Ceiling Mouted AHU C Manual en Oct 16 2017
Ceiling Mouted AHU C Manual en Oct 16 2017
Climate 5000
AHU20~150C4E | AHU20~150C6E
Read the manual carefully prior to installation and operation the unit!
Table of Contents
3 Engineering installation............................... 12
3.1 Delivery, unloading and storage ..........12
3.1.1 Delivery ..........................12
3.1.2 Unloading ........................12
3.2 Installation.............................12
3.2.1 Installation preparation .............12
3.2.2 Equipment installation .............12
3.2.3 Connection of heat exchanger ......13
3.2.4 Electrical equipment installation .....13
3.2.5 Trap installation ...................14
5 Maintenance.................................................. 16
5.1 Fan and motor .........................16
5.2 Filter ..................................16
5.3 Heat exchanger ........................16
8 Notes ............................................................. 19
- AHU60C4L/R210/240E
- AHU70C4L/R300/320E
- AHU80C4L/R300/320E
- AHU90C4L/R280/350E
- AHU100C4L/R350/420E
- AHU120C4L/R320/390E
- AHU150C4L/R390/440E
- AHU20C6L/R130/170E
- AHU25C6L/R130/170E
- AHU30C6L/R130/190E
- AHU40C6L/R150/200E
- AHU50C6L/R190/240E
- AHU60C6L/R190/220E
- AHU70C6L/R280/300E
- AHU80C6L/R280/300E
- AHU90C6L/R260/320E
- AHU100C6L/R320/390E
- AHU120C6L/R300/360E
- AHU150C6L/R360/420E
• Air volume: 2000~15000 m³/h
• External total pressure: 80~290 Pa
• Cooling capacity: 11.6~108.0 kW
• Heating capacity: 21.0 ~190.0 kW
• The standard of power supply: 380V/ 3N/ 50Hz
• Maximum working pressure of unit: ≤ 1.6MPa
2 Product information
• High performance heat exchanger
2.1 Product overview The air handling unit use unique pipe arrange-
ment of heat exchanger, which could improve
The air handling unit is a unit that improve indoor 10%-30% heat exchange efficiency compared
air quality by adjust indoor temperature, humidity with traditional pipe laying.
and purified indoor air which cooling, dehumidified
or heating a proportion of indoor return air and • Unique design of air inlet and outlet
outdoor fresh air or fully fresh air with external
cool water or hot water passing heat exchanger The filter of air inlet is flange structure, which
and exhausted by fan. can also be non-woven filter in accordance with
the requirements of clients.
• Extensive performance and usage
• International advanced processing and
The air handling unit can be extensively used in manufacturing technology
public buildings and various industrial occa-
sions, such as shopping mall, hotel, hall, The company has the most advanced panel
gymnasium, textile, metallurgy, machinery, processing equipment and manufacturing line
health, electronic instrument, etc.. for heat, which provides reliable quality guaran-
tee for air handling unit.
2.2 Nomenclature
Product Type:
C:Celling Suspend
J:Remote Jet
Air Flow: *100m /h
3 V:Vertical Type
HI:Horizontal Type I
S:Series Single Skin HⅡ:Horizontal Type Ⅱ
Omitted:Series Double Skin HⅢ:Horizontal Type Ⅲ
Air Handling Unit
Value Level: 1000~9000
Category: Climate
Brand: Bosch
• ‘Bosch Climate 5000’ will be more for communication purpose (brochure/ website etc.)
• Standard Power Supply is 380V/ 50Hz/ 3 Phase
Figure 1. Nomenclature
1 2 3
C
6 5
Air Flow m3/h 2000 2500 3000 4000 5000 6000 7000 8000 9000 10000 12000 15000
Nominal Cooling
kW 11.6 13.9 17.5 22.7 29.2 35.9 42.6 47.1 51.5 57.1 67.6 86.1
Capacity
Nominal Heating
kW 21.0 26.5 32.1 42.6 53.8 64.7 75.9 83.1 92.5 103.5 125.4 157.1
Capacity
Water Flow m3/h 0.55 0.66 0.83 1.08 1.39 1.71 2.03 2.25 2.45 2.72 3.22 4.10
Water Pressure
kPa 23 15 24 17 30 35 53 62 28 31 33 39
Drop
Static Pressure
Pa 80 80 80 130 130 130 180 180 190 230 230 230
(Ⅰ)
Total Pressure
Pa 150 150 150 170 210 210 300 300 280 350 320 390
(Ⅰ)
Static Pressure
Pa 130 130 130 180 180 180 240 240 240 290 290 290
(Ⅱ)
Total Pressure
Pa 190 190 210 220 260 240 320 320 350 420 390 440
(Ⅱ)
Table 3. 4PR parameters
• 6PR parameters
AHU AHU AHU AHU AHU AHU AHU AHU AHU AHU AHU AHU
Model Unit
20C6E 25C6E 30C6E 40C6E 50C6E 60C6E 70C6E 80C6E 90C6E 100C6E 120C6E 150C6E
Air Flow m3/h 2000 2500 3000 4000 5000 6000 7000 8000 9000 10000 12000 15000
Nominal Cooling
kW 13.8 17.9 23.0 29.7 37.1 46.9 52.6 59.3 64.1 71.5 86.0 108.0
Capacity
Nominal Heating
kW 25.0 31.5 38.0 50.7 63.0 76.6 88.8 98.6 109.0 128.0 152.0 190.0
Capacity
Water Flow m3/h 0.66 0.85 1.09 1.42 1.77 2.24 2.54 2.83 3.06 3.41 4.10 5.15
Water Pressure
kPa 15 25 43 36 24 78 40 47 23 25 29 26
Drop
Static Pressure
Pa 60 60 60 110 110 110 160 160 160 210 210 210
(Ⅰ)
Total Pressure
Pa 130 130 130 150 190 190 280 280 260 320 300 360
(Ⅰ)
Static Pressure
Pa 110 110 110 160 160 160 220 220 220 270 270 270
(Ⅱ)
Total Pressure
Pa 170 170 190 200 240 220 300 300 320 390 360 420
(Ⅱ)
Table 4. 6PR parameters
• Cooling condition: • Heating condition:
- Inlet air temp 27°C DB/19.5°C WB - Inlet air temp 21°C DB
- Inlet water temp 7°C, outlet water temp 12°C. - Inlet water temp 60°C.
• AHU40CE-150CE
AHU20CE 1107 816 540 265 234 / 124 167 756 485
8736862517(2017/09)
AHU25CE 1107 964 540 265 234 / 138 167 904 485
10 | Product information
AHU50CE 1187 1716 540 265 234 178 89 167 1656 485
AHU60CE 1187 1820 592 293 256 208 104 169 1760 537
AHU70CE 1241 2081 592 304 268 238 119 167 2021 537
AHU80CE 1292 2116 647 337 295 258 129 167 2056 592
AHU90CE 1292 2347 647 337 295 258 129 167 2287 592
AHU100CE 1184 2434 679 337 295 258 129 167 2374 624
AHU120CE 1238 2457 775 401 342 318 159 167 2397 720
AHU150CE 1265 2528 903 401 342 318 159 167 2468 848
Table 5. Ouline dimensions for AHU20CE-150CE
• Remark:
Condensate pipe should use DN25 externally threaded tubes.
Climate 5000
Product information | 11
• Installation characteristics
The double-shell structure of Bosch ceiling
handling unit is derived from ingenious ad-
vanced technology, which is more solid than
the single-shell structure of other manufactur-
ers. And the high-quality components also
ensure safety operation and longer service life,
which dramatically saves the cost and time of
users.
3 Engineering installation
The maximum length of the hoisting and the
3.1 Delivery, unloading and storage transported unit is 6150mm. The stress of unit
hoisting must be on the pedestal and the angle of
3.1.1 Delivery hoisting ropes is no more than 60°.
After the goods arrived, please check whether the
unit and accessories are all ready and have no 3.1.2.2 The method of carrying unit with forklift
damage. If there are any problems found, please Please pay attention to the center of gravity of
record them in time and give feedback to manu- unit and shovel pedestal when carrying with forklift.
facturer promptly with signature of the shipper.
3.1.2.3 Storage
3.1.2 Unloading
► Putthe pedestal of unit downward on the flat
backing board.
3.1.2.1 Hoisting diagram employed by unit
► The shell cannot be stressed directly.
Notice: Risk of falling!
► Do not remove the external plastic package.
Anti-sliding pin shall be used on both
sides of the hoisting steel, to prevent ► Store the goods at ventilated place.
any slip or slope caused by gravity
shifting.
3.2 Installation
• Selection of hoisting steel pipe
- When the shipping weight is less than 2000 3.2.1 Installation preparation
Kg, employ steel pipe with a diameter and
Notice: Risk of unit damage!
thickness of no less than Φ 42*6.
Do not climb and tread on the unit!
- When the shipping weight is less than 4000
Kg, employ steel pile with a diameter and
► Find the installation instruction at the spot
thickness of less than Φ 48*10.
where equipment and accessories material are
placed, assemble the spare parts and random
accessories.
Water inlet
气流
进水
Automatic
KA KM AC contactor
control switch
M Motor
4 Unit start-up
4.1 Confirmation
• Before start-up, please ensure
- All transportation safety devices are dismantled.
- There is no loose material inside of the unit
- Air flue and various power lines are well
connected
- All components are in right operation
- The pipe of trap is full of water.
4.2 Fan
Notice: Risk of injury!
Do not start the fan when the regulating
valve is closed; do not open or dis-
mantle the access door of the unit
during unit operation.
► Check rotating direction of the fan, which shall
be the same with rotating mark of the fan.
► Check whether the protector of motor is working
normally.
4.4 Humidifier
Start it in accordance with the type of humidifier to
be installed and with reference to the separated
instruction of humidifier.
5 Maintenance
Notice: Beware of electric shock!
The main power shall be cut off before
any maintenance is implemented. All
parts which is easy to be worn shall be
checked regularly (at least once a quarter).
5.2 Filter
It is suggested that the air filter shall be washed
once a week, especially when the air volume and
cooling capacity are reducing
• The following maintenance works shall be
done every six months,
► Clean the dust on regulating valve.
► Check regulating valve can move freely after
removing the driver.
► Check the driver of regulating valve.
Cold (hot) water is not cold (hot) Decrease (increase) water temperature
Leakage
Uneven installation Leveling
7 Packing list
Packing List
CTN: 1
Model and
Type Name Quantity Unit
specification
Local
Unit See data plate 1 Set
machine
Manual —— 1 Copy
Print
Accessories
Packing list —— 1 Copy
8 Notes