Ref. Certif. No.
FR_703748
IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT
(IECEE) CB SCHEME
CB TEST CERTIFICATE
Product Moulded-case Circuit-breaker
Name and address of the applicant SCHNEIDER ELECTRIC INDUSTRIES SAS
35, rue Joseph Monier CS 30323
92506 RUEIL-MALMAISON
FRANCE
Name and address of the manufacturer SCHNEIDER ELECTRIC INDUSTRIES SAS
31 rue Pierre Mendes France, Eybens
38050 GRENOBLE Cedex 9
FRANCE
Name and address of the factory See annex
Note: When more than one factory, please report on page 2 Additional Information on page 2
Ratings and principal characteristics See Annex
Trademark (if any)
Customer’s Testing Facility (CTF) Stage used /
Series EasyPact
Model / Type Ref. CVS100N, CVS160N, CVS250N
Additional information (if necessary may also be Supersedes CBTC FR 687603/M2 dated 08/12/2016. Update
reported on page 2) further to the evolution of the standard(s) and technical
modifications
Additional Information on page 2
A sample of the product was tested and found to IEC 60947-1:2007(ed.5) +A1:2010 +A2:2014
be in conformity with IEC 60947-2:2016
As shown in the Test Report Ref. No. which CBTC n° NL-25536 / TR 3304174.50,
forms part of this Certificate test reports n° 160119940004 Amendment No.1, 1811990008
This CB Test Certificate is issued by the National Certification Body
LCIE – Laboratoire Central des Industries Electriques
33, avenue du Général Leclerc – BP8
FR 92 266 Fontenay aux Roses Cedex
www.lcie.fr
Date: 27/08/2018 Signature: Jean-François BRUEL
Certification Officer
1/2
Ref. Certif. No.
FR_703748
ANNEX
Name and address of the factories:
SCHNEIDER (BEIJING) MEDIUM & LOW VOLTAGE Co., Ltd
No 2, Liang Shui He 2nd Street, Beijing Economic Technological Development area
100176 BEIJING – CHINA
Schneider Electric India Private Limited
Survey #215, Gagillapur Village, Medak Road
HYDERABAD ANDHRA PRADESH - INDIA
References, ratings and main characteristics :
Thermo-magnetic trip unit TMD (3P and 4P):
CVS100N: 16/25/32/40/50/63/80/100A
CVS160N: 100/125/160A
CVS250N: 200/250A
Rated current, In
Magnetic trip unit MA (only for 3P):
CVS100N: 2,5/6,3/12,5/25/50/100A
CVS160N: 100/150A
CVS250N: 220A
Conventional thermal current, Ith See rated current
Operational voltage, Ue 220/240V, 380/415V, 440V
3P
Number of poles
4P (N marked, without overcurrent protection)
Frequency 50/60 Hz
Insulation voltage, Ui 690 V
Impulse withstand voltage, Uimp 8 kV
Utilization category A
Reference temperature 40 °C
Rated ultimate short-circuit breaking capacity,
90kA/AC220/240V, 50kA/AC380/415V, 50kA/AC440V
Icu
Rated service short-circuit breaking capacity,
90kA/AC220/240V, 50kA/AC380/415V, 38kA/AC440V
Ics
Device suitable for isolation Yes
LCIE – Laboratoire Central des Industries Electriques
33, avenue du Général Leclerc – BP8
FR 92 266 Fontenay aux Roses Cedex
www.lcie.fr
Date: 27/08/2018 Signature: Jean-François BRUEL
Certification Officer
2/2