Example 7: D Firas Mohamme Dr. Power Year Electrical 4
Example 7: D Firas Mohamme Dr. Power Year Electrical 4
Firas Mohammed
Example 7
A three-phase unbalanced source with the following phase-to-neutral voltages
300 120
Vabc 20090
100 30
is applied to the circuit in Figure below. The load series impedance per
phase is ZS = 10 + j40 and the mutual impedance between phases is Zm = j5.
The load and source neutrals are solidly grounded. Determine
1
(a) The load sequence impedance matrix, Z 012 A Z abc A
(b) The symmetrical components of voltage.
(c) The symmetrical components of current.
(d) The load phase currents.
(e) The complex power delivered to the load in terms of symmetrical
components, S 3 3(V0 I 0 V1 I1 V2 I 2 )
* * *
(f) The complex power delivered to the load by summing up the power in each
phase, S 3 3(Va I a Vb I b Vc I c )
* * *
Solution:
The results are
10 j50 0 0
Z 012 0 10 j35 0
0 0 10 j 35
26
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
42.2650 120
V012 193.1852 135
86.9473 84.8961
0.8289161.3099
I 012 5.3072150.9454
2.3886 158.9507
7.9070165.4600
I abc 5.819014.8676
2.7011 96.9315
S 3 1036 .8 j 3659 .6
Example 8
Draw the zero sequence network for the system shown in Figure below:
27
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Solution
Example 9
The neutral of each generator is grounded through a current limiting resistor of
8.333% on a 100MVA base. The generators are running at no-load at rated
voltage and in phase, all network data is expressed on a 100MVA base.
Find : fault current for 3-phase, 1-phase. L-L, L-L-G.
Item kV Rating % X1 % X2 % X0
G1 20 15 15 5
G2 20 15 15 5
T1 20/200 10 10 10
T2 20/200 10 10 10
L1-2 200 12.5 12.5 30
L1-3 200 15 15 35
L2-3 200 25 25 71.25
28
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Solution:
29
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
3-phase fault
Va1 10
I a1 j 4.54 p.u.
Z1 j 0.22
I af I a1 j 4.54 p.u.
1.00
j1.266 p.u.
j (0.35 0.22 0.22)
I af 3I a 0 j 3.80 p.u.
30
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Va1 1.00
I a1 j 2.816 p.u.
Z2Z0 j 0.35 * j 0.22
( Z1 ) j 0.22
Z2 Z0 j 0.35 j 0.22
Va1 Z1 I a1 1.00 ( j 0.22) * ( j 2.816)
I a2 j1.729 p.u.
Z2 j 0.22
Va1 Z1 I a1 1.00 ( j 0.22) * ( j 2.816)
I a0 j1.087 p.u.
Z0 j 0.35
I f I b I c 2 I ao (a 2 a)( I a1 I a 2 )
Example 10
Draw the positive, negative and zero sequence networks for the following at
bus 2.
(a) Balanced three-phase
(b) Single phase-to-ground
(c) Phase–to-phase
31
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
32
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
+ ve sequence
33
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Example 11
A L-L-G fault occurs at point B in the system shown below. Determine the
voltages and currents at the fault
∆- -∆
A B C D
G M
Xn= 0.03
X1= 0.2 X= 0.12 X= 0.1 X1= 0.3
X1= X2= 0.3
X2= 0.2 XO=1.4 X2= 0.4
XO= 0.08 XO= 0.1
M L-L-G
Phase B-Phase C-G
X1= 1
X2= 1
Solution: XO= oo
A L-L-G is represented by the parallel connection of the +Ve, -Ve and Zero
sequence networks.
Ia1 Ia2 Ia0
Z1
Va1 Va2 Va0
Z2 Zo
Ea
~
34
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
j0.3
A B C D
j0.12 j0.1
j0.3
j0.2 j1 j0.3
EG
~ ~ EM
~ EM
j0.12 j0.1
j0.3
j0.2 j1 j0.4
j0.12
j1.4
j0.08 j0.1
3Zn=j0.09
0.3 1 0.2
j (( ) 0.1 0.3)( 0.12)
Z1 2 1 0 . 2
0.3 1 0.2
( 0.1 0.3) ( 0.12)
2 1 0.2
0.3 1 0.2
j (( ) 0.1 0.4)( 0.12)
Z2 2 1 0. 2
0.3 1 0.2
( 0.1 0.4) ( 0.12)
2 1 0.2
0.14
j (0.12)( 0.1)
Zo 2
0.14
(0.12 0.1)
2
Ea
I a1 3.9 p.u.
Z2ZO
Z1
Z2 ZO
ZO
I a 2 I a1 1.34 p.u.
Z2 Z O
I ao I a1 I a 2 2.56 p.u.
Vao Va1 Va 2 I a 2 Z 2 j 0.267 p.u.
I a I ao I a1 I a 2 0
36
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Example 12
Consider a system with sequence impedances given by Z1 = j0.2577, Z2
=j0.2085, and Z0 = j0.14; find the voltages and currents at the fault point for a
single line-to-ground fault.
Solution:
The sequence currents are given by
1
I 0 I1 I 2
j (0.2577 0.2085 0.14)
Ib Ic 0
The sequence voltages are as follows:
V1 Ea1 I1Z1
0.23 p.u.
The phase voltages are thus
Va Va 0 Va1 Va 2 0
Vb a 2Va 0 aVa1 Va 2
(1240 )(0.57) (1120 )(0.34) (0.23)
0.86 113.64 p.u.
Vc aVa 0 a 2Va1 Va 2
(1120 )(0.57) (1240 )(0.34) (0.23)
0.86113.64 p.u.
Example 13
Three 15-MVA, 30-kV synchronous generators A, B, and C are connected
via three reactors to a common bus bar, as shown in Figure below. The
neutrals of generators A and B are solidly grounded, and the neutral of
generator C is grounded through a reactor of 2.0 Ω. The generator data and the
reactance of the reactors are tabulated below. A line-to-ground fault occurs on
phase a of the common bus bar. Neglect prefault currents and assume
generators are operating at their rated voltage. Determine the fault current in
phase a.
38
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Solution:
The generator base impedance is
The reactor per-unit reactance, and the per-unit generator C neutral reactor are
39
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed
Example 14
Repeat example 15 for a bolted line-to-line fault between phases b and c.
Solution:
The positive-sequence fault current in phase a is
Example 15
Repeat example 15 for a bolted double line-to-ground fault on phases b
and c.
Solution:
The positive- and zero-sequence fault currents in phase a are
40