1. All electrical works shall comply in accordance with these plans and specifications. The applicable provisions
of the latest edition of the Philippine Electrical Code (PEC). The rules and regulation of the local enforcing
authority and the requirements of the local power company. The electrical works shall be done under the
immediate supervision of a duly registered electrical engineer.
3. All wires shall be copper and thermoplastic insulated type "thw" unless otherwise indicated in the plan. The LEGEND AND SYMBOLS
minimum size of wire for power and lighting circuit homerun shall be 3.5mm² and insulated for 600 volts.
Smallest raceway shall be 15mmø trade/nominal size. CAN LIGHT RECESSED
4. All outlet boxes shall be galvanized gage no. 16 deep types with factory knockouts. s 1 1-SINGLE POLE SWITCH
5. All materials to be used shall be brand new and approved type for the particular location and purpose of
s 2 2-SINGLE POLE SWITCH
usage. s 3 3-SINGLE POLE SWITCH
6. Grounding system shall be provided to all lighting and power circuit as per Philippine Electrical Code
s 2W TWO WAY SWITCH
requirement. s 3W THREE WAY SWITCH
1 SCALE
GENERAL NOTES 1:100