HP/LP Bypass Automation: Function Description
HP/LP Bypass Automation: Function Description
the requirements of the bypass operation and Figure 1 HP-Bypass controller (2 lines)
allows the easy implementation of safety including safety function
functions or other quick opening or quick
closing functions. The life conserving
operation of the heavily stressed valves and With a few standardized interface signals the
pipework, especially by accurate steam Sulzer bypass controller can be tied easily
desuperheating in all operating modes and into an overall plant automation. The duty of
transients, poses a special challenge for the the HP bypass controller can be summarized
Sulzer bypass controller. for the different operating conditions as
follows:
2. HP bypass controller • Boiler start up
The Sulzer HP bypass controller is an The controller has to control and increase
integrated system with the functions signal the boiler steam pressure according to the
conditioning, control and valve positioning steam production of the boiler. The bypass
(Figure 1). The type of operator interface has to divert the steam flow to the reheater,
can be tailored to the needs of the individual thus ensuring a proper steam flow through
plant. The below described functions for superheater and reheater. The bypass
start up as well as for shut down are fully controller has to control the temperature of
automated. the steam to the reheater whenever steam is
flowing through the bypass.
• Turbine start up
The HP bypass controller has to control the
steam pressure until the boiler master
controller can take over the pressure control.
BP1
Generator Pressure
OP! YT BPE2 BD2 Controller
Pressure BP2
Controller Rate Limiter
C Ym
TT Temperature RTL M
Controller A SCO M
X A
X
TT
Reheater
S
Cold Reheat Line C YT
PS
PT Pressure Transmitter C C Ymin
TT Temperature Transmitter
YT Position Transmitter Pmin p
PS Pressure Switch
start up follow
functions:
Figure 3 HP-Bypass pressure controller
• pressure controller
• temperature controller
• injection water isolation valve control
• safety function
generator Controller
T RH YT
P RH P RH C
FT
C
FT
PT
Condenser
1. Overview (Diagram D)
2.1 Startup
The “fixed pressure mode” is active when the “startup mode”, the “follow mode “ and
the “shut down mode” is not active.
The “follow mode” is active when the BP valve is closed and the DEH signal “HP
Turbine loaded” is on or the DCS signal “Boiler fire on” is off . or when the. Further
the “Follow mode” is on when BP controller is in manual.
At startup, with no pressure in the boiler the setpoint generator is in the “min pressure”
condition. The pressure setpoint “Ps actual” is then set at pressure value “Pmin”. And
the pressure controller open the BP valve to a minimum position value “Ymin” (see: 3.
Pressure Controller).
As soon as the main steam pressure is above “Pmin” the “pressure ramp” condition is
activated. The pressure setpoint “Ps demand” is increased, whenever the BP valve
position “Yset” exceed the position value “Ym”. The increase of the pressure setpoint
is limited by the gradient limiter and only positive pressure gradient are allowed
during “pressure ramp” operation, decrease of the pressure setpoint “Ps actual” is not
permitted in this operation mode.
As soon as the main steam pressure reaches “Psync” the “startup mode” is deselected
and the “fixed pressure mode” is activated. The pressure setpoint “Ps demand” is set at
the current last pressure setpoint “Ps actual”. In “fixed pressure mode” the “Pressure
setpoint” can be adjusted by the operator.
When the “HP turbine loaded” the BP valve will close automatically due to pressure
drop. As soon the BP valve is closed the setpoint generator will switch over to “follow
mode” (see: 2.2 Load Operation). In this mode pressure setpoint “Ps actual” will
follow main steam pressure.
In case of pressurized boiler at startup the “restart” condition is selected while the BP
valve is closed. In the “restart” condition the pressure setpoint “Ps actual” is following
the main steam pressure but only negative pressure gradients are allowed. As soon as
the boiler pressure starts to increase the bypass valve will start to open. When the BP
valve open the setpoint generator will go to “pressure ramp” condition if the pressure
is still below “Psync” or to “fixed pressure mode” if the pressure at startup is already
above “Psync”.
P re s s u r e / L o a d / F lo w
100 % S ta rt S e q u e n c e .
Turbine on
M in P re s s u re F ix e d
80 % P re s s Ram p P r e s s u re . F o llo w
60 %
40 % P sync S H -P r e s s u r e P S H
T u r b in e L o a d
20 %
S t e a m F lo w
P m in
F ire o n T im e
T u rb in e lo a d e d
B P v a lv e
100 %
Y BP
50 %
Ym
Y m in
T im e
During load operation, i.e. when the HP turbine is taking over all the produced steam,
the bypass valves are closed. The “follow mode” is activated.
In the “follow mode” the pressure setpoint “Ps actual” is following the actual main
steam pressure. The maximum pressure gradient is limited, depending on the actual
main steam pressure. A differential pressure “dP” is added to the pressure setpoint “Ps
actual” to keep the BP valve closed (see: 3. Pressure Controller).
If the main steam pressure is increasing above the Bypass controller setpoint “Ps
actual + dP” the BP valve starts to open. The setpoint generator is switched over to
“fixed Pressure mode”.
D e s ig n P re s s u re (P m a x + d P m a x )
P re s s .
M a x . P re s s u re (P m a x )
B yp a s s fa s t o p e n in g
(P s a c tu a l + d P m a x )
B yp a s s C o n tro lle r S e tp o in t
(P s a c tu a l + d P )
P re s s u re s e tp o in t
(P s a c tu a l)
M o d ifie d S lid in g P re s s u re
Load
At “Shut down mode” the pressure setpoint “Ps actual” is following the main steam
pressure but only negative gradients are allowed. As soon as the boiler pressure starts
to increase the BP valve start to open.
After the “Shut down mode” is deselected the setpoint generator is on “fixed pressure
mode”. At “fixed pressure mode” the setpoint generator controls the actual pressure.
As soon the boiler shuts down the BP valve is closing and the pressure generator is
switched to “follow mode”. In “follow mode” the pressure setpoint will again follow
the actual main steam pressure.
P re s s u re / L o a d / F lo w
100 %
F o llo w Shut
F ix e d
m ode down
p re s s u re F o llo w m o d e
80 % m ode
P r e s s .-S e tp o in t
60 %
M a in S te a m P r e s s u r e
40 %
S te a m F lo w
20 % T u r b in e L o a d
T u rb in e o ff F ire o ff T im e
B P v a lv e
100 %
Y BP
50 %
The pressure controller has one M/A station to control the BP valve.
At signals “BP open “ the BP valve will open to 100%. During this signal controller is
set manual and follow the valve position. After the signal the controller set automatic
At signal “BP close trip” the BP valve will be closed by the close command signal to
to the valve. The controller is set to manual.
In “follow mode” when the “dP on” is active a differential pressure is added to the
pressure setpoint “Ps actual” to keep BP valve close.
At “startup mode” when the “min pressure” condition is active the BP valve are
opened to a minimum position “Ymin”. The “Ymin on“ is deselcted when position is
above the minimum position “Ymin”.
The “BP close trip” command is generated when the BP outlet temperature exeed the
pressure “Tmax”.
The temperature controller has one M/A station to control the sprayvalve BPE valve.
The temperature controller is set automatic mode as soon the BP valve is open.
When the BP valve closes the spraywater valve closes also, and the temperature
controller is set to manual.
The spraywater isolation valve is open as soon the BP valve is open. When the BP
valve is closed the spraywater isolation valve is closed again.
Maximum pressure /DA [Mpa] Pmax 20 Max. range of pressure set point
Fast opening release /TB [Mpa] Pfo 15 General release for fast opening
pressure
Fast opening /TB [Mpa] dp max 0.5 Control deviation fast opening
P steam high
1. Overview (Diagram D)
100 %
80 % M in P re s s u re L o a d P re s s u re
60 %
40 % H o t re h e a t p re s s
P m in T u r b in e L o a d
20 %
S te a m F lo w
F ire o n T im e
T u rb in e lo a d e d
B P v a lv e
100 %
Y LBP
50 %
T im e
The pressure controller is receiving the actual hot reheat steam pressure signal (1 out
of 2 selection of two transmitter signals) and the pressure setpoint “Ps RHH actual”
from the setpoint generator. It is generating the LBP valves position demand signal.
The maximal LBP valve opening is limited by the steam flow to the condensator. As
soon the “LBP steam flow” the LBP valve start to close.
The “LBP close trip” command for the LBP valve is generated from condenser
protection switches. Each one of the following criteria are activating the “LBP close
trip” command:
- Condenser press. high (2 out of 3)
- Condenser temp. high
- Condenser level high
- LBP spraywater pressure low.
The temperature controller is receiving the actual signal Fw “LBP spraywater flow”
from the transmitter. The spraywater setpoint Fws is calculated out of the steam
pressure, steam temperature and LBP valve position . The controller is generating the
spraywater valve position demand signal.
The temperature controller has one M/A station to control the sprayvalve LP-BPE
valve.
The temperature controller is set to automatic mode as soon the LBP valve is open.
When the LBP valve is closed the spraywater valve is also closed, the controller is set
to manual.
The spraywater isolation valve is open as soon the LBP valve is open. When the LBP
valve is closed the spraywater isolation valve is closed again.