iDRA Controller
iDRA Controller
®
NEWPORT Electronics, Inc.
http://www.newportUS.com/i
Additional products from
®
NEWPORT Electronics, Inc.
Counters Rate Meters
Frequency Meters Timers
PID Controllers Totalizers
Clock/Timers Strain Gauge
Printers Meters
Process Meters Voltmeters
On/Off Multimeters
Controllers Soldering Iron
Recorders Testers
Relative pH pens
Humidity pH Controllers
Transmitters pH Electrodes
Thermocouples RTDs
Thermistors Thermowells
Wire Flow Sensors
For Immediate Assistance
®
In the U.S.A. and Canada: 1-800-NEWPORT
In Mexico: (95) 800-NEWPORTSM
Or call your local NEWPORT Office.
NEWPORTnet On-Line Service SM
Internet e-mail
www.newportUS.com [email protected]
It is the policy of NEWPORT to comply with all worldwide safety and EMC/EMI regulations that apply. NEWPORT is constantly
pursuing certification of its products to the European New Approach Directives. NEWPORT will add the CE mark to every
appropriate device upon certification.
The information contained in this document is believed to be correct but NEWPORT Electronics, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
TRADEMARK NOTICE: , NEWPORT, NEWPORT®, newportUS.com, and the “Meter Bezel Design” are
trademarks of NEWPORT Electronics, Inc.
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577;
6,243,021 / CANADA 2052599; 2052600/ ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150;
2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The ® is a Trademark of OMEGA
Engineering, Inc. Used Under License. Other US and International Patents pending or applied for.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as it contains important information relating to safety and EMC.
TABLE OF CONTENTS
Part 1: Introduction............................................................................................2
1.1 Description .................................................................................2
1.2 Safety Considerations ...............................................................3
1.3 Before You Begin .......................................................................4
Part 2: Setup.......................................................................................................5
2.1 Optional Remote Programmer Front Panel ............................5
2.2 Front Panel Connections...........................................................6
2.3 Electrical Installation .................................................................7
2.3.1 Power Connections........................................................7
2.3.2 Thermocouple - Input Connection................................8
2.3.3 Two / Three / Four Wire RTD-Hookup ...........................9
2.3.4 Process Current - Wiring Hookup...............................10
2.3.5 Process Voltage - Wiring Hookup ...............................10
2.3.6 Wiring Outputs - Wiring Hookup.................................11
i
LIST OF FIGURES:
Figure 2.1 Optional Remote Programmer Front Panel ............................ 5
Figure 2.2 Input and Output Connections .................................................6
Figure 2.3 Main Power Connections ..........................................................7
Figure 2.4 Thermocouple Wiring Hookup..................................................8
Figure 2.5 Two/Three/Four-wire RTD
a) RTD-1000 ohm and 500 ohm Wiring Hookup.....................9
b) RTD-100 ohm Wiring Hookup..............................................9
Figure 2.6 Process Current Wiring Hookup
(Internal and External Excitation) ...........................................10
Figure 2.7 Process Voltage Wiring Hookup
a) With Sensor Excitation ......................................................10
b) Without Sensor Excitation.................................................10
Figure 2.8 Output Connections:
a) Mechanical Relay and SSR Outputs – Wiring Hookup ...11
b) Pulse Outputs – Wiring Hookup........................................11
Figure 2.9 Isolated Analog Output Wiring Hookup .................................11
Figure 2.10 Snubber Circuits Wiring Hookup............................................12
Figure 2.11 Typical Application...................................................................12
Figure 2.12 Communication Outputs:
a) RS-232 Output – Wiring Hookup.......................................13
b) RS-485 Output – Wiring Hookup.......................................13
Figure 2.13 Excitation Output .....................................................................13
Figure 3.1 Flow Chart for ID and Set Points Menu..................................15
Figure 3.2 Flow Chart for Configuration Menu........................................18
Figure 3.3 Flow Chart for Input Type Menu .............................................18
Figure 3.4 Flow Chart for Reading Configuration Menu.........................21
Figure 3.5 Flow Chart for Alarm 1 Menu ..................................................25
Figure 3.6 Flow Chart for Alarm 2 Menu ..................................................29
Figure 3.7 Flow Chart for Loop Break Time/Field Calibration ...............30
Figure 3.8 Flow Chart for Output 1 Menu.................................................32
Figure 3.9 Flow Chart for Analog Output Menu.......................................39
Figure 3.10 Flow Chart for Ramp and Soak Menu ....................................41
Figure 3.11 Flow Chart for ID Code Menu..................................................43
Figure 3.12 Flow Chart for Communication Option Menu........................45
Figure 3.13 Flow Chart for Display Color Selection Menu .......................51
LIST OF TABLES:
Table 2.1 Optional Remote Programmer Front Panel Annunciators .....5
Table 2.2 Connectors .................................................................................6
Table 2.3 Fuse Requirement......................................................................7
Table 2.4 TC Wire Color Chart...................................................................8
Table 3.1 Button Function in Configuration Mode ................................14
Table 3.2 Conversion Table .....................................................................24
Table 4.1 Input Properties........................................................................58
Table 5.1 Factory Preset Values..............................................................59
ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
1
PART 1
INTRODUCTION
1.1 Description
This device can be purchased as a controller, with outputs or as a signal
conditioner.
• The standard features include three outputs with a choice of relay, SSR, or
dc pulse outputs and isolated analog voltage or current output. Options
include programmable RS-232 or RS-485 serial communication or excitation.
Analog Output is fully scalable and may be configured as retransmission to
follow your display. Universal power supply accepts 90 to 240 Vac. Low voltage
power option accepts 24 Vac or 20 to 36 Vdc.
2
1.2 Safety Considerations
This device is marked with the International Caution Symbol. It is
important to read this manual before installing or commissioning this
device as it contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
• Do not exceed voltage rating on the label located on the top of the
instrument housing.
• Always disconnect power before changing signal and power
connections.
• Do not use this instrument on a work bench without its case for safety
reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain
and power requirements. Install without exposing bare wire outside the
connector to minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
The following steps in this manual for configuring your device are
explained by using the optional Remote Programmer Display (iDRP).
If you have the Serial Communications Option (-C24) you can easily
configure the controller on your computer or on-line.
To Disable Outputs:
To ensure that menu changes are properly stored, Standby Mode should
be used during setup of the instrument. During Standby Mode, the
instrument remains in a ready condition, but all outputs are disabled.
Standby Mode is useful when maintenence of the system is necessary.
When the instrument is in "RUN" Mode, push d twice to disable all
outputs and alarms. It is now in "STANDBY" Mode. Push d once more
to resume "RUN" Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
4
PART 2
SETUP
Refer to the Quick Start Guide for assembly and disassembly
instructions.
Table 2.1
Optional Remote Programmer Front Panel Annunciators
1 Output 1/Setpoint 1/ Alarm 1 indicator
2 Output 2/Setpoint 2/ Alarm 2 indicator
°C °C unit indicator
°F °F unit indicator
a Changes display to Configuration Mode and
advances through menu items*
b Used in Program Mode and Peak Recall*
c Used in Program Mode and Valley Recall*
d Accesses submenus in Configuration Mode
and stores selected values*
* See Part 3 Operation: Configuration Mode
5
2.2 Front Panel Connections
The front panel connections are shown in Figures 2.2 and 2.3.
1 2 3 4 5 6 7 8 9 10
6
2.3 Electrical Installation
For the low voltage power option, in order to maintain the same degree of
protection as the standard high voltage input power units (90 - 240 Vac),
always use a Safety Agency Approved DC or AC source with the same
Overvoltage Category and pollution degree as the standard AC unit
(90 - 240 Vac).
The figure below shows the wiring hookup for any thermocouple type.
For example, for Type K hookup, connect the yellow wire to the "2" terminal and
the red wire to the "1(-)" terminal.
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message. For safety purpose you may want to
set up your alarm to be triggered when input is open. See Alarm 1 and 2
chapters for details.
8
2.3.3 Two/Three/Four-Wire RTD
The figures below show the input connections and input connector jumpers
(shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD.
4-WIRE
4-WIRE
3-WIRE
3-WIRE
2-WIRE
2-WIRE
Figure 2.5 a) RTD-1000 ohm and b) RTD-100 ohm Wiring Hookup
500 ohm Wiring Hookup
The two-wire connection is simplest method, but does not compensate for
lead-wire temperature change and often requires calibration to cancel lead-wire
resistance offset.
The three-wire connection works best with RTD leads closely equal in
resistance. The device measures the RTD, plus upper and lower lead drop
voltage and the subtracts twice the measured drop in the lower supply current
lead producing excellent lead-resistance cancellation for balanced
measurements.
When configuring your controller, select RTD Type and RTD value in the Input
Type menu (see Part 3).
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message except in case of 500/1000 Ω 2-wire
RTD. In this case the display shows -OPN “Input (-) Open” message.
For safety purpose you may want to set up your alarm to be triggered
when input is open. See Alarm 1 and 2 chapters for details.
9
2.3.4 Process Current
The figure below shows the wiring hookup for Process Current 0 – 20 mA.
0-20 mA
Internal 0-20 mA
Excitation External
Excitation
RL
1 V or 10 V 1 V or 10 V
100 mV 100 mV
Return Return
RETURN
OUTPUT 1 OUTPUT 2
OUTPUT 1 OUTPUT 2
C 0.5 A (T)
SSR PULSE
NO External PULSE
Load
C RETURN
3 A (T)
NC RELAY PULSE
NO External PULSE
Load
Figure 2.8
a) Mechanical Relay and SSR b) Pulse Output
Outputs Wiring Hookup Wiring Hookup
1 2 3 4 5 6 7 8 9 10
RETURN
CURRENT
VOLTAGE
11
This device has snubber circuits designed to protect the contacts of the
mechanical relays when it switches to inductive loads (i.e. solenoids, relays).
These snubbers are internally connected between the Common (C) and
Normally Open (NO) relay contacts of Output 1 and Output 2.
OUTPUT 1 OUTPUT 2
C
NC
NO
C
NC RC CIRCUIT
100 0.033
NO 1/4 W OR
VARISTOR
275 V
TEMPERATURE dc INPUT
CONTROLLER CONTROL SSR LOAD
SIDE SIDE HEATER
4 1
Vac Vac
3 2
0 or 5 Vdc,
TYPICALLY FAST BLOW
FUSE
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT
TEMPERATURE ac INPUT
CONTROLLER CONTROL LOAD
SIDE SSR SIDE HEATER
4 1
Vac Vac
3 2
FAST BLOW
Vac FUSE
DRIVING
SSR
Tx -Tx / Rx
Rx +Tx / Rx
RTN
This device has built-in excitation. The connections are shown below.
-
24 Vdc Excitation is not available
+ if communication (-C24)
or low power (-DC) option
is installed.
13
PART 3
OPERATION: Configuration Mode
3.1 Introduction
The following configuration section is explained by using the Optional
Remote Programmer Display, you may also configure your device on your
computer using the Serial Communications Option.
The instrument has two different modes of operation. The first, Run Mode, is
used to display values for the Process Variable, and to display or clear Peak and
Valley values. The other mode, Menu Configuration Mode, is used to navigate
through the menu options and configure the controller. Part 3 of this manual will
explain the Menu Configuration Mode. For your instrument to operate properly,
the user must first "program" or configure the menu options.
Turning your Controller On for the First Time
The device becomes active as soon as it is connected to a power source. It has
no On or Off switch. The device at first momentarily shows the software version
number, followed by reset RST, and then proceeds to the Run Mode
For first-time users: Refer to the QuickStart Manual for basic operation and
set-up instructions.
Table 3.1 Button Function in Configuration Mode
• To enter the Menu, the user must first press a button.
a • Use this button to advance/navigate to the next menu item. The user can
MENU
navigate through all the top level menus by pressing a.
• While a parameter is being modified, press a to escape without saving the parameter.
• Press the up b button to scroll through “flashing” selections. When a numerical
value is displayed press this key to increase value of a parameter that is
b currently being modified.
(UP) • Holding the b button down for approximately 3 seconds will speed up the rate at
which the set point value increments.
• In the Run Mode press b causes the display to flash the PEAK value – press
again to return to the Run Mode.
• Press the down c button to go back to a previous Top Level Menu item.
• Press this button twice to reset the controller to the Run Mode.
• When a numerical value is flashing (except set point value) press c to scroll
c digits from left to right allowing the user to select the desired digit to modify.
(DOWN) • When a setpoint value is displayed press c to decrease value of a setpoint that
is currently being modified. Holding the c button down for approximately 3
seconds will speed up the rate at which the setpoint value is decremented.
• In the Run Mode press c causes the display to flash the VALLEY value – press
again to return to the Run Mode.
• Press the enter d button to access the submenus from a Top Level Menu item.
d • Press d to store a submenu selection or after entering a value — the display will
ENTER flash a STRD message to confirm your selection.
• To reset flashing Peak or Valley press d.
• In the Run Mode, press d twice to enable Standby Mode with flashing STBY.
Reset: Except for Alarms, modifying any settings of the menu configuration
will reset the instrument prior to resuming Run Mode.
14
3.2 Menu Configuration
It is required that you put the controller in the Standby Mode for any
configuration change other than Setpoints & Alarms.
15
3.2.1 ID Number
SEE ID MENU SELECTION IN CONFIGURATION SECTION FOR
ENABLE/DISABLE OR CHANGE ID CODE.
If ID Code is Disabled or set as Default (0000) the menu will skip ID step
to Set Point Menu.
If ID Code is set to Full Security Level and user attempts to enter the
Main Menu, they will be prompted for an ID Code.
Use numbers that are easy for you to remember. If the ID Code is
forgotten or lost, call customer service with your serial number to access
and reset the default to 0000.
16
3.2.2 Set Points
SETPOINT 1:
Holding b & c buttons down for approximately 3 seconds will speed up the
rate at which the set point value increments or decrements.
Press b & c 4) Continue to use b and c to enter your 4-digit Setpoint 1 value.
Press d 5) Display shows STRD stored message momentarily and then
advance to SP2 only, if a change was made, otherwise press a
to advance to SP2 Setpoint 2 Menu.
SETPOINT 2:
17
3.2.3 Configuration Menu
18
Input Type (Thermocouple)
ENTER INPUT TYPE MENU:
THERMOCOUPLE SUBMENU:
Use the Input Type (Thermocouple) (RTD) or (Process) and verify your
Electrical Installation (see Section 2.3). See the following pages for (TC),
(RTD), (Process) menus.
19
Input Type (RTD)
ENTER INPUT TYPE MENU:
RTD SUBMENU:
20
Input Type (Process)
ENTER INPUT TYPE MENU:
Press a 1) Press a, if necessary, until CNFG prompt appears.
Press d 2) Display advance to INPT Input Menu.
Press d 3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is PROC, press a to skip to
step 6 (PROC stops flashing).
PROCESS SUBMENU:
Press b 4) Scroll through the available selection to PROC (flashing).
Press d 5) Display shows STRD stored message momentarily and then
PROC (not flashing).
Press d 6) Display flashes previous Process type selection. i.e. 0-10
(see below for Process types selection).
Press b 7) Scroll through the available Process types to the selection of
your choice.
Press d 8) Display shows STRD stored message and then advances to
RDG Reading Configuration Menu.
Process Types: 100 mV 1 V 10 V 0 – 20 mA
Display: 0-0.1 0-1.0 0-10 0-20
For 4-20 mA Input select 0-20 mA and adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under Input/Reading Submenu.
If Process was selected in the Input Type Menu the display will
advance to IN.RD Input/Reading Submenu, otherwise the
display advances to the ALR1 Alarm 1 Menu.
22
Reading Configuration (If Process was selected)
INPUT/READING (SCALE AND OFFSET) SUBMENU:
Input Voltage or Current can be converted or scaled into values appropriate for
the process or signal being measured. So, a reading may be displayed, for
example, in units of weight or velocity instead of in amperes or volts.
The instrument determines Scale and Offset values based on two user-provided
input values entered with the corresponding readings. Note that “In1” Input 1 and
“In2” Input 2 are represented and entered as a product of the input
voltage/current and the conversion number from the Table 3.1.
Press d 14) Press d at the IN.RD prompt. Display shows IN1 Input 1
Submenu.
Press d 15) Display shows Input 1 value with 1st digit flashing.
Press b & c 16) Use b and c buttons to enter IN1 value.
The IN1 value = min. input value * conversion number.
23
Conversion number is a coefficient of conversion between input values
and real full display range (10000 counts, shown as 9999). See Table 3.2
below for proper conversion number.
Example =
0-1V = 0 - 100.0
In 1 = 0
Rd 1 = 0
Inp 2 = 9999
Rd 2 = 100.0
24
3.2.6 Alarm 1
This unit is equipped with three physical outputs that can only be configured as
follows:
a) Alarm 1, Alarm 2 & Analog Output
b) Output 1, Alarm 2 & Analog Output
25
ALARM 1 ENABLE/DISABLE SUBMENU:
Unlatched Mode: Relay remains latched only as long as the alarm condition is
true.
26
CONTACT CLOSURE SUBMENU:
Press d 11) Display flashes previous selection. Press b to N.ç. Normally
Closed or N.o. Normally Open.
Press d 12) Display shows STRD stored message momentarily and then
advances to AçTV only, if it was changed, otherwise press a to
advance to AçTV Active Submenu.
Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.
ACTIVE SUBMENU:
Press d 13) Display flashes previous selection. Press b to scroll through
the available selections: ABoV Above, BELo Below, HI.Lo
HI/Low and BAND Band. (Band is active if _DEV Deviation was
selected).
Press d 14) Display shows STRD stored message momentarily and then
advances to A.P.oN only, if it was changed, otherwise press a to
advance to A.P.oN Alarm Enable/Disable at Power On Submenu.
Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.
The Band for the AL 1 would be following the Setpoint 1 value
The Band for the AL 2 would be following the Setpoint 2 value.
The Band or the Deviation Value should be entered under:
AL1 High (if they want Alarm 1)
AL2 High (if they want Alarm 2)
AL Low value is ignored in the Band mode.
Example: if customer requires a Deviation Value of ±10 degrees around a
setpoint (using Output 2 as alarm)
Alarm 2: - Deviation
Contact Closure type: Deviation---Band
AL2 High: 10 (Band they want around Setpoint 2)
Then the Band Value is to be entered under AL2 HI: 10 not 80+10 = 90
27
ALARM ENABLE/DISABLE AT POWER ON:
Press d 17) Display flashes 1st digit of previous value. Use b and c to
enter new value.
Press b & c 18) Use b and c to enter Alarm 1 Low Value.
Press d 19) Display shows STRD storage message momentarily and
then advances to ALR.H only, if it was changed, otherwise press
a to advance to ALR.H Alarm 1 Hi Value Submenu.
Press d 20) Display flashes 1st digit of previous value. Use b and c to
enter new value.
Press b & c 21) Use b and c to enter Alarm1 Hi Value.
Press d 22) Display shows STRD stored message momentarily and then
advances to the next menu only, if it was changed, otherwise
press a to advance to the next menu.
28
3.2.7 Alarm 2
This unit is equipped with three physical outputs that can only be configured as:
a) Alarm 1, Alarm 2 & Analog Output
b) Output 1, Alarm 2 & Analog Output
Alarm 2 menu items are identical to Alarm 1 Menu, except Alarm 2 does
not have Alarm enable/disable at Power On submenu item. Modifying
Alarm Settings will not reset the instrument.
29
3.2.8 Loop Break Time/Field Calibration
It is required
that you put
the controller
in the Standby Mode
for any configuration
change other than Set
Points & Alarms.
Loop Break is an additional safety feature intended to monitor the rate of change of the
process value, while approaching the SP1. It is strictly intended as an additional warning
system, therefore its use is entirely optional. An active Loop Break will cause the Process
Value digits to blink in a rotating pattern. If the process value reaches the set point the
blinking will stop and B.TIM is completed successfully, otherwise BR.AL Break Alarm
warning will flash, and Output 1 will be turned off.
Loop Break Time Value allows the user to determine the time interval in MM:SS (from
zero to 99 minutes and 59 seconds) that the Process Value changes at least 10 counts
or if the Input Type is either RTD or Thermocouple, the value changes 4° Fahrenheit or
2° Celsius. At the specified time interval, if the process value change is less than the
stated rate, flashing B.TIM will be displayed, the output 1 will be de-energized, and
Alarm 1 energized. Loop break time will be disabled when the Process Value (PV) enters
the control band.
30
READING ADJUST SUBMENU:
Press d 10) Display flashes 1st digit of previous reading adjust value.
Press b & c 11) Press b and c buttons to enter a new Reading Adjust value
(-1999 to 9999).
Press d 12) Display shows STRD stored message momentarily and then
advances to SP.DV Setpoint Deviation Menu.
Reading Offset Adjust allows the user to fine tune a minor error of the transducer,
however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ± R.ADJ).
Reading Adjust is adjustable between -1999 to 9999. For Temperature reading only, not
Process.
Be sure that the TC being used to calibrate the meter is of the type
selected in the TC submenu. Place the TC in an ice-bath (or other
0°C / 32°F environment). In ambient temperature conditions: connect the
TC to the meter, apply power to the meter.
* If you accidently engage the flashing 0000 (CAL° alert) simply re-press
the last button you pressed, to avoid unintentionally mis-calibrating your meter.
31
3.2.9 Output 1
This unit is equipped with three physical outputs that can only be configured as
follows:
a) Alarm 1, Alarm 2 & Analog Output It is required that you put
b) Output 1, Alarm 2 & Analog Output the controller in the
Standby Mode for any
configuration change other
than Set Points & Alarms.
32
ENTER OUTPUT 1 MENU:
Press a 1) Press a, if necessary, until CNFG prompt appears.
Press d 2) Display advances to INPT Input Menu.
Press a 3) Press a, if necessary, until Display advances to OUT1 Output
1 Menu.
Press d 4) Display advances to SELF Self Submenu.
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
The output is now under the direct control of the operator and
can be adjusted in the Run Mode (M00.0 to M99.9), by
pressing the b and c buttons, where M calls for the Manual
(Self) Control. For example, setting of M50.0 of an Output make
it ON 50% of the time.
33
MAXIMUM/PERCENT HIGH SUBMENU:
Specify in percent, the maximum value (99) for control output. If the output is
time proportional (Relay, SSR, or Pulse), then the maximum duty-cycle, in
percent, is specified.
Press d 12) Display flashes 1st digit of previous “Percent High” setting.
Press b & c 13) Use b and c buttons to enter a new value for “Percent High”.
Press d 14) Display shows STRD stored message momentarily and then
advances to CTRL Control Type Submenu.
Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90,
cause the minimum on the control output to be 1 V and the maximum on the
control output to be 9 V. The same setting on a time proportional output, will
cause 10% duty cycle for the minimum control output and 90% duty cycle for
maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI
is at other values than the default (%LO = 00, %HI = 99), SOAK is disabled.
The ON/OFF control is a coarse way of controlling the process. The “Dead
Band” improves the cycling associated with the On/Off control. The PID control is
best for processes where the set point is continuously changing and/or a tight
control of the process variable is required. PID control requires tuning and
adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate"
terms by a trial-and-error method. The instrument provides an "Auto Tuning"
feature making the tuning process automatic, possibly optimum.
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it would
be called Direct Acting. If a negative error should cause the output to increase
(i.e. heating), it would be called Reverse Acting.
35
START AUTO TUNE PID:
To start Auto Tune PlD select PID, enable Auto PID and enable Start PID.
Sometimes Auto PID parameter needs fine tuning i.e. for each 5°F over
shoot increase the Proportional Band (PB) by 15% and for each ±1°F
fluctuation at the Setpoint (SP) increase reset by 20%.
Once started, display shows A.TUN with letters blinking in the rotating
pattern. When auto tune stops, display will show process value. Do not
perform any operations or settings before first stopping Auto Tune. Any
alarms or other output is disabled during Auto Tune.
If “AUTO PID” was “DISABLED”, the display will show the following
three submenus. This allows the user to manually enter values for
Proportional, Reset and Rate terms corresponding to P, I, and D. It also
can be used for Auto PID for disabling unwanted parameter i.e. PI enter
0000 for Rate.
Press d 30) Display flashes 1st digit of the previous P PRoP Proportional
band value.
Press b & c 31) Press b and c buttons to enter a new “Proportional Band”
value.
Press d 32) Display shows STRD stored message momentarily and then
advances to REST only, if it was changed, otherwise press a to
advance to REST Reset Setup Submenu.
36
RESET SETUP SUBMENU:
Press d 33) Display flashes 1st digit of the previous I REST Reset value.
Press b & c 34) Press b and c buttons to enter a new “Reset” value.
Press d 35) Display shows STRD stored message momentarily and then
advances to RATE only, if it was changed, otherwise press a to
advance to RATE Rate Setup Submenu.
Press d 36) Display flashes 1st digit of previous D RATE Rate value.
Press b & c 37) Press b and c buttons to enter a new RATE value.
Press d 38) Display shows STRD stored message momentarily and then
advances to the CYCL only, if it was changed, otherwise press a
to advance to CYCL Cycle Time submenu for RTD and
Thermocouple types.
Press d 39) Display flashes 1st digit of the previous CYCL Cycle Time
value.
Press b & c 40) Press b and c buttons to enter a new “Cycle Time” value.
(1 to 199 seconds)
Press d 41) Display shows STRD stored message momentarily and then
advances to DPNG only, if it was changed, otherwise press a to
advance to DPNG Damping Factor Submenu.
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).
37
DAMPING FACTOR SUBMENU:
DEADBAND SUBMENU:
Press d 45) Display flashes 1st digit of the previous DEAD Deadband
value.
Press b & c 46) Press b and c buttons to enter a new “Deadband” value.
Press d 47) Display shows STRD stored message and then advances to
ANLG only, if it was changed, otherwise press a to advance to
ANLG Analog Output Menu.
Dead Band units are the same as Proportional Band units.
38
3.2.10 Analog Output (Retransmission)
This unit is equipped with three physical outputs that can only be configured as
follows:
a) Alarm 1, Alarm 2 & Analog Out
b) Output 1, Alarm 2 & Analog Out
Analog Output is available only if the Analog Output option board is factory
installed.
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
39
READING 1:
Press d 8) Display flashes 1st digit of previous “Reading 1” value.
Press b & c 9) Enter “Reading 1” value. (Example 0000).
Press d 10) Display advances to OUT.1 Out 1 Submenu.
OUT 1:
Press d 11) Display flashes 1st digit of previous “Out 1” value.
Press b & c 12) Enter “Out 1” value. (Example 00.00).
Press d 13) Display advances to RD2 Reading 2 Submenu.
READING 2:
Press d 14) Display flashes 1st digit of previous “Reading 2” value.
Press b & c 15) Enter “Reading 2” value. (Example 9999).
Press d 16) Display advances to OUT.2 Out 2 Submenu.
OUT 2:
Press d 17) Display flashes 1stt digit of previous “Out 2” value.
Press b & c 18) Enter “Out 2” value. (Example 10.00)
Press d 19) Display advances to the ALR2 Alarm 2 Menu.
The above example is for 0-10 V of the entire range of the Process Input
and Analog Output. For 0-20 mA output you need to set “Analog Type” to
Current and OUT 2 to 20.00.
40
3.2.11 Ramp & Soak
Alarm must be DISABLED if Ramp is ENABLED.
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
41
Ramp & Soak provides users with the flexibility to slowly bring the Process
Variable (PV) to the desired setpoint. Ramp & Soak values are specified in
HH.MM format. The Ramp value indicates the time specified to bring the process
variable to Setpoint 1 (SP1). Once the set point is reached, the PID takes over
and the Process Variable will be controlled at the desired set point indefinitely. If
Soak is enabled, PID will control the Process Variable at the specified Setpoint
for the duration of Soak time and then will turn off Output 1. To start a new
Ramp/Soak cycle, reset the instrument by pressing a and then c button.
An active Ramp/Soak will change SP1 one degree above the PV and will cause
the most significant digit to blink. The SP1 will be incremented by one degree
until it reaches the original SP1. The minimum Ramp time must be at least twice
the time that it will take the PV to reach the Setpoint Value (SV) with OUT 1 fully
ON.
Press d 10) Display flashes 1st digit of previous stored “Ramp Value”.
Press b & c 11) Press b and c buttons to enter a new “Ramp Value”.
Press d 12) Display shows STRD stored message momentarily and then
advances to “Soak Value” Submenu.
Press d 13) Display flashes 1st digit of previous stored “Soak Value”.
Press b & c 14) Press b and c buttons to enter a new “Soak Value”.
Press d 15) Display shows STRD stored message and advances to the
ID ID Code Menu.
The Ramp and Soak time is 00:00 to 99:59 i.e. HH.MM. (from zero to 99 hours
and 59 minutes) During Ramp & Soak do not perform any operations or settings
before first stopping it. Any alarms or other output are disabled during this time.
To stop Ramp & Soak first put instrument into Standby Mode, then go to Ramp &
Soak Menu and disable it.
42
3.2.12 ID CODE
Press d 7) Display flashes the first digit of previous entered “ID Code”
number.
Press b & c 8) Press b and c buttons to enter your new “ID Code” number.
Press d 9) Display shows STRD stored message momentarily and then
advances to the FULL Full Security Submenu.
43
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:
If you want to change your default “ID Code” you can do it now,
otherwise press a and menu will skip to FULL Full Security
Submenu.
Press b & c 12) Press b and c buttons to enter your new “ID Code” number.
Press d 13) Display shows STRD stored message momentarily and then
advances to the FULL Full Security Submenu.
44
3.2.13 COMMUNICATION OPTION
Purchasing the controller with Serial Communications permits an instrument to be
configured or monitored from an IBM PC compatible computer using software
available at the website listed on this manual or on the CD-ROM enclosed with
your shipment. For complete instructions on the use of the Communications
Option, refer to the Serial Communications Reference Manual.
46
STOP BIT SUBMENU:
Press d 15) Display flashes previous selection for “Stop Bit”.
Press b 16) Scroll through the available selections: 1-BIT, 2-BIT.
Press d 17) Display shows STRD stored message momentarily and then
advances to BUS.F only, if it was changed, otherwise press a to
advance to BUS.F Bus Format Submenu.
BUS FORMAT SUBMENU:
Determines Communications Standards and Command/Data Formats for
transferring information into and out of the controller via the Serial
Communications Bus. Bus Format submenus essentially determine how and
when data can be accessed via the Serial Communications of the device.
Press d 18) Display advances to M.BUS Modbus Submenu.
MODBUS PROTOCOL SUBMENU:
Press d 19) Display flashes previous selection for M.BUS.
Press b 20) Scroll through the available selections: NO, YES.
Press d 21) Display shows STRD stored message momentarily and then
advances to _LF_ only, if it was changed, otherwise press a to
advance to _LF_ Line Feed submenu.
To select iSeries Protocol, set Modbus submenu to “No”.
To select Modbus Protocol, set Modbus submenu to “Yes”.
If Modbus Protocol was selected, the following Communications
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not
attempt to change these parameters.
47
Press d 25) Display flashes previous selection for “Echo”.
Press b 26) Scroll through the available selections: NO, YES.
Press d 27) Display flashes STRD stored message momentarily and then
advances to STND only if it was changed, otherwise press a to
advance to STND Communication Standard Submenu.
48
DATA FORMAT SUBMENU:
Preformatted data can be sent automatically or upon request from the controller.
Use the Data Format Submenus to determine what data will be sent in this
preformatted data string. Refer to the iSeries Communications Manual for more
information about the data format. At least one of the following suboptions must
be enabled and hence output data to the Serial Bus.
This menu is applicable for Continuous Mode of RS-232 communication.
51
ALARM 2 DISPLAY COLOR SUBMENU:
Press d 11) Display flashes previous selection for “Alarm 2 Color Display”.
Press b 12) Scroll through the available selections: GRN, RED or AMBR.
Press d 13) Display shows STRD stored message momentarily and then
momentarily shows the software version number, followed by
RST Reset, and then proceeds to the Run Mode.
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the Display to change color every time when both Alarm 1
and Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Example 1:
Output 1 & Alarm 2: SSR
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200, Alarm 1
HI Value “ALR.H” = 400
Color Display Setup: Normal Color “N.CLR” = Green, Alarm 1 Color
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Example 2:
Output 1 & Alarm 2: Pulse
Alarm Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300, Alarm 1
Low Value “ALR.L” = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
52
Example 3:
Output 1: Relay, Setpoint 1: 200
Alarm 2: Relay, Setpoint 2: 200
Alarm 1 Setup: Deviation, Band, “ALR.H” = 20
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Reset: The instrument automatically resets after the last menu of the
Configuration Mode has been entered. After the instrument resets, it
advances to the Run Mode.
53
PART 4
SPECIFICATIONS
RTD Input (ITS 68)
Accuracy 100/500/1000 Ω Pt sensor,
±0.5°C temp; 0.03% reading process 2-, 3- or 4-wire;
0.00385 or 0.00392 curve
Resolution
1°/0.1°; 10 µV process Voltage Input
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc
Temperature Stability
1) RTD: 0.04°C/°C Input Impedance
2) TC @ 25°C (77°F): 0.05°C/°C 10 MΩ for 100 mV
Cold Junction Compensation 1 MΩ for 1 or 10 Vdc
3) Process: 50 ppm/°C
Current Input
NMRR 60 dB 0 to 20 mA (5 ohm load)
54
CONTROL ALARM 1 & 2(programmable):
Action: Reverse (heat) or direct (cool) Type
Modes Same as Output 1 & 2
Time and Amplitude Proportional
Control Modes; selectable Manual or Operation High/low, above/below,
Auto PID, Proportional, Proportional band, latch/unlatch, normally
with Integral, Proportional with open/normally closed and
Derivative with Anti-reset Windup and process/deviation; front panel
ON/OFF configurations
Rate OUTPUT 3
0 to 399.9 seconds ANALOG OUTPUT (programmable)
Isolated, Retransmission 0 to 10 Vdc or
Reset 0 to 20 mA, 500 Ω max.
0 to 3999 seconds Accuracy is 1% of FS,
for Scaling Gain from
Cycle Time 0.03 to 100 mV per count
1 to 199 seconds; set to 0 for ON/OFF Isolation is 1000 Vdc
operation Linearity is 0.2%
Gain COMMUNICATIONS
0.5 to 100% of span; Setpoints 1 or 2 (Optional in place of excitation)
Damping RS-232/RS-422/RS-485/MODBUS:
0000 to 0008 Selectable from menu; both ASCII and
modbus protocol selectable from menu.
Soak Programmable 300 to 19.2 K baud;
00.00 to 99.59 (HH:MM), or OFF complete programmable setup
capability; program to transmit current
Ramp to Setpoint display, alarm status, min/max, actual
00.00 to 99.59 (HH:MM), or OFF measured input value and status.
CONTROL OUTPUT 1
Configurable as Alarm 1, On/Off, PID
and Ramp and Soak
Relay
SPDT type, 250 Vac or 30 Vac @ 3 A
(Resistive Load);
SSR
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous
DC Pulse
Non-Isolated; 10 Vdc @ 20 mA
55
EXCITATION
24 Vdc @ 25 mA Environmental Conditions
Not available for: 0 to 55°C (32 to 131°F),
Low Power Option (-DC) or 90% RH non-condensing
Serial Communication Option (-C24) 0 to 50°C (32 to 122°F) for UL only.
90% RH non-condensing
INSULATION
Power to Input/Output
2300 Vac per 1 min. test Dimensions iDRA
92.5H x 125.2D x 32.1 mm W
1500 Vac per 1 min. test (3.64 x 4.93 x 1.27")
(Low Voltage/Power Option) 204g (0.45lb)
Power to Relays/SSR Outputs
2300 Vac per 1 min. test Optional Remote Programmer iDRP:
Relays/SSR to Relay/SSR Outputs 48H x 96x 39 mm D
2300 Vac per 1 min. test (1.89 x 3.78 x 1.55")
RS-232/485 to Inputs/Outputs 159g (0.35lb)
500 Vac per 1 min. test
1/8 DIN Panel Cutout
Approvals Optional Remote Programmer iDRP:
FM, UL, C-UL, and 45 H x 92 mm W
see CE Approval Section (1.772" x 3.622 ")
GENERAL
Line Voltage/Power
90-240 Vac +/-10%, 50-400 Hz*
110-375 Vdc, equivalent voltage
5 W, power consumption
* No CE compliance above 60 Hz
56
Table 4.1 Input Properties
TC Input Type Range Accuracy
Iron-Constantan -210 to 760°C 0.4°C
J -346 to 1400°F 0.7°F
-270 to -160°C 1.0°C
K CHROMEGA®-
ALOMEGA®
-160 to 1372°C
-454 to -256°F
0.4°C
1.8°F
-256 to 2502°F 0.7°F
-270 to -190°C 1.0°C
Copper-Constantan -190 to 400°C 0.4°C
T -454 to -310°F 1.8°F
-310 to 752°F 0.7°F
-270 to -220°C 1.0°C
CHROMEGA- -220 to 1000°C 0.4°C
E Constantan -454 to -364°F 1.8°F
-364 to 1832°F 0.7°F
-50 to 40°C 1.0°C
Pt/13%Rh-Pt 40 to 1788°C 0.5°C
R -58 to 104°F 1.8°F
104 to 3250°F 0.9°F
-50 to 100°C 1.0°C
Pt/10%Rh-Pt 100 to 1768°C 0.5°C
S -58 to 212°F 1.8°F
212 to 3214°F 0.9°F
200 to 640°C 1.0°C
30%Rh-Pt/ 640 to 1820°C 0.5°C
B 6%Rh-Pt 212 to 1184°F 1.8°F
1184 to 3308°F 0.9°F
5%Re-W/ 0 to 2354°C 0.4°C
C 26%Re-W 32 to 4253°F 0.7°F
-250 to -100°C 1.0°C
Nicrosil-Nisil -100 to 1300°C 0.4°C
N -418 to -148°F 1.8°F
-148 to 2372°F 0.7°F
J -200 to 900°C 0.4°C
L DIN -328 to 1652°F 0.7°F
Pt, 0.00385, 100 Ω, 200 to 900°C 0.4°C
RTD 500 Ω, 1000 Ω -328 to 1652°F 0.7°F
Pt, 0.00392, 100 Ω, -200 to 850°C 0.4°C
RTD 500 Ω, 1000 Ω -328 to 1562°F 0.7°F
Voltage 0 to 100 mV, 0 to 1 V, 0.03% rdg
PROCESS
0 to 10 Vdc 0.03% rdg
PROCESS Current 0 to 20 mA, 4 to 20 mA 0.03% rdg
57
PART 5 FACTORY PRESET VALUES
Table 5.1 Factory preset value
MENU ITEMS FACTORY PRESET VALUES NOTES
Set Point 1 (SP1) 000.0
Set Point 2 (SP2) 000.0
Input:
Input Type (INPT) TC, type K
Reading Configuration (RDG):
Decimal Point (DEC.P) FFF.F
Temperature unit (TEMP) °F
Filter value (FLTR) 0004
Alarm 1 & 2:
Alarm 1 (ALR1) Disable (DSBL)
Alarm 2 (ALR2) Enable (ENBL)
Absolute/Deviation (ABSO/DEV) Absolute (ABSO)
Latch/Unlatch (LTCH/UNLT) Unlatch (UNLT)
Contact Closure (CT.CL) Normally Open (N.O.)
Active (ACTV) Above (ABOV)
Alarm At Power On (A.P.ON) Disable (DSBL) Alarm 1 only
Alarm Low (ALR.L) -100.0
Alarm High (ALR.H) 400.0
LOOP:
Loop Break Time (LOOP) Disable (DSBL)
Loop Value (B.TIM) 00:59
Reading Adjust Value (R.ADJ) 000.0
Setpoint Deviation (SP.dV) Disable (DSBL)
OUTPUT 1:
Self (SELF) Disabled (DSBL)
% Low Value (%LO) 0000
% High Value (%HI) 0099
Control Type (CTRL) On/Off
Action Type (ACTN) Reverse (RVRS)
Dead Band (DEAD) 020.0
PID Auto (AUTO) Disable (DSBL)
Anti Integral (ANTI) Disable (DSBL)
Proportion Value (PROP) 020.0
Reset Value (REST) 0180
Rate Value (RATE) 0000
Cycle Value (CYCL) 0007
Damping Factor (DPNG) 0003
ANALOG OUTPUT (Retransmission)
Analog Output (ANLG) Enabled (ENBL)
Current/Voltage (CURR/VOLT) Voltage (VOLT)
Scale and Offset Reading: 0 - 999.9 cts, Output: 0 - 10 V
58
MENU ITEMS FACTORY PRESET VALUES NOTES
Ramp & Soak (RAMP):
Ramp (RAMP) Disable (DSBL)
Soak (SOAK) Disable (DSBL)
Ramp Value (RAMP) 00:00
Soak Value (SOAK) 00:00
ID:
ID Value 0000
Full ID (FULL) Disable (DSBL)
Set Point ID (ID.SP) Disable (DSBL)
Communication Parameters:
Baud Rate (BAUD) 9600
Parity (PRTY) Odd
Data bit (DATA) 7 bit
Stop Bit 1 bit
Modbus Protocol (M.BUS) No
Line Feed (LF) No
Echo (ECHO) Yes
Standard Interface (STND) RS-232 (232C)
Command Mode (MODE) Command (CMD)
Separation (SEPR) Space (SPCE)
Alarm Status (STAT) No
Reading (RDNG) Yes
Peak No
Valley (VALY) No
Units (UNIT) No
Multipoint Address (ADDR) 0001
Transmit Time (TR.TM) 0016
Display Color (COLR):
Normal Color (N.CLR) Green (GRN)
Alarm 1 Color (1.CLR) Red (RED)
Alarm 2 Color (2.CLR) Amber (AMBR)
59
PART 6
CE APPROVALS INFORMATION
This product conforms to the EMC directive 89/336/EEC amended by
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.
60
NOTES
61
NOTES
62
NOTES
63
Warranty/Disclaimer
NEWPORT Electronics, Inc. warrants this unit to be free of defects in materials and workmanship for a period of one
(1) year from the date of purchase. In addition to NEWPORT’s standard warranty period, NEWPORT Electronics will
extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is
returned to NEWPORT.
If the unit should malfunction, it must be returned to the factory for evaluation. NEWPORT’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon
examination by NEWPORT, if the unit is found to be defective it will be repaired or replaced at no charge.
NEWPORT’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not
limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized
modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence
of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification;
misapplication; misuse or other operating conditions outside of NEWPORT’s control. Components which wear are not
warranted, including but not limited to contact points, fuses, and triacs.
NEWPORT is pleased to offer suggestions on the use of its various products. However, NEWPORT neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the use of its products in accordance with information provided by NEWPORT, either verbal or written.
NEWPORT warrants only that the parts manufactured by it will be as specified and free of defects.
NEWPORT MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER,
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY
WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY
DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the
total liability of NEWPORT with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon
which liability is based. In no event shall NEWPORT be liable for consequential, incidental or special
damages.
CONDITIONS: Equipment sold by NEWPORT is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications
or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,
or used on humans, or misused in any way, NEWPORT assumes no responsibility as set forth in our basic
WARRANTY / DISCLAIMER language, and additionally purchaser will indemnify NEWPORT and hold NEWPORT
harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
Return Requests/Inquiries
Direct all warranty and repair requests/inquiries to the NEWPORT Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO NEWPORT, PURCHASER MUST OBTAIN AN
AUTHORIZED RETURN (AR) NUMBER FROM NEWPORT’S CUSTOMER SERVICE DEPARTMENT (IN
ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the
outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the FOR NON-WARRANTY REPAIRS, consult
following information available BEFORE NEWPORT for current repair charges. Have the
contacting NEWPORT: following information available BEFORE contacting
1. P.O. number under which the product was NEWPORT:
PURCHASED, 1. P.O. number to cover the COST of
2. Model and serial number of the product the repair,
under warranty, and 2. Model and serial number of product, and
3. Repair instructions and/or specific 3. Repair instructions and/or specific problems
problems relative to the product. relative to the product.
NEWPORT’s policy is to make running changes, not model changes, whenever an improvement is possible.
This affords our customers the latest in technology and engineering.
NEWPORT is a registered trademark of NEWPORT Electronics, Inc.
© Copyright 2006 NEWPORT Electronics, Inc. All rights reserved. This document may not be copied,
photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in
whole or in part, without prior written consent of NEWPORT Electronics, Inc.
For immediate technical or application assistance please call:
M4165/N/0206