100% found this document useful (6 votes)
2K views14 pages

BESS Proposal Description of Narada For 1MW 1.5MWh

The document provides a proposal from Narada Power Source Co. for a 1MW/1.5MWh lithium iron phosphate (LFP) battery energy storage system (BESS). The proposal includes a general description, overview of customer requirements, design and construction details, estimated battery capacity retention over 10 years, and specifications for the battery components including the 51.2V 250Ah LFP cells, modules, and racks. The fully integrated BESS system would be housed in a single 40-foot container and include batteries, racks, battery management system, fire suppression system, HVAC, and power conversion system to meet the customer's needs.

Uploaded by

Serg Marushko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (6 votes)
2K views14 pages

BESS Proposal Description of Narada For 1MW 1.5MWh

The document provides a proposal from Narada Power Source Co. for a 1MW/1.5MWh lithium iron phosphate (LFP) battery energy storage system (BESS). The proposal includes a general description, overview of customer requirements, design and construction details, estimated battery capacity retention over 10 years, and specifications for the battery components including the 51.2V 250Ah LFP cells, modules, and racks. The fully integrated BESS system would be housed in a single 40-foot container and include batteries, racks, battery management system, fire suppression system, HVAC, and power conversion system to meet the customer's needs.

Uploaded by

Serg Marushko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

Narada Proposal for 1MW/1.

5MWh Lithium BESS


(LFP Battery, NESP series)

Customer

Project

Date of Submission

Version V1.0

Version Date 28th.Sep 2020

Address: Block C, No. 822, Wen'er West Road,


Hangzhou, Zhejiang, China

Narada Power Source Co., Ltd Contact Phone: 0571-56975900

Fax:0571-56975688

E-mail: [email protected]

Narada Power Source Co. Ltd.


Content

I. General Description.................................................................................................1

II. Customer Requirements....................................................................................... 1

III. Brief Introduction of Design and Construction................................................. 2

IV. Estimated Retention............................................................................................. 4

V. Battery Component Specification........................................................................5

VI. BMS System.......................................................................................................... 8

VII. Control Logic of Fire Suppression System......................................................9

VIII. Completely Integrated System....................................................................... 12

Narada Power Source Co. Ltd.


I. General Description

We, Zhejiang Narada Power Source Co., Ltd is a leading company of lead acid battery,
lithium battery and Battery Energy Storage System in China and is expanding to worldwide
Telecom power solution and Renewable energy storage market. We have been involving
and leading 95% of Chinese Energy projects, and are eager to provide proper power
solution worldwide.
Base on specification & requirements of customer, we made a primarily design of
1MW/1.5MWh BESS system.
We would like to provide a general description for your review.

II. Customer Requirements

2.1 BESS System Requirement

The project requirement is 1MW/1.5MWh in a new electricity market.

2.2 Scope of Supply

We will offer proposals for the requirements as below:


1) Storage batteries;
2) Battery installation rack;
3) BMS;
4) Fire suppression system;
5) HVAC;
6) Container solution;

Narada Power Source Co. Ltd. 1


III. Brief Introduction of Design and Construction

3.1 Features

This system adopts the outdoor container BESS system, which contains Narada LFP
battery: NESP series, intelligent battery management system and the group technology.
We can supply safe, reliable, stable power supply solutions, to provide comprehensive
high quality energy.
The BESS communication single layout drawing shows the design of BESS and how
the AC, DC, and control sections are interconnected. In DC section, one battery bank is
made up with certain number of racks in accordance with the PCS configuration and the
banks connect to a PCS module. Several combinations of PCS and battery banks
establish BESS.

Narada Power Source Co. Ltd. 2


3.2 BESS Configuration (1MW/1.5MWh)

Items Unit Value


Power at POC MW 1.00
Requirement Energy MWh 1.50
Single Way Efficiency % 96%
Max Power at D.C. MWdc 1.04
Install Energy at D.C.@BOL MWh 1.56
SOC min % 5%
SOC max % 95%
System Specification DOD% % 85%
C-Rate C 0.67
Autonomy Time Hr 1.76
Battery K-factor 0.95
Needed Capacity MWh 1.93
Module Type 51.2NESP250
Module Capacity Ah 250
Module Voltage V 51.2
Modules Per Rack pcs 15
Rack Rated Voltage V 768
Rack Minimum Voltage V 672
Battery System
Rack Maximum Voltage V 864
Energy Per Rack MWh 0.19
Total Battery Rack Strings 10
Battery No pcs 150
Final Energy MWh 1.92
Final DOD% % 85.6%
BMS Battery Management System set 10
Rack Battery Cabinet set 20
Container Size ft 40
Install Rack No per Container set 10
Install Energy per Container MWh 1.92
No of Container(F90 Fire Retard) set 1
Battery Container
Fire Protection System set 1
DC Combiner Cabinet set 2
Thermal Management System set 2
Auxiliary Electrics set 1
Inverter Power kW 500
PCS
Inverter No pcs 2

Narada Power Source Co. Ltd. 3


IV. Estimated Retention

Years Degradation Rate AC Max.Usable Capacity(MWh)


0 100.00% 1.75
1 95.49% 1.67
2 92.41% 1.62
3 89.33% 1.56
4 87.68% 1.54
5 85.67% 1.50
6 84.22% 1.47
7 82.42% 1.44
8 80.63% 1.41
9 78.50% 1.37
10 76.20% 1.33

Note:
Battery Type 51.2NESP250
Rack Nominal Voltage 768 V
Average DOD% 86%
Annual Cycle No 365 Cycle
Annual Throughput 313.9 C
Type Factor 0.8
String Factor 0.55
BOL Capacity Yes
Minimum SOC 5%
Maximum SOC 95%
Percentage of Usable Capacity 90%

Narada Power Source Co. Ltd. 4


V. Battery Component Specification

51.2NESP250
Component Appearance Type Description Capacity

Cell FE125 Energy/Power Cell 400Wh


(125Ah)

Module 51.2NESP250 16S2P 12.8kWh


Configuration

768VDC Rack with


Rack One rack for 51.2NESP250 15 192kWh
two cabinets Modules& one BPU

5.1 Cell

Item Condition / Note Specification


Nominal Characteristics
Capacity Nominal charge / discharge at 25℃ ≥125Ah@1C

Narada Power Source Co. Ltd. 5


Nominal Voltage Average for nominal discharge 3.2 V
Operating Voltage Range 0%~100% SOC 2.50 ~ 3.65 V
Constant current 125 A (1 C)
Nominal Charge Constant voltage 3.65 V
End condition (Cut off) 5.25 A
Fast Continuous Charge current 125A (1 C)
Charge Current (25℃)
Max Continuous Charge Current 250A (2C)
Constant current 125A (1 C)
Nominal Discharge
End voltage(Cut off) 2.50 V
Discharge Current (25℃) Max Continuous Discharge Current 375A (3C)
Physical Characteristics
Weight / 2.35±0.2 kg
Width*Height*Depth / 130±1 *235±1*36±1 (mm)
Suitable for Temperature
Charge 0 ~ 45℃
Operating Temperature
Discharge -20~55 ℃
≤1M 0 ~ 35℃, 50%~80%SOC
Storage Temperature >1M,≤6M 5~30℃, 50%~80%SOC
≥6M 0~30℃ , 50%~80%SOC

5.2 Module

Items Energy type

Rated Energy 250Ah(12.8 kWh)


Connections 2P16S
Nominal Voltage 51.2V
Mini Voltage 44.8V
Max Voltage 57.6V
Allowed Current 250A(1C)
Recommended Current 125A(0.5C)
Applications (Duration) 2h-4h
Size (W*D*H) 400*602*265
Cooling Forced
Weight 94kg

Narada Power Source Co. Ltd. 6


5.3 Rack

Number of Modules per rack 15


DC Voltage Range [Vdc] 672-864V
Size [W x D x H, mm] 500*650*2400 (2pcs)
Weight [kg] Approx. 1798 kg
Total Rack Energy [kWh] 192 kWh
Rack IP (With door) IP20
Rack Configuration 15 Modules Series
Cooling Air Cooling

Narada Power Source Co. Ltd. 7


VI. BMS System

6.1 Battery Monitor System Configuration

6.2 Unique Balancing Technologies

 Non-destructive active balancing


Charging Balance Discharging
 High balancing current, almost no heat dissipation
 Balancing regardless of circumstances

6.3 Smart Management System

 High accuracy voltage/current detection


 High current non-destructive active balance
 High efficiency balancing strategy
 Multi-protection
 Applicable SoC estimation
 High reliability
 Intellectual BMS interface
 Historical events log

Narada Power Source Co. Ltd. 8


6.4 Main Characters of Narada BMS
SCADA
 Highly precise current temperature
 High efficient balance controlling
 Highly precise voltage inspection
BMS
 Active balance for heavy current
 Multiple protection for safety
 Practical evaluation of SoC
Narada PCS controller
 Records of historical events
 Better user experience
 Smart BMS interface
 High reliability

VII. Control Logic of Fire Suppression System

For Narada Lithium BESS system, Fire suppression system is installed, Control Logic
of Fire Protection System is described as below. The below described are based on
Siemens products for reference, product selection may be different in specific projects.

7.1. The main components of fire protection system

Fire suppression system for each container


Quantity for each Container
Items Unit
10/20ft 40 ft
1 Fire alarm control panel pcs 1 1
2 Smoke Detector pcs 1 2
3 Heat Detector pcs 1 2
4 Light & Sound Alarm pcs 1 1
5 Light & Sound Alarm (Outdoor) pcs 1 1
6 Manual Call Point pcs 1 2
7 Input Output Module set 1 1
9 Fire extinguisher pcs 1 1
Note: Fire Alarm Control Panel is one unit for each plant

Narada Power Source Co. Ltd. 9


7.2. Control logic

Control of fire alarm


 “Smoke detector” & “Temperature detector” are installed and connected to “Light &
Sound Alarm” via “signal Input Output Module”.
 Whenever the Sensitivity of smoke is over 2.5%/m, or temperature increasing is
higher than 10 degC per min, system may consider there is risk of fire and will trigger
local alarm system with “Light & Sound Alarm”. And report to DMS system for remote
notice.
 Or if any anyone find the risk of fire, can press “Manual Call Point” to trigger fire
alarm;
 “Auto Fire extinguisher” is available both in & out of container; and the agent is
FM-200.
 Whenever got a fire alarm, a visually check is required and fire alarm can be
recovered manually after confirm fire risk is terminated.

7.3. Hardware & Diagram

For detail, please refer document <JB-TBZL-FC726_datasheet_en>.


System Overview

Narada Power Source Co. Ltd. 10


Networking topologies

Narada Power Source Co. Ltd. 11


VIII. Completely Integrated System