FTA1100J Diesel Engine Fire Pump Controllers Product Description

The document describes a diesel engine fire pump controller product. It lists the controller's standard features which include monitoring and controlling the fire pump system. It also lists optional features like special enclosures, mounting options, additional alarms, and pressure transducers.

Uploaded by

rahu2260
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
722 views2 pages

FTA1100J Diesel Engine Fire Pump Controllers Product Description

The document describes a diesel engine fire pump controller product. It lists the controller's standard features which include monitoring and controlling the fire pump system. It also lists optional features like special enclosures, mounting options, additional alarms, and pressure transducers.

Uploaded by

rahu2260
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

FTA1100J Diesel Engine Fire Pump Controllers

Product Description

• MAIN SWITCH IN MANUAL


• SYSTEM PRESSURE LOW
• ENGINE RUNNING
• ENGINE FAIL TO START
• ENGINE TEMPERATURE HIGH
• ENGINE OIL PRESSURE LOW
• ENGINE OVERSPEED
• ENGINE ALTERNATE ECM
• ENGINE FUEL INJECTOR MALFUNCTION
• FUEL LEVEL LOW
• AUTOMATIC SHUTDOWN DISABLED
• CHARGER MALFUNCTION
• BATTERY #1 TROUBLE
• BATTERY #2 TROUBLE
• Minimum Run Timer / Off Delay Timer
• Programmable Daylight Saving Time Option
• Weekly Test Timer
Description – Firetrol® combined automatic and manual • Engine Run Time Meter
Mark IIXG based diesel engine fire pump controllers are • Digital Pressure Display
intended for starting and monitoring fire pump diesel • USB Host Controller and Port
engines. They are suitable for use with both mechanical • Solid State Pressure Transducer
and electronic type engines. The controller is available for • Data Log
12 or 24 volt negative ground systems, using lead acid • Event Log (3000 events)
or Nickel-Cadmium batteries. The controller monitors, • Simultaneous Display of Battery Voltages, Charging
displays and records fire pump system information. Rates, AC Volts, Pressure and Alarm Messages
• Disk Error Message
Approvals – Firetrol fire pump controllers are listed by • Disk Near Full Message
Underwriters’ Laboratories, Inc., in accordance with • Pressure Error Message
UL218, Standard for Fire Pump Controllers, CSA, Standard • Fail to Start Message
for Industrial Control Equipment (cUL), and approved by • Low Suction Pressure Message
Factory Mutual. They are built to meet or exceed the • Crank Cycle Status Indication (Displays Cranking Bat-
requirements of the approving authorities as well as tery, Number of Starting Attempts and Crank/Rest
NEMA and the latest editions of NFPA 20, Installation Time Remaining)
of Centrifugal Fire Pumps, and NFPA 70, National Electri- • 300 psi (20.7 bars) wet parts (solid state pressure
cal Code. transducer, solenoid valve, plumbing) for fresh water
applications
• NEMA Type 2 enclosure (IEC IP22)
Standard Features – The following are included as stan- • Each standard controller comes with user set options
dard with each controller: for:
• AC Line & Battery circuit breakers • AC Power Loss Start • Interlock Alarm
• Manual-Off-Auto selector switch • Low Pressure Aud. • Low Suction
• Manual test push-button • Main Sw. Mis-Set • Manual Test
• Two manual crank push-buttons • Pump Run Alarm • Remote Start
• Two 10 Amp battery chargers with 4 stage charging • User Defined Input • Weekly Test Setup
cycle, selectable AC voltage (110 / 220), selectable DC • Low Pump Rm Temp • Low Reservoir
voltage (12 / 24), and selectable battery type (Lead • Relief Valve Open • High Fuel Level
Acid, Ni-Cad 9/18 Cell, Ni-Cad 10/20 Cell) • High Reservoir
• Door mounted display/interface panel featuring a 128
x 64 pixel backlit LCD graphical display, Membrane
Type User Control Push-buttons and easy to read LED
Indicators for:
• AC POWER AVAILABLE
• ALARM
• MAIN SWITCH IN AUTO
Special Enclosures -CPL Contacts for remote indication, system
-T NEMA Type 3R (IEC IP22), Painted Steel 115% over pressure (for use with PLD engines only)
-E NEMA Type 4 (IEC IP 66), Painted Steel -CTS Built-in low suction pressure alarm panel (Includes select-
-F NEMA Type 4X (IEC IP66) #304 Stainless able auto/manual reset, audible, visible and remote alarms
Steel, Brushed Finish and mounted and wired pressure switch)
-FXP NEMA Type 4X (IEC IP66) #304 Stainless -EE Additional contacts for remote indication, engine trouble - 1
Steel, Painted Finish set provided as standard
-FD NEMA Type 4X (IEC IP66) #316 Stainless -EF Additional contacts for remote indication, main switch
Steel, Brushed Finish mis-set - 1 set provided as standard
-FDB NEMA Type 4X (IEC IP66) #316 Stainless -EH Contacts for remote indication, relief valve discharge1
Steel, 12 Gauge, Seam Welded, -EJ Audible & Visible flow meter on alarm1
Brushed Finish -EK Contacts for remote indication, flow meter on1 (Requires
-FDP NEMA Type 4X (IEC IP66) #316 Stainless option -EJ)
Steel, Painted Finish -JR Visible jockey pump running indication
-G NEMA Type 12 (IEC IP54) -JT Audible and visible jockey pump trouble indication
-LC Contacts for remote indication, high fuel level1
Mounting Legs -LD Audible & Visible fuel spill alarm1
-N31 Standard 12” Mounting Legs -LE Contacts for remote indication, fuel spill1 (Requires option
-N31S 12” Mounting Legs, Stainless Steel -LD)
-LG Contacts for remote indication, reservoir high1
Anti-Condensation Space Heaters -PE Contacts for remote indication, low system pressure
-H 120 Volt Space Heater (Pump On Demand)
-J 120 Volt Space Heater with Thermostat
-K 120 Volt Space Heater with Humidistat Miscellaneous
-L 240 Volt Space Heater -AZ Low pump room temperature switch, mounted and wired
-M 240 Volt Space Heater with Thermostat -BA 220-240 Volt operation
-N 240 Volt Space Heater with Humidistat -EL Series pumping, high zone controller
-EM Series pumping, mid zone controller
Pressure Transducers, Solenoid Valves, Plumbing -EN Series pumping, low zone controller
-B 0-600 psi (0-41.4 bars) wet parts for fresh water applications -IEC CE Marking with Externally Mounted Wet Parts
-C 0-300 psi (0-20.7 bars) wet parts for copper corrosive -IECI CE Marking (Internal Wet Parts)
applications -OSP OSHPD Seismic Certification (State of California) (Requires
-D 0-600 psi (0-41.4 bars) wet parts for copper corrosive Option -SEI)
applications -S Tropicalization
-SEI Seismic Certification (in accordance with IBC)
Alarms -USBX External USB Port
-AC Additional contacts for remote indication, engine running - 2 -ZPA Customized, annual service display message (factory
sets provided as standard programmed)
-AJ Contacts for remote indication, engine overspeed -ZPN Serial Modbus RTU over Ethernet TCP/IP
-AK Contacts for remote indication, low oil pressure using 5150 Connectivity Module
-AL Contacts for remote indication, high water temperature -ZPM Serial Modbus RTU over 2-wire or 4-wire RS485
-AM Contacts for remote indication, engine failed to start
-AN Contacts for remote indication, battery / charger failure FTA1100-K1 Low fuel level switch, 16” max insertion length2
-AP Contacts for remote indication, main switch in manual FTA1100-K1-X High/Low fuel level switch - specify levels/tank
-AR Contacts for remote indication, main switch in off dimensions
-AS Contacts for remote indication, main switch in auto FTA1100-K2 Low fuel level switch, 25” max. insertion length2
-AT Contacts for remote indication, pump room trouble1 FTAK21 380-480 volt operation (transformer)2
-AV Contacts for remote indication, low pump room Export packaging (Wooden crating to conform to IPPC Standards)
temperature1
-AW Contacts for remote indication, reservoir low1
-AY Contacts for remote indication, low suction pressure1 1
- Initiating switches by others
-COM Visible low suction pressure alarm, 2
- Shipped loose for installation by the customer
Manual reset only (Includes reset push-button, initiating
pressure switch not included)1