Setting Up PowerFlex 70 Drive With Encoder As Speed Reference

This document provides instructions for setting up a PowerFlex 70 drive to use an encoder as the speed reference for an existing machine. Key steps include: - Setting parameter P90 to "Encoder" - Configuring parameter P412 for the encoder type - Setting parameter P413 to the encoder's pulses per revolution - Setting parameter P190 to "Bipolar" if needed for a quadrature encoder - Ordering an encoder feedback option board if the drive does not have one installed already - Verifying encoder polarity is correct to avoid speed reference differences
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views

Setting Up PowerFlex 70 Drive With Encoder As Speed Reference

This document provides instructions for setting up a PowerFlex 70 drive to use an encoder as the speed reference for an existing machine. Key steps include: - Setting parameter P90 to "Encoder" - Configuring parameter P412 for the encoder type - Setting parameter P413 to the encoder's pulses per revolution - Setting parameter P190 to "Bipolar" if needed for a quadrature encoder - Ordering an encoder feedback option board if the drive does not have one installed already - Verifying encoder polarity is correct to avoid speed reference differences
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

01/03/2019 52442 - Setting up PowerFlex 70 drive with Encoder as Speed Reference

Setting up PowerFlex 70 drive with Encoder as Speed Reference


52442 | Date Created: 05/27/2008 | Last Updated: 01/11/2018
Print
Access Level: Everyone

Question
My drive is required to follow the speed of an existing machine to a good degree of accuracy. Can I use an
encoder as its speed reference?

Environment
Bulletin 20A PowerFlex 70 drive

Answer
Yes you can configure a PowerFlex 70 drive with an Encoder as a Speed Reference.

In addition to the normal setup parameters (accel / decel rates, minimum / maximum speed), set the following
parameters:

Parameter P90 [Speed Ref A Sel] = Encoder

Parameter P412 [Motor Feedback Type] = set to specifications of encoder

Parameter P413 [Encoder PPR] = set to specifications of encoder

Parameter P190 [Direction Mode] = Bipolar if required, but this will only work with a quadrature encoder

If your drive is an Enhanced Control drive and does not have the encoder card order the following part:

Encoder Feedback Option Board, 5/12 VDC, Incremental. 20A-ENC-1

Reference PowerFlex 70 Adjustable Frequency AC Drives Users Manual


(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20a-um001_-en-p.pdf) Publication
20A-UM001.

Reference PowerFlex 70 Adjustable Frequency AC Drive Technical Data Manual


(http://literature.rockwellautomation.com/idc/groups/literature/documents/td/20a-td001_-en-p.pdf) Publication
20A-TD001.

Verify that the drive encoder polarity is correct or you may cause speed reference differences based on
commanded and actual speed.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/52442/page/3 1/2
01/03/2019 52442 - Setting up PowerFlex 70 drive with Encoder as Speed Reference

Attachments

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or
subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not
intended to constitute application, design, software or other professional engineering advice or services.
Before making any decision or taking any action, which might affect your equipment, you should consult a
qualified professional advisor.

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY


OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY
TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY
IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF
ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE,
EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN


RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE
IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-
INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus,
this disclaimer may not apply to you.

This page is best viewed in Internet Explorer 11, Edge, Firefox 41, Chrome 46, Safari 9 or newer.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/52442/page/3 2/2

You might also like