DATASHEET - NZMB1-A100
Circuit-breaker, 3p, 100A
Part no. NZMB1-A100
Catalog No. 259079
EL-Nummer 4358704
(Norway)
Similar to illustration
Delivery program
Product range Circuit-breaker
Protective function System and cable protection
Standard/Approval IEC
Installation type Fixed
Release system Thermomagnetic release
Construction size NZM1
Number of poles 3 pole
Standard equipment Box terminal
Switching capacity
400/415 V 50 Hz Icu kA 25
Rated current = rated uninterrupted current
Rated current = rated uninterrupted current In = Iu A 100
Setting range
Overload trip
Ir A 80 - 100
Short-circuit releases
Non-delayed Ii = In x … 6 - 10
Short-circuit releases Irm A 600 - 1000
Technical data
General
Standards IEC/EN 60947
Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Ambient temperature, storage °C - 40 - + 70
Operation °C -25 - +70
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC g 20 (half-sinusoidal shock 20 ms)
60068-2-27
Safe isolation to EN 61140
Between auxiliary contacts and main contacts V AC 500
between the auxiliary contacts V AC 300
Mounting position Vertical and 90° in all directions
09/22/2021 Eaton 259079 ED2021 V83.0 EN 1/9
With XFI earth-fault release:
- NZM1, N1, NZM2, N2: vertical and
90° in all directions
with plug-in unit
- NZM1, N1, NZM2, N2: vertical, 90°
right/left
with withdrawable unit:
- NZM3, N3: vertical, 90° right/left
- NZM4, N4: vertical
with remote operator:
- NZM2, N(S)2, NZM3, N(S)3,
NZM4, N(S)4: vertical and 90° in all
directions
Direction of incoming supply as required
Degree of protection
Device In the operating controls area: IP20 (basic degree of protection)
Enclosures With insulating surround: IP40
With door coupling rotary handle: IP66
Terminations Tunnel terminal: IP10
Phase isolator and strip terminal: IP00
Other technical data (sheet catalogue) Temperature dependency, Derating
Circuit-breakers
Rated current = rated uninterrupted current In = Iu A 100
Rated surge voltage invariability Uimp
Main contacts V 6000
Auxiliary contacts V 6000
Rated operational voltage Ue V AC 440
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V 690
Use in unearthed supply systems V ≦ 440
Switching capacity
Rated short-circuit making capacity Icm
240 V Icm kA 63
400/415 V Icm kA 53
440 V 50/60 Hz Icm kA 53
Rated short-circuit breaking capacity Icn Icn
Icu to IEC/EN 60947 test cycle O-t-CO Icu kA
240 V 50/60 Hz Icu kA 30
400/415 V 50/60 Hz Icu kA 25
440 V 50/60 Hz Icu kA 25
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO Ics kA
240 V 50/60 Hz Ics kA 30
400/415 V 50/60 Hz Ics kA 25
440 V 50/60 Hz Ics kA 18.5
Maximum back-up fuse, if the expected short-circuit currents at the installation
location exceed the switching capacity of the circuit-breaker.
Utilization category to IEC/EN 60947-2 A
Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) Operations 20000
Lifespan, electrical
AC-1
400 V 50/60 Hz Operations 7500
415 V 50/60 Hz Operations 7500
Max. operating frequency Ops/h 120
Total break time at short-circuit ms < 10
Terminal capacity
Standard equipment Box terminal
Optional accessories Screw connection
Tunnel terminal
connection on rear
Round copper conductor
Box terminal
Solid mm
2 1 x (10 - 16)
09/22/2021 Eaton 259079 ED2021 V83.0 EN 2/9
2 x (6 - 16)
Stranded mm
2
1 x (10 - 70)
3)
2 x (6-25)
3)
Up to 95 mm² can be connected depending on the cable manufacturer.
Tunnel terminal
Solid mm
2 1 x 16
Stranded
1-hole mm
2 1 x (25 - 95)
Bolt terminal and rear-side connection
Direct on the switch
Solid mm
2 1 x (10 - 16)
2 x (6 - 16)
Stranded mm
2
1 x (10 - 70)
3)
2 x 25
3)
Up to 95 mm² can be connected depending on the cable manufacturer.
Al circular conductor
Tunnel terminal
Solid mm
2 1 x 16
Stranded
Stranded mm
2 1 x (25 - 95)
Bolt terminal and rear-side connection
Direct on the switch
Solid mm
2 1 x (10 - 16)
2 x (10 - 16)
Stranded mm
2 1 x (25 - 35)
2 x (25 - 35)
Cu strip (number of segments x width x segment thickness)
Box terminal
min. mm 2 x 9 x 0.8
max. mm 9 x 9 x 0.8
Copper busbar (width x thickness) mm
Bolt terminal and rear-side connection
Screw connection M6
Direct on the switch
min. mm 12 x 5
max. mm 16 x 5
Control cables
mm
2 1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation In A 100
Equipment heat dissipation, current-dependent Pvid W 21.9
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
09/22/2021 Eaton 259079 ED2021 V83.0 EN 3/9
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system
protection ([email protected] [AJZ716013])
Rated permanent current Iu A 100
Rated voltage V 440 - 440
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz kA 25
Overload release current setting A 80 - 100
Adjustment range short-term delayed short-circuit release A 0-0
Adjustment range undelayed short-circuit release A 600 - 1000
Integrated earth fault protection No
Type of electrical connection of main circuit Frame clamp
Device construction Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting No
DIN rail (top hat rail) mounting optional Yes
Number of auxiliary contacts as normally closed contact 0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as change-over contact 0
With switched-off indicator No
With under voltage release No
Number of poles 3
Position of connection for main current circuit Front side
Type of control element Rocker lever
Complete device with protection unit Yes
Motor drive integrated No
Motor drive optional No
Degree of protection (IP) IP20
09/22/2021 Eaton 259079 ED2021 V83.0 EN 4/9
Characteristics
09/22/2021 Eaton 259079 ED2021 V83.0 EN 5/9
Let-through current
09/22/2021 Eaton 259079 ED2021 V83.0 EN 6/9
Let-through energy
09/22/2021 Eaton 259079 ED2021 V83.0 EN 7/9
Dimensions
① Blow out area, minimum clearance to adjacent parts
09/22/2021 Eaton 259079 ED2021 V83.0 EN 8/9
Additional product information (links)
Temperature dependency, Derating http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=17.172
CurveSelect characteristics program http://www.eaton.eu/DE/Europe/Electrical/CustomerSupport/ConfigurationTools/CharacteristicsProgram/
index.htm
additional technical information for NZM power switch https://es-assets.eaton.com/DOCUMENTATION/PDF/nzm_technic_de_en.pdf
09/22/2021 Eaton Industries GmbH 9/9