Type Tests Defined in IEC 61439
Type Tests Defined in IEC 61439
1. Type tests:
1. Temperature rise limits
2. Dielectric properties
3. Short-circuit resistance
4. Effectiveness of the protective circuit
5. Clearances and creepage distances
6. Mechanical operation
7. Degree of protection (IP)
And there are also six tests designed to check the construction quality are
added to the above type tests in standard IEC 61439-1.
1. Type tests
1.1 Temperature rise limits
Verification in temperature rise limits test is one of the most critical in
determining the reliability and long service capability of a low voltage
assembly and must not be overlooked. Excessive temperatures result in
premature ageing of components and insulation, and ultimately failure.
Current ratings of components are valid only when the temperature
around them is within the limits specified by the component
manufacturer.
When temperature rise verification is carried out by test, the manufacturer
can select from three options to suit the design and the total time to be
devoted to testing:
Option 1
The incoming circuit and at least one outgoing circuit of each rating are
loaded to their rated current. If a circuit of each basic type is not included
in the test, further tests are carried out until one outgoing circuit of each
type has been included. This approach is suitable where a specific
arrangement and design of assembly is to be verified with the minimum
amount of testing .
As the outgoing circuits are tested with a diversity (loading) factor of
unity, it does, however, result in a more onerous test than necessary for
most applications.
Option 2
Outgoing circuits are temperature rise tested individually to verify they
are capable of carrying their rated current. The incoming circuit is then
supplied to its rated current. This is distributed through as many outgoing
circuits as practical, including one outgoing circuit of each basic type and
in the most onerous configuration, with each circuit loaded to its rated
current multiplied by the rated diversity (loading) factor .
Again, this test regime is only suitable for a specific arrangement and
design of assembl y, but it does better reflect the normal loading of an
assembly.
Option 3
This alternative has been included to enable modular assembly systems
to be fully verified . Horizontal busbars, vertical busbars and outgoing
functional units are tested individually. The assembly as a whole is then
verified as in Option 2.
Note that temperatures rises are given in Kelvin to differentiate them from
temperatures given in °C.
The continuity of the protective circuit is also checked at a high fault
current that could occur following accidental detachment of a conductor.
When modular devices and equipment are installed in accordance with the
specified conditions, the distances are observed for the insulation
voltages of these devices. Experience has shown that the greatest risk is
in the wiring.
Connections, bundles of conductors and busbars must be meticulously
checked.
Extinguishing must take place in less than 30 seconds . All elements that
make up LV assemblies comply with this requirement.
The control unit is supplied with all the controls and metering necessary
to accurately set the temperature of the glow wire. The wire current is
continuously variable by means of the panel mounted controller and is
monitored by the built in ammeter. A digital temperature indicator is fitted
which, in conjunction with the thermocouple supplied, accurately
measures the glow wire temperature.
The electrical circuit of the control unit is fully protected by fuses and
a miniature circuit breaker and incorporates mains on off switching and
push button control of the output current. Self contained cabinet with
large viewing window and dark colored interior.