4.1 Introduction
The per-unit (pu) system is used extensively in power system
calculations. The representation simplifies the vast scaling of sizes from
super-large generation and transmission networks to the industrial distribution
system or a residential load. The definition of the per-unit value of any
quantity is given as:
(1)
(2)
(3)
(4)
(5)
If any two of these quantities are chosen arbitrarily, the other two become
fixed. For example, selecting base values for voltage and power fixes the base
1
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
values for current and impedance. Therefore, on a per phase basis the
following relationships hold:
(6)
(7)
EXAMPLE 4.1
Calculate the base impedance and base current for a single-phase system if the
base voltage is 7.2 kV and the base apparent power is 10 MVA.
For three-phase systems, we use the total or three-phase power and the
line-to-line voltage as the base. For currents and impedance values, it is
common practice to convert the system to a wye-connected network, and use
the phase current and phase impedance as the bases. Hence, the base
impedance and the base current can be computed directly from the three-phase
values of the base apparent power and the line-to-line base voltage. Delta-
connections for the moment are converted to wye-connected equivalents.
Recall for wye-connections, VLL= √3Vp, and from Equations 8 and 7 we
find:
(8)
2
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
and
EXAMPLE 4.2
A three-phase system delivers 18,000 kW to a pure resistive wye-connected
load. The line-to-line voltage at the load terminals is 108 kV. Assuming the
three-phase power base is 30,000 kVA and the voltage base is 120 kV, find
the following per unit quantities for the load:
a) the per unit voltage,
b) the per unit power,
c) the per unit current, and
d) the per unit impedance.
3
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
4
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
To verify the results, first calculate the actual current, which is:
To verify the results, first calculate the actual impedance, which is:
5
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
(9)
(10)
6
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
EXAMPLE 4.3
A three-phase 13.0 kV transmission line delivers 8 MVA at 13.6 kV to a
resistive load. The per phase impedance of the line is (0.01 + j0.05) p.u. on a
13.0 kV, 8 MVA base. What is the voltage drop across the line in per unit and
in volts?
a) Choose the base voltage to be 13 kV and the base power equal to 8 MVA.
The base current and the load current are:
b) The actual values for the line-to-line voltage drop and the phase voltage
drop are:
7
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
EXAMPLE 4.4
The per phase reactance of a three-phase, 220 kV, 6.25 kVA transmission line
is 8.4ohm. Find the reactance value in per unit, based on the rated values of
the line. Convert the per unit reactance value to a 230 kV, 7.5 kVA base.
a)
b)
8
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
EXAMPLE 4.5
Consider the system in Figure 1 below. Find the new per-unit values for each
element of the system based on a 2.0 MVA system base. Draw the impedance
diagrams of the system.
The per-unit values for each element of the three-phase system shown above
are as follows:
Machine 1 1.00 MVA, 11 kV, Z = j0.1 pu
Machine 2 0.50 MVA, 11 kV, Z = j0.15 pu
Machine 3 2.00 MVA, 12 kV, Z = j0.05 pu
Transmission Line Z = 10 + j20 ohm
Transformer 1 2.00 MVA, 11 / 33 kV, Z = j0.15 pu
Transformer 2 3.00 MVA, 33 / 11 kV, Z = j0.10 pu
a) The power base for the entire system is 2.00 MVA. The base voltages are
chosen for the following areas as:
9
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
The per-unit values for each element of the above system can be obtained by
using Equation 10 as follow:
10
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
EXAMPLE 4.6
Draw an impedance diagram for the electric power system shown in Figure 4
showing all impedances in per unit on a 100-MVA base. Choose 20 kV as the
voltage base for generator. The three-phase power and line-line ratings are
given below.
G1 : 90 MVA 20 kV X = 9%
T1 : 80 MVA 20/200 kV X = 16%
T2 : 80 MVA 200/20 kV X = 20%
G2 : 90 MVA 18 kV X = 9%
Line: 200 kV X = 120 ohm
Load: 200 kV S = 48 MW +j64 Mvar
11
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
Solution:
The base voltage VBG1on the LV side of T1 is 20 kV. Hence the base on its
HV side is
This fixes the base on the HV side of T2 at VB2 = 200 kV, and on its LV side
at
The generator and transformer reactances in per unit on a 100 MVA base, are:
12
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
EXAMPLE 4.7
The one-line diagram of a three-phase power system is as shown in Figure 6.
Impedances are marked in per unit on a 100MVA, 400kV base. The load at
bus 2 is S2 = 15.93 MW-j33.4 Mvar, and at bus 3 is S3 = 77 MW +j14 Mvar.
It is required to hold the voltage at bus 3 at 400∟0 o kV. Working in per unit,
determine the voltage at buses 2 and 1.
13
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
Solution:
EXAMPLE 4.8
The one-line diagram of a three-phase power system is as shown in Figure 7.
The transformer reactance is 20 percent on a base of 100-MVA, 23/115-kV
and the line impedance is Z = j66.125ohm. The load at bus 2 is S2=184.8 MW
+j6.6 Mvar, and at bus 3 is S3 = 0MW+j20 Mvar. It is required to hold the
voltage at bus 3 at 115∟0o kV. Working in per unit, determine the voltage at
buses 2 and 1.
14
4th Year Electrical Power Lecture 4 Dr.Firas Mohammed
Solution:
15