1. The dual-duct system employs two air ducts, one for cold air and one for warm air, which are mixed in zones as needed. 2. It allows simultaneous cooling and heating of different zones while maintaining precise temperature and humidity control. 3. However, it is not widely used today due to its high energy consumption from the need to simultaneously cool and heat air streams.

Uploaded by

Mohsen Hassan
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views

Lecture No.12 (Systems)

1. The dual-duct system employs two air ducts, one for cold air and one for warm air, which are mixed in zones as needed. 2. It allows simultaneous cooling and heating of different zones while maintaining precise temperature and humidity control. 3. However, it is not widely used today due to its high energy consumption from the need to simultaneously cool and heat air streams.

Uploaded by

Mohsen Hassan
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Air conditioning systems lecture No.

(12)

D) Dual- duct system


The dual-duct system employs two air ducts; one cold air duct and one
warm air duct from the air-handler to the conditioned spaces. Figure below
shows the schematic of a dual duct, constant volume system. As shown in the
figure, the supply air fan splits the flow into two streams. One stream flow
through the cooling coil and gets cooled and dehumidified to about 52°F,
while the other stream flows thru the heating coil and is heated to about 95–
110°F.

Fig(1): Dual duct constant volume


The cold and hot streams flow through separate and parallel ducts. The
ducts are not necessarily of equal size, depending upon building heating and
cooling loads. Before each conditioned space or zone, the cold and hot air
streams are mixed in required proportions using a mixing box arrangement,
which is controlled by the zone thermostat.
The total volume of air supplied to each zone remains constant;
however, the supply air temperature varies depending upon load.

(1)
Air conditioning systems lecture No.(12)

The system is well suited for providing temperature control of


individual spaces or zones. Return air is accomplished through a single duct
system.
The advantages include:
1. Cooling in some zones and heating in other zones can be achieved
simultaneously;
2. Good temperature and humidity control - system is very responsive to
variations in the zone load, thus it is possible to maintain required conditions
precisely;
3. Zoning of central equipment is not required;
4. Adaptable to either constant volume or VAV systems;
5. Since total airflow rate to each zone is constant, it is possible to maintain
proper IAQ and room air distribution.
6. No seasonal changeover is necessary.
The disadvantages include:
1. Occupies more space for running of two ducts have to be sized to handle
the entire air flow rate, if required.
2. High first cost for installation of two supply ducts throughout the building;
3. Not very energy efficient due to the need for simultaneous cooling and
heating of the air streams.
4. Large number of mixing boxes to maintain;
5. Difficult to use economizer cycle;
6. Does not operate as economically as other VAV systems.
Dual duct systems are no longer popular due to their high energy
consumption; however, they are occasionally used in hospitals where VAV is

(2)
Air conditioning systems lecture No.(12)

inappropriate. Use of VAV control on the main air supply fan to reduce
airflow during low loads can improve their efficiency somewhat.
When the humidity must be kept below a specified value under all operating
conditions, and the dual duct system cannot accomplish this, these two
alternative systems can be considered.

Fig(2): simplified control schematic of dual duct system

(3)
Air conditioning systems lecture No.(12)

E) Multi zone system

fig(3): simplified control schematic of a multizone system with hot and cold plenum
reset.
The multizone central units provide a single supply duct for each zone
and obtain zone control by mixing hot and cold air at the central unit in
response to room or zone thermostat.
For a comparable number of zones, this system provides greater
flexibility than the single duct and involves lower cost than the dual duct
system.
Multizone equipment is similar in some to the dual duct system, but the
hot and cold airstreams are proportioned and mixed at the air handler instead
of at each zone served.

(4)
Air conditioning systems lecture No.(12)

The Multizone system is best suited to applications having high


sensible heat load and limited ventilation requirements. The use of multiple
duct runs and control systems can make initial costs of this system high
compared to other all air systems. In addition obtaining very close control of
this system may require a large capacity in refrigeration and air handling
equipment, increasing both initial and operating costs.
Why use All-Air Central Systems?
1. The arrangement provides uniform air distribution through a network of
ducts and is most suitable for large area coverage, irrespective of width,
length, or depth of coverage. The constant volume system is suitable for
use in areas having similar cooling requirements.
2. The central plant is located in unoccupied areas which consolidates
operation and maintenance remotely and permits the optimum choice of
filtration systems, odor, and noise attenuation.
3. The complete air conditioning plant including the supply and return air fans
can be located away from the conditioned space. Due to this it is possible
to use a wide variety of air filters and avoid noise in the conditioned space.
4. Changeover from summer to winter and vice versa is relatively simple in
all air systems.
5. It offers the greatest potential for energy conservation by utilizing the
outdoor air effectively. Systems can include energy conservation options
such as airside economizer and heat recovery devices. During favorable
ambient conditions, say during night, outside air can be conveniently
utilized in place of mechanical refrigeration.
6. It provides a wide choice of zoning and humidity control under all operating
conditions. It is a good choice where close zone temperature and humidity
control is required. By using high-quality controls it is possible to maintain
(5)
Air conditioning systems lecture No.(12)

the temperature and relative humidity of the conditioned space within ±


0.15°C (DBT) and ± 0.5%, respectively.
7. It provides good design flexibility for optimum air distribution, draft
control, and local requirements.
8. The central system is easily adaptable to fire and smoke removal systems
during emergency conditions.
9. It is suited for applications requiring unusual exhaust makeup.
10. It allows simultaneous cooling and heating in various zones to maintain
precise zone temperature and humidity conditions.
11. It is possible to provide good room air distribution and ventilation under
all conditions of load.
12. Building pressurization can be achieved easily.
Disadvantages of All-Air Central Systems:
1. Significant space, almost 10 to 15% of total depending on the economy of
scale, may be needed for AHU room/duct risers.
2. Requires additional duct clearances which may add to building height.
Vertical airshafts can reduce the usable floor space.
3. Air balancing requires great care and is difficult to achieve particularly in
large systems.
4. The logic control to achieve optimum conditions requires expert design
planning and experience. There are various options among all-air systems; to
insure the right selection requires a foresight of control logic and sequence.
5. May encounter hot or cold spots, particularly in perimeter zones consisting
of large glazing.
6. Installation and accessibility of equipment demands close cooperation
between architectural, mechanical, and structural engineers.

(6)
Air conditioning systems lecture No.(12)

7. The reheat control option with all-air systems is very energy inefficient
because it requires overcooling, and than reheating, for effective humidity
control.
Applications of All Air Systems:
All air systems can be used in both comfort as well as industrial air
conditioning applications. They are especially suited to buildings that require
individual control of multiple zones, such as office buildings, classrooms,
laboratories, hospitals, hotels, ships etc. They are also used extensively in
applications that require very close control of the conditions in the conditioned
space such as clean rooms, computer rooms, operation theatres, research
facilities etc.

(7)
‫‪Air conditioning systems‬‬ ‫)‪lecture No.(12‬‬

‫‪1 .‬يمكن تبريد في بعض المناطق و التدفئة في المناطق األخرى أن يتحقق في وقت واحد ؛‬
‫‪2 .‬درجة الحرارة والرطوبة جيدة التحكم ‪ -‬النظام هو استجابة للغاية للتغيرات في منطقة التحميل ‪،‬‬
‫وبالتالي فمن الممكن للحفاظ على الشروط المطلوبة على وجه التحديد ؛‬
‫‪3 .‬ليس مطلوبا تقسيم المعدات المركزية؛‬
‫‪4 .‬إما قابلة للتكيف مع حجم ثابت أو أنظمة ‪ VAV‬؛‬
‫‪5 .‬منذ إجمالي معدل تدفق الهواء إلى كل منطقة هو ثابت ‪ ،‬فمن الممكن للحفاظ على نوعية الهواء‬
‫الداخلي السليم وتوزيع الهواء في الغرف‪.‬‬
‫‪6 .‬ال التحول الموسمي هو ضروري‪.‬‬

‫‪1 .‬تحتل مساحة أكبر لتشغيل اثنين من القنوات يجب أن يكون الحجم للتعامل مع كامل معدل تدفق‬
‫الهواء ‪ ،‬إذا لزم األمر‪.‬‬
‫‪2 .‬تكلفة عالية األولى لتركيب اثنين من قنوات العرض في جميع أنحاء المبنى ؛‬
‫‪3 .‬ال فعالة جدا بسبب الحاجة للتبريد والتدفئة من تيارات الهواء في وقت واحد الطاقة‪.‬‬
‫‪4 .‬عدد كبير من االختالط صناديق للحفاظ على ؛‬
‫‪5 .‬من الصعب استخدام دورة المقتصد ؛‬
‫‪6 .‬ال تعمل من الناحية االقتصادية كما نظم ‪ VAV‬األخرى‬
‫النظام المتعدد المناطق‬
‫الوحدات المركزية منطقة متعددة توفر القناة العرض واحد لكل منطقة والحصول على السيطرة المنطقة‬
‫عن طريق خلط الهواء الساخن والبارد في الوحدة المركزية استجابة الغرفة أو ترموستات المنطقة‪.‬‬
‫لعدد مماثل من المناطق‪ ،‬ويوفر هذا النظام المرونة أكبر من قناة واحدة وينطوي على تكلفة أقل من‬
‫نظام مجاري الهواء المزدوجة‪.‬‬
‫المعدات ‪ Multizone‬يشبه في بعض لنظام مجاري الهواء المزدوجة‪ ،‬ولكن بنسب تيارات الهواء‬
‫الساخنة والباردة ومختلطة في الهواء بدال من معالج في كل منطقة يخدم‪.‬‬
‫نظام ‪ Multizone‬هو األنسب لتطبيقات وجود ارتفاع الحمل الحراري معقولة ومتطلبات التهوية‬
‫محدودة‪ .‬استخدام مجاري الهواء أشواط متعددة وأنظمة التحكم يمكن أن تجعل التكاليف األولية لهذا‬
‫النظام عالية بالمقارنة مع غيرها من جميع أنظمة الهواء‪ .‬باإلضافة الحصول على السيطرة على مسافة‬

‫)‪(8‬‬
‫‪Air conditioning systems‬‬ ‫)‪lecture No.(12‬‬

‫قريبة جدا من هذا النظام قد تتطلب قدرة كبيرة في مجال التبريد ومعدات مناولة الهواء‪ ،‬وزيادة كل من‬
‫التكاليف األولية والتشغيلية‪.‬‬
‫لماذا استخدام جميع نظم الهواء الوسطى؟‬
‫‪ . 1‬يوفر هذا الترتيب توزيع الهواء موحدة من خالل شبكة من القنوات و هو األكثر مناسبة ل تغطية‬
‫مساحة كبيرة ‪ ،‬بغض النظر عن العرض‪ ،‬الطول‪ ،‬أو عمق التغطية‪ .‬نظام حجم ثابت هو مناسبة‬
‫لالستخدام في المناطق ذات متطلبات التبريد مماثلة‪.‬‬
‫‪ . 2‬ويقع المصنع المركزي في المناطق غير المأهولة والتي تعزز التشغيل والصيانة عن بعد و يسمح‬
‫الخيار األمثل ل أنظمة الترشيح ‪ ،‬ورائحة‪ ،‬و تخفيف الضوضاء ‪.‬‬
‫‪ . 3‬الستكمال محطة تكييف الهواء بما في ذلك مراوح هواء العرض و العودة يمكن أن يكون موجودا‬
‫بعيدا عن الحيز المكيف ‪ .‬نتيجة لهذا فإنه من الممكن استخدام مجموعة واسعة من مرشحات الهواء ‪،‬‬
‫وتجنب الضجيج في الحيز المكيف ‪.‬‬
‫‪ . 4‬التحول من الصيف الى الشتاء و العكس بالعكس هو بسيط نسبيا في جميع أنظمة الهواء ‪.‬‬
‫‪ . 5‬أنها توفر إمكانية أكبر للحفاظ على الطاقة من خالل االستفادة من الهواء الخارجي على نحو فعال‪.‬‬
‫واالنظمة يمكن ان تتضمن خيارات الحفاظ على الطاقة وتشمل خيارات مثل المقتصد الهواء الجانبي‬
‫و أجهزة استرداد الحرارة ‪ .‬خالل الظروف المحيطة مواتية‪ ،‬يقول أثناء الليل‪ ،‬الهواء الخارجي يمكن‬
‫استخدامه بسهولة مكان التبريد الميكانيكي ‪.‬‬
‫‪ . 6‬أنها توفر خيارات واسعة للمناطق و السيطرة على الرطوبة في جميع ظروف التشغيل ‪ .‬بل هو‬
‫خيار جيد حيث يتطلب درجة حرارة منطقة قريبة و السيطرة على الرطوبة‪ .‬باستخدام سيطرة عالية‬
‫الجودة فمن الممكن للحفاظ على درجة الحرارة و الرطوبة النسبية للمساحة المكيفة في حدود ‪0.15 ±‬‬
‫‪ ) C ( DBT °‬و ‪ ، ٪ 0.5 ±‬على التوالي ‪.‬‬
‫‪ . 7‬أنه يوفر مرونة التصميم الجيد للتوزيع األمثل الهواء ‪ ،‬السيطرة على تيار الهواء ‪ ،‬والمتطلبات‬
‫المحلية ‪.‬‬
‫‪ . 8‬النظام المركزي قابلة للتكيف بسهولة مع الحرائق وأنظمة إزالة دخان خالل الظروف الطارئة ‪.‬‬
‫‪ . 9‬هي مناسبة للتطبيقات التي تحتاج الى تراكيب استثنائية للعادم‪.‬‬
‫‪ . 10‬ألنها تتيح التبريد والتدفئة في وقت واحد في مناطق مختلفة للحفاظ على درجة الحرارة والرطوبة‬
‫وفق شروط دقيقة ‪.‬‬
‫‪ . 11‬من الممكن أن تقدم توزيع جيدة لهواء الغرفة وكذلك التهوية في ظل جميع ظروف الحمل‪.‬‬
‫)‪(9‬‬
‫‪Air conditioning systems‬‬ ‫)‪lecture No.(12‬‬

‫‪ . 12‬بناء الضغط يمكن ان يتحقق بسهولة‪.‬‬


‫مساوئ جميع نظم الهواء المركزي‪:‬‬
‫‪ . 1‬مساحة كبيرة ‪ ،‬ما يقرب من ‪ 10‬إلى ‪ ٪15‬من إجمالي المساحة اعتمادا على اقتصاديات الحجم‬
‫الكبير ‪ ،‬الحاجة لغرفة ‪ / AHU‬ومجاري الهواء‪.‬‬
‫‪ . 2‬يتطلب تراخيص القناة اإلضافية التي قد تضيف إلى بناء االرتفاع‪ .‬يمكن ‪ airshafts‬العمودي تقليل‬
‫مساحة قابلة لالستخدام‪.‬‬
‫‪ . 3‬تتطلب موازنة الهواء عناية كبيرة وصعوبة التحقيق خاصة في األنظمة الكبيرة ‪.‬‬
‫‪ . 4‬سيطرة المنطق لتحقيق الظروف المثلى يتطلب تصميم تخطيط الخبراء و الخبرة‪ .‬هناك خيارات‬
‫مختلفة بين أنظمة جميع الهواء ؛ لضمان اختيار الصحيح يتطلب التبصر السيطرة منطق و التسلسل‪.‬‬
‫‪ . 5‬قد تواجه المناطق الساخنة أو الباردة ‪ ،‬خصوصا في محيط المناطق التي تكون من الزجاج الكبيرة‪.‬‬
‫‪ . 6‬التركيب و سهولة الحصول على المعدات يتطلب التعاون الوثيق بين المهندسين المعمارية‬
‫والميكانيكية و المدني ‪.‬‬
‫‪ . 7‬خيار التحكم بأعادة التسخين مع جميع نظم الهواء هي الطاقة غير فعالة للغاية ألنه يتطلب تبريد‬
‫فائق ‪ ،‬و إعادة تسخين هو للسيطرة الفعالة على الرطوبة‪.‬‬
‫التطبيقات‬
‫يمكن استخدام جميع أنظمة الهواء في كل من الراحة وكذلك تطبيقات تكييف الهواء الصناعية‪ .‬هي‬
‫مناسبة خاصة ألنها المباني التي تتطلب سيطرة فردية من المناطق متعددة‪ ،‬مثل مباني المكاتب‬
‫والفصول الدراسية والمختبرات والمستشفيات والفنادق والسفن الخ كما أنها تستخدم على نطاق واسع‬
‫في التطبيقات التي تتطلب مراقبة وثيقة للغاية من األوضاع في الفضاء مثل الغرف المكيفة النظيفة‪،‬‬
‫وغرف الكمبيوتر‪ ،‬وغرف العمليات‪.‬‬

‫)‪(10‬‬

You might also like