Narada Proposal for 1MW/1.
5MWh Lithium BESS
(LFP Battery, NESP series)
Customer
Project
Date of Submission
Version V1.0
Version Date 28th.Sep 2020
Address: Block C, No. 822, Wen'er West Road,
Hangzhou, Zhejiang, China
Narada Power Source Co., Ltd Contact Phone: 0571-56975900
Fax:0571-56975688
E-mail: [email protected]
Narada Power Source Co. Ltd.
Content
I. General Description.................................................................................................1
II. Customer Requirements....................................................................................... 1
III. Brief Introduction of Design and Construction................................................. 2
IV. Estimated Retention............................................................................................. 4
V. Battery Component Specification........................................................................5
VI. BMS System.......................................................................................................... 8
VII. Control Logic of Fire Suppression System......................................................9
VIII. Completely Integrated System....................................................................... 12
Narada Power Source Co. Ltd.
I. General Description
We, Zhejiang Narada Power Source Co., Ltd is a leading company of lead acid battery,
lithium battery and Battery Energy Storage System in China and is expanding to worldwide
Telecom power solution and Renewable energy storage market. We have been involving
and leading 95% of Chinese Energy projects, and are eager to provide proper power
solution worldwide.
Base on specification & requirements of customer, we made a primarily design of
1MW/1.5MWh BESS system.
We would like to provide a general description for your review.
II. Customer Requirements
2.1 BESS System Requirement
The project requirement is 1MW/1.5MWh in a new electricity market.
2.2 Scope of Supply
We will offer proposals for the requirements as below:
1) Storage batteries;
2) Battery installation rack;
3) BMS;
4) Fire suppression system;
5) HVAC;
6) Container solution;
Narada Power Source Co. Ltd. 1
III. Brief Introduction of Design and Construction
3.1 Features
This system adopts the outdoor container BESS system, which contains Narada LFP
battery: NESP series, intelligent battery management system and the group technology.
We can supply safe, reliable, stable power supply solutions, to provide comprehensive
high quality energy.
The BESS communication single layout drawing shows the design of BESS and how
the AC, DC, and control sections are interconnected. In DC section, one battery bank is
made up with certain number of racks in accordance with the PCS configuration and the
banks connect to a PCS module. Several combinations of PCS and battery banks
establish BESS.
Narada Power Source Co. Ltd. 2
3.2 BESS Configuration (1MW/1.5MWh)
Items Unit Value
Power at POC MW 1.00
Requirement Energy MWh 1.50
Single Way Efficiency % 96%
Max Power at D.C. MWdc 1.04
Install Energy at D.C.@BOL MWh 1.56
SOC min % 5%
SOC max % 95%
System Specification DOD% % 85%
C-Rate C 0.67
Autonomy Time Hr 1.76
Battery K-factor 0.95
Needed Capacity MWh 1.93
Module Type 51.2NESP250
Module Capacity Ah 250
Module Voltage V 51.2
Modules Per Rack pcs 15
Rack Rated Voltage V 768
Rack Minimum Voltage V 672
Battery System
Rack Maximum Voltage V 864
Energy Per Rack MWh 0.19
Total Battery Rack Strings 10
Battery No pcs 150
Final Energy MWh 1.92
Final DOD% % 85.6%
BMS Battery Management System set 10
Rack Battery Cabinet set 20
Container Size ft 40
Install Rack No per Container set 10
Install Energy per Container MWh 1.92
No of Container(F90 Fire Retard) set 1
Battery Container
Fire Protection System set 1
DC Combiner Cabinet set 2
Thermal Management System set 2
Auxiliary Electrics set 1
Inverter Power kW 500
PCS
Inverter No pcs 2
Narada Power Source Co. Ltd. 3
IV. Estimated Retention
Years Degradation Rate AC Max.Usable Capacity(MWh)
0 100.00% 1.75
1 95.49% 1.67
2 92.41% 1.62
3 89.33% 1.56
4 87.68% 1.54
5 85.67% 1.50
6 84.22% 1.47
7 82.42% 1.44
8 80.63% 1.41
9 78.50% 1.37
10 76.20% 1.33
Note:
Battery Type 51.2NESP250
Rack Nominal Voltage 768 V
Average DOD% 86%
Annual Cycle No 365 Cycle
Annual Throughput 313.9 C
Type Factor 0.8
String Factor 0.55
BOL Capacity Yes
Minimum SOC 5%
Maximum SOC 95%
Percentage of Usable Capacity 90%
Narada Power Source Co. Ltd. 4
V. Battery Component Specification
51.2NESP250
Component Appearance Type Description Capacity
Cell FE125 Energy/Power Cell 400Wh
(125Ah)
Module 51.2NESP250 16S2P 12.8kWh
Configuration
768VDC Rack with
Rack One rack for 51.2NESP250 15 192kWh
two cabinets Modules& one BPU
5.1 Cell
Item Condition / Note Specification
Nominal Characteristics
Capacity Nominal charge / discharge at 25℃ ≥125Ah@1C
Narada Power Source Co. Ltd. 5
Nominal Voltage Average for nominal discharge 3.2 V
Operating Voltage Range 0%~100% SOC 2.50 ~ 3.65 V
Constant current 125 A (1 C)
Nominal Charge Constant voltage 3.65 V
End condition (Cut off) 5.25 A
Fast Continuous Charge current 125A (1 C)
Charge Current (25℃)
Max Continuous Charge Current 250A (2C)
Constant current 125A (1 C)
Nominal Discharge
End voltage(Cut off) 2.50 V
Discharge Current (25℃) Max Continuous Discharge Current 375A (3C)
Physical Characteristics
Weight / 2.35±0.2 kg
Width*Height*Depth / 130±1 *235±1*36±1 (mm)
Suitable for Temperature
Charge 0 ~ 45℃
Operating Temperature
Discharge -20~55 ℃
≤1M 0 ~ 35℃, 50%~80%SOC
Storage Temperature >1M,≤6M 5~30℃, 50%~80%SOC
≥6M 0~30℃ , 50%~80%SOC
5.2 Module
Items Energy type
Rated Energy 250Ah(12.8 kWh)
Connections 2P16S
Nominal Voltage 51.2V
Mini Voltage 44.8V
Max Voltage 57.6V
Allowed Current 250A(1C)
Recommended Current 125A(0.5C)
Applications (Duration) 2h-4h
Size (W*D*H) 400*602*265
Cooling Forced
Weight 94kg
Narada Power Source Co. Ltd. 6
5.3 Rack
Number of Modules per rack 15
DC Voltage Range [Vdc] 672-864V
Size [W x D x H, mm] 500*650*2400 (2pcs)
Weight [kg] Approx. 1798 kg
Total Rack Energy [kWh] 192 kWh
Rack IP (With door) IP20
Rack Configuration 15 Modules Series
Cooling Air Cooling
Narada Power Source Co. Ltd. 7
VI. BMS System
6.1 Battery Monitor System Configuration
6.2 Unique Balancing Technologies
Non-destructive active balancing
Charging Balance Discharging
High balancing current, almost no heat dissipation
Balancing regardless of circumstances
6.3 Smart Management System
High accuracy voltage/current detection
High current non-destructive active balance
High efficiency balancing strategy
Multi-protection
Applicable SoC estimation
High reliability
Intellectual BMS interface
Historical events log
Narada Power Source Co. Ltd. 8
6.4 Main Characters of Narada BMS
SCADA
Highly precise current temperature
High efficient balance controlling
Highly precise voltage inspection
BMS
Active balance for heavy current
Multiple protection for safety
Practical evaluation of SoC
Narada PCS controller
Records of historical events
Better user experience
Smart BMS interface
High reliability
VII. Control Logic of Fire Suppression System
For Narada Lithium BESS system, Fire suppression system is installed, Control Logic
of Fire Protection System is described as below. The below described are based on
Siemens products for reference, product selection may be different in specific projects.
7.1. The main components of fire protection system
Fire suppression system for each container
Quantity for each Container
Items Unit
10/20ft 40 ft
1 Fire alarm control panel pcs 1 1
2 Smoke Detector pcs 1 2
3 Heat Detector pcs 1 2
4 Light & Sound Alarm pcs 1 1
5 Light & Sound Alarm (Outdoor) pcs 1 1
6 Manual Call Point pcs 1 2
7 Input Output Module set 1 1
9 Fire extinguisher pcs 1 1
Note: Fire Alarm Control Panel is one unit for each plant
Narada Power Source Co. Ltd. 9
7.2. Control logic
Control of fire alarm
“Smoke detector” & “Temperature detector” are installed and connected to “Light &
Sound Alarm” via “signal Input Output Module”.
Whenever the Sensitivity of smoke is over 2.5%/m, or temperature increasing is
higher than 10 degC per min, system may consider there is risk of fire and will trigger
local alarm system with “Light & Sound Alarm”. And report to DMS system for remote
notice.
Or if any anyone find the risk of fire, can press “Manual Call Point” to trigger fire
alarm;
“Auto Fire extinguisher” is available both in & out of container; and the agent is
FM-200.
Whenever got a fire alarm, a visually check is required and fire alarm can be
recovered manually after confirm fire risk is terminated.
7.3. Hardware & Diagram
For detail, please refer document <JB-TBZL-FC726_datasheet_en>.
System Overview
Narada Power Source Co. Ltd. 10
Networking topologies
Narada Power Source Co. Ltd. 11
VIII. Completely Integrated System
Narada Power Source Co. Ltd. 12