Solutions Manual For Power System Analysis and Design 6th Edition by Glover Ibsn 9781305632134 PDF Free
Solutions Manual For Power System Analysis and Design 6th Edition by Glover Ibsn 9781305632134 PDF Free
Chapter 2
Fundamentals
1
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Full all chapters instant download please go to Solutions Manual, Test Bank site: downloadlink.org
2.1 (a) A1 = 6∠30° = 6 [ cos30° + j sin 30°] = 5.20 + j 3
5
(b) A2 = −4 + j 5 = 16 + 25 ∠ tan −1 = 6.40 ∠128.66° = 6.40e j128.66°
−4
(c) A3 = ( 5.20 + j 3) + ( −4 + j 5 ) = 1.20 + j 8 = 8.01∠81.50°
(d) A4 = ( 6∠30° )( 6.40 ∠128.66° ) = 38.414∠158.658° = −35.78 + j13.98
(e) A5 = ( 6∠30° ) / ( 6.40∠ − 128.66° ) = 0.94 ∠158.66° = 0.94e j158.66°
( )
(c) I = 5 / 2 ∠ − 15° + 4∠ − 60° = ( 3.42 − j 0.92 ) + ( 2 − j 3.46 )
= 5.42 − j 4.38 = 6.964∠ − 38.94°
− j6 6∠ − 90°
2.4 (a) I1 = 10∠0° = 10 = 7.5∠ − 90° A
8 + j6 − j6 8
I 2 = I − I1 = 10∠0° − 7.3∠ − 90° = 10 + j 7.5 = 12.5∠36.87° A
V = I 2 ( − j 6 ) = (12.5∠36.87° ) ( 6∠ − 90° ) = 75∠ − 53.13° V
(b)
2
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
(d) Z = − j 25 Ω
I = V Z = ( 277∠30° ) ( 25∠ − 90° ) = 11.08∠120° A
i(t ) = 11.08 2 cos (ω t + 120° ) = 15.67cos (ω t + 120° ) A
(b) Z = 3 + j8 − j 4 = 3 + j 4 = 5∠53.1° Ω
(c) I = (100∠0° ) ( 5∠53.1° ) = 20∠ − 53.1° A
The current lags the source voltage by 53.1°
Power Factor = cos53.1° = 0.6 Lagging
3
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
The circuit transformed to phasor domain is shown below:
4
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
(c) p(t ) = υ (t )i(t ) = 391.7 × 15.67 cos (ω t + 30° ) cos (ω t + 120° )
1
= 6.138 × 103 cos ( −90° ) + cos ( 2ω t + 150° ) = 3.069 × 103 cos ( 2ω t + 150° ) W
2
P = VI cos (δ − β ) = 277 × 11.08cos ( 30° − 120° ) = 0 W
Q = VI sin (δ − β ) = 277 × 11.08sin ( −90° )
= −3.069 kVAR Absorbed = +3.069 kVAR Delivered
pf = cos (δ − β ) = cos ( −90° ) = 0 Leading
( 2)
2
(c) P = V 2 R = 359.3 10 = 6455 W Absorbed
X = ( 359.3 2 )
2
(d) Q = V 2 25 = 2582 VAR S Delivered
( 2 ) 10 = 889.8 W
2
(c) P = I 2 R = 13.34
5
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.14 (a) I = 2∠0° kA
V = Z I = ( 3∠ − 45° )( 2∠0° ) = 6∠ − 45° kV
υ (t ) = 6 2 cos ( ω t − 45° ) kV
p(t ) = υ (t )i (t ) = 6 2 cos (ω t − 45° ) 2 2 cos ω t
1
= 24 cos ( −45° ) + cos ( 2ω t − 45° )
2
= 8.49 + 12cos ( 2ω t − 45° ) MW
(b) P = VI cos ( δ − β ) = 6 × 2cos ( −45° − 0° ) = 8.49 MW Delivered
(c) Q = VI sin (δ − β ) = 6 × 2sin ( −45° − 0° )
= −8.49 MVAR Delivered = + 8.49 MVAR Absorbed
(d) pf = cos (δ − β ) = cos ( −45° − 0° ) = 0.707 Leading
2.15 (a) I = 4
( )
2 ∠60°
( 2∠30°) = 2 ∠30° A
6
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.16 (a) Z = 10 + j 120 π × 0.04 = 10 + j15.1 = 18.1∠56.4° Ω
pf = cos56.4° = 0.553 Lagging
(b) V = 120 ∠0° V
The current supplied by the source is
I = (120 ∠0° ) (18.1∠56.4° ) = 6.63∠ − 56.4° A
The real power absorbed by the load is given by
P = 120 × 6.63 × cos56.4° = 440 W
which can be checked by I 2 R = ( 6.63 ) 10 = 440 W
2
2
2.17 (a) S = V I * = Z I I * = Z I = jω LI 2
Q = Im[ S ] = ω LI 2 ←
di
(b) υ (t ) = L = − 2ω L I sin (ω t + θ )
dt
p(t ) = υ (t ) ⋅ i(t ) = −2ω L I 2 sin (ω t + θ ) cos (ω t + θ )
= −ω L I 2 sin 2 (ω t + θ ) ←
= − Q sin 2 (ω t + θ ) ←
Average real power P supplied to the inductor = 0 ←
Instantaneous power supplied (to sustain the changing energy in the magnetic field) has
a maximum value of Q. ←
2.18 (a) S = V I * = Z I I * = Re Z I 2 + j Im Z I 2
= P + jQ
∴P = Z I 2 cos ∠Z ; Q = Z I 2 sin ∠Z ←
(b) Choosing i(t ) = 2 I cos ω t ,
Then υ (t ) = 2 Z I cos (ω t + ∠Z )
∴ p(t ) = υ (t ) ⋅ i(t ) = Z I 2 cos (ω t + ∠Z ) ⋅ cos ω t
= Z I 2 cos ∠Z + cos ( 2ω t + ∠Z )
= Z I 2 [ cos ∠Z + cos2ω t cos ∠Z − sin 2ω t sin ∠Z ]
= P (1 + cos2ω t ) − Q sin 2ω t ←
7
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
1
(c) Z = R + jω L +
jωC
From part (a), P = RI 2 and Q = QL + QC
1 2
where QL = ω LI 2 and QC = − I
ωC
which are the reactive powers into L and C, respectively.
Thus p(t ) = P (1 + cos2ω t ) − QL sin 2ω t − QC sin 2ω t ←
If ω 2 LC = 1, QL + QC = Q = 0
←
Then p(t ) = P (1 + cos2ω t )
*
150 5
2.19 (a) S = V I * = ∠10° ∠ − 50° = 375 ∠60°
2 2
= 187.5 + j 324.8
P = Re S = 187.5 W Absorbed
Q = Im S = 324.8 VAR SAbsorbed
(b) pf = cos ( 60° ) = 0.5 Lagging
(c) QS = P tan QS = 187.5 tan cos−1 0.9 = 90.81VAR S
QC = QL − QS = 324.8 − 90.81 = 234 VAR S
1 1
2.20 Y1 = = = 0.05∠ − 30° = ( 0.0433 − j 0.025 ) S = G1 − jB1
Z1 20∠30°
1 1
Y2 = = = 0.04∠ − 60° = ( 0.02 − j 0.03464 ) S = G2 + jB2
Z 2 25∠60°
P1 = V 2 G1 = (100 ) 0.0433 = 433 W Absorbed
2
8
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.21 (a)
1 1 1
2.22 (a) Y1 = = = = 0.16∠ − 51.34°
Z1 ( 4 + j 5 ) 6.4∠51.34°
= ( 0.1 − j 0.12 ) S
1 1
Y2 = = = 0.1S
Z 2 10
P 1000
P = V 2 ( G1 + G2 ) ⇒ V = = = 70.71 V
G1 + G2 ( 0.1 + 0.1)
P1 = V 2 G1 = ( 70.71) 0.1 = 500 W
2
9
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.23 S = V I * = (120∠0° )(15∠ − 30° ) = 1800∠ − 30°
= 1558.85 − j 900
P = Re S = 1558.85 W Delivered
Q = Im S = −900 VAR S Delivered = +900 VAR SAbsorbed
The complex power delivered by the source is equal to the total complex power absorbed
by the load.
PL = 120 kW
pfL = 0.85 Lagging
θ L = cos−1 0.85 = 31.79°
10
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
QL = PL tan ( 31.79° )
SL = PL + jQL = 141.18∠31.79° kVA
I = SL / V = 141,180 / 480 = 294.13A = 74.364 kVAR
= 86.512 kVAR
∴ SS = PS + jQS = 120 + j ( 74.364 + 86.512 ) = 200.7∠53.28° kVA
The input voltage is given by VS = SS / I = 682.4 V (rms)
The power factor at the input is cos53.28° = 0.6 Lagging
(b) Applying KVL, VS = 480 ∠0° + j1.0 ( 294.13∠ − 31.79° )
= 635 + j 250 = 682.4∠21.5° V (rms)
( pf )S = cos ( 21.5° + 31.79° ) = 0.6 Lagging
Pold = 50 kW; cos−1 0.8 = 36.87° ; θOLD = 36.87°; Qold = Pold tan (θ old )
= 37.5 kVAR
∴ Sold = 50,000 + j 37,500
11
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.28 S1 = 15 + j 6.667
S 2 = 3 ( 0.96 ) − j 3 sin ( cos −1 0.96 ) = 2.88 − j 0.84
S3 = 15 + j 0
STOTAL = S1 + S2 + S3 = ( 32.88 + j 5.827 ) kVA
(i) Let Z be the impedance of a series combination of R and X
*
V V2
Since S = V I = V = * , it follows that
*
Z Z
( 240 )
2
V2
Z =
*
= = (1.698 − j 0.301) Ω
S ( 32.88 + j 5.827 )103
∴ Z = (1.698 + j 0.301) Ω ←
Then R= = 1.7518 Ω
( 32.88)103
( 240 )
2
X= = 9.885 Ω
( 5.827 )103
∴ Z = (1.7518 j 9.885 ) Ω ←
2.29 Since complex powers satisfy KCL at each bus, it follows that
S13 = (1 + j1) − (1 − j1) − ( 0.4 + j 0.2 ) = −0.4 + j1.8 ←
S31 = − S13* = 0.4 + j1.8 ←
12
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
θ ′ = cos−1 ( 0.8 ) = 36.87°
V 2 (1000 )
2
V1∠δ1 − V2 ∠δ 2 V1 V
2.31 (a) I12 = = ∠δ1 − 90° − 2 ∠δ 2 − 90°
X ∠90° X X
V V
Complex power S12 = V1 I12* = V1∠δ1 1 ∠90° − δ1 − 2 ∠90° − δ 2
X X
V12 V1V2
= ∠90° − ∠90° + δ1 − δ 2
X X
∴ The real and reactive power at the sending end are
V12 VV
P12 = cos90° − 1 2 cos ( 90° + δ1 − δ 2 )
X X
V1V2
= sin (δ1 − δ 2 ) ←
X
V12 VV
Q12 = sin 90° − 1 2 sin ( 90° + δ1 − δ 2 )
X X
V
= 1 V1 − V2 cos (δ1 − δ 2 ) ←
X
Note: If V1 leads V2 , δ = δ1 − δ 2 is positive and the real power flows from node 1 to
node 2. If V1 Lags V2 , δ is negative and power flows from node 2 to node 1.
(b) Maximum power transfer occurs when δ = 90° = δ1 − δ 2 ←
V1V2
PMAX = ←
X
2.32 4 Mvar minimizes the real power line losses, while 4.5 Mvar minimizes the MVA power
flow into the feeder.
13
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.33
Qcap MW Losses Mvar Losses
0 0.42 0.84
0.5 0.4 0.8
1 0.383 0.766
1.5 0.369 0.738
2 0.357 0.714
2.5 0.348 0.696
3 0.341 0.682
3.5 0.337 0.675
4 0.336 0.672
4.5 0.337 0.675
5 0.341 0.682
5.5 0.348 0.696
6 0.357 0.714
6.5 0.369 0.738
7 0.383 0.766
7.5 0.4 0.801
8 0.42 0.84
8.5 0.442 0.885
9 0.467 0.934
9.5 0.495 0.99
10 0.525 1.05
2.35
14
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
(.3846 + .4950 ) + j (10 − 1.923 − 4.950 ) − (.4950 − j 4.950 ) V10
− (.4950 − j 4.950 ) (.3846 + .4950 ) + j (10 − 1.923 − 4.95) V20
1.961∠ − 48.69°
=
1.961∠ − 78.69°
0.8796 + j 3.127 −0.4950 + j 4.950 V10 1.961∠ − 48.69°
=
−0.4950 + j 4.950 −0.8796 + j 3.127 V20 1.961∠ − 78.69°
2.36 Note that there are two buses plus the reference bus and one line for this problem. After
converting the voltage sources in Fig. 2.29 to current sources, the equivalent source
impedances are:
=
( 0.5099∠78.69°)( 0.1∠ − 90°) = 0.1237∠ − 87.27°
0.4123∠75.96°
= 0.005882 − j 0.1235 Ω
The rest is left as an exercise to the student.
2.37 After converting impedance values in Figure 2.30 to admittance values, the bus admittance
matrix is:
1 −1 0 0
−1 1 + 1 + 1 + 1 − j1 −
1
− j1
−
1
2 3 4 3 4
Ybus = 1 1 1 1 1
0 − − j1 3 − j1 + j + j − j
4
3 4 2
1 1 1 1 1
0 − − j + j 4 − j 3
4 4 4
Writing nodal equations by inspection:
1 −1 0 0 V10 1∠0°
−1 ( 2.083 − j1) ( −0.3333 + j1) −0.25 V20 = 0
0 ( −0.3333 + j1) ( 0.3333 − j 0.25 ) − j 0.25 V30 0
0 ( −0.25 ) − j 0.25 ( 0.25 − j 0.08333) V40 2∠30°
15
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.38 The admittance diagram for the system is shown below:
where Y11 = y10 + y12 + y13 ; Y22 = y20 + y12 + y23 ; Y23 = y13 + y23 + y34
Y44 = y34 ; Y12 = Y21 = − y12 ; Y13 = Y31 = − y13 ; Y23 = Y32 = − y23
2.39 (a)
−14.5 8 4 2.5 V1 0
8 −17 4
5 V2 0
(b) j =
4 4 −8.8 0 V3 1∠ − 90°
2.5 5 0 −8.3 V4 0.62∠ − 135°
YBUS V = I ; YBUS
−1
YBUS V = YBUS
−1
I
16
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
0.7187 0.6688 0.6307 0.6194
0.6688 0.7045 0.6242 0.6258
where −1
YBUS = Z BUS = j Ω
0.6307 0.7045 0.6840 0.5660
0.6194 0.6258 0.5660 0.6840
V = YBUS
−1
I
V1 0
0
V
where V = 2 and I =
V3 1∠ − 90°
V4 0.62∠ − 135°
Then solve for V1 , V2 , V3 , and V4 .
240
2.40 (a) VAN = ∠0° = 138.56∠0° V (Assumed as Reference)
3
VAB = 240∠30° V; VBC = 240∠ − 90° V; I A = 15∠ − 90° A
VAN 138.56 ∠0°
ZY = = = 9.24∠90° = ( 0 + j 9.24 ) Ω
IA 15∠ − 90°
IA 15
(b) I AB = ∠30° = ∠ − 90° + 30° = 8.66∠ − 60°A
3 3
VAB 240∠30°
Z∆ = = = 27.71∠90° = ( 0 + j 27.71) Ω
I AB 8.66∠ − 60°
Note: ZY = Z ∆ / 3
208 Z∆
Van = ∠ − 30° = 4 + j 3 = 5∠36.87° Ω
3 3
Van 120.1∠ − 30°
Ia = = = 24.02∠ − 66.87° A
( Z ∆ / 3) 5∠36.87°
17
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
S3φ = 3Van I a* = 3 (120.1∠ − 30° )( 24.02∠ + 66.87° )
= 8654∠36.87° = 6923 + j 5192
P3φ = 6923 W; Q3φ = 5192 VAR; both absorbed by the load
pf = cos ( 36.87° ) = 0.8 Lagging; S3φ = S3φ = 8654 VA
(b)
2.43 (a) Transforming the ∆-connected load into an equivalent Y, the impedance per phase of
the equivalent Y is
60 − j 45
Z2 = = ( 20 − j15 ) Ω
3
With the phase voltage V1 = 1203 3 = 120 V taken as a reference, the per-phase equivalent
circuit is shown below:
18
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
(b) Phase voltage at load terminals V2 = 120∠0° − ( 2 + j 4 )( 5 ∠0° )
= 110 − j 20 = 111.8∠ − 10.3° V
The line voltage magnitude at the load terminal is
(c) The current per phase in the Y-connected load and in the equiv.Y of the ∆-load:
V2
I1 = = 1 − j 2 = 2.236∠ − 63.4° A
Z1
V2
I2 = = 4 + j 2 = 4.472 ∠26.56° A
Z2
2200 3
Phase voltage at the load terminals is V2 = = 2200 V taken as Ref.
3
Total complex power at the load end or receiving end is
SR( 3φ ) = 560.1( 0.707 + j 0.707 ) + 132 = 528 + j 396 = 660∠36.87° kVA
19
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
With phase voltage V2 as reference,
= 12 kW + j81kVAR
(c) The three-phase sending power is
SS (3φ ) = 3V1 I * = 3 ( 2401.7∠4.58° )(100∠36.87° )
= 540 kW + j 477 kVAR
2.45 (a)
SS 25.001 × 103
IS = = = 30.07 A
3VLL 3 ( 480 )
(b) The ammeter reads zero, because in a balanced three-phase system, there is no neutral
current.
2.46 (a)
20
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Z∆ / 3
Using voltage division: VAN = Van
( Z ∆ / 3) + Z LINE
208 10∠30°
= ∠0°
3 10∠30° + ( 0.8 + j 0.6 )
=
(120.09 )(10∠30°) = 1200.9∠30°
9.46 + j 5.6 10.99∠30.62°
= 109.3∠ − 0.62° V
Z eq = 10 ∠30 ° || (− j 20)
= 11.547 ∠0 °Ω
Z eq
VAN = Van
Z eq + Z LINE
(
= 208 3 ) (11.54711.547
+ 0.8 + j 0.6 )
1386.7
= = 112.2∠ − 2.78° V
12.362∠2.78°
Load voltage Line-to-Line VAB = 3 (112.2 ) = 194.3 V
2.47
15 × 103
(a) I G1 = ∠ − cos−1 0.8 = 23.53∠ − 36.87° A
8 ( 460 )( 0.8 )
460
VL = VG1− Z LINE1 I G1 = ∠0° − (1.4 + j1.6 )( 23.53∠ − 36.87° )
3
= 216.9∠ − 2.73° V Line to Neutral
Load Voltage VL = 3 216.9 = 375.7 V Line to line
21
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
30 × 103
(b) I L = ∠ − 2.73° − cos−1 0.8 = 57.63∠ − 39.6° A
3 ( 375.7 )( 0.8 )
I G 2 = I L − I G1 = 57.63 ∠ − 39.6° − 23.53∠ − 36.87°
= 34.14∠ − 41.49° A
VG 2 = VL + Z LINE 2 I G 2 = 216.9∠ − 2.73° + ( 0.8 + j1)( 34.14∠ − 41.49° )
= 259.7∠ − 0.63° V
Generator 2 line-to-line voltage VG 2 = 3 ( 259.7 )
= 449.8 V
(c) SG 2 = 3VG 2 I G* = 3 ( 259.7∠ − 0.63° )( 34.14∠41.49° )
2
2.48 (a)
3 ( 480 )
2
X∆ = = 49.37 Ω
14 × 103
(e) I C = VLL / X ∆ = 480 / 49.37 = 9.72 A
PL 23 × 103
I LINE = = = 27.66 A
3 VLL 3 480
22
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
2.49 (a) Let ZY = Z A = Z B = ZC for a balanced Y-load
Z ∆ = Z AB = Z BC = Z CA
Using equations in Fig. 2.27
ZY2 + ZY2 + ZY2
Z∆ = = 3 ZY
ZY
and
Z ∆2 Z
ZY = = ∆
Z∆ + Z∆ + Z∆ 3
(b) Z A =
( j10 )( − j 25)
= − j 50 Ω
j10 + j 20 − j 25
ZB =
( j10 )( j 20 ) = j 40 Ω; Z =
( j 20 )( − j 25) = − j 100 Ω
C
j5 j5
2
2.50 Replace delta by the equivalent WYE: ZY = − j Ω
3
Per-phase equivalent circuit is shown below:
2
Noting that j 1.0 − j = − j 2 , by voltage-divider law,
3
− j2
V1 = (100∠0°) = 105∠0°
− j 2 + j 0.1
173.2∠30°
Then I A′B′ = = 86.6∠120°
− j2
∴ i2 (t ) = 86.6 2 cos (ω t + 120° )
= 122.5cos (ω t + 120° ) A ←
23
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
1
2.51 On a per-phase basis S1 = (150 + j120 ) = ( 50 + j 40 ) kVA
3
( 50 − j 40 )103 =
∴ I1 = ( 25 − j 20 ) A
2000
Note: PF Lagging
Load 2: Convert ∆ into an equivalent Y
1
Z 2Y = (150 − j 48 ) = ( 50 − j16 ) Ω
3
2000∠0°
∴ I2 = = 38.1∠17.74°
50 − j16
= ( 36.29 + j 11.61) A
Note: PF Leading
1
S3 per phase = (120 × 0.6 ) − j 120 sin( cos−1 0.6 ) = ( 24 − j 32 ) kVA
3
( 24 + j32 )103 =
∴ I3 = (12 + j 16 ) A
2000
Note:PF Leading
Voltage at the sending end: VAN = 2000∠0° + ( 73.29 + j 7.61)( 0.2 + j 1.0 )
2160
2.52 (a) Let VAN be the reference: VAN = ∠0° ≃ 2400∠0° V
3
Total impedance per phase Z = ( 4.7 + j 9 ) + ( 0.3 + j1) = ( 5 + j10 ) Ω
2400∠0°
∴ Line Current = = 214.7∠ − 63.4° A = I A ←
5 + j10
With positive A-B-C phase sequence,
I B = 214.7∠ − 183.4° A; I C = 214.7∠ − 303.4° = 214.7∠56.6° A ←
24
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
(b) (VA′N ) LOAD = 2400∠0° − ( 214.7∠ − 63.4° )( 0.3 + j1)
= 2400∠0° − 224.15∠9.9° = 2179.2 − j 38.54
= 2179.5∠ − 1.01° V ←
(V )
B′N LOAD
= 2179.5∠ − 121.01° V □ ; (VC ′N ) LOAD = 2179.5∠ − 241.01° V □
25
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Solutions Manual for Power System Analysis and Design 6th Edition by Glover IBSN 9781305632134
Full Download: http://downloadlink.org/product/solutions-manual-for-power-system-analysis-and-design-6th-edition-by-glover-ibs
26
© 2017 Cengage Learning®. May not be scanned, copied or duplicated, or posted to a publicly accessible website, in whole or in part.
Full all chapters instant download please go to Solutions Manual, Test Bank site: downloadlink.org