This document provides information about Modbus registers for the MPC-10 & TEC-10 controllers, including register numbers, types, descriptions, and units. It lists over 30 read-only and read-write registers containing engine data like hours, speed, temperature, and fault statuses. It notes that changing values via Modbus will temporarily override locally entered values until power is cycled or register 40240 is written to with a 1 to save changes.

Uploaded by

carlos torres
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views6 pages

MPC-10 & TEC-10 Modbus Map 2.28.2019

This document provides information about Modbus registers for the MPC-10 & TEC-10 controllers, including register numbers, types, descriptions, and units. It lists over 30 read-only and read-write registers containing engine data like hours, speed, temperature, and fault statuses. It notes that changing values via Modbus will temporarily override locally entered values until power is cycled or register 40240 is written to with a 1 to save changes.

Uploaded by

carlos torres
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Software Release: [App: 02.09.10051.00; Config: 2.9.

20024 or greater]

MPC-10 & TEC-10 RS485 Modbus Registers


NOTE: The registers labeled Read/Write will allow the operator to change values through the
Modbus as a temporary modification. If power is cycled to the MPC-10 / TEC-10, the values
changed via Modbus will revert back to the last value entered locally. Writing a 1 to register 40240
will allow saving register changes to controller.

REGISTER # TYPE DESCRIPTION UNITS


40001-40002 Read Only Current Engine Hours (32 Bit) Hours
40003 Read Only Actual Engine Speed RPM
40004 Read Only System Voltage (12.5 will read 125) VDC
40005 Read Only Actual Engine Oil Pressure kPa
40006 Read Only Actual Engine Temperature Celsius
40007 Read Only Controller State (Active State: Numeral Indicated) Numerals
0 = ECU Stabilize Delay
1 = Engine Stopped
2 = Controller in Standby
3 = Prestart 1 Delay
4 = Check Safe to Start
5 = Prestart 2 Delay
6 = Crank On
7 = Crank Rest
8 = False Start Check
9 = Engine Warmup Delay
10 = Line Fill 1 Delay
11 = Line Fill 2 Delay
12 = Running Loaded
13 = Running Cooldown Delay
14 = Energize to Stop Delay
15 = Engine Spindown Delay
16 = Wait to Start Delay
40008 Read Only Active Shutdown Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Overspeed SD (0 or 1)
1 = Underspeed SD (0 or 1)
2 = Overcrank SD (0 or 1)
3 = Low Oil Pressure SD (0 or 1)
4 = High Engine Temp SD (0 or 1)
5 = Low Fuel SD (0 or 1)
6 = Low Discharge Pressure SD (0 or 1)
7 = High Discharge Pressure SD (0 or 1)
8 = No Speed Signal During Crank SD (0 or 1)
9 = Low Lube Level SD (0 or 1)
10 = Fuel Leak SD (0 or 1)
11 = Fuel Filter Restriction SD (0 or 1)
12 = Reserved Reserved
13 = Reserved Reserved
14 = Reserved Reserved
15 = Remote Stop SD (0 or 1)
Software Release: [App: 02.09.10051.00; Config: 2.9.20024 or greater]

40009 Read Only Active Shutdown Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Coolant Level SD (0 or 1)
1 = High Level SD (0 or 1)
2 = Low Level SD (0 or 1)
3 = High Flow SD (0 or 1)
4 = Low Flow SD (0 or 1)
5 = Reserved Reserved
6 = Reserved Reserved
7 = Water in Fuel SD (0 or 1)
8 = Low Suction SD (0 or 1)
9 = High Suction SD (0 or 1)
10 = Reserved Reserved
11 = High Engine Oil Temp SD (0 or 1)
12 = Low Gear Box Pressure SD (0 or 1)
13 = High Gear Box Pressure SD (0 or 1)
14 = Reserved Reserved
15 = Red Lamp Status (0 or 1)
40010 Read Only Active Shutdown Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Pivot Alignment SD (0 or 1)
1 = INDEX Coolant Level SD (0 or 1)
2 = Speed Signal Lost While Running SD (0 or 1)
3 = Reserved Reserved
4 = Reserved Reserved
5 = Reserved Reserved
6 = Reserved Reserved
7 = Reserved Reserved
8 = Reserved Reserved
9 = Reserved Reserved
10 = Reserved Reserved
11 = Reserved Reserved
12 = Reserved Reserved
13 = Reserved Reserved
14 = Reserved Reserved
15 = Reserved Reserved
40011 Read Only Actual System Level Feet
40012 Read & Write Modbus Engine Start/Stop Auto Mode Only (Stop = 0, Start = 1) (0 or 1)
40013 Read & Write Maximum Engine Speed Setpoint RPM
40014 Read Only Actual Ambient Temp Celsius
40015 Read & Write Auto/Manual Mode (Manual = 0, Auto = 1) (0 or 1)
40016 Read & Write Running Loaded Speed in Auto Setpoint RPM
40017 Read & Write Manual Only (Manual Only Enabled = 1, Disabled = 0) (0 or 1)
40018 Read & Write Prestart 1 Auto Only (0 or 1)
(Prestart Auto Only = 1, Prestart Auto & Manual = 0)
40019 Read & Write Prestart 2 Auto Only (0 or 1)
(Prestart Auto Only = 1, Prestart Auto & Manual = 0)
40020 Read Only J1939.Actual Engine Torque Percent
40021 Read Only Reserved Reserved
40022 Read Only J1939.Diesel Particulate Filter Outlet Temperature Celsius
40023 Read Only J1939.Diesel Particulate Filter Intake Temperature Celsius
Software Release: [App: 02.09.10051.00; Config: 2.9.20024 or greater]

40024 Read Only J1939.Exhaust Temperature Celsius


40025 Read Only J1939.Engine Exhaust Manifold Bank 1 Temperature Celsius
40026 Read Only J1939.Boost Pressure kPa
40027 Read Only J1939.Engine Fuel Temperature Celsius
40028 Read Only J1939.Engine Intercooler Temperature Celsius
40029 Read Only J1939.Diesel Particulate Filter Ash Load Percent Percent
40030 Read Only J1939.Diesel Exhaust Fluid Tank Temperature Celsius
40031 Read Only J1939.Engine Fuel Delivery Pressure kPa
40032 Read Only J1939.Barometric Pressure kPa
40033 Read Only J1939.Air Filter Diff. Pressure kPa
40034 Read Only J1939.Exhaust Gas Temperature Celsius
40035 Read Only J1939.Hydraulic Pressure kPa
40036 Read Only J1939.Hydraulic Temperature Celsius
40037 Read Only J1939.Diesel Particulate Filter Active Regeneration Status: The Numerals
following is a description of enumeration values.
0 = Not Active
1 = Active
2 = Regeneration Needed
3 = Not Available
40038 Read & Write System Level Engine Start (Auto) Feet
40039 Read & Write System Level Engine Stop (Auto) Feet
40040 Read & Write System Level Maintain Value (Auto) Feet
40041 Reserved Reserved Reserved
40042 Reserved Reserved Reserved
40043-40044 Read Only Actual Discharge Pressure kPa
40045-40046 Read & Write Pressure Engine Start (Auto) kPa
40047-40048 Read & Write Pressure Engine Stop (Auto) kPa
40049-40050 Read & Write Pressure Maintain Value (Auto) kPa
40051-40200 Read Only Reserved Reserved
40201 Read Only Version.App.1 Numerals
40202 Read Only Version.App.2 Numerals
40203 Read Only Version.App.3 Numerals
40204 Read Only Version.App.4 Numerals
40205 Read Only Version.Config.1 Numerals
40206 Read Only Version.Config.2 Numerals
40207 Read Only Version.Config.3 Numerals
40208 Read Only Reserved Reserved
40210 Read Only J1939.Engine Catalyst Tank Level Percent
40211 Read Only J1939.Diesel Particulate Filter 1 Soot Load Percent Percent
40212 Read Only J1939.Diesel Particulate Filter Regeneration Inhibit Switch (Inhibit (0 or 1)
Switch Active = 1)
40213 Read Only The following is a description of bits:
0 = J1939.Diesel Particulate Filter Active Regeneration (0 or 1)
Inhibited Due to Inhibit Switch (Inhibited = 1)
1 = Reserved Reserved
2 = Reserved Reserved
3 = Reserved Reserved
4 = Reserved Reserved
5 = Reserved Reserved
Software Release: [App: 02.09.10051.00; Config: 2.9.20024 or greater]

6 = Reserved Reserved
7 = Reserved Reserved
8 = Reserved Reserved
9 = Reserved Reserved
10 = Reserved Reserved
11 = Reserved Reserved
12 = Reserved Reserved
13 = Reserved Reserved
14 = Reserved Reserved
15 = Reserved Reserved
40214 Read Only Controller State Timer Seconds
40215 Read Only Target Engine Speed from Controller RPM
40216 Read Only All Purpose Auto Start Function: (Active Function: Numeral Numerals
Indicated)
0 = Single Contact
1 = Local Start Button
2 = Two Contact Maintained
3 = Pressure Transducer
4 = Level Transducer
40217 Read & Write Pressure Maintain Deadband (Auto) kPa
40218 Read & Write System Level Maintain Deadband (Auto) Feet
40219 Reserved Reserved Reserved
40220 Read & Write Ambient Temperature Engine Start (Auto) Celsius
40221 Read & Write Ambient Temperature Engine Stop (Auto) Celsius
40222 Reserved Reserved Reserved
40223 Reserved Reserved Reserved
40224 Read & Write Minimum Engine Speed Setpoint RPM
40225 Read Only Service Reminder - Air Filter Life Hours
40226 Read Only Service Reminder - Air Filter Life Remaining Hours
40227 Read Only Service Reminder - Battery Life Hours
40228 Read Only Service Reminder - Battery Life Remaining Hours
40229 Read Only Service Reminder - Belt Life Hours
40230 Read Only Service Reminder - Belt Life Remaining Hours
40231 Read Only Service Reminder - Fuel Filter Life Hours
40232 Read Only Service Reminder - Fuel Filter Life Remaining Hours
40233 Read Only Service Reminder - Oil Filter Life Hours
40234 Read Only Service Reminder - Oil Filter Life Remaining Hours
40235 Read Only Service Reminder - Oil Life Hours
40236 Read Only Service Reminder - Oil Life Remaining Hours
40237 Read Only Service Reminder - Overhaul Life Hours
40238 Read Only Service Reminder - Overhaul Life Remaining Hours
40239 Read Only Actual Fuel Level Percent
40240 Read & Write Modbus EEPROM Values Save (Save = 1) (0 or 1)
40241 Read Only Modbus EEPROM Values Saved Confirmation (0 or 1)
(Saved = 1)
40242 Read Only Active Warning Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Low Fuel Warn (0 or 1)
1 = Fuel Leak Warn (0 or 1)
2 = Fuel Filter Restriction Warn (0 or 1)
Software Release: [App: 02.09.10051.00; Config: 2.9.20024 or greater]

3 = Low Lube Level Warn (0 or 1)


4 = Coolant Level Warn (0 or 1)
5 = Water in Fuel Warn (0 or 1)
6 = No Flow Warn (0 or 1)
7 = High Engine Oil Temp Warn (0 or 1)
8 = Low Oil Pressure Warn (0 or 1)
9 = High Engine Temp Warn (0 or 1)
10 = High Discharge Pressure Warn (0 or 1)
11 = Low Discharge Pressure Warn (0 or 1)
12 = High Suction Warn (0 or 1)
13 = Low Suction Warn (0 or 1)
14 = High Level Warn (0 or 1)
15 = Low Level Warn (0 or 1)
40243 Read Only Active Warning Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = High Flow Warn (0 or 1)
1 = Low Flow Warn (0 or 1)
2 = Reserved (0 or 1)
3 = Reserved (0 or 1)
4 = Low Gear Box Pressure Warn (0 or 1)
5 = High Gear Box Pressure Warn (0 or 1)
6 = Reserved (0 or 1)
7 = Reserved (0 or 1)
8 = Reserved (0 or 1)
9 = Low Engine Temp Warn (0 or 1)
10 = Reserved (0 or 1)
11 = Reserved (0 or 1)
12 = Run To Destruct Warn (0 or 1)
13 = Battery High Warn (0 or 1)
14 = Battery Low Warn (0 or 1)
15 = Amber Lamp Status (0 or 1)
40244 Read Only Active Warning Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Pivot Alignment Warn (0 or 1)
1 = Reserved Reserved
2 = Reserved Reserved
3 = Reserved Reserved
4 = Reserved Reserved
5 = Reserved Reserved
6 = Reserved Reserved
7 = Reserved Reserved
8 = Reserved Reserved
9 = Reserved Reserved
10 = Reserved Reserved
11 = Reserved Reserved
12 = Reserved Reserved
13 = Reserved Reserved
14 = Reserved Reserved
15 = Reserved Reserved
40245-40246 Read Only J1939.Aftertreatment 1 Diesel Particulate Filter Time to Next Seconds
Active Regeneration
Software Release: [App: 02.09.10051.00; Config: 2.9.20024 or greater]

40247 Read & Write Remote Alarm Acknowledgement (0 or 1)


40500 Read Only J1939.DM1 SPN Numerals
40501 Read Only J1939.DM1 FMI Numerals