YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 1
MANUAL NO. TOEP C710606 15C
2 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
V1000
Quick Start Guide
ENGLISH
1 Safety Instructions and General Warnings . . . . . . . . . . 2
2 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Keypad Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5 Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6 Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 3
1 Safety Instructions and General Warnings
General Warnings
WARNING
• Read and understand this manual before installing, operating or servicing this drive.
• All warnings, cautions, and instructions must be followed.
• All work must be performed by qualified personnel.
• The drive must be installed according to this manual and local codes.
• Heed the safety messages in this manual.
The operating company is responsible for any injuries or equipment damage resulting from
failure to heed the warnings in this manual.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
The following conventions are used to indicate Safety messages in this manual:
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a property damage message.
4 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
1 Safety Instructions and General Warnings
Safety Warnings
WARNING
Electrical Shock Hazard
• Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This product
must not be modified.
• Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains
charged even after the power supply is turned off. The charge indicator LED will extinguish
when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes
after all indicators are off and measure the DC bus voltage level to confirm safe level.
• Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
• Do not perform work on the drive while wearing loose clothing, jewelry or without eye
protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye
protection before beginning work on the drive.
• Never short the output circuits of the drive.
Do not short the output circuits of the drive. Failure to comply could result in death or serious
injury.
Sudden Movement Hazard
• Stay clear of the motor during rotational Auto-Tuning. The motor may start operating
suddenly.
During automatic starting of equipment, the machine may start moving suddenly, which could
result in death or serious injury.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 5
1 Safety Instructions and General Warnings
WARNING
• System may start unexpectedly upon application of power, resulting in death or serious
injury.
Clear all personnel from the drive, motor, and machine area before applying power. Secure
covers, couplings, shaft keys, and machine loads before applying power to the drive.
Fire Hazard
• Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply
before applying power.
• Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
• Do not connect AC line power to output terminals U, V, and W.
• Make sure that the power supply lines are connected to main circuit input terminals R/
L1, S/L2, T/L3 (or R/L1 and S/L2 for single-phase drives).
Do not connect the AC power line to the output motor terminals of the drive. Failure to comply
could result in death or serious injury by fire as a result of drive damage from line voltage
application to output terminals.
CAUTION
Crush Hazard
• Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive
falling.
Burn Hazard
• Do not touch the heatsink or braking resistor hardware until a powered-down cooling
period has elapsed.
6 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
1 Safety Instructions and General Warnings
NOTICE
Equipment Hazard
• Observe proper electrostatic discharge procedures (ESD) when handling the drive and
circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
• Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
• Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
• Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive.
The drive is suitable for circuits capable of delivering not more than 30,000 RMS symmetrical
Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400V Class).
7 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
1 Safety Instructions and General Warnings
8 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
2 Mechanical Installation
ENGLISH
2 Mechanical Installation
Upon Receipt
Please perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact your sup-
plier.
• Verify receipt of the correct model by checking the information on the nameplate. If you
have received the wrong model contact your supplier.
Installation Environment
For optimum performance life of the drive, install the drive in an environment that meets the
conditions listed below.
Environment Conditions
Installation Area Indoors
-10°C to +40°C (NEMA Type 1)
-10°C to +50°C (Open-Chassis Type)
Ambient Temperature When using an enclosure panel, install a cooling fan or air conditioner in the
area to ensure that the air temperature inside the enclosure does not exceed the
specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20°C to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
Surrounding Area • combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Altitude 1000 m or less
Vibration 10 - 20 Hz at 9.8 m/s2, 20 - 55 Hz at 5.9 m/s2
Orientation Install the drive vertically to maintain maximum cooling effects.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 9
2 Mechanical Installation
Dimensions
d W1
H2
H2
W1
2A0010B 108 128 129 96 118 5 - - 58 M4 1.7
2A0012B 108 128 137.5 96 118 5 - - 58 M4 1.7
2A0020B 140 128 143 128 118 5 - - 65 M4 2.4
2A0030F 140 254 140 122 248 6 13 6.2 55 M5 3.8
H1
H
10 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
2 Mechanical Installation
d
W1
Model Dimensions (mm) Weight
H3
H2
CIMR-VC Fig. W H D W1 H1 H2 H3 H5 D1 d (kg)
2A0030A 140 247 140 122 248 6 13 13 55 M5 3.6
2A0040A 140 247 140 122 248 6 13 13 55 M5 3.6
2A0056A 180 285 163 160 284 8 15 15 75 M5 5.3
2A0069A 220 335 187 192 336 7 15 15 78 M6 8.7
H1
H
C
4A0018A 140 247 140 122 248 6 13 13 55 M5 3.6
4A0023A 140 247 140 122 248 6 13 13 55 M5 3.6
H5
D1
D
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 11
3 Electrical Installation
3 Electrical Installation
The figure below shows the main and control circuit wiring.
DC reactor Thermal Braking
(option) relay resistor
(opt)
Link
+2 +1 㪄 B1 B2
Fuses U
L1 R/L1 U/T1
Power V
Supply
L2 Filter S/L2 V1000 V/T2 M
T/L3 <1> W
L3 W/T3
Main
Switch Forward/Stop S1
Shielded
Cable
Reverse/Stop S2
Ground
External Fault S3
Fault Reset S4
Multi-speed 1 S5
Multi-speed 2 S6
+24 V 8 mA
MA Multi-function relay output
MB Fault 250 Vac / 30 Vdc (10 mA to 1A)
Multi-function 24 V (default setting)
digital inputs MC
(default setting) SINK
DIP
switch S3 SOURCE
SC
P1
During run
0V
Multi-function photo-
coupler output
Shielded ground P2 48 Vdc, 2 to 50 mA
terminal Frequency agree
Photocoupler (default setting)
PC
Pulse Input common
RP (max. 32kHz)
MP Pulse train output
+V Analog input power supply
2 kΩ +10.5 Vdc, max. 20 mA (max. 32 kHz)
A1 Multi-function analog input 1 (Output frequency)
0 to 10 V (20 kΩ) Monitor outputs
A2 Multi-function analog input 2 AM (default setting)
0 to 10 V (20 kΩ) or
Analog output
AC 0/4 to 20 mA (250 Ω) 0 to +10 Vdc (2mA)
AC (Output frequency)
H2 R−
Safe Disable Memobus comm.
inputs S+ RS-485/422
H1 max. 115 kBps
S−
HC IG
Symbols:
Use twisted pair cables. Indicates a main circuit terminal.
12 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
3 Electrical Installation
Wiring Specification
Main Circuit
Use the fuses and line filters listed up in the table below when wiring the main circuit. Make
sure not to exceed the given tightening torque values.
Recom. Main Circuit Terminal Sizes
Model EMC Filter [Schaffner] Main Fuse
Motor R/L1,S/L2,T/L3, U/
CIMR-VC [Ferraz] cable T1,V/T2,W/T3, - , B1, B2
(mm²) +1, +2
BA0001 TRS5R 2.5 M3.5 M3.5 M3.5
BA0002 FS5855-10-07 TRS10R 2.5 M3.5 M3.5 M3.5
BA0003 TRS20R 2.5 M3.5 M3.5 M3.5
BA0006 TRS35R 2.5 M4 M4 M4
FS5855-20-07
BA0010 TRS50R 4 M4 M4 M4
BA0012 FS5855-30-07 TRS60R 6 M4 M4 M4
BA0018 FS5855-40-07 A6T80 10 M5 M5 M5
2A0001 TRS5R 2.5 M3.5 M3.5 M3.5
2A0002 TRS5R 2.5 M3.5 M3.5 M3.5
FS5856-10-07
2A0004 TRS10R 2.5 M3.5 M3.5 M3.5
2A0006 TRS15R 2.5 M3.5 M3.5 M3.5
2A0010 TRS25R 2.5 M4 M4 M4
FS5856-20-07
2A0012 TRS35R 4 M4 M4 M4
2A0020 FS5856-30-07 TRS60R 6 M4 M4 M4
2A0030 FS5973-35-07 A6T70<1> 10 M4 M4 M5
2A0040 FS5973-60-07 A6T100<1> 16 M4 M4 M5
2A0056 A6T150<1> 25 M6 M5 M6
FS5973-100-07
2A0069 A6T200<1> 35 M8 M5 M6
4A0001 TRS2.5R 2.5 M4 M4 M4
FS5857-5-07
4A0002 TRS5R 2.5 M4 M4 M4
4A0004 TRS10R 2.5 M4 M4 M4
4A0005 TRS20R 2.5 M4 M4 M4
FS5857-10-07
4A0007 TRS20R 2.5 M4 M4 M4
4A0009 TRS20R 2.5 M4 M4 M4
4A0011 FS5857-20-07 TRS30R 2.5 M4 M4 M4
4A0018 A6T50<1> 6 M4 M4 M5
FS5972-35-07
4A0023 A6T60<1> 10 M4 M4 M5
4A0031 A6T70<1> 10 M5 M5 M5
FS5972-60-07
4A0038 A6T80<1> 16 M5 M5 M6
<1> For UL compliance a different fuse type has to be used. For details refer to the Technical Manual.
Tightening Torque Values
Tighten the main circuit terminals using the torque values provided by the table below.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 13
3 Electrical Installation
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within
the specification listed below. For safe wiring it is recommended to use solid wires or flexi-
ble wires with ferrules. The stripping length respectively ferrule length should be 8 mm.
Wire Type Wire size (mm2)
Solid 0.2 to 1.5
Flexible 0.2 to 1.0
Flexible with ferrule 0.25 to 0.5
E E
N L1
L3 L2 L1
EMC EMC
Filter Drive Drive
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Filter R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
Grounding Grounding
Surface Surface
(remove any (remove any
paint) paint)
Wiring distance as Wiring distance as
short as possible short as possible
14 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
3 Electrical Installation
Ground Connection
Take the following precautions when grounding the drive.
• Never share the ground wire with other devices such as welding machines, etc.
• Always use a ground wire, that complies with electrical equipment technical standards.
Keep ground wires as short as possible. Leakage current is caused by the drive. Therefore,
if the distance between the ground electrode and the ground terminal is too long, potential
on the ground terminal of the drive will become unstable.
• When using more than one drive, do not to loop the ground wire.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 15
3 Electrical Installation
• For external control power supply use a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating
faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.
• If flexible wires with ferrules are connected they might fit tightly into the terminals. To
disconnect them, grasp the wire end with a pair of pliers, release the terminal using a
straight-edge screw driver, turn the wire for about 45°, and pull it gently out of the termi-
nal. For details, refer to the Technical Manual. Use this procedure for removing the wire
link between HC, H1 and H2 when the Safe Disable function is utilized.
S2 S1
R+ R- S+ S- IG S3
P1 P2 PC A1 A2 +V AC AM AC MP
There are three DIP switches, S1 to S3, located on the terminal board
16 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
3 Electrical Installation
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 17
4 Keypad Operation
4 Keypad Operation
LED Operator and Keys
The LED operator is used to program the drive, to start/
stop it, and to display fault information. The LEDs indi-
cate the drive status.
STOP
Down Arrow Key Scrolls down to select parameter numbers, setting values, etc.
18 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
4 Keypad Operation
:
Output Frequency
Output Current
Output Voltage
XX XX XX
The Verify Menu lists up all
Verify Menu
parameters which are unequal to
XX XX XX the default setting.
The motor can not be started.
XX
Parameter Setting Mode
In the Parameter Setting Mode all
drive parameters can be set up.
XX
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 19
5 Start Up
5 Start Up
Drive Setup Procedure
The illustration below shows the basic setup procedure. Each step is explained more detailed
on the following pages.
START
Run the motor without load, check the operation and verify, if the
upper controller (e.g. PLC,...) commands to the drive work as
desired.
Connect the load, run the motor and check the operation
20 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
5 Start Up
Power On
Before turning on the power supply,
• Make sure all wires are connected properly.
• Make sure no screws, loose wire ends or tools are left in the drive.
• After turning the power on, the drive mode display should appear and no fault or alarm
should be displayed.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 21
5 Start Up
Auto-Tuning (T1- )
Auto-Tuning automatically sets up the motor data relevant drive parameters. Three different
modes are supported
CAUTION
Never touch the motor until the Auto-Tuning is finished. Even thought the motor may not be
rotating when Auto-Tuning, voltage is still applied to the motor during the tuning process.
For Auto-Tuning enter the Auto-Tuning menu and perform the steps shown in the figure
below. The number of name plate data to be entered depends on the selected type of Auto-
Tuning. This example shows Rotational Auto-Tuning.
Drive mode Enter the Auto- Select the tuning
display Tuning Mode method
Set up all name The tuning start During the tuning the After successful tuning
plate data display appears display flashes “End” is displayed
If Auto-Tuning can not be performed for some reason (no-load operation impossible etc.),
then set up the maximum frequency and voltage in the E1- parameters and enter the
motor data manually into the E2- parameters.
22 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
5 Start Up
I/O Setup
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 23
5 Start Up
Test Run
Perform the following steps to start up the machine after all parameter settings have been
done.
1. Run the motor without load and check if all input, outputs and the sequence work as
desired.
2. Connect the load to the motor.
3. Run the motor with load and make sure that there is no vibrations, hunting or motor
stalling occurs.
After taking the steps listed above, the drive should be ready to run the application and per-
form the basic functions. For special setups like PID control etc. refer to the Technical Man-
ual.
24 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
6 Parameter Table
6 Parameter Table
This parameter table shows the most impor- Par. Name Description
tant parameters. Default settings are bold Selects the stopping method when
type. Refer to the Technical Manual for a the run command is removed.
complete list of parameters. Stopping
0:Ramp to Stop
1:Coast to Stop
b1-03 Method
Par. Name Description 2:DC Injection Braking to Stop
Selection
3:Coast with Timer (a new run
Initialization Parameters command is ignored if received
Selects which parameters are before the timer expires)
Access accessible via the digital operator. Reverse
A1-01 Level 0:Operation only 0:Reverse enabled
b1-04 Operation
Selection 1:User Parameters 1:Reverse prohibited
Selection
2:Advanced Access Level
Switches the output phase order.
Selects the Control Method of the Phase Order
b1-14 0:Standard
drive. Selection
Control 1:Switch phase order
0: V/f Control
A1-02 Method DC Injection Braking
2: Open Loop Vector (OLV)
Selection
5: PM Open Loop Vector (PM) DC Sets the frequency at which DC
Note: Not initialized with A1-03! Injection Injection Braking starts when
Resets all parameters to default. b2-01 Braking Ramp to Stop (b1-03 = 0) is
(returns to 0 after initialization) Start selected. If b2-01< E1-09, DC
0:No Initialize Frequency Injection Braking starts at E1-09.
1110: User Initialize (The user Sets the DC Injection Braking cur-
Initialize DC
A1-03 must first set user parameter values rent as a percentage of the drive
Parameters Injection
and then store them using parame- b2-02 rated current.
ter o2-03) Braking
In OLV the DC excitation current is
2220: 2-Wire Initialization Current
determined by E2-03.
3330: 3-Wire Initialization
DC Inj.
Operation Mode Selection Braking
Sets the time of DC Injection Brak-
0:Operator - d1- values Time/DC
b2-03 ing at start in units of 0.01 seconds.
Frequency 1:Analog input A1 or A2 Excitation
Disabled when set to 0.00 seconds.
b1-01 Reference 2:Serial Com - RS-422/485 Time at
Selection 3:Option board Start
4:Pulse Input (Terminal RP) DC Inj.
Sets the DC Injection Braking time
0:Operator - RUN and STOP keys Braking
Run b2-04 at stop. Disabled when set to 0.00
1:Terminals - Digital Inputs Time at
b1-02 Command seconds.
2:Serial Com - RS-422/485 Stop
Selection
3:Option board connected Acceleration/ Deceleration
Accel Sets the acceleration time 1 from 0
C1-01
Time 1 to the max. output frequency.
Decel Sets the deceleration time 1 from
C1-02
Time 1 the max. output frequency to 0.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 25
6 Parameter Table
26 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
6 Parameter Table
A1 Signal 0:0 to +10 V (neg. input is zeroed) Sets the motor overload protection.
H3-01 Motor Over- 0:Disabled
Level Sel. 1:0 to +10 V (bipolar input)
L1-01 load Prot. 1:Standard fan cooled motor
A1 Sel. 2:Standard blower cooled motor
H3-02 Assign a function to terminal A1.
Function Sel. 3:Vector motor
Sets the input value in % at 10 V Motor Over- Sets the motor overload protection
H3-03 A1 Gain
analog input. L1-02 load Prot. time in min. Normally no change is
Sets the input value in % at 0 V Time necessary.
H3-04 A1 Bias
analog input. Stall Prevention
0:0 to +10 V (neg. input is zeroed) 0:Disabled - Motor accelerates at
A2 Signal
1:0 to +10 V (bipolar input) active acceleration rate and may
H3-09 Level Selec-
2:4 to 20 mA (9 bit input) Stall stall with too heavy load or too
tion
3:0 to 20 mA Prevention short accel time.
A2 L3-01 Selection 1:General Purpose - Hold
H3-10 Assign a function to terminal A2. during acceleration when current is
Function Sel.
Acceleration above L3-02.
Sets the input value in % at
H3-11 A2 Gain 2:Intelligent - Acceleration in the
10 V/20 mA analog input.
shortest possible time.
Sets the input value in % at
H3-12 A2 Bias Stall Prev.
0 V/0 mA/4 mA analog input. Sets the current level for stall pre-
L3-02 Level dur-
Analog Input Setting vention during acceleration.
ing Accel.
AM Enter value equal to U1- 0:Disabled - Deceleration as set.
H4-01 Monitor monitor values. Example: Enter Stall Prev.
OV might occur.
Selection “103” for U1-03. Selection
L3-04 1:General Purpose - Deceleration
during
Sets terminal AM output voltage is hold if DC bus voltage rises
H4-02 AM Gain Decel.
equal to 100% monitor value. high.
Sets terminal AM output voltage 0:Disabled - Motor stall or
H4-02 AM Bias Stall Prev.
equal to 0% monitor value. overload might occur.
L3-05 Selection
1:Decel Time 1 - Reduce speed
during Run
using C1-02.
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 27
6 Parameter Table
28 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
6 Parameter Table
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 29
7 Troubleshooting
7 Troubleshooting
General Fault and Alarms
Faults and alarms indicate problems in the drive or in the machine.
An alarm is indicated by a code on the data display and the flashing ALM LED. The drive
output is not necessarily switched off.
A fault is indicated by a code on the data display and the ALM LED is on. The drive output
is always switched off immediately and the motor coast to stop.
To remove an alarm or reset a fault, trace the cause, remove it and reset the drive by pushing
the Reset key on the operator or cycling the power supply.
This lists up the most important alarms and faults only. Please refer to the Technical Manual
for a complete list.
LED Display AL FLT Cause Corrective Action
The software base block function is assigned
Base Block to one of the digital inputs and the input is • Check the digital inputs function selection.
off. The drive does not accept Run com- • Check the upper controller sequence.
mands.
The torque limit was reached during deceler-
ation for longer than 3 sec. when in Open • Check the load.
Control Fault
Loop Vector control • Set the torque limit to the most appropriate
• The load inertia is too big. setting (L7-01 through L7-04).
• The torque limit is too low. • Check the motor parameters.
• The motor parameters are wrong.
Control Circuit
Fault • Cycle the drive power supply.
There is a problem in the drive’s control cir-
• Initialize the drive.
to cuit.
• Replace the drive if the fault occurs again.
30 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
7 Troubleshooting
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 31
7 Troubleshooting
32 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
ENGLISH
7 Troubleshooting
YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide 33
7 Troubleshooting
Auto-Tuning Errors
LED Operator
Display Cause Corrective Action
34 YASKAWA ELECTRIC TOEP C710606 15C YASKAWA AC Drive - V1000 Quick Start Guide
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of
the back cover.
3 Addition: Dimensions
September 2008 Chapter2 New models: CIMR-VC2A0030A to 2A0069A
CIMR-VC4A0018A to 4A0038A
YASKAWA TOBP C730600 22A V1000 Option Unit CC-Link Communications Installation Manual 35
YASKAWA AC Drive V1000
Compact Vector Control Drive
Quick Start Guide
EUROPEAN HEADQUARTERS
YASKAWA ELECTRIC EUROPE GmbH
Hauptstraβe 185, 65760 Eschborn, Germany
Phone: +49 (0)6196 569 300 Fax: +49 (0)6196 569 398
E-mail: [email protected] Internet: http://www.yaskawa.eu.com
YASKAWA ENGINEERING EUROPE GmbH
Hauptstraβe 185, 65760 Eschborn, Germany
Phone: +49 (0)6196 569 520 Fax: +49 (0)6196 569 598
E-mail: [email protected] Internet: http://www.yaskawa-eng.eu.com
UNITED KINGDOM
YASKAWA ELECTRIC EUROPE GmbH
Unit 3, Centurion Court, Brick Close, Kiln Farm, Milton Keynes, Bucks MK11 3JB, United Kingdom
Phone: +44 (0)1908 556815 Fax: +44 (0)1908 565891
Internet: http://www.yaskawa.eu.com
ITALY
YASKAWA ELECTEIC EUROPE GmbH
Via TRABUCCHI N°28 41013 Castelfranco E.(MO), Italy
Phone: +39 (0)59 92 2121 Fax: +39 (0)59 92 2168
E-mail: [email protected] Internet: http://www.yaskawa.eu.com
U.S.A.
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: +1 847 887 7000 Fax: +1 847 887 7370
Internet: http://www.yaskawa.com
JAPAN
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan
Phone: +81 (0)3 5402 4511 Fax: +81 (0)3 5402 4580
Internet: http://www.yaskawa.co.jp
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2007-2008 YASKAWA ELECTRIC CORPORATION. All rights reserved.