximum no. Defines the operating speed of the fan at maximum DHW S0 - 140 121 (G20)
S1
of fan revs output (x 50 =RPM) 115 (G31)
Fan speed 40 - 80 56 (G20)
S2 Defines the operating speed of the fan during the ignition phase
Ignition phase (x 50 =RPM) 56 (G31)

Victrix Tera 32 1
Cus-
Id
Parameter Description Range Default tomised
Parameter
value
DHW minimum no. Defines the operating speed of the fan at minimum DHW 20 - 60 28 (G20)
S0
of fan revs output (x 50 =RPM) 28 (G31)
DHW maximum no. Defines the operating speed of the fan at maximum DHW S0 - 140 128 (G20)
S1
of fan revs output (x 50 =RPM) 121 (G31)
Fan speed 40 - 80 56 (G20)
S2 Defines the operating speed of the fan during the ignition phase
Ignition phase (x 50 =RPM) 56 (G31)
USER

Victrix Tera 38 1
Cus-
Id
Parameter Description Range Default tomised
Parameter
value
DHW minimum no. Defines the operating speed of the fan at minimum DHW 20 - 60 27 (G20)
S0
of fan revs output (x 50 =RPM) 28 (G31)
DHW maximum no. Defines the operating speed of the fan at maximum DHW S0 - 140 122 (G20)
S1
of fan revs output (x 50 =RPM) 122 (G31)
Fan speed 40 - 80 56 (G20)
S2 Defines the operating speed of the fan during the ignition phase
Ignition phase (x 50 =RPM) 56 (G31)
MAINTENANCE TECHNICIAN

50
3.12 PASSWORD-PROTECTED SPECIAL FUNCTIONS. The display now shows the countdown of days alternated with
Attention: the boiler is equipped with some special functions, access the current flow temperature, as well as the normal operating
to which is granted if this is in stand-by ( ) . symbols of the boiler.
IMPORTANT NOTE: if the boiler is connected to the CARV2 the In case of failure or lack of supply voltage, the function is sus-
“stand-by” function can only be activated via the remote control pended and will resume when the normal operating conditions

INSTALLER
panel. are reset from the point where it was interrupted.
Press and hold the When the time expires, the boiler automatically goes back to
“ ” button for more “Stand-by” mode, the function can also be stopped by pressing
than 5 seconds. The dis- the button “ ”.
play will show two dashes
“--” flashing. Now enter
the password to access the 3.14 AUTOMATIC VENT FUNCTION (dL).
programming menus. In the case of new central heating systems and in particular mode
for floor systems, it is very important that deaeration is performed
48 correctly. The function consists of the cyclic activation of the
pump (100 s ON, 20 s OFF) and the 3-way valve (120 s D.H.W.,
To enter the first digit, use 120 s C.H.).
the buttons to adjust the The function is activated by accessing the special “dl” function as
DHW “ ”; to enter the described in Paragraph 3.12.
second digit, use the but- The function lasts for 16.5 hours and it can be stopped by simply
tons to adjust the central

USER
pressing the button “ ”.
he at i ng te mp e r atu re
Activation of the function is signalled by the countdown shown
“ ”. To confirm the
on the indicator (20).
49 password and access the
menu, press the operating
mode button “ ”. 3.15 FLUE INSTALLATION (FU).
Once the menu has been accessed, it is possible to cyclically scroll To activate the “Flue” function access the special functions as
the three available functions (dl, MA, FU) by pressing the DHW described in Paragraph 3.12 and select the “FU” function.
buttons “ ”, to access the menu press the button “ ” to N.B.: before performing the test, ensure that the

MAINTENANCE TECHNICIAN
exit wait 15 minutes or press the button “ ”. condensate drain trap has been filled correctly and
check that there are no obstructions in the air intake
3.13 SCREED HEATER FUNCTION. circuit and flue exhaust and that the sealed chamber is
The boiler is equipped with a function to perform the thermal perfectly closed and the flue has already been installed.
shock on new radiant panel systems, as required by the applicable
standard. Using this function activates the fan at a fixed speed (6000 rpm)
Attention: contact the manufacturer of the radiant panels for the for 15 minutes.
thermal shock characteristics and its correct execution.
In this phase the symbols ( ) and ( ) are displayed flashing,
N.B.: to be able to activate the function there must be no remote while the symbol ( ) is displayed permanently on, the function
control connected, while in case of system divided into zones it can be stopped by simply pressing the button “ ”.
must be properly connected, both hydraulically and electrically.
The function is activated from boiler in OFF mode by pressing
and holding the buttons “Reset”, “Info” and “Stand-by” for more
tan 5 seconds.
The function lasts in total 7 days, 3 days at the lower temperature
set and 4 days at the higher temperature set (Fig. 50).
After activating the func-
tion, the lower set (range TM (°C) 51
20 - 45 °C default = 25 °C)
and the higher set (range
25 - 55 °C default = 45 °C)
UPPER (A)
SET
appear in sequence. The
temperature is selected by
means of the buttons “
50 ” and confirmed by
pressing the button LOWER (B)
SET
“ ”.
(C)
DAYS

51
3.16 MAINTENANCE FUNCTION (MA). 3.18 SOLAR PANELS COUPLING FUNCTION.
Using this function you can activate some operating devices of the The boiler is prepared to receive pre-heated water from a system
boiler without starting it, thus verifying the functionality. of solar panels up to a maximum temperature of 65°C. In any case,
The function is active for 15 minutes and it can be stopped by it is always necessary to install a mixing valve on the hydraulic
pressing the button “ ”. circuit upstream of the boiler, on the cold water inlet.
INSTALLER

To activate the “Maintenance” function access the special functions To optimise the operation,where the probe is not already fitted
as described in Paragraph 3.12 and select the “MA” function. on the boiler, the solar inlet probe kit is available on request (see
wiring diagram Fig. 39):
The following loads can be activated within this function: - if there is no probe kit, it is advisable to set parameter A6 (DHW
- Fan (Fn): the fan is brought to ignition speed. Using the buttons thermostat) at “1”;
“ ” you can increase or decrease the fan speed. - otherwise, where the kit is installed or the probe is already present
- Circulator (Pu): the circulator is brought to maximum speed, in the boiler, parameter A6 must be left at “0”. This kit allows
the relative speed is shown on the display, using the buttons connecting a probe on the domestic cold water inlet pipe of the
“ ” you can increase or decrease the circulator speed. boiler to prevent unnecessary ignitions in systems with water
heating through solar systems or alternative sources. The boiler
- Three-way (3d): the symbol is shown on the display according will not turn on if the inlet water is sufficiently hot.
to the position of the valve, DHW ( ) or central heating
In both conditions (probe present or not), we recommend setting
( ), using the buttons “ ” you can change the valve parameter t3 (solar delay timing) at a time sufficient to let the water
position, taking care to wait for the completion of passage be- inside the D.H.W. circuit upstream of the boiler drain.
tween statuses.
The greater the distance from the storage tank, the longer wait
- Configurable relay (rl): the configurable relay in the boiler is
time will have to be set.
USER

energised.
With these adjustments made, when a domestic withdrawal is
requested, once the time set on parameter “t3” has passed, if the
3.17 "CHIMNEY SWEEP” FUNCTION. water entering the boiler is at a temperature that is equal to or
When activated, this function forces the boiler to variable output greater than that set, the boiler will not turn on.
for 15 minutes.
Note: in order for the boiler to work properly, the temperature
In this state all adjustments are excluded and only the safety selected on the mixing valve must be 5°C higher than the tem-
thermostat and the limit thermostat remain active. To activate the perature selected on the boiler control panel.
chimney sweep function, press the “ ” button until activation
of the function in the absence of DHW requests.
MAINTENANCE TECHNICIAN

Its activation on the boiler display is confirmed by the indicators 3.19 PUMP ANTI-BLOCK FUNCTION.
flashing at the same time (17 and 18 Fig. 37). The boiler has a function that starts the pump at least once every
24 hours for the duration of 30 seconds in order to reduce the
This function allows the risk of the pump becoming blocked due to prolonged inactivity.
technician to check the
combustion parameters.
Once the function is ac- 3.20 3-WAY ANTI-BLOCK SYSTEM.
tivated, it is possible to Both in “domestic hot water” and in “domestic hot water-central
select whether to make heating” phase the boiler is equipped with a function that starts the
the chick in CH status or three-way motorised group 24 hours after it was last in operation,
DHW status by opening running it for a full cycle so as to reduce the risk of the three-way
52
any hot water cock. group becoming blocked due to prolonged inactivity.
Using the buttons “ ” you can select between three predefined
power levels: 3.21 RADIATORS ANTIFREEZE FUNCTION.
-“0%” If the system return water is below 4°C, the boiler starts up until
- Max CH output (P2) reaching 42°C.
- Max DHW output (P0).
While by using the buttons “ ” you can select the power from
0% to max DHW output (P0), with intervals of 1%.
The central heating or DHW operating mode is displayed by the
relative symbols or .
After the checks, deactivate the function by switching the boiler
off and then back on again.

52
3.22 CASING REMOVAL. • Front panel (Fig. 54).
To facilitate boiler maintenance the casing can be completely 4) Remove the cover caps (c) and loosen screws (d).
removed as follows:
5) Pull the front panel (e) towards you and release it from its lower
• Lower grid (Fig. 53). seat.
1) Loosen the two screws (a). • Front (Fig. 55).

INSTALLER
2) Press the hooks inwards, which block the lower grid (b). 6) Loosen the two screws (g).
3) Remove the grid (b). 7) Pull the front (f) slightly towards you.
8) Release front (f) from pins (h) pulling it towards you while
pushing it upwards at the same time.

USER
3
3
2

2 4
a

a b e

MAINTENANCE TECHNICIAN
1 5
d
c
1 4
d e1
53 c 54

8 8

6 f 6

g
55

53
• Control panel (Fig. 56). • Sides (Fig. 57).
9) Press the hooks on the side of the control panel (i). 11) Loosen screws (k) of side fastening (j).
10) Tilt the control panel (i) towards you. 12) Remove the sides by extracting them from their rear seat (Ref. X).
INSTALLER

10 9

i
USER

9
56

Ref.
Rif. X
MAINTENANCE TECHNICIAN

11 X

k X
X
11

12 k

12
X
11
X
j
k

11
j
k

57

54
4 TECHNICAL DATA. 4.1 VARIABLE HEAT OUTPUT.
N.B.: the power data in the table have been obtained with in-
take-exhaust pipe measuring 0.5 m in length. Gas flow rates refer
to net calorific value at a temperature of 15°C and at a pressure
of 1013 mbar.

Victrix Tera 28 1.
METHANE (G20) PROPANE (G31)
HEAT HEAT GAS FLOW RATE GAS FLOW RATE
MODULATION MODULATION
OUTPUT OUTPUT BURNER BURNER

(kW) (kcal/h) (%) (m3/h) (%) (kg/h)


28.3 24295 99 3.06 99 2.25
27.5 23650 97 2.98 97 2.19
D.H.W.
26.5 22790 93 2.87 92 2.11
25.5 21930 89 2.76 88 2.03
24.1 20717 85 2.61 82 1.91
23.5 20210 81 2.54 80 1.87
22.5 19350 78 2.44 75 1.79
21.5 18490 74 2.33 71 1.71
20.5 17630 70 2.22 67 1.63
19.5 16770 66 2.11 63 1.55
18.5 15910 62 2.01 59 1.47
17.5 15050 58 1.90 55 1.39
16.5 14190 54 1.79 51 1.31
15.5 13330 CH 50 1.68 47 1.24
14.5 12470 45 1.58 42 1.16
+
13.5 11610 41 1.47 38 1.08
12.5 10750 D.H.W. 37 1.36 34 1.00
11.5 9890 33 1.26 30 0.92
10.5 9030 29 1.15 26 0.84
9.5 8170 24 1.04 22 0.76
8.5 7310 20 0.93 18 0.68
7.5 6450 16 0.82 14 0.61
6.5 5590 11 0.72 10 0.53
5.5 4730 7 0.61 6 0.45
4.5 3870 2 0.50 2 0.37
4.3 3689 1 0.48 1 0.35
Victrix Tera 32 1.
METHANE (G20) PROPANE (G31)
HEAT HEAT GAS FLOW RATE GAS FLOW RATE
MODULATION
OUTPUT OUTPUT BURNER BURNER

(kW) (kcal/h) (%) (m3/h) (kg/h)


32.0 27520 99 3.45 2.53
31.0 26660 96 3.34 2.45
D.H.W.
30.0 25800 92 3.24 2.38
29.0 24940 89 3.13 2.30
28.0 24080 85 3.03 2.22
27.0 23220 81 2.92 2.14
26.0 22360 78 2.81 2.06
25.0 21500 74 2.70 1.98
24.0 20640 71 2.60 1.91
23.0 19780 67 2.49 1.83
22.0 18920 63 2.38 1.75
21.0 18060 60 2.28 1.67
20.0 17200 56 2.17 1.59
19.0 16340 53 2.06 1.51
18.0 15480 49 1.96 1.44
17.0 14620 CH 45 1.85 1.36
16.0 13760 + 42 1.74 1.28
15.0 12900 D.H.W. 38 1.63 1.20
14.0 12040 35 1.53 1.12
13.0 11180 31 1.42 1.04
12.0 10320 27 1.31 0.96
11.0 9460 24 1.21 0.88
10.0 8600 20 1.10 0.81
9.0 7740 17 0.99 0.73
8.0 6880 13 0.88 0.65
7.0 6020 9 0.77 0.57
6.0 5160 5 0.66 0.49
5.0 4300 2 0.55 0.41
4.9 4214 1 0.54 0.40

55
Victrix Tera 38 1.
METHANE (G20) PROPANE (G31)
HEAT HEAT GAS FLOW RATE GAS FLOW RATE
MODULATION MODULATION
OUTPUT OUTPUT BURNER BURNER

(kW) (kcal/h) (%) (m3/h) (%) (kg/h)


37.9 32594 D.H.W. 99 4.13 99 3.03
32.0 27520 CH + 80 3.46 81 2.54
6.3 5404 1 0.69 1 0.50
6.1 5246 D.H.W. 1 0.67 - -

4.2 COMBUSTION PARAMETERS.


G20 G31
Supply pressure mbar (mm H2O) 20 (204) 37 (377)
Victrix Tera 28 1
Gas nozzle diameter mm 5.00 3.80
Flue flow rate at nominal heat output kg/h 44 43
Flue flow rate at min heat output kg/h 8 7
CO2 at Nom./Min. Q. % 9.70 / 8.80 11.40 - 10.60
CO with 0% O2 at Nom./Min. Q. ppm 360 / 7 560 / 9
NOX with 0% O2 at Nom./Min. Q. mg/kWh 65 / 22 81 / 55
Flue temperature at nominal output °C 70 70
Flue temperature at minimum output °C 64 63

Victrix Tera 32 1
Gas nozzle diameter mm 6.00 4.30
Flue flow rate at nominal heat output kg/h 51 50
Flue flow rate at min heat output kg/h 9 9
CO2 at Nom./Min. Q. % 9.50 - 8.60 11.20 / 10.00
CO with 0% O2 at Nom./Min. Q. ppm 300 / 5 430 / 5
NOX with 0% O2 at Nom./Min. Q. mg/kWh 56 / 18 89 / 39
Flue temperature at nominal output °C 57 60
Flue temperature at minimum output °C 58 60

Victrix Tera 38 1
Gas nozzle diameter mm 6.70 4.90
Flue flow rate at nominal heat output kg/h 63 65
Flue flow rate at min heat output kg/h 11 12
CO2 at Nom./Min. Q. % 9.20 / 8.50 10.09 / 9.41
CO with 0% O2 at Nom./Min. Q. ppm 290 / 10 292 / 7
NOX with 0% O2 at Nom./Min. Q. mg/kWh 70 / 14 71 / 19
Flue temperature at nominal output °C 59 59
Flue temperature at minimum output °C 51 54

Combustion parameters: measuring conditions of useful efficien-


cy (flow temperature/return temperature= 80 / 60 °C), ambient
temperature reference = 15°C.

56
4.3 TECHNICAL DATA.
Victrix Tera 28 1 Victrix Tera 32 1 Victrix Tera 38 1
Domestic hot water nominal heat input kW (kcal/h) 28.8 (24773) 32.6 (28047) 39,0 (33567)
Central heating nominal heat input kW (kcal/h) 24.6 (21194) 28.6 (24588) 32,7 (28139)
Minimum heat input kW (kcal/h) 4.5 (3862) 5.1 (4413) 6,3 (5436)
Domestic hot water nominal heat output (useful) kW (kcal/h) 28.3 (24295) 32.0 (27520) 37,9 (32594)
Central heating nominal heat output (useful) kW (kcal/h) 24.1 (20717) 28.0 (24080) 32,0 (27520)
Minimum heat output (useful) kW (kcal/h) 4.3 (3689) 4.9 (4214) 6,1 (5246)
*Effective thermal efficiency 80/60 Nom./Min. % 97.8 / 95.5 97.9 / 95.5 97,8 / 96,5
*Effective thermal efficiency 50/30 Nom./Min. % 106.1 / 106.1 106.0 / 108.2 105,3 / 104,3
*Effective thermal efficiency 40/30 Nom./Min. % 108.2 / 108.3 107.9 / 108.2 107,1 / 107,4
Casing losses with burner On/Off (80-60°C) % 0.34 / 0.20 0.30 / 0.30 0,24 / 0,40
Chimney losses with burner On/Off (80-60°C) % 0.02 / 1.70 0.02 / 2.20 0,01 / 2,50
Central heating circuit max. operating pressure bar 3 3 3
Maximum heating temperature °C 90 90 90
Adjustable central heating temperature (max operating field) °C 20 - 85 20 - 85 20 - 85
System expansion vessel total volume l 5.8 6.4 7,1
Expansion vessel pre-charged pressure bar 1.0 1.0 1,0
Appliance water content l 2.2 2.41 3,8
Head available with 1000 l/h flow rate kPa (m H2O) 26.4 (2.7) 30.1 (3.1) 30,7 (3,1)
Hot water production useful heat output kW (kcal/h) 28.3 (24295) 32.0 (27520) 37,9 (32594)
Domestic hot water adjustable temperature °C 30 - 60 30 - 60 30 - 60
Domestic hot water circuit min. pressure (dynamic) bar 0.3 0.3 0,3
Domestic hot water circuit max. operating pressure bar 10 10 10
Flow rate capacity in continuous duty (∆T 30°C) l/min 14.1 16.5 18,6
Weight of full boiler kg 35.8 37.91 40,50
Weight of empty boiler kg 33.6 35.50 36,70
Electrical connection V/Hz 230 / 50 230 / 50 230 / 50
Nominal power absorption A 0.6 0.76 0,95
Installed electric power W 80 105 120
Pump absorbed power W 41 51 54
EEI value - ≤ 0.20 - Part. 3 ≤ 0.20 - Part. 3 ≤ 0,20 - Part. 3
Equipment electrical system protection - IPX5D IPX5D IPX5D
Max temperature of combustion products °C 75 75 75
Max. flue overheating temperature °C 120 120 120
NOX class - 6 6 6
Weighted NOX mg/kWh 35.0 30.0 39,0
Weighted CO mg/kWh 20.0 15.0 68,0
C13 / C13x / C33 / C33x / C43 / C43x / C53 / C63 / C83
Type of appliance (**)
/ C83x / C93 / C93x / B23 / B33 / B53p
Victrix Tera 38 1 C13 / C13x / C33 / C33x / C43 / C43x / C53 / C53x / C63 / C63x / C83 / C83x
(**) Type of appliance / C93 / C93x / B23p / B33 / B53p
Category II 2H3P

- The data relating to domestic hot water performance refer to - * Efficiencies refer to the net calorific value.
a dynamic inlet pressure of 2 bar and an inlet temperature of - The weighted NOx value refer to the net calorific value.
15°C; the values are measured immediately at the boiler outlet,
considering that to obtain the data declared, mixing with cold
water is required.

57
4.4 KEY FOR DATA NAMEPLATE.

Md Cod. Md
Sr N° CHK Cod. PIN
Type
Qnw/Qn min. Qnw/Qn max. Pn min. Pn max.
PMS PMW D TM
NOx Class
CONDENSING

N.B.: the technical data are provided on the data plate on the boiler

ENG
Md Model
Cod. Md Model code
Sr N° Serial Number
CHK Check
Cod. PIN PIN code
Type Type of installation (ref. CEN TR 1749)
Qnw min. Minimum DHW heat input
Qn min. Central heating minimum heat input
Qnw max. DHW maximum heat input
Qn max. Central heating maximum heat input
Pn min. Minimum heat output
Pn max. Maximum heat output
PMS Maximum system pressure
PMW Maximum domestic hot water pressure
D Specific flow rate
TM Maximum operating temperature
NOx Class NOx Class
CONDENSING Condensing boiler

58
4.5 TECHNICAL PARAMETERS FOR COMBINATION BOILERS (IN COMPLIANCE WITH REGULATION 813/2013).
Efficiencies in the following tables refer to the gross calorific value.
Model/s: Victrix Tera 28 1
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: YES
Element Symbol Value Unit Element Symbol Value Unit
Seasonal energy efficiency of central
Nominal heat output Pn 24 kW ηs 93 %
heating
For heating only boilers and combination boilers: useful heat output For central heating only and combination boilers: effective efficiency
At nominal heat output in high temper- At nominal heat output in high temper-
P4 24.0 kW η4 88.1 %
ature mode (*) ature mode (*)
At 30% of nominal heat output in a low At 30% of nominal heat output in a low
P1 8.0 kW η1 97.6 %
temperature mode (**) temperature mode (**)
Auxiliary electricity consumption Other items
At full load elmax 0.010 kW Heat loss in standby Pstby 0.057 kW
At partial load elmin 0.005 kW Ignition burner energy consumption Pign 0.000 kW
mg /
In standby mode PSB 0.002 kW Emissions of nitrogen oxides NOX 35
kWh
For combination central heating appliances
Domestic hot water production effi-
Stated load profile XL ηWH 87 %
ciency
Daily electrical power consumption Qelec 0.122 kWh Daily gas consumption Qfuel 22.406 kWh
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return
temperature.

Model/s: Victrix Tera 32 1


Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: YES
Element Symbol Value Unit Element Symbol Value Unit
Seasonal energy efficiency of central
Nominal heat output Pn 28 kW ηs 93 %
heating
For heating only boilers and combination boilers: useful heat output For central heating only and combination boilers: effective efficiency
At nominal heat output in high temper- At nominal heat output in high temper-
P4 28.0 kW η4 87.85 %
ature mode (*) ature mode (*)
At 30% of nominal heat output in a low At 30% of nominal heat output in a low
P1 9.3 kW η1 97.58 %
temperature mode (**) temperature mode (**)
Auxiliary electricity consumption Other items
At full load elmax 0.012 kW Heat loss in standby Pstby 0.0573 kW
At partial load elmin 0.006 kW Ignition burner energy consumption Pign 0.000 kW
mg /
In standby mode PSB 0.002 kW Emissions of nitrogen oxides NOX 30
kWh
For combination central heating appliances
Domestic hot water production effi-
Stated load profile XL ηWH 87 %
ciency
Daily electrical power consumption Qelec 0.131 kWh Daily gas consumption Qfuel 22.362 kWh
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return
temperature.

59
Model/s: Victrix Tera 38 1
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: YES
Element Symbol Value Unit Element Symbol Value Unit
Seasonal energy efficiency of central
Nominal heat output Pn 32 kW ηs 93 %
heating
For heating only boilers and combination boilers: useful heat output For central heating only and combination boilers: effective efficiency
At nominal heat output in high temper- At nominal heat output in high temper-
P4 32.0 kW η4 88.1 %
ature mode (*) ature mode (*)
At 30% of nominal heat output in a low At 30% of nominal heat output in a low
P1 10.6 kW η1 97.7 %
temperature mode (**) temperature mode (**)
Auxiliary electricity consumption Other items
At full load elmax 0.042 kW Heat loss in standby Pstby 0.055 kW
At partial load elmin 0.007 kW Ignition burner energy consumption Pign 0.000 kW
mg /
In standby mode PSB 0.002 kW Emissions of nitrogen oxides NOX 34
kWh
For combination central heating appliances
Domestic hot water production effi-
Stated load profile XL ηWH 85 %
ciency
Daily electrical power consumption Qelec 0.124 kWh Daily gas consumption Qfuel 23.108 kWh
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return
temperature.

60
4.6 PRODUCT FICHE (IN COMPLIANCE WITH
REGULATION 811/2013).

Victrix Tera 28 1 Victrix Tera 32 1

punto soluzioni srl "!! ABC


VICTRIX TERA 28 1 punto soluzioni srl "!! ABC
VICTRIX TERA 32 1

LXL LXL

A+++ A+ A+ A+++ A+ A+
A++ A ++ A A A++ A ++ A A
A+ B A+ B
A A C A A C
B D B D
C E C E
D F D F

24
54
kW
28
54
kW
34
52 dB kW 34
55 dB kW

2019 811/2013 2019 811/2013

Parameter Value Parameter Value


Annual energy consumption for the central heating Annual energy consumption for the central heating
44.1 GJ 51 GJ
mode (QHE) mode (QHE)
Annual electricity consumption for the domestic hot Annual electricity consumption for the domestic hot
27 kWh 29 kWh
water function (AEC) water function (AEC)
Annual fuel consumption for the domestic hot water Annual fuel consumption for the domestic hot water
17 GJ 17 GJ
function (AFC) function (AFC)
Room central heating seasonal efficiency (ηs) 93 % Room central heating seasonal efficiency (ηs) 93 %
Water heating energy efficiency ( ηwh) 87 % Water heating energy efficiency ( ηwh) 87 %

For proper installation of the appliance refer to chapter 1 of this


booklet (for the installer) and current installation regulations.
For proper maintenance refer to chapter 3 of this booklet (for
the maintenance technician) and adhere to the frequencies and
methods set out herein.

61
Victrix Tera 38 1

punto soluzioni srl "!! ABC


VICTRIX TERA 38 1

LXL

A+++ A+ A+
A++ A ++ A A
A+ B
A A C
B D
C E
D F

32
54
kW
34
54 dB kW

2019 811/2013

Parameter Value
Annual energy consumption for the central heating
99 GJ
mode (QHE)
Annual electricity consumption for the domestic hot
27 kWh
water function (AEC)
Annual fuel consumption for the domestic hot water
18 GJ
function (AFC)
Room central heating seasonal efficiency (ηs) 93 %
Water heating energy efficiency ( ηwh) 85 %

62
4.7 PARAMETERS FOR FILLING IN THE PACKAGE The remaining values must be obtained from the technical data
FICHE. sheets of the products used to make up the assembly (e.g. solar
In case you should wish to install an assembly, starting from the devices, integration heat pumps, temperature controllers).
Victrix Tera (28, 32 or 38) boiler, use the assembly charts in Fig. Use board Fig. 60 for “assemblies” related to the central heating
60 and 63. mode (e.g.: boiler + temperature controller).
To complete it properly, fill the relevant spaces (as shown in the Use board Fig. 63 for “assemblies” related to the domestic hot
assembly sheet facsimile Fig. 58 and 61) with the values shown water function (e.g.: boiler + solar thermal system).
in tables (Fig.  59 and 62.

Facsimile for filling in the package fiche for room central heating systems.

1
Seasonal central heating energy efficiency of the boiler
‘I’ %
Temperature control Class I = 1 %, Class II = 2 %, 2
From temperature Class III = 1.5 %, Class IV = 2 %,
Class V = 3 %, Class VI = 4 %, + %
control board Class VII = 3.5 %, Class VIII = 5 %

Supplementary boiler Seasonal central heating energy efficiency of the room


(%)
From boiler board 3
( - ‘I’ ) x 0.1 = ± %
Solar contribution Classification of the
From the board of the solar device tank
Efficiency of the A* = 0.95, A = 0.91,
Dimensions of the Volume of the
manifold (in %) B = 0.86, C = 0.83,
manifold (in m2) tank (in m3)
D-G = 0.81 4
( ‘III’ x + ‘IV’ x ) x (0.9 x ( / 100) x = + %
Supplementary heat pump Seasonal central heating energy efficiency of the
From the heat pump room (%) 5
board
( - ‘I’ ) x ‘II’ = + %
Solar contribution and supplementary heat pump
4 5 6
Select the lowest
value 0.5 x O 0.5 x = - %
7
Seasonal central heating energy efficiency of the set
%
Seasonal central heating energy efficiency class of the set

G F E D C B A A+ A++ A+++
< 30 % ≥ 30 % ≥ 34 % ≥ 36 % ≥ 75 % ≥ 82 % ≥ 90 % ≥ 98 % ≥ 125 %≥ 150 %

Boiler and supplementary heat pump installed with low temperature heat emitters
at 35 °C?
7
FFrom the board of the heat
pump
+ ( 50 x ‘II’ ) =
%
The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy
efficiency after installation since such efficiency is affected by additional factors, such as the heat loss
in the distribution system and the size of the products compared to the size and features of the building.

58

63
Parameters for filling in the assembly chart.

Parameter Victrix Tera 28 1 Victrix Tera 32 1 Victrix Tera 38 1


‘I’ 93 93 93
‘II’ * * *
‘III’ 1.11 0.95 0.84
‘IV’ 0.44 0.37 0.33

* to be established by means of table 5 of Regulation 811/2013 in case of “assembly” including a heat pump to integrate the
boiler. In this case the boiler must be considered as the main appliance of the assembly.
59

Room central heating system package fiche.

1
Seasonal central heating energy efficiency of the boiler ____ %
Temperature control Class I = 1 %, Class II = 2 %, 2
From temperature Class III = 1.5 %, Class IV = 2 %,
Class V = 3 %, Class VI = 4 %, + %
control board Class VII = 3.5 %, Class VIII = 5 %

Supplementary boiler Seasonal central heating energy efficiency of the room


(%)
From boiler board 3
( - ______ ) x 0.1 = ± %
Solar contribution Classification of the
From the board of the solar device tank
Efficiency of the A* = 0.95, A = 0.91,
Dimensions of the Volume of the
manifold (in %) B = 0.86, C = 0.83,
manifold (in m2) tank (in m3)
D-G = 0.81 4
( ____ x + ____ x ) x (0.9 x ( / 100) x = + %
Supplementary heat pump Seasonal central heating energy efficiency
From the heat pump (in %) 5
board
( - _____ ) x _______ = + %
Solar contribution and supplementary heat pump
4 5 6
Select the lowest
value 0.5 x O 0.5 x = - %
7
Seasonal central heating energy efficiency of the set
%
Seasonal central heating energy efficiency class of the set

G F E D C B A A+ A++ A+++
< 30 % ≥ 30 % ≥ 34 % ≥ 36 % ≥ 75 % ≥ 82 % ≥ 90 % ≥ 98 % ≥ 125 %≥ 150 %

Boiler and supplementary heat pump installed with low temperature heat emitters
at 35 °C?
7
From the board of the heat
pump
+ ( 50 x ______ ) =
%
The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy
efficiency after installation since such efficiency is affected by additional factors, such as the heat loss
in the distribution system and the size of the products compared to the size and features of the building.

60

64
Facsimile for filling in the domestic hot water production system package fiche.

Water heating energy efficiency of combination boiler 1


‘I’ %
Stated load profile:

Solar contribution
From the board of the solar device
Auxiliary electricity
2
( 1.1 x ‘I’ - 10 % ) x ‘II’ - ‘III’ - ‘I’ = + %
3
Water heating energy efficiency of the assembly in
average climate conditions %

Water heating energy efficiency class of the assembly in average climate conditions

G F E D C B A A+ A++ A+++
M < 27 % ≥ 27 % ≥ 30 % ≥ 33 % ≥ 36 % ≥ 39 % ≥ 65 % ≥ 100 % ≥ 130 % ≥ 163 %

L < 27 % ≥ 27 % ≥ 30 % ≥ 34 % ≥ 37 % ≥ 50 % ≥ 75 % ≥ 115 % ≥ 150 % ≥ 188 %

XL < 27 % ≥ 27 % ≥ 30 % ≥ 35 % ≥ 38 % ≥ 55 % ≥ 80 % ≥ 123 % ≥ 160 % ≥ 200 %

XXL < 28 % ≥ 28 % ≥ 32 % ≥ 36 % ≥ 40 % ≥ 60 % ≥ 85 % ≥ 131 % ≥ 170 % ≥ 213 %

Water heating energy efficiency class in colder and hotter climate conditions
3 2
Colder: - 0.2 x =
%
3 2
Hotter: + 0.4 x = %
The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy
efficiency after installation since such efficiency is affected by additional factors, such as the heat loss
in the distribution system and the size of the products compared to the size and features of the building.

61

65
Parameters for filling in the DHW package fiche.

Parameter Victrix Tera 28 1 Victrix Tera 32 1 Victrix Tera 38 1


‘I’ 87 87 85
‘II’ * * *
‘III’ * * *


* to be determined according to Regulation 811/2013 and transient calculation
methods as per Notice of the European Community no. 207/2014.
62

Domestic hot water production system package fiche.

Water heating energy efficiency of combination boiler 1


_____ %
Stated load profile:

Solar contribution
From the board of the solar device
Auxiliary electricity
2
( 1.1 x _____ - 10 % ) x _____ - ____ - ______ = + %
3
Water heating energy efficiency of the assembly in
average climate conditions %

Water heating energy efficiency class of the assembly in average climate conditions

G F E D C B A A+ A++ A+++
M < 27 % ≥ 27 % ≥ 30 % ≥ 33 % ≥ 36 % ≥ 39 % ≥ 65 % ≥ 100 % ≥ 130 % ≥ 163 %

L < 27 % ≥ 27 % ≥ 30 % ≥ 34 % ≥ 37 % ≥ 50 % ≥ 75 % ≥ 115 % ≥ 150 % ≥ 188 %

XL < 27 % ≥ 27 % ≥ 30 % ≥ 35 % ≥ 38 % ≥ 55 % ≥ 80 % ≥ 123 % ≥ 160 % ≥ 200 %

XXL < 28 % ≥ 28 % ≥ 32 % ≥ 36 % ≥ 40 % ≥ 60 % ≥ 85 % ≥ 131 % ≥ 170 % ≥ 213 %

Water heating energy efficiency class in colder and hotter climate conditions
3 2
Colder: - 0.2 x =
%
3 2
Hotter: + 0.4 x = %
The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy
efficiency after installation since such efficiency is affected by additional factors, such as the heat loss
in the distribution system and the size of the products compared to the size and features of the building.

63

66
67
This instruction booklet

Cod. 1.040295ENG - rev. ST.002849/007 - 09/20


is made of ecological paper

immergas.com

Immergas S.p.A.
42041 Brescello (RE) - Italy
Tel. 0522.689011
Fax 0522.680617

IMMERGAS SPA - ITALY


CERTIFIED COMPANY
UNI EN ISO 9001:2015

Design, manufacture and post-sale assistance of gas


boilers, gas water heaters and related accessories

You might also like