0% found this document useful (0 votes)
84 views2 pages

Production of Chlorine Dioxide: Using Diluted Naclo and HCL Solutions

The document discusses the Oxiperm Pro system for producing chlorine dioxide to disinfect drinking water systems. It produces chlorine dioxide on-demand using diluted sodium chlorite and hydrochloric acid solutions. Chlorine dioxide is highly effective at removing biofilms and preventing Legionella and other pathogens. The Oxiperm Pro is available in various sizes suitable for small buildings up to large waterworks. It provides reliable disinfection through its stable chlorine dioxide solution and low operating costs.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views2 pages

Production of Chlorine Dioxide: Using Diluted Naclo and HCL Solutions

The document discusses the Oxiperm Pro system for producing chlorine dioxide to disinfect drinking water systems. It produces chlorine dioxide on-demand using diluted sodium chlorite and hydrochloric acid solutions. Chlorine dioxide is highly effective at removing biofilms and preventing Legionella and other pathogens. The Oxiperm Pro is available in various sizes suitable for small buildings up to large waterworks. It provides reliable disinfection through its stable chlorine dioxide solution and low operating costs.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

GRUNDFOS alldos

OXIPERM PRO

production of chlorine dioxide


using diluted NaClO2 and HCl solutions
General No chance for pathogens
Oxiperm Pro systems produce chlorine dioxide using diluted Legionella are rod-shaped bacteria that quickly reproduce in
solutions of sodium chlorite (NaClO2 7.5%) and hydrochloric acid temperatures between 30 and 40 °C. They can enter the lungs
(HCl 9%). They are available in four capacity levels, producing 5, when a person inhales aerosols containing Legionella when
10, 30 and 60 g/h of chlorine dioxide respectively. This capacity is showering. Legionella can cause a life-threatening form of
sufficient to treat up to 150 m³ of drinking water per hour at the pneumonia known as legionellosis. The ideal breeding ground
maximum admissible concentration of 0.4 mg/l ClO2. Chlorine for legionella in drinking water systems can be found in
dioxide is produced on demand from diluted solutions using the biofilm, a slimy layer on the inside of water pipes, where other
reliable sodium chlorite / hydrochloric acid, in accordance with the pathogens also build up and reproduce. Legionella also establish
German Drinking Water Directive. themselves in amoebae, which offer them protection against
The chlorine dioxide solution produced is stored in an integrated or conventional disinfection methods.
external batch tank and is added to the drinking water system as Using Oxiperm Pro ensures reliable removal of the biofilm with
required using the integrated dosing pump or an external dosing all pathogens and Legionella present in piping and prevents
pump. reinfestation. Oxiperm Pro OCD-162-5 and -10 systems are
designed for small or medium-sized buildings with water flows
Applications
up to 25 m3/h. Oxiperm Pro OCD-162-30 and -60 systems are
An ideal means of ensuring the purity of drinking water is to suited for disinfection tasks in waterworks or applications in the
use chlorine dioxide as a disinfectant. Chlorine dioxide is highly food and beverage industry.
effective against all types of germs and has a long dwell time in the
tubing system, which means it disinfects even without re-dosing. Benefits of the Oxiperm Pro system
The big advantage of chlorine dioxide over other disinfectants is its • Compact system, also for confined spaces
effectiveness against biofilms. It destroys the existing biofilm, thus • Low operating costs
removing the breeding ground for microorganisms, and prevents it • Stable product solution, can be stored for several days
from building up again. • Integrated measured value logging
Ideal application areas for Oxiperm Pro include combating germs • Little installation work
and pathogens, such as legionella in building installations, • Robust design
disinfecting small cooling water systems, drinking water in water
plants or industrial processes.
Chlorine dioxide is often used in the food and beverage industry for
disinfection of process water or for CIP and bottle washing because
it doesn’t change the taste or smell of the treated water.
Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence

Technical data
Capacities OCD-162-5: 5 g/h ClO2 OCD-162-30: 30 g/h ClO2
OCD-162-10: 10 g/h ClO2 OCD-162-60: 60 g/h ClO2
Protection level IP 65 electronics, dosing pumps, solenoid valve
Admissible concentration of chemicals • HCl (according to EN 939) 9 percent by weight
• NaClO2 (according to EN 938) 7.5 percent by weight
Admissible temperature • Admissible ambient temperature: 5 to 35 °C
• Admissible operation water temperature: 10 to 30 °C
• Admissible chemicals temperature: 10 to 35 °C
Admissible operation water pressure 3 to 6 bars
Admissible relative air humidity Max. 80 % (not condensing)
Total volume of Reaction tank Reservoir tank (up to max. level alarm)
reaction tank and reservoir tank OCD-162-5 1.00 litre OCD-162-5 1.00 litre
OCD-162-10 1.80 litres OCD-162-10 1.80 litres
OCD-162-30 6.10 litres OCD-162-30 7.00 litres
OCD-162-60 13.40 litres OCD-162-60 13.90 litres
Filling volume of Reaction tank Reservoir tank
reaction tank and reservoir tank OCD-162-5 0.87 litres OCD-162-5 0.87 litres
OCD-162-10 1.67 litres OCD-162-10 1.67 litres
OCD-162-30 5.52 litres OCD-162-30 6.50 litres
OCD-162-60 11.96 litres OCD-162-60 13.00 litres
Concentration of the chlorine dioxide solution 2 g/l (2.000 ppm)
Material System rack PP
Fastening sleeves stainless steel
Solenoid valve PVC

Subject to change.
Reaction / reservoir tank PVC
Internal hoses PTFE
Gaskets FPM
Options • Integrated digital dosing pump DDI for product solution or integrated
mechanical dosing pump DMI or DMX for product solution
• OCD-162-5 and -10: without integrated dosing pump for product solution
Connections ClO2 dosing line 230 V hose 4/6 (162-5 and -10), 9/12 (162-30 and -60)
115 V hose 1/8” x 1/4” (162-5 and -10), 1/4” x 3/8” (162-30 and -60)
Dilution water 230 V hose 6/9 or 6/12 or PVC pipe DN 8
115 V hose 1/4” x 3/8”

Effectiveness diagram 100

80
pH > 7.5
Residual germs [%]

60

residual
40 germs
with HCIO
residual
20
germs
with CIO2
0
0,01 0,02 0,03 0,04 0,05 0,06

Concentration of disinfectant [mg/l]

www.grundfosalldos.com