0% found this document useful (0 votes)
253 views15 pages

Example 7: D Firas Mohamme Dr. Power Year Electrical 4

This document provides an example problem and solution regarding symmetrical components analysis of an unbalanced three-phase system with a line-to-line-to-ground fault. The example gives the sequence impedance matrix, symmetrical components of voltage and current, complex power calculations using both symmetrical components and phase quantities, and drawings of the positive, negative, and zero sequence networks for the faulted system. It also provides additional examples and solutions involving symmetrical components analysis of generators, transmission lines, and faults.

Uploaded by

Ahmad Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
253 views15 pages

Example 7: D Firas Mohamme Dr. Power Year Electrical 4

This document provides an example problem and solution regarding symmetrical components analysis of an unbalanced three-phase system with a line-to-line-to-ground fault. The example gives the sequence impedance matrix, symmetrical components of voltage and current, complex power calculations using both symmetrical components and phase quantities, and drawings of the positive, negative, and zero sequence networks for the faulted system. It also provides additional examples and solutions involving symmetrical components analysis of generators, transmission lines, and faults.

Uploaded by

Ahmad Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

4th Year Electrical Power Lecture 5-Part 4 Dr.

Firas Mohammed

Example 7
A three-phase unbalanced source with the following phase-to-neutral voltages
300  120 
 
Vabc   20090 
 100  30 
 
is applied to the circuit in Figure below. The load series impedance per
phase is ZS = 10 + j40 and the mutual impedance between phases is Zm = j5.
The load and source neutrals are solidly grounded. Determine
1
(a) The load sequence impedance matrix, Z 012  A Z abc A
(b) The symmetrical components of voltage.
(c) The symmetrical components of current.
(d) The load phase currents.
(e) The complex power delivered to the load in terms of symmetrical
components, S 3  3(V0 I 0  V1 I1  V2 I 2 )
* * *

(f) The complex power delivered to the load by summing up the power in each
phase, S 3  3(Va I a  Vb I b  Vc I c )
* * *

Solution:
The results are
10  j50 0 0 
Z 012   0 10  j35 0 
 0 0 10  j 35

26
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

 42.2650  120 
 
V012   193.1852  135 
86.9473  84.8961 
 
 0.8289161.3099 
 
I 012   5.3072150.9454 
2.3886  158.9507 
 
 7.9070165.4600 
 
I abc   5.819014.8676 
2.7011  96.9315 
 
S 3  1036 .8  j 3659 .6

Example 8
Draw the zero sequence network for the system shown in Figure below:

27
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

Solution

Example 9
The neutral of each generator is grounded through a current limiting resistor of
8.333% on a 100MVA base. The generators are running at no-load at rated
voltage and in phase, all network data is expressed on a 100MVA base.
Find : fault current for 3-phase, 1-phase. L-L, L-L-G.

Item kV Rating % X1 % X2 % X0
G1 20 15 15 5
G2 20 15 15 5
T1 20/200 10 10 10
T2 20/200 10 10 10
L1-2 200 12.5 12.5 30
L1-3 200 15 15 35
L2-3 200 25 25 71.25

28
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

Solution:

29
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

 3-phase fault

Va1 10
I a1     j 4.54 p.u.
Z1 j 0.22
I af  I a1   j 4.54 p.u.

 Single line - to- ground (S-L-G)


Ea
I ao  I a1  I a 2 
( Z ao  Z a1  Z a 2 )

1.00
   j1.266 p.u.
j (0.35  0.22  0.22)
I af  3I a 0   j 3.80 p.u.

30
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

 Line-Line fault (L-L)


I a0  0
Va1 10
I a1   I a 2     j 2.27 p.u.
Z1  Z 2 j (0.22  0.22)
I bf   I cf   j 3 ( j 2.27 )  3.936 p.u.

 Double line - to- ground (D-L-G)

Va1 1.00
I a1     j 2.816 p.u.
Z2Z0 j 0.35 * j 0.22
( Z1  ) j 0.22 
Z2  Z0 j 0.35  j 0.22
Va1  Z1 I a1 1.00  ( j 0.22) * ( j 2.816)
I a2    j1.729 p.u.
Z2 j 0.22
Va1  Z1 I a1 1.00  ( j 0.22) * ( j 2.816)
I a0    j1.087 p.u.
Z0 j 0.35
I f  I b  I c  2 I ao  (a 2  a)( I a1  I a 2 )

 2( j1.087)  ( j 2.816  j1.729)  j3.261p.u.

Example 10
Draw the positive, negative and zero sequence networks for the following at
bus 2.
(a) Balanced three-phase
(b) Single phase-to-ground
(c) Phase–to-phase

31
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

(d) Double phase-to-ground faults for the following system.


Transmission Line Data
Line Bus Bus Seq R X B Srat
1 2 3 pos 0.00000 0.16000 0.00000 1.0000
zero 0.00000 0.50000 0.00000
2 2 3 pos 0.00000 0.16000 0.00000 1.0000
zero 0.00000 0.50000 0.00000
Transformer Data
Trans. HV Bus LV Bus Seq R X C Srat
1 2 1 pos 0.00000 0.05000 1.00000 1.0000
Y Y zero 0.00000 0.05000
2 3 4 pos 0.00000 0.05000 1.00000 1.0000
Y D zero 0.00000 0.05000
Generator Data
No. Bus Srated Ra Xd" Xo Rn Xn Con
1 1 1.0000 0.0000 0.200 0.0500 0.0000 0.0400 Y
2 4 1.0000 0.0000 0.200 0.0500 0.0000 0.0400 Y

32
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

+ ve sequence

zero sequence - ve sequence

33
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

Example 11
A L-L-G fault occurs at point B in the system shown below. Determine the
voltages and currents at the fault

∆- -∆
A B C D
G M
Xn= 0.03
X1= 0.2 X= 0.12 X= 0.1 X1= 0.3
X1= X2= 0.3
X2= 0.2 XO=1.4 X2= 0.4
XO= 0.08 XO= 0.1
M L-L-G
Phase B-Phase C-G
X1= 1
X2= 1
Solution: XO= oo

A L-L-G is represented by the parallel connection of the +Ve, -Ve and Zero
sequence networks.
Ia1 Ia2 Ia0

Z1
Va1 Va2 Va0
Z2 Zo
Ea

~
34
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

j0.3
A B C D

j0.12 j0.1
j0.3

j0.2 j1 j0.3

EG
~ ~ EM
~ EM

+Ve Sequence Network


j0.3
A B C D

j0.12 j0.1
j0.3

j0.2 j1 j0.4

-Ve Sequence Network


j1.4
A B C j0.1

j0.12
j1.4

j0.08 j0.1

3Zn=j0.09

35 Zero Sequence Network


4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

0.3 1  0.2
j (( )  0.1  0.3)(  0.12)
Z1  2 1  0 . 2 
0.3 1  0.2
(  0.1  0.3)  (  0.12)
2 1  0.2
0.3 1  0.2
j (( )  0.1  0.4)(  0.12)
Z2  2 1  0. 2 
0.3 1  0.2
(  0.1  0.4)  (  0.12)
2 1  0.2
0.14
j (0.12)(  0.1)
Zo  2 
0.14
(0.12   0.1)
2
Ea
I a1   3.9 p.u.
Z2ZO
Z1 
Z2  ZO
ZO
I a 2   I a1  1.34 p.u.
Z2  Z O

I ao   I a1  I a 2  2.56 p.u.
Vao  Va1  Va 2  I a 2 Z 2  j 0.267 p.u.

I a  I ao  I a1  I a 2  0

I b  I ao  a 2 I a1  aI a 2  (3.84  j 4.54 ) p.u.

I c  I ao  aI a1  a 2 I a 2  (3.84  j 4.54 ) p.u.


Ground current Ig = Ia + Ib + Ic = 3Iao = -7.68 p.u.
Va = Vao + Va1 + Va2 = 3* j0.267 = j0.801 p.u.
Vb = Vc = 0

36
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

Example 12
Consider a system with sequence impedances given by Z1 = j0.2577, Z2
=j0.2085, and Z0 = j0.14; find the voltages and currents at the fault point for a
single line-to-ground fault.

Solution:
The sequence currents are given by

1
I 0  I1  I 2 
j (0.2577  0.2085  0.14)

 1.65  90 p.u.


Therefore
I a  3I 0  4.95  90  p.u.

Ib  Ic  0
The sequence voltages are as follows:

V1  Ea1  I1Z1

 10  (1.65  90 )(0.257790 )


 0.57 p.u.
V2  I 2 Z 2

 (1.65  90 )(0.208590 )


 0.34 p.u.
V0   I 0 Z0 [pp

 (1.65  90 )(0.1490 )


37
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

 0.23 p.u.
The phase voltages are thus

Va  Va 0  Va1  Va 2  0
Vb  a 2Va 0  aVa1  Va 2
 (1240 )(0.57)  (1120 )(0.34)  (0.23)
 0.86  113.64 p.u.
Vc  aVa 0  a 2Va1  Va 2
 (1120 )(0.57)  (1240 )(0.34)  (0.23)
 0.86113.64 p.u.

Example 13
Three 15-MVA, 30-kV synchronous generators A, B, and C are connected
via three reactors to a common bus bar, as shown in Figure below. The
neutrals of generators A and B are solidly grounded, and the neutral of
generator C is grounded through a reactor of 2.0 Ω. The generator data and the
reactance of the reactors are tabulated below. A line-to-ground fault occurs on
phase a of the common bus bar. Neglect prefault currents and assume
generators are operating at their rated voltage. Determine the fault current in
phase a.

38
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

Solution:
The generator base impedance is

The reactor per-unit reactance, and the per-unit generator C neutral reactor are

The positive-sequence impedance network, and the zero sequence impedance


network is shown in Figure below.

The positive-sequence impedance is

The negative-sequence impedance network is the same as the positive-


sequence impedance network, except for the value of the generator negative-
sequence reactance. Therefore, the negative-sequence impedance is

39
4th Year Electrical Power Lecture 5-Part 4 Dr. Firas Mohammed

The zero-sequence impedance is

The line-to-ground fault current in phase a is

Example 14
Repeat example 15 for a bolted line-to-line fault between phases b and c.

Solution:
The positive-sequence fault current in phase a is

The fault current is

Example 15
Repeat example 15 for a bolted double line-to-ground fault on phases b
and c.

Solution:
The positive- and zero-sequence fault currents in phase a are

The fault current is

40

You might also like