Electrical Cable Sizing
Scope Of Presentation
General Considerations
Methodology
Case Study – OXY Project
Cable Electrical Data
Conclusion
Electrical Cable Sizing
1. General Considerations
Short Circuit Current Rating
Voltage Drop
Cable Current Rating
Max. cable loop impedance for earth fault
Other Frequency
Electrical Cable Sizing
2. Methodology
Full Load Current Calculation
Cable Volt Drop Calculation
HV Cable Sizing (Short Circuit Rating)
Resistance Data
Electrical Cable Sizing
3. Case Study – OXY Project
General Data
HV Cable Sizing
LV Cable Sizing
Electrical Cable Sizing
4. Cable Electrical Data
Cable Resistance
Cable Reactance
Cable Current Rating
Cable Short Circuit Rating
*Nexans Technical Data for
Electrical Cable Sizing
5. Conclusion
Current Rating
Correction of the cable current ampacity shall be
more than full current
Voltage Drop
Calculated voltage drop value shall be less than
project requirement
Electrical Cable Sizing
5. Conclusion
Thermal Short Circuit Capacity
Calculated short circuit value shall be more
than system’s short circuit rating
*The largest cable size shall be used based on the above
point
Electrical Cable Sizing
1.1 HV Cable Sizing
(Short Circuit Rating)
I × t
A=
k
where :
A Cable conductor cross-sectional area (mm2)
I Short circuit current (A)
t Duration of short circuit (s).
For feeders protected by circuit breakers, t = 0.4s.
For feeders protected by fuses, t = 0.25s.
K cable conductor material, insulation and the safe
temperature rise of the insulation.
Electrical Cable Sizing
1.2 Voltage Drop (DEP 33.64.10.10-Gen.)
< 5% based on continuous maximum current loading
and rated voltage in A.C cables
< 20% of the rated equipment voltage during motor
starting
< 5% from minimum system voltage at distribution
board and the minimum equipment operation voltage
in D.C cables
Electrical Cable Sizing
1.3 Cable Current Rating
Onshore (Refer to section 1.3.1)
Depth of laying (IEE wiring regulation 16th
1991)
Soil thermal resistivity
Ground/ambient temperature
Electrical Cable Sizing
1.3 Cable Current Rating
Offshore (Refer to section 1.3.1)
Ground/ambient temperature
Grouping of cables
Electrical Cable Sizing
2.1 Full Load Current Calculation
Refer to Vendor data or Handbook
Electrical Cable Sizing
2.1 Full Load Current Calculation
Formula
3-Phase Circuit for AC System
Single Phase Circuit for AC System
DC System
Electrical Cable Sizing
2.2 Cable Volt Drop Calculation
3-Phase Circuit for A.C System
Single Phase Circuit for A.C System
D.C System
Electrical Cable Sizing
2.3 HV Cable Sizing
(Short Circuit Rating)
HV power cables will also be sized
based on their short circuit withstand
capability
Electrical Cable Sizing
2.3 HV Cable Sizing
(Short Circuit Rating)
I × t
A=
k
where :
A Cable conductor cross-sectional area (mm2)
I Short circuit current (A)
t Duration of short circuit (s).
For feeders protected by circuit breakers, t = 0.4s.
For feeders protected by fuses, t = 0.25s.
K cable conductor material, insulation and the safe
temperature rise of the insulation (Refer to Appendix – B).
Electrical Cable Sizing
2.4 Resistance Data
Normally resistance of cable is provided at
20oC by vendor
Electrical Cable Sizing
2.4 Resistance Data
Formula for actual resistance as a function of
temperature:
R = Ro (1 + A (T - 20oC))
Ro : Resistance at T = 20oC
T : Conductor temperature oC
Α : 0.00393 for copper
Electrical Cable Sizing
3.1 General Data
Correction factor for HV & LV single cables is
0.94 x 1 = 0.94
Correction factor for HV & LV multicore cables is
0.94 x 0.85 = 0.80
Starting current for all 6.6kV motors < 550% of full
load current
Starting current of low voltage motor < 600% of full
load current
Electrical Cable Sizing
3.1 General Data
Voltage drop under steady state and motor starting
conditions with the following limitations:
4% during steady state condition from origin of supply and
user terminals
20% during motor starting
2% on feeders to lighting and small power distribution boards
2.5% average on lighting and small power sub-circuits
4% for d.c systems
Electrical Cable Sizing
3.2 HV Cable Sizing
Short circuits conditions
6.6kV cable sizing calculation
Electrical Cable Sizing
3.3 LV Cable Sizing
Short Circuit Conditions
415V Cable sizing calculations
Electrical Cable Sizing
3-Phase Circuit for A.C System
kW ×1000
I FL =
3 × VSYS × COSθ × EFF
Where:
kW Equipment Load
VSYS System voltage (V)
IFL Full load current (A)
θ Angle in which the current lags the voltage (degree)
Eff Power Efficiency
Electrical Cable Sizing
Single phase circuit for AC system
kW ×1000
I FL =
VSYS × COSθ × EFF
Electrical Cable Sizing
D.C System
kW × 1000
I FL =
VSYS
Electrical Cable Sizing
3-Phase Circuit for A.C System
3 × l × I FL × ( R cos θ + X sin θ ) ×100
%VDROP =
VSYS × n ×1000
Where:
VSYS System voltage (V)
%VDROP Volt drop (%)
l Length (m)
IFL Full load current (A)
R Cable resistance (Ω / km)
X Cable reactance (Ω / km)
θ Angle in which the current lags the voltage (degree)
n Number of cables in parallel per phase
Electrical Cable Sizing
Single Phase Circuit for A.C system
2 × l × I FL × ( R cos θ + X sin θ ) ×100
%VDROP =
VSYS × n ×1000
Electrical Cable Sizing
D.C System
2 × l × I FL × R × 100
%VDROP =
VSYS × n × 1000
Electrical Cable Sizing