1.2.1 CT VT RATIOS
PH CT Secondary = 1 A
PH CT Primary = 400 A
EF CT Secondary = 1 A
EF CT Primary = 400 A
PH VT Primary = 132 Kv
PH VT Selection = Line to Ground
PH VT Secondary = 63.5V
Doc ID : ADR239B/IM/01
Ref ID : ADR239B/IM/SG
Rev No. : 01
Page No. : 4 of 9
ADR239B
Length = 44.5 Km
Doc ID : ADR239B/IM/01
Ref ID : ADR239B/IM/SG
Rev No. : 01
Page No. : 5 of 9
ADR239B
1.2.5 FACTORS
This defines direction of the operation. (Operating region of zone)
Alfa = -15°°
Beta = 165°°
Note :
Beta – Alfa = 180
165 – (– 15) = 180
1.2.6 ZONESETTINGS
1.2.6.1 Z1 settings:
OP Mode = Forward
Fwd-RP1 = As per guide line of power grid (Page 3, Section 7, - Refer MICOM P442/4 Setting)
Note: Refer complete Band (Forward + Reverse) while in ADR239B, we set forward and reverse
separately.
FWD-RP1 = (30/2) X CTR/PTR
= 15 x 0.3333
= 4.999 Ω
Fwd-RP1 = 5.0 Ω
Rew-RP1 = 5.0 Ω
Doc ID : ADR239B/IM/01
Ref ID : ADR239B/IM/SG
Rev No. : 01
Page No. : 6 of 9
ADR239B
BLDANG1 = Disabled
TAG1 = -5°°
tDZ1 = 0 Sec (As Zone 1 is an instantaneous operation, we want instant results)
trDZ1 = 0 Sec
Zone 1 Ext = Disabled
1.2.6.2 Z2 Setting:
OP Mode = Forward
Z2 setting is 120% of protective line length. (Guideline Page1 Section 2)
Fwd-RP2 = As per guideline, Page 3, Section 7 (MICOM Relay P442/4)
= (60/2) x CTR/PTR
= 30 x 0.3333
= 9.999 Ω
Fwd-RP2 = 10.00 Ω
Rev-RP2 = 10.00 Ω
= 75 x (CTR/PTR)
= 75 x 0.3333
= 24.997
Fwd-RG2 = 25.00
Rev_RG2 = 25.00
BLDANG2 = Disabled
TANG2 = 0°°
Doc ID : ADR239B/IM/01
Ref ID : ADR239B/IM/SG
Rev No. : 01
Page No. : 7 of 9
ADR239B
1.2.6.3 Z3 Setting:
Z3 setting = 120% (Protected line length + next longest line)
This is as per guideline given by power grid (Page 1, Section 3)
Z3 Distance = 120% of [44.5 + 41]
Z3 Distance = 1.2 x 85.5
Z3 Distance = 102.6 Km
Assumed line Impedance and construction is uniform for both lines.
= 125 x CTR/PTR
= 125 x 0.3333
= 41.6625
Fwd-RG3 = 41.66
Rev-RG3 = 41.66
BLDANG 3 = Disabled
TANG3 = 0°°
TDZ3 = 0.8 Sec (As Per Guideline Page1, Section 3 )
trDZ3 = 0 Sec
Doc ID : ADR239B/IM/01
Ref ID : ADR239B/IM/SG
Rev No. : 01
Page No. : 8 of 9
ADR239B
Case 2 :
• Total Reverse Zone % = ____________100______________
Total positive sequence reactance
= ____________100______________
[|Z1| Sin (71.6692)] x Line Length
= ____________100______________
0.4350 x Sin(71.6692) x 44.5
= 5.44%
OP Mode = Reverse
Fwd-RP4 = As per the guideline (Page 2, Section4) says “The resistive reach should be equal to
Zone-2 resistive reach”
Fwd-RP4 = (60/2) x (CTR/ PTR)
= 30 x 0.3333
= 9.999 Ω
Fwd-RP4 = 10.00 Ω
Rev-RP4 = 10.00 Ω
= 75 x CTR/PTR
= 75 x 0.3333
= 24.997 Ω
Fwd-RG4 = 25.00 Ω
Rev-RG4 = 25.00 Ω
Doc ID : ADR239B/IM/01
Ref ID : ADR239B/IM/SG
Rev No. : 01