CB Test Certificate

This document is a CB Test Certificate from LCIE - Laboratoire Central des Industries Electriques certifying that moulded-case circuit-breakers manufactured by Schneider Electric Industries SAS have been tested and found to comply with IEC 60947-1 and IEC 60947-2. The certificate provides details on the product name and references, manufacturer and factory information, applicable ratings and standards, and test report numbers. It certifies the EasyPact CVS100N, CVS160N, and CVS250N series circuit-breakers.

Uploaded by

TILAK RAJ Kamboj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
382 views2 pages

CB Test Certificate

This document is a CB Test Certificate from LCIE - Laboratoire Central des Industries Electriques certifying that moulded-case circuit-breakers manufactured by Schneider Electric Industries SAS have been tested and found to comply with IEC 60947-1 and IEC 60947-2. The certificate provides details on the product name and references, manufacturer and factory information, applicable ratings and standards, and test report numbers. It certifies the EasyPact CVS100N, CVS160N, and CVS250N series circuit-breakers.

Uploaded by

TILAK RAJ Kamboj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ref. Certif. No.

FR_703748

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT
(IECEE) CB SCHEME

CB TEST CERTIFICATE

Product Moulded-case Circuit-breaker

Name and address of the applicant SCHNEIDER ELECTRIC INDUSTRIES SAS


35, rue Joseph Monier CS 30323
92506 RUEIL-MALMAISON
FRANCE

Name and address of the manufacturer SCHNEIDER ELECTRIC INDUSTRIES SAS


31 rue Pierre Mendes France, Eybens
38050 GRENOBLE Cedex 9
FRANCE

Name and address of the factory See annex

Note: When more than one factory, please report on page 2 Additional Information on page 2

Ratings and principal characteristics See Annex

Trademark (if any)

Customer’s Testing Facility (CTF) Stage used /

Series EasyPact
Model / Type Ref. CVS100N, CVS160N, CVS250N

Additional information (if necessary may also be Supersedes CBTC FR 687603/M2 dated 08/12/2016. Update
reported on page 2) further to the evolution of the standard(s) and technical
modifications

Additional Information on page 2

A sample of the product was tested and found to IEC 60947-1:2007(ed.5) +A1:2010 +A2:2014
be in conformity with IEC 60947-2:2016

As shown in the Test Report Ref. No. which CBTC n° NL-25536 / TR 3304174.50,
forms part of this Certificate test reports n° 160119940004 Amendment No.1, 1811990008

This CB Test Certificate is issued by the National Certification Body


LCIE – Laboratoire Central des Industries Electriques
33, avenue du Général Leclerc – BP8
FR 92 266 Fontenay aux Roses Cedex
www.lcie.fr

Date: 27/08/2018 Signature: Jean-François BRUEL


Certification Officer

1/2
Ref. Certif. No.

FR_703748

ANNEX
Name and address of the factories:

SCHNEIDER (BEIJING) MEDIUM & LOW VOLTAGE Co., Ltd


No 2, Liang Shui He 2nd Street, Beijing Economic Technological Development area
100176 BEIJING – CHINA

Schneider Electric India Private Limited


Survey #215, Gagillapur Village, Medak Road
HYDERABAD ANDHRA PRADESH - INDIA

References, ratings and main characteristics :

Thermo-magnetic trip unit TMD (3P and 4P):


CVS100N: 16/25/32/40/50/63/80/100A
CVS160N: 100/125/160A
CVS250N: 200/250A
Rated current, In
Magnetic trip unit MA (only for 3P):
CVS100N: 2,5/6,3/12,5/25/50/100A
CVS160N: 100/150A
CVS250N: 220A

Conventional thermal current, Ith See rated current

Operational voltage, Ue 220/240V, 380/415V, 440V


3P
Number of poles
4P (N marked, without overcurrent protection)
Frequency 50/60 Hz

Insulation voltage, Ui 690 V

Impulse withstand voltage, Uimp 8 kV

Utilization category A

Reference temperature 40 °C
Rated ultimate short-circuit breaking capacity,
90kA/AC220/240V, 50kA/AC380/415V, 50kA/AC440V
Icu
Rated service short-circuit breaking capacity,
90kA/AC220/240V, 50kA/AC380/415V, 38kA/AC440V
Ics
Device suitable for isolation Yes

LCIE – Laboratoire Central des Industries Electriques


33, avenue du Général Leclerc – BP8
FR 92 266 Fontenay aux Roses Cedex
www.lcie.fr