Sequence Impedance - Capacitance Data

The document provides electrical specifications for various sizes of 35kV aluminum conductor cables, including conductor size, number of wires, impedance values, and ampacity ratings. It lists these details for different cable configurations including full sized, 2/3 sized, 1/2 sized, 1/3 sized and 1/6 sized cables. The specifications are based on assumptions of a 3 phase installation with one cable per phase, burial depth of 36 inches, ambient temperature of 20°C, and conductor temperature of 90°C.

Uploaded by

gerrzen64
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views

Sequence Impedance - Capacitance Data

The document provides electrical specifications for various sizes of 35kV aluminum conductor cables, including conductor size, number of wires, impedance values, and ampacity ratings. It lists these details for different cable configurations including full sized, 2/3 sized, 1/2 sized, 1/3 sized and 1/6 sized cables. The specifications are based on assumptions of a 3 phase installation with one cable per phase, burial depth of 36 inches, ambient temperature of 20°C, and conductor temperature of 90°C.

Uploaded by

gerrzen64
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Electricals 35kV, AL, 100% TRXLP, CN, PE JKT

Neutral Trefoil Flat Spaced @7.5 Inches Flat Spaced Touching


Conductor Capacitance
Size No. of Size of (pF/ft) Pos/Neg Sequence Zero Sequence Impedance Pos/Neg Sequence Zero Sequence Impedance Pos/Neg Sequence Zero Sequence Impedance
Size Ampacity Ampacity Ampacity
Wires Wires Impedance (ohms/1000ft) (ohms/1000ft) Impedance (ohms/1000ft) (ohms/1000ft) Impedance (ohms/1000ft) (ohms/1000ft)

1/0 Full 16 14 37.66 0.21237 +j 0.05281 0.39254 +j 0.08462 230 0.22806 +j 0.09053 0.38496 +j 0.08819 245 0.21320 +j 0.05776 0.39062 +j 0.08483 230
1/0 2/3 11 14 37.66 0.21184 +j 0.05289 0.45396 +j 0.13148 230 0.22302 +j 0.09354 0.43985 +j 0.13613 247 0.21215 +j 0.05804 0.45120 +j 0.13168 230
2/0 Full 20 14 40.17 0.16934 +j 0.05106 0.31746 +j 0.06602 262 0.18758 +j 0.08541 0.31260 +j 0.06878 277 0.17063 +j 0.05549 0.31610 +j 0.06619 261
3/0 Full 25 14 43.23 0.13519 +j 0.04897 0.25564 +j 0.05278 297 0.15584 +j 0.07952 0.25268 +j 0.05484 311 0.13723 +j 0.05358 0.25473 +j 0.05296 296
4/0 Full 20 12 46.56 0.10839 +j 0.04703 0.20367 +j 0.04337 338 0.13085 +j 0.07265 0.20195 +j 0.04480 349 0.11112 +j 0.05138 0.20311 +j 0.04352 336
4/0 1/2 10 12 46.56 0.10682 +j 0.04745 0.28901 +j 0.08260 340 0.12124 +j 0.08343 0.28255 +j 0.08640 358 0.10814 +j 0.05278 0.28753 +j 0.08290 339
350 1/3 18 14 55.60 0.06583 +j 0.04465 0.23002 +j 0.06828 448 0.08041 +j 0.07707 0.22592 +j 0.07179 457 0.06735 +j 0.04893 0.22923 +j 0.06859 444
500 1/3 16 12 63.11 0.04763 +j 0.04217 0.16729 +j 0.04656 543 0.06465 +j 0.06940 0.16524 +j 0.04866 526 0.04986 +j 0.04622 0.16719 +j 0.04687 536
750 1/6 12 12 73.63 0.03230 +j 0.03999 0.18874 +j 0.06210 677 0.04478 +j 0.06902 0.18546 +j 0.06529 647 0.03412 +j 0.04470 0.18848 +j 0.06265 666
1000 1/6 16 12 82.15 0.02569 +j 0.03790 0.14630 +j 0.04401 778 0.03996 +j 0.06330 0.14431 +j 0.04604 698 0.02801 +j 0.04253 0.14604 +j 0.04434 748
1250 1/6 20 12 89.82 0.02206 +j 0.03671 0.11940 +j 0.03496 858 0.03732 +j 0.05850 0.11774 +j 0.03627 731 0.02467 +j 0.04071 0.11908 +j 0.03513 806
Impedance and ampacity based on a 3 phase installation with one cable per phase, in the configuration as noted in the table header. Assuming a 75% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C conductor temperature, and an earth RHO of 90°C.cm/W