0% found this document useful (0 votes)
57 views

Final Exam in Building Design 1

This document provides general electrical notes for a project. It specifies that all electrical work must comply with the Philippine Electrical Code and local regulations. Wiring methods include intermediate metallic conduit for feeders and risers, and PVC conduit for lighting and power receptacles. All wires must be copper and thermoplastic insulated for 600V. The minimum wire size is 3.5mm2 for power and lighting circuits. Outlet boxes must be galvanized and 16 gauge with knockouts. Grounding must be provided per code. Mounting heights are specified for devices.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views

Final Exam in Building Design 1

This document provides general electrical notes for a project. It specifies that all electrical work must comply with the Philippine Electrical Code and local regulations. Wiring methods include intermediate metallic conduit for feeders and risers, and PVC conduit for lighting and power receptacles. All wires must be copper and thermoplastic insulated for 600V. The minimum wire size is 3.5mm2 for power and lighting circuits. Outlet boxes must be galvanized and 16 gauge with knockouts. Grounding must be provided per code. Mounting heights are specified for devices.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL ELECTRICAL NOTES:

1. All electrical works shall comply in accordance with these plans and specifications. The applicable provisions
of the latest edition of the Philippine Electrical Code (PEC). The rules and regulation of the local enforcing
authority and the requirements of the local power company. The electrical works shall be done under the
immediate supervision of a duly registered electrical engineer.

2. Wiring method shall be as follows :

A. Feeders and risers - intermediate metallic conduit


B. Lighting, power receptacle - polyvinyl chloride conduit sch. 40 branch ckt. & auxiliary

3. All wires shall be copper and thermoplastic insulated type "thw" unless otherwise indicated in the plan. The LEGEND AND SYMBOLS
minimum size of wire for power and lighting circuit homerun shall be 3.5mm² and insulated for 600 volts.
Smallest raceway shall be 15mmø trade/nominal size. CAN LIGHT RECESSED
4. All outlet boxes shall be galvanized gage no. 16 deep types with factory knockouts. s 1 1-SINGLE POLE SWITCH

5. All materials to be used shall be brand new and approved type for the particular location and purpose of
s 2 2-SINGLE POLE SWITCH
usage. s 3 3-SINGLE POLE SWITCH

6. Grounding system shall be provided to all lighting and power circuit as per Philippine Electrical Code
s 2W TWO WAY SWITCH
requirement. s 3W THREE WAY SWITCH

7. Mounting height of wiring devices shall be as follows :


s 4W FOUR WAY SWITCH
DUPLEX CONVENIENCE OUTLET
a. light switch - 1.20 m above finish floor OUTDOOR WALL LED LIGHTS
b. convenience outlet - 0.30 m above finish floor AIR-CONDITIONING UNIT
c. panel board - 1.50 m above finish floor 1
DP1 CIRCUIT HOMERUN INDICATING PANEL DISTRIBUTION
d. fire alarm station outlet - 1.50 m. above finish floor
DP1
DISTRIBUTION PANEL 1
e. push button outlet - 1.20 m above finish floor
MAIN DISTRIBUTION PANEL
f. fire alarm & vibrating bell - 0.30 m below ceiling line MDP

1 SCALE
GENERAL NOTES 1:100

You might also like