TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 1a
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail :
[email protected] HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION : 21ST MAY 2012
TRANSFORMER OIL TEST REPORT
THE CHIEF TERMINAL MANAGER,
NAME OF THE CONSUMER :
M/S INDIAN OIL CORPORATION LTD.,
KORUKKUPET,
TRANSFORMER SPECIFICATION:-
CHENNAI- 600 021
LOCATION : OUTDOOR
Make : ALSTHOM
Rating : 100 KVA
Voltage HV / LV : 433 / 415Volts
Maker’s Serial No. : 7688C
Next Oil Filtration Due on : 21ST MAY 2013
TEST KIT DETAILS:-
Make : VA Power India
Serial Number : S 200315
Kit Calibration Due Date : 23-08-2012
Input : 230 V. AC, Output : 0 – 60KV, Freq.: 50HZ Single Phase
TESTED BDV VALUES:- TEST GAP BETWEEN ELECTRODES : 2.5mm
OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.
NO. OF As per Speciation
Before Filtration After Filtration Test Result
TEST Value
1 31 50
2 30 50
3 29 50
4 40KV SATISFACTORY
31 50
5 30 50
6 30 50
TOTAL 181 250
AVERAGE 30.1 KV 50 KV
BOTTOM Sample withstood 40KV for One minute
ACIDITY TEST:- 0.15 MILLIGRAM OF KOH / GRAM OF OIL
Maximum permissible value : 0.30 mg of KOH
FOR DURGA SWITCHGEARS
(AUTHORISED SIGNATORY)
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 1b
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : [email protected]
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION : 21ST MAY 2012
TRANSFORMER OIL TEST REPORT
THE CHIEF TERMINAL MANAGER,
NAME OF THE CONSUMER :
M/S INDIAN OIL CORPORATION LTD.,
KORUKKUPET,
TRANSFORMER SPECIFICATION:-
CHENNAI- 600 021
LOCATION : INDOOR
Make : INDO TECH
Rating : 500 KVA
Voltage HV / LV : 11000 / 433 Volts
Maker’s Serial No. : IT 16654
Next Oil Filtration Due on : 21ST MAY 2013
TEST KIT DETAILS:-
Make : VA Power India
Serial Number : S 200315
Kit Calibration Due Date : 23-08-2012
Input : 230 V. AC, Output : 0 – 60KV, Freq.: 50HZ Single Phase
TESTED BDV VALUES:- TEST GAP BETWEEN ELECTRODES : 2.5mm
OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.
NO. OF As per Speciation
Before Filtration After Filtration Test Result
TEST Value
1 33 50
2 32 50
3 33 50
4 40KV SATISFACTORY
30 50
5 31 50
6 31 50
TOTAL 190 250
AVERAGE 31.6 KV 50 KV
TOP & BOTTOM Samples ---- withstood 40KV for One minute
ACIDITY TEST:- 0.17 MILLIGRAM OF KOH / GRAM OF OIL
Maximum permissible value : 0.30 mg of KOH
FOR DURGA SWITCHGEARS
(AUTHORISED SIGNATORY)
TEST REPORT
FOR
TRANSFORMER OIL FILTRATION
M/S INDIAN OIL CORPORATION LTD.,
KORUKKUPET,
CHENNAI – 600 021.
Carried out
On
21ST May 2012
FOR
M/S AKSHAYA ELECTRICALS, PERAMBUR. CHENNAI.
JOB CARRIED OUT BY : DURGA SWITCHGEARS
A-GRADE CONTRACTORS EA 2616
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai – 600 051.