Electrical Cable Sizing Presentation

The document discusses the methodology for electrical cable sizing. It covers general considerations like short circuit ratings and voltage drop. It then describes calculating full load current, voltage drop, and using cable ratings to select appropriately sized high voltage and low voltage cables. A case study of an OXY project is presented as an example application of the cable sizing methodology.

Uploaded by

zona amrulloh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (4 votes)
1K views29 pages

Electrical Cable Sizing Presentation

The document discusses the methodology for electrical cable sizing. It covers general considerations like short circuit ratings and voltage drop. It then describes calculating full load current, voltage drop, and using cable ratings to select appropriately sized high voltage and low voltage cables. A case study of an OXY project is presented as an example application of the cable sizing methodology.

Uploaded by

zona amrulloh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

Electrical Cable Sizing

Scope Of Presentation
 General Considerations
 Methodology
 Case Study – OXY Project
 Cable Electrical Data
 Conclusion

Electrical Cable Sizing


1. General Considerations
 Short Circuit Current Rating
 Voltage Drop
 Cable Current Rating
 Max. cable loop impedance for earth fault
 Other Frequency

Electrical Cable Sizing


2. Methodology
 Full Load Current Calculation

 Cable Volt Drop Calculation

 HV Cable Sizing (Short Circuit Rating)

 Resistance Data

Electrical Cable Sizing


3. Case Study – OXY Project
 General Data

 HV Cable Sizing

 LV Cable Sizing

Electrical Cable Sizing


4. Cable Electrical Data
 Cable Resistance
 Cable Reactance
 Cable Current Rating
 Cable Short Circuit Rating

*Nexans Technical Data for

Electrical Cable Sizing


5. Conclusion
 Current Rating
 Correction of the cable current ampacity shall be
more than full current

 Voltage Drop
 Calculated voltage drop value shall be less than
project requirement

Electrical Cable Sizing


5. Conclusion
 Thermal Short Circuit Capacity
 Calculated short circuit value shall be more
than system’s short circuit rating

*The largest cable size shall be used based on the above


point

Electrical Cable Sizing


1.1 HV Cable Sizing
(Short Circuit Rating)

I × t
A=
k
where :
A Cable conductor cross-sectional area (mm2)
I Short circuit current (A)
t Duration of short circuit (s).
For feeders protected by circuit breakers, t = 0.4s.
For feeders protected by fuses, t = 0.25s.
K cable conductor material, insulation and the safe
temperature rise of the insulation.

Electrical Cable Sizing


1.2 Voltage Drop (DEP 33.64.10.10-Gen.)

 < 5% based on continuous maximum current loading


and rated voltage in A.C cables

 < 20% of the rated equipment voltage during motor


starting

 < 5% from minimum system voltage at distribution


board and the minimum equipment operation voltage
in D.C cables

Electrical Cable Sizing


1.3 Cable Current Rating

 Onshore (Refer to section 1.3.1)


 Depth of laying (IEE wiring regulation 16th
1991)
 Soil thermal resistivity
 Ground/ambient temperature

Electrical Cable Sizing


1.3 Cable Current Rating

 Offshore (Refer to section 1.3.1)


 Ground/ambient temperature
 Grouping of cables

Electrical Cable Sizing


2.1 Full Load Current Calculation

 Refer to Vendor data or Handbook

Electrical Cable Sizing


2.1 Full Load Current Calculation
 Formula
 3-Phase Circuit for AC System

 Single Phase Circuit for AC System

 DC System

Electrical Cable Sizing


2.2 Cable Volt Drop Calculation
 3-Phase Circuit for A.C System

 Single Phase Circuit for A.C System

 D.C System

Electrical Cable Sizing


2.3 HV Cable Sizing
(Short Circuit Rating)

 HV power cables will also be sized


based on their short circuit withstand
capability

Electrical Cable Sizing


2.3 HV Cable Sizing
(Short Circuit Rating)

I × t
A=
k
where :
A Cable conductor cross-sectional area (mm2)
I Short circuit current (A)
t Duration of short circuit (s).
For feeders protected by circuit breakers, t = 0.4s.
For feeders protected by fuses, t = 0.25s.
K cable conductor material, insulation and the safe
temperature rise of the insulation (Refer to Appendix – B).

Electrical Cable Sizing


2.4 Resistance Data

 Normally resistance of cable is provided at


20oC by vendor

Electrical Cable Sizing


2.4 Resistance Data
 Formula for actual resistance as a function of
temperature:

R = Ro (1 + A (T - 20oC))

Ro : Resistance at T = 20oC
T : Conductor temperature oC
Α : 0.00393 for copper

Electrical Cable Sizing


3.1 General Data
 Correction factor for HV & LV single cables is
0.94 x 1 = 0.94

 Correction factor for HV & LV multicore cables is


0.94 x 0.85 = 0.80

 Starting current for all 6.6kV motors < 550% of full


load current

 Starting current of low voltage motor < 600% of full


load current
Electrical Cable Sizing
3.1 General Data
 Voltage drop under steady state and motor starting
conditions with the following limitations:

 4% during steady state condition from origin of supply and


user terminals

 20% during motor starting

 2% on feeders to lighting and small power distribution boards

 2.5% average on lighting and small power sub-circuits

 4% for d.c systems

Electrical Cable Sizing


3.2 HV Cable Sizing

 Short circuits conditions

 6.6kV cable sizing calculation

Electrical Cable Sizing


3.3 LV Cable Sizing

 Short Circuit Conditions

 415V Cable sizing calculations

Electrical Cable Sizing


3-Phase Circuit for A.C System

kW ×1000
I FL =
3 × VSYS × COSθ × EFF
Where:
kW Equipment Load
VSYS System voltage (V)
IFL Full load current (A)
θ Angle in which the current lags the voltage (degree)
Eff Power Efficiency

Electrical Cable Sizing


Single phase circuit for AC system

kW ×1000
I FL =
VSYS × COSθ × EFF

Electrical Cable Sizing


D.C System

kW × 1000
I FL =
VSYS

Electrical Cable Sizing


3-Phase Circuit for A.C System

3 × l × I FL × ( R cos θ + X sin θ ) ×100


%VDROP =
VSYS × n ×1000
Where:
VSYS System voltage (V)
%VDROP Volt drop (%)
l Length (m)
IFL Full load current (A)
R Cable resistance (Ω / km)
X Cable reactance (Ω / km)
θ Angle in which the current lags the voltage (degree)
n Number of cables in parallel per phase

Electrical Cable Sizing


Single Phase Circuit for A.C system

2 × l × I FL × ( R cos θ + X sin θ ) ×100


%VDROP =
VSYS × n ×1000

Electrical Cable Sizing


D.C System

2 × l × I FL × R × 100
%VDROP =
VSYS × n × 1000

Electrical Cable Sizing