Catalog Thiet Bi Dien Ls Aptomat MCCB Elcb Ls
Catalog Thiet Bi Dien Ls Aptomat MCCB Elcb Ls
I 1
Green Innovators of Innovation
2 I
I 3
Meta solution
MCCB = ELCB
4 I
Metasol
Molded Case Circuit Breaker / Earth Leakage Circuit Breaker
I 5
MCCB/ELCB
Metasol MCCB
Upgrade breaking capacity
460V
85kA
ABL400c ABL800c
85kA 85kA
75kA
65kA
ABH400c ABS800c
ABL125c ABL250c 50 50
60kA 60kA
50kA
ABH50c ABH125c ABH250c ABS400c
25 35 35 35
37kA
ABS125c ABS250c ABN400c ABN800c
ABS100e 25 25 25 35
26kA
ABN250c
18
18kA
ABS50c ABS60c ABN100c
10 10 10
14kA
ABS30c ABN50c ABN60c
5 5 5
6 I
Short-circuit breaking capacity
Metasol ELCB
Upgrade breaking capacity
460V
85kA
EBL400c EBL800c
85kA 85kA
75kA
65kA
50kA
37kA
26kA
18kA
14kA
I 7
MCCB/ELCB Compatible and standard
● 100% compatible with Meta-MEC series.
Metasol MCCB
AF
30AF 50AF 60AF 100AF 125AF 250AF 400AF 630AF 800AF
Type
ABN100c
18kA
ABN50c ABN60c ABN250c ABN400c ABN630c ABN800c
ABN 14kA 14kA 26kA 37kA 37kA 37kA
ABN100e
31kA
8 I
● Same external dimension with MCCB and ELCB.
60 mm
50mm
Metasol ELCB
AF
30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF
Type
EBN50c EBN60c EBN100c EBN250c EBN400c EBN800c
EBN 14kA 14kA 18kA 26kA 37kA 37kA
EBL400c EBL800c
EBL 85kA 85kA
I 9
MCCB/ELCB System overview
10 I
System overview
Breaker
Internal auxiliaries
Plug-in kit (ELCB only)
Rotary handle (Direct)
Rotary handle (Direct, Key lock)
Rotary handle Extended)
Rear terminal
Terminal cover (Short, Long)
Insulation barrier
Handle lock
Remote operation
I 11
MCCB/ELCB Internal accessories
● ●
●
●
Internal accessories
Internal accessories can be commonly used in all Metasol MCCB and ELCB
(Notice: Exception of SHT, UVT in ELCB)
12 I
Internal accessories
AX AL AL AX AX AL AL AX
SHT/UVT SHT/UVT
AX AL AL AX
SHT/UVT
53 103 203 I 13
MCCB/ELCB External accessories
External accessories
Designed for various mount and user safety.
14 I
External accessories
Plug-in base
It makes to extract and/or rapidly replace the circuit breaker without having to
touch connections. (Easy replacement and maintenance)
Locking device
- Fixed padlock
- Removable padlock
- Key lock device on direct handle
Insulation barrier
These allow the insulation characteristics between the phases at the
connections to be increased.
Remote operation
It is a device that makes it possible to turn on / off the breaker even in the remote
place. It is safe because it does not have to operate the handle of the circuit
breaker by hand, and it is suitable for automation.
I 15
Marking and configuration
MCCB
MCCB model
•ABN: Economic type
•ABS: Standard type
•ABH: High capacity type
Standardized characteristics
Ui: Rated insulation voltage
Uimp: Impulse withstand
voltage
Ue: Rated operational voltage
Icu: Ultimate breaking
capacity
Ics: Service breaking capacity
Symbol indicating
suitability for isolation
as defined by IEC 947-2
MCCB
Upstream connections
Fixing hole
Product name
Brand name
Operating handle
Certification mark
Company logo
Fixing hole
Downstream connections
16 I
ELCB
ELCB model
•EBN: Economic type
•EBS: Standard type
•EBH: High capacity type
Symbol indicating
suitability for isolation
as defined by IEC 947-2
ELCB
Upstream connections
Fixing hole
Brand name
Product name
Operating handle
Residual current (I▵n) setting
Company logo
Certification mark
Fixing hole
Downstream connections
I 17
External configuration
MCCB
① Handle
•Function of indications
- "On" "Off" "Trip"
•Resetting Handle
When the handle indicates "Tripped" position
it must first be reset by moving the handle to
the "Off" position and then closing is possible
•trip-Free even if the handle is held at "On", the
Terminal
Breaker will trip if an over current flows
•Suitable for Verification of the main contact
position under abnormal conditions because
the handle doesn’t indicate open position Arc-Extinguishing
unit
② Arc-Extinguishing unit
LS patent technique PASQ Contact
Arc-Extinguishing unit
PASQ : Puffer Assisted Self-Quenching
•Reduction of arc voltage for a short time Mechanism
Hybrid Grid
chamber Ass’y
Trip
18 I
ELCB
① Residual
indication LED
③ Residual
detection unit
(ZCT + Main board)
I 19
Quick selection table
Molded Case Circuit Breakers
MCCBs
AF 30AF 50AF 60AF
Rated current, In A (3, 5, 10) Note) 1, 15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60
Rated operational AC (V) 460 690 690 690 690 690 690
voltage, Ue DC (V) - 500 500 500 500 500 500
Rated insulation voltage, Ui V 460 1,000 1,000 1,000 1,000 1,000 1,000
AF
Type 30AF 50AF 60AF 100AF 125AF 250AF
7.4
ABN100c 50
4.5
18kA
ABN50c ABN60c ABN250c
ABN 14kA 14kA 26kA
130
115
ABN100e
84
50
31kA
20 I
100AF 125AF 250AF
15, 20, 30, 40, 50, 60, 75, 100 15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
8 8 8 8 8 8 8 8 8
50
8.2
5
47
4.5
100
50
155
135
59.4
102
126
144
165
50
60 58
60 60
90 35
64
70 64
68
105 68.5
82
(Fig. 2) (Fig. 3) 86.85
I 21
Quick selection table
Molded Case Circuit Breakers
MCCBs
AF 400AF
AF
Type 400AF 800AF 1000AF 1200AF
13
ABN400c ABN800c
ABN 37kA 37kA 52.5
48
257
225
215
150
41
48
ABH400c
ABH 65kA 95
105
109
ABL400c ABL800c ABL1000b ABL1200b
ABL 85kA 85kA 85kA 85kA 113
145
(Fig. 4)
22 I
800AF 1000AF 1200AF
8 8 8 6 6 6 6 6
8 10 14 - - - - -
25 45 65 50 75 50 50 75
37 65 85 65 85 65 65 85
45 75 100 65 85 65 65 85
50 85 125 100 125 100 100 125
10 20 40 - - - - -
10 20 40 - - - - -
100 100 75 50 50 50 50 50
210×280×109mm 220×400×105mm 220×400×105mm
(Fig 5) (Fig 6) (Fig 6)
50 page 52 page 52page 54page 52page
104 page 105 page 105page 105page 105page
113 page 114 page 114page 115page 114page
93
48.5
17
13.5
116
56
8
9
18
53
25
21.4
280
243
150
96
25
400
110
98.5
95
105
90
40
109
113 17
44 48.5
20
145 70 70 102.5
220 105
122.5
159
(Fig. 5) (Fig. 6) 230
I 23
Quick selection table
Motor protection Molded Case Circuit Breakers
MCCBs
AF 30AF 50AF 60AF
Metasol MCCB
7.4
AF 50
30AF 50AF 60AF 100AF 125AF 250AF
4.5
Type
130
115
84
50
(Fig. 1)
24 I
100AF 125AF 250AF
8 8 8 8 8
5 8 10 8 10
10 26 35 26 35
18 37 50 37 50
22 42 50 42 50
35 85 100 85 100
10 20 30 20 30
100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
42 page 44 page 46 page
106 page 107 page 107 page
109 page 110 page 111 page
8.2
8.2
50 47
5
4.5
59.4
100
50
102
126
144
165
155
135
50
60 58
60
60 35
90
64 70 64
68 105 68.5
82 86.85
(Fig. 2) (Fig. 3)
I 25
Quick selection table
ZCT Molded Case Circuit Breakers
MCCBs
AF 30AF 50AF 60AF
Rated current, In A 15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60
Metasol MCCB
Ø7.4
AF
Type 30AF 50AF 60AF 100AF 125AF 250AF 50
Ø4.5
130
ABN
84
50
22 58
60
ABH50cM ABH125cM ABH250cM 50
ABH 50kA 50kA 50kA 64
75
68
(Fig. 1) 82
26 I
100AF 125AF 250AF
8 8 8 8 8 8
5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
42 page 44 page 46 page
101 page 102 page 103 page
109 page 110 page 111 page
Ø8.2
Ø 8.2
50 47
Ø5
Ø4.5
59.4
100
50
102
126
144
165
155
135
50
60 58
60
60 35
90 64
64 70
68 105 68.5
82 86.85
(Fig. 2) (Fig. 3)
I 27
Quick selection table
ZCT Molded Case Circuit Breakers
MCCBs
AF 400AF
Rated operational
AC (V) 690 690 690 690
voltage, Ue
AF
Type 400AF 800AF
ABN400c ABN800c
ABN 37kA 37kA
ABS400c ABS800c
ABS 50kA 65kA
ABH400c
ABH 65kA
ABL400c ABL800c
ABL 85kA 85kA
28 I
800AF
8 8 8
8 10 14
25 45 65
37 65 85
45 75 100
50 85 125
100 100 75
210×280×109mm
(Fig 5)
50 page
104 page
113 page
Ø13.5
Ø13
56
Ø8
Ø8
52.5 53
25
48
257
225
215
280
243
150
150
96
41
48
95
95
105
105
109 109
113 113
145 145
(Fig. 4) (Fig. 5)
I 29
Quick selection table
Earth Leakage Circuit Breakers
ELCBs
AF 30AF 50AF 60AF
Rated residual current, I▵n mA 30, 100/200/500mA 30, 100/200/500mA 30, 100/200/500mA 30, 100/200/500mA
Rated operational voltage, Ue AC (V) 220/460 220/460 220/460 220/460
Residual current off-time at I▵n sec ≤0.1 sec ≤0.1 sec ≤0.1 sec ≤0.1 sec
50
AF
Ø 4.5
50 60
EBH50c EBH125c EBH250c
EBH 50kA 50kA 64
50kA 75
66.5
68
82
(Fig. 1)
30 I
100AF 125AF 250AF
60, 75, 100 15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
6 6 6
18 37 50 26 37 50
35 85 100 65 85 100
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
62 page 64 page 66 page
101 page 102 page 103 page
116 page 117 page 118 page
Ø8.2
Ø 8.2
Ø5
50
Ø4.5
47
100
102
144
165
135
155
50
50
7
4.7
60 58 60
60 35
90 64
64 70
66.5
68 105
68.5
82
86.85
(Fig. 2) (Fig. 3)
I 31
Quick selection table
Earth Leakage Circuit Breakers
ELCBs
AF 400AF
Residual current off-time at I▵n sec ≤0.1 sec ≤0.1 sec ≤0.1 sec ≤0.1 sec
AF
400AF 800AF 1000AF 1200AF
Ø8
Type
EBN400c EBN800c
EBN 37kA 37kA
257
225
215
150
EBH400c
EBH 65kA 95
105
109
EBL400c EBL800c
EBL 85kA 85kA 113
145
(Fig. 4)
32 I
800AF 1000AF 1200AF
6 6 6 - -
≤0.1 sec ≤0.1 sec ≤0.1 sec ≤0.1 sec ≤0.1 sec
37 65 85 85 85
50 85 125 125 125
100 100 75 - -
210×280×109mm 220×565×105mm
(Fig. 5) (Fig. 6)
70 page 72 page
104 page 105 page
120 page 121 page
93
48.5
17
116
90
Ø 13.5
9
Ø8
18
21.4
206
25
400
360
110
280
243
98.5
150
96
525
165
165
95
105
90
40
109 17
44 48.5
20
113 70 70 102.5
220 105
122.5
145 159
(Fig. 5) (Fig. 5) 231
I 33
30AF MCCB
ABE30b
Ratings
c2 Note) - -
For more information d 80 80
•Drawings ▶ 108 page Weight, kg Standard 0.5 0.7
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 2p 3p
•Connection and mounting ▶ 127 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut
34 I
Ordering types
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL
Note) For more detail see 74 page
External accessories
ABE30b Name
I 35
30AF MCCB
ABS30c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 106 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. The short-circuit breaking capacities in ( ) are applied to the rated current in (3, 5, 10A)
2. Depth by door cut size : c1 for large cut, c2 for small cut
3. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
36 I
Ordering types
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page
External accessories
ABS30c Name
I 37
50AF MCCB
ABN50c, ABS50c, ABH50c
Ratings
ABS54c Plug-in
Mounting Standard Screw fixing
d
a 50 75 100 50 75 100 60 90 120
c2
a c1 b 130 130 155
c1 Note) 60 60 60
b
c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 106, 107 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9 0.7 1 1.2
•Trip curves ▶ 101, 102 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
38 I
Ordering types
External accessories
ABN50c
ABH50c Name
ABS50c
I 39
60AF MCCB
ABN60c, ABS60c
Ratings
ABS64c Plug-in
Mounting Standard Screw fixing
d
a 50 75 100 50 75 100
c2
a c1 b 130 130
c1 Note) 60 60
b
c2 Note) 64 64
For more information d 82 82
•Drawings ▶ 109 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 2p 3p
•Connection and mounting ▶ 127 page CE marking ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
40 I
Ordering types
External accessories
ABN50c
Name
ABS50c
I 41
100AF MCCB
ABN100c, ABN100e
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 109 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
3. The Ics(service breaking capacity) of ABN100e are in ( )
42 I
Ordering types
External accessories
ABN100c Name
I 43
125AF MCCB
ABS125c, ABH125c, ABL125c
Ratings
c2 Note) 64 64 64
For more information d 82 82 84
•Drawings ▶ 110 page Weight, kg Standard 0.7 1 1.2 0.7 1 1.2 0.7 1 1.2
•Trip curves ▶ 102 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
3. The Ics(service breaking capacity) of ABL125AF are in ( )
44 I
Ordering types
I 45
250AF MCCB
ABN250c, ABS250c, ABH250c, ABL250c
Ratings
c2 Note) 64 64 64 64
For more information
d 82 82 87 87
•Drawings ▶ 111 page
Weight, kg Standard 0.7 1 1.2 0.7 1 1.2 1.1 1.2 1.6 1.1 1.2 1.6
•Trip curves ▶ 103 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 127 page
CE marking ○ ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
3. The Ics(service breaking capacity) of ABL250AF are in ( )
46 I
Ordering types
I 47
400AF MCCB
ABN400c, ABS400c, ABH400c, ABL400c
Ratings
48 I
Ordering types
External accessories
IBL400 Insulation barrier
T1-43A Terminal cover (Long) - 2, 3pole
T1-44A Terminal cover (Long) - 4pole
N-70 Rotary handle (Direct)
E-70U Rotary handle (Extended)
MI-43 Mechanical interlock - 2, 3pole
MI-44 Mechanical interlock - 4pole
PB-I3-FR Plug-in kit
MOP-M4 Remote operation
Note) For more detail see 82 page
I 49
800AF MCCB
ABN800c, ABS800c, ABL800c
Ratings
ABS803c
Rated impulse withstand voltage, Uimp 8kV
50 I
Ordering types
External accessories
IBL800 Insulation barrier
T1-63A Terminal cover (Long) - 2, 3pole
T1-64A Terminal cover (Long) - 4pole
N-80 Rotary handle (Direct)
E-80U Rotary handle (Extended)
MI-83S Mechanical interlock - 2, 3pole
MI-84S Mechanical interlock - 4pole
PB-J3-FR Plug-in kit
MOP-M5 Remote operation
Note) For more detail see 82 page
I 51
1000/1200AF MCCB
ABS1000b/1200b, ABL1000b/1200b
Ratings
Certification Pole 3p 4p 3p 4p
CE marking ABS1003b ABS1004b ABS1203b ABS1204b
○ × ○ ×
For more information
•Drawings ▶ 114 page ABL1003b ABL1004b ABL1203b ABL1204b
•Trip curves ▶ 105 page × × × ×
Note) 1. Please specify the frequency when ordering.
2. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
52 I
Ordering types
I 53
1200AF Electronic MCCB
ABS1203bE
Ratings
Certification Pole 3p
d
c2
a c1 a 220
b 400
b
54 I
Ordering types
AL
Option of below items for T-position Contact rating for auxiliary and alarm switches
AX1 Auxiliary switch (1c) AC DC
AX2 Auxiliary switch (2c) Voltage Current (A) Voltage Current (A)
AL1 Alarm switch (1c) R T
(V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm switch (2c)
125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) switch
250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) switch
500 10 5 250 0.2 0.03
I 55
30AF ELCB
EBS30c
Ratings
d
a 75 100
c2
a c1 b 130 130
c1 Note) 60 60
b
c2 Note) 64 64
For more information d 82 82
•Drawings ▶ 116 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. The short-circuit breaking capacities in ( ) are applied to the rated current in (5, 10A)
4. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
5. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.
56 I
Ordering types
External accessories
EBS30c Name
I 57
50AF ELCB
EBN50c, EBS50c, EBH50c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 116, 117 page Weight, kg Standard 0.5 0.7 0.7 0.9 1 1.2
•Trip curves ▶ 101, 102 page
•Accessories ▶ 74 page Certification Pole 2p 3p 3p 4p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : C1 for large cut, C2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.
58 I
Ordering types
I 59
60AF ELCB
EBN60c, EBS60c
Ratings
d
a 75 75 100
c2
a c1 b 130 130 130
c1 Note) 60 60 60
b
c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 116 page Weight, kg Standard 0.7 0.7 0.9
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 3p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○
Note) 1. Depth by door cut size : C1 for large cut, C2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.
60 I
Ordering types
Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page
External accessories
EBS60c
Name
EBN60c
I 61
100AF ELCB
EBN100c
Ratings
c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 116 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 101 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.
62 I
Ordering types
Electrical auxiliaries
Rated residual current, I▵n: 100/200/500mA
Rated current, In AX Auxiliary switch
2-pole 3-pole 4-pole
AL Alarm switch R T
60 A EBN102c/60/100 EBN103c/60/100 EBN104c/60/100
AX+AL Combination switch
75 A EBN102c/75/100 EBN103c/75/100 EBN104c/75/100
100 A EBN102c/100/100 EBN103c/100/100 EBN104c/100/100 Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page
External accessories
EBN100c Name
I 63
125AF ELCB
EBS125c, EBH125c
Ratings
64 I
Ordering types
I 65
250AF ELCB
EBN250c, EBS250c, EBH250c
Ratings
c2 Note) 64 64 64
For more information d 87 87 87
•Drawings ▶ 118 page Weight, kg Standard 1.1 1.2 1.2 1.5 1.2 1.5
•Trip curves ▶ 103 page
•Accessories ▶ 74 page Certification Pole 2p 3p 3p 4p 3p 4p
•Connection and mounting ▶ 127 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.
66 I
Ordering types
External accessories
EBH type (50kA/460V) EBN250c
EBS250c Name
Rated residual current, Rated residual current,
Rated EBH250c
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 4-pole 3-pole 4-pole IB23 Insulation barrier
100 A EBH203c/100/30 EBH204c/100/30 EBH203c/100/100 EBH204c/100/100 Terminal cover (Long)
TCL33
125 A EBH203c/125/30 EBH204c/125/30 EBH203c/125/100 EBH204c/125/100 - Inde type, D-handle type, N-handle type
150 A EBH203c/150/30 EBH204c/150/30 EBH203c/150/100 EBH204c/150/100 Terminal cover (Short)
TCS33
175 A EBH203c/175/30 EBH204c/175/30 EBH203c/175/100 EBH204c/175/100 - Inde type, D-handle type, N-handle type
200 A EBH203c/200/30 EBH204c/200/30 EBH203c/200/100 EBH204c/200/100 DH250 Rotary handle (Direct)
225 A EBH203c/225/30 EBH204c/225/30 EBH203c/225/100 EBH204c/225/100 DHK250 Rotary handle (Direct, Key lock)
250 A EBH203c/250/30 EBH204c/250/30 EBH203c/250/100 EBH204c/250/100 EH250 Rotary handle (Extended)
RTB3 Rear terminal (Bar)
RTR3 Rear terminal (Round)
Handle lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary handle.
• D-handle type: This cover is used with D-handle.
• N-handle type: This cover is used with N-handle.
I 67
400AF ELCB
EBN400c, EBS400c, EBH400c, EBL400c
Ratings
68 I
Ordering types
I 69
800AF ELCB
EBN803c, EBS803c, EBL803c
Ratings
c2 Note) 113
For more information d 145
•Drawings ▶ 120 page Weight, kg Standard 11.5
•Trip curves ▶ 104 page
•Accessories ▶ 75 page Certification Pole 3p
•Connection and mounting ▶ 127 page CE marking -
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.
70 I
Ordering types
E-80U N-80
External accessories
IBL800 Insulation barrier
T1-63A Terminal cover (Long) - 2, 3pole
T1-64A Terminal cover (Long) - 4pole
N-80 Rotary handle (Direct)
E-80U Rotary handle (Extended)
MI-83S Mechanical interlock - 2, 3pole
MI-84S Mechanical interlock - 4pole
Note) For more detail see 82 page
I 71
1000/1200AF ELCB
EBS1003b, EBS1203b
Ratings
72 I
Ordering types
Breaker types Contact operation for auxiliary and alarm switches
EBS type (85kA/460V ) MCCB On Off Trip
AL
Option of below items for T-position Contact rating for auxiliary and alarm switches
AX1 Auxiliary switch (1c) AC DC
AL1 Alarm switch (1c) Voltage Current (A) Voltage Current (A)
AX1+AL1 Auxiliary (1c) + Alarm (1c) switch R T
(V) Resistive load Inductive load (V) Resistive load Inductive load
Note) R-position is not available.
125 20 20 30 6 5
250 20 20 125 0.4 0.05
500 10 5 250 0.2 0.03
I 73
Accessories
SHT
Shunt trip
AX
Auxiliary UVT
switch
Undervoltage
trip
AL
Left-hand seat Right-hand seat
Alarm switch
AX
Auxiliary
switch
AX+AL
AL
Alarm
Combination switch switch
Maximum possibilities
ABN100c ABH125c ABH250c EBN100c EBH125c EBH250c
Position Type
2p 3/4p 2p 3/4p 2/3/4p 2/3/4p 3/4p 2/3/4p
AX - 1 - 1 1 1 1 1
Left-hand
AL - 1 - 1 1 1 1 1
seat
AX+AL - 1 - 1 1 1 1 1
AX 1 1 1 1 1 - - -
Right-hand AL 1 1 1 1 1 - - -
seat AX+AL 1 1 1 1 1 - - -
SHT/UVT 1 1 1 1 1 - - -
74 I
Electrical auxiliaries of 400~800AF
AL AL AL AL
SHTSHT SHTSHT
UVTUVT UVTUVT
AX AX AX AX
Maximum possibilities
MCCB ELCB
Position Type
(400~800AF) (400~800AF)
AX 2 2
Left-hand
AL 2 2
seat
SHT/UVT 1 1
AX 2 -
Right-hand
AL 2 -
seat
SHT/UVT 1 -
I 75
Accessories
Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker
AX
AX2
AX3 (4)
AL
AL2
AL3 (4)
SHT (UVT)
SHT (UVT) 2
AX+AL
AX+AL2
AX+AL3 (4)
AX2+AL
AX2+AL2
AX2+AL3 (4)
AX+SHT (UVT)
76 I
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker
AX+SHT (UVT) 2
AX2+SHT (UVT)
AX2+SHT (UVT) 2
AL+SHT (UVT)
AL+SHT (UVT) 2
AL2+SHT (UVT)
AL2+SHT (UVT) 2
AX+AL+SHT (UVT)
AX+AL+SHT (UVT) 2
AX2+AL2+SHT (UVT)
AX2+AL2+SHT (UVT) 2
I 77
Accessories
Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage
Main breaker
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker
EBL 403c/404c
L-type - -
EBL 803c
Test lead wire (30~250AF)
Pole 3, 4 pole 3 pole 3 pole
AX
AX2
Test button AL
AL2
SHT (UVT)
Note) 1. When you touch the lead wire under energized condition,
you will be in danger of electric shock.
2. Do not energize on both ends of lead wire. AX+AL
3. Do not pull out the lead wire excessively or impact on the
product.
AX+AL2
AX2+AL
AX2+AL2
AX2+SHT (UVT)
AL+SHT (UVT)
AL2+SHT (UVT)
AX+AL+SHT (UVT)
AX2+AL2+SHT (UVT)
78 I
Auxiliary and alarm switch
Contact (AX+AL)
MCCB On Off Trip
AX
AL
Rating (AX+AL)
Conventional thermal current, Ith 5A
I 79
Accessories
The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include
coil clearing contacts that automatically clear the signal circuit when the breaker has tripped. This is not
available for ELCBs of 30~250AF .
Power consumption
Control voltage, Ue MCCB/ELCB
AC (VA) DC (W)
DC 12V - 1.5
80 I
Undervoltage release, UVT
The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between
20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be
re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed.
This is not available for ELCBs of 30~250AF .
AC/DC 48
AC/DC 100~125
・AC: 85~1.1Vn ・AC: 0.2~0.7Vn
AC 200~240 / DC 200~240 Continuous
・DC: 85~1.25Vn ・DC: 0.2~0.7Vn
AC 380~440
AC 440~480
Terminal numbering
Auxiliary switch (AX) Alarm switch (AL) Shunt trip (SHT) Undervoltage trip (UVT)
I 81
Accessories
External accessories
Wide range of external accessories provides user-friendly solution for mounting, cable connection, insulation, safety lock and remote control.
Insulation barrier
Terminal cover
Rear terminal
Rotary handle
(Direct)
Breaker
Rotary handle
(Direct, Key lock)
Rear terminal
Terminal cover
Pad handle Lock
Insulation barrier
Remote operation
82 I
Rotary handles
Direct type
The rotary handle operating mechanism is available in either the direct version or in the extended version on the
compartment door. It is always fitted with a compartment door lock and on a request it can be supplied with a key
lock in the open position.
Type
Key lock
(DH 30~250AF) Breaker type
Direct type
Direct type Extended type
(Key lock) MCCB ELCB
Extended type
Type suffix according to the mounting position
(30~250AF)
Load
On On
(400~800AF)
I 83
Accessories
D-handle
Tripped
Push to trip
Line
Load
On On On
84 I
Installing the D-handle
Off
Cutting panel
I 85
Accessories
Locked
D-handle
Unlocked
Operating
Off position test
Remove
CAUTIONthe key if you operate the handle.
If the door is opened with
much pressure when the On
position of handle is On or
Trip, the handle lock lever
will be demaged.
Push to trip
Off Tripped
Locking system
Key lock
Open panel door
Locked
Unlocked
Off position
86 I
E-handle
DH100
DH100
DH100 DH125
DH125
DH125 DH250
DH250
DH250 DHK-type
DHK-type
DHK-type
Tripped
Push to trip
Load
On On On
I 87
Accessories
E-handle
Off
Off Off Off
Cutting panel
88 I
Locked
Unlocked
Operating
Off position test
Remove
CAUTIONthe key if you operate the handle.
If the door is opened with
much pressure when the Reset On
position of handle is On or
Trip, the handle lock lever
will be demaged.
Off
Locking system
Releasing
Note : In case of EH100/125/250 Semi Type, it is possible to lock E-handle only in the condition of OFF.
I 89
Accessories
N-handle
How to mount
1) Drilling on the panel door (N-30c, 40c, 50c) (N-70, N-80)
① All the N handles require the same size of
mounting hole.
② Drill the holes according to the Fig. 1
Mounting base
Dimension A
* S : Vertical mounting
N-30c :103
N-40c : 103
<Fig 1> N-50c : 103
<Fig 2>
Mounting base
(3) Fixing
① Fixing a breaker and a handle at the (N-30c, 40c, 50c) (N-70, N-80)
same time.
a) As shown in the Fig. 3 a breaker and
a handle can be fixed at the same
time on a mounting base with the 4
(long) screws enclosed.
<Fig 3>
<Fig 4>
90 I
② Fixing a handle and a breaker step by step
a) Check if there is any thin membrane in the mounting
hole of the breaker cover and remove it, If exists.
b) Have the breaker handle and the lever of N handle
be located in the position shown in Fig. 4.
c) Fix the N handle on the breaker with the 2 (short)
screws enclosed.
d) Fix the breaker on a mounting base with the 2 (long)
<Fig 5>
screws
(4) Fixing front plate and lock plate Locking plate
① Set the front plate and the locking plate on the door Door
as shown in Fig. 6 fix them with screws. Front plate
<Fig 6>
Bad-tilt
<Fig 7>
<Fig 8>
<Fig 9>
b) In the event the door does not lock after closing the door
This happens if the distance between the door panel and
the mounting base the panels of the door is long.
Loosen the adjusting screw in the lock plate and move the
plate in the direction of the arrow as shown in Fig. 10.
<Fig 10>
I 91
Accessories
N-handle
On (1) Operation in the door closed
① To have the breaker On turn the handle to be vertical. <Fig. 11>
② To have the breaker Off turn the handle to be horizontal. <Fig. 12>
Off
<Fig 11>
<Fig 12>
(3) Operation of the breaker in the door open
On On
① When the door is open the breaker will not be on as the lock lever operates.
② To release the locking pull the lock lever to be nearly horizontal position. Then
the breaker can be closed. <Fig. 14>
③ If the door is closed the lock lever will be reset automatically.
Off
Off
<Fig 13>
Padlocking
① Lockable at On or Off state with a padlock. (Padlock is not supplied)
(N-30, 40, 50)
- Lockable at Off state with a padlock is an optional spec.
② Pull the lock plate on the front of the handle and fasten the lock. <Fig. 15>
③ If the breaker is tripped after padlocking at on state, the handle will point to
the Trip.
④ Padlock diameter should be 3.5 ~ 6mm
(N-70, N-80)
Note: Terminal covers for 400AF and 800AF MCCBs are in acrylic.
<Fig 14>
<Fig 15>
92 I
Terminal covers
The terminal covers are applied to the circuit-breaker to prevent accidental contact with live parts and thereby guarantee protection
against direct contacts.
Two types by length are available and provide IP20 degree of protection.
Also, covers ara classified in to 2 different type: Independent, Attachable and detachable with D or N handle
Inde D-handle N-handle Inde D-handle N-handle MCCB ELCB Short type Long type
TBS22 - - - - - 2P
ABE30b - 10 -
TBS23 - - - - - 3P
TCS12 - - TCL12
- - 2P
TCS/T-12 - - TCL/T-12
TCS13 TCS13 TCS13 TCL13 TCL13 TCL13 ABN50c/60c/100c/100e EBN50c/60c/100c
3P 5.5 30
TCS/T-13 TCS/T-13 TCS/T-13 TCL/T-13 TCL/T-13 TCL/T-13 ABS30c/50c/60c EBS30c/50c/60c
TCS14 TCS14 TCS14 TCL14 TCS14 TCS14
4P
TCS/T-14 TCS/T-14 TCS/T-14 TCL/T-14 TCL/T-14
TCS22 - - TCL22 - -
2P
TCS/T-22 - - TCL/T-22 - - ABS125c
TCS23 TCS23 TCL23 TCL23 EBS125c
3P ABH50c/125c 5.5 40
TCS/T-23 TCS/T-23 TCL/T-23 TCL/T-23 EBH50c/125c
TCS24 TCS24 TCL24 TCL24 ABL125c
4P
TCS/T-24 TCS/T-24 TCL/T-24
TCS33 TCS33 TCL33 TCL33 EBN250c,
2, 3P ABN250c, ABS250c
TCS/T-33 TCS/T-33 TCL/T-33 TCL/T-33
EBS250c 5.5 50
TCS34 TCS34 TCL34 TCL34 ABH250c, ABL250c
4P
TCS/T-34 TCS/T-34 TCL/T-34 EBH250c
- - - T1-43A - - 2, 3P
ABN/S/H/L400c EBN/S/H/L400c - 120
- - - T1-44A - - 4P
- - - T1-63A - - 2, 3P
ABN/S/L630c/800c EBN/S/L630c/800c - 141
- - - T1-63A A - - 4P
A
TCS (Short type) TCL (Long type)
TCS/T (Short type) TCL/T (Long type) Short type construction Long type construction
I 93
Accessories
Insulation barriers
Insulation barrier allows the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into the
corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.
Breaker
Type
MCCB ELCB
ABN50c/60c/100c/100e EBN50c/60c/100c
IB-13
ABS30c/50c/60c EBS30c/50c/60c
ABS125c
EBS125c
ABH50c/125c
EBH50c/125c
IB-23 ABN250c, ABS250c
EBN250c, EBS250c
ABH250c
EBH250c
ABL125c, ABL250c
94 I
Rear connection terminals
Rear connection terminals are used to adapt the circuit breakers to switchboards or
other applications that require rear connection.
There are two kinds of rear connection terminals.
- Flat type
- Round type
CL
CL CL
I 95
Accessories
Mechanical interlock
The mechanical interlock is installed on the front of two breakers mounted side by side, in either the 3-pole or 4-pole version
and prevents simultaneous closing of the two breakers. So it is suitable for consisting of manual sourcechangeover system.
MI 4 3
Type AF Pole
Mechanical 1 100AF 3 3P
interlock 2 125AF 4 4P
3 250AF
4 400AF
8 800AF
ABS30c, ABS50c, ABS60c, ABN50c, ABN60c, EBS30c, EBS50c, EBS60c, EBN50c, EBN60c,
MI-13, 14
ABN100c, ABN100e EBN100c
MI-23, 24 ABS125c, ABH50c, ABH125c, ABL125c EBS125c, EBH50c, EBH125c
MI-33, 34 ABN/S/H/L250c EBN/S/H250c
MI-43, 44 ABN/S/H/L400c EBN/S/H/L400c
MI-83, 84 ABN/S/L800c EBN/S/L800c
Note) MI is not applicable to 2-pole version breakers of 100AF and 125AF.
Layout
Padlock dimensions
A
A
Normal PB-A3-FR
Single-row PB-A3-1DB
Plug-in type MCCB ABN100c
(Plug-in terminal built) Double-row PB-A3-2DB
Line-only PB-A3-FRL
Normal PB-C3-FR
Single-row PB-C3-1DB
ABH125c
Double-row PB-C3-2DB
Line-only PB-C3-FRL
ABH250c Normal PB-D3-FR
400AF Normal/Line-only PB-I3-FR/PB-I3-FRL
800AF Normal PB-J3-FR
ABH103c plug-in type
Normal Double-row
I 97
Accessories
Remote operation
Motor operator
Motor operators can also be operated by manual. The motor drives a mechanism which switches
TD & TS toggle handle to the "On" and “Off/Reset” positions.
- The manual actuator handle is located on the front of the cover.
- Manual or Automatic operation can be selected.
- Applicable to 2, 3 and 4-pole breakers.
ABN53c, ABN54c,
ABN63c, ABN64c,
ABN103c, ABN104c,
① DC24V
ABN103d, ABN104d, ≤3A (DC24V)
- MOP-M1 ② AC110V~DC110V 700 700 10,000 120
ABN103e, ABN104e, ≤0.5A (AC)
③ AC230V/DC220V
ABS33c, ABS34c,
ABS53c, ABS54c,
ABS63c ABS64c
ABS103c, ABS104c,
① DC24V
ABH53c, ABH54c, ≤3A (DC24V)
- MOP-M2 ② AC110V~DC110V 840 840 10,000 120
ABH103c ABH104c ≤0.5A (AC)
③ AC230V/DC220V
ABL103c ABL104c
ABN202c, ABN203c, ABN204c,
① DC24V
ABS202c, ABS203c, ABS204c, ≤3A (DC24V)
MOP-M3 ② AC110V~DC110V 840 840 10,000 120
ABH202c ABH203c ABH204c ≤0.5A (AC)
③ AC230V/DC220V
ABL202c ABL203c ABL204c
ABN402c, ABN403c, ABN404c,
① DC24V
ABS402c, ABS403c, ABS404c, ≤6A (DC24V)
MOP-M4 ② AC110~DC110V 1,200 1,200 4,000 60
ABH402c, ABH403c, ABH404c, ≤0.8A (AC)
③ AC230V/DC220V
ABL402c ABL403c ABL404c
ABS1003b, ABS1004b,
ABS1203b ABS1204b ≤6A (DC24V)
- MOP-M6 ① AC230V/DC220V 1,500 1,500 2,500 20
ABL1003b, ABL1004b, ≤0.8A (AC)
ABL1203b ABL1204b
Remote operation
Standard connection
1) Remote On and Off of MCCB and manual operation
2) Be careful not to change the polarity at DC24V
P1(+) P2(-) S1 S2 S4
E E
Ue
ON OFF
P1(+) P2(-) S1 S2 S4
ALb ALa
ALc
Ue
E E
ON OFF
98 I
Manual operation
1) Insert the manual handle into the slot of Motor operator surface and rotate it clockwise.
2) It must be rotated just 180° clockwise for safe operation of micro switch in the motor operator.
3) Return the manual handle after the manual operation
4) Turn the slide switch back to the position of Auto.
CAUTIOn: When the circuit breaker is tripped by trip button in the Off status,
it is impossible to operate motor operator automatically It must be reset by manual operation.
Manual handle
Automatic operation
1) Set the slide switch to Auto, then internal power is closed automatically.
2) Operating frequency should be less than these below regulated values.
MOP-M1~M3, M7 (120 operations per hour) , MOP-M4 (60 operations per hour) ,
MOP-M5, M6 (20 operations per hour)
3) Use the On/Off switch in the range of regulated values.
4) It may interfere near communication equipments because of internal switching power supply.
It’s recommended that a noise filter be installed to power supply.
5) Please do not input On/Off signals at the same time during the automatic operation.
6) If the circuit breaker has a UVT attached inside, charge a UVT on the rated voltage before performing
Motor operator.
Motor operator
Feature
① On position indication (Red color)
② Trip position indication (White color) ⑥
①
③ Off position indication (Green color)
②
④ Button for push to trip
⑤ On/Off/Reset selection lever
⑥ Manual/Auto selection lever
③
⑤
MOP-M4/M5/M6
MOP-M2, M3
MOP-M1
I 99
Type numbering system
MCCB
AB S 10 3 C M / 100A AX T SHT=220V
MCCB Type Ampere frame Pole Series Application Rated current Position & Type Control voltage
General of accessory
N N-type 3 30AF 2 2-pole Right
-
S S-type 5 50AF 3 3-pole purpose T LWT Side SHT
Motor Lead
H H-type 6 60AF 4 4-pole Mounting AC/DC 12V
M Wire
L L-type 10 100/125AF protection Left AC/DC 24V
type
20 225/250AF R LWT Side AC/DC 48V
40 400AF Mounting AC/DC 60V
80 800AF Right AC/DC
100 1,000AF Rated current Accessory T TBT side 100V~130V
Terminal
120 1200AF 3A 150A AX Auxiliary switch mounting AC/DC
Block
5A 175A AL Alarm switch Left 200V~250V
type
10A 200A SHT Shunt trip R TBT side AC 380V~450V
15A 225A Undervoltage mounting AC 440V~500V
UVT UVT
20A 250A trip
30A 300A Rotary handle AC/DC 24V
DH AC/DC 48V
40A 350A (Direct)
50A 400A Rotary handle AC/DC
EH 100V~110V
60A 500A (Extended)
75A 630A RTR AC/DC
Rear terminal 200V~220V
100A 700A RTB
125A 800A AC 380V~440V
150A 1200A AC 440V~480V
* Warning: Mounting accessories is not available at the left side of 2pole MCCB (Up to 125AF)
ELCB
EB S 10 3 C / 100A 30mA AX R
100I
Characteristics curves
ABE30b
Min.
Ambient temp. 40
Max.
Operational time
Min.
ABN/S, EBN/S
Rated current compensation rate (%)
MCCB
Magnetic trip range
ABN50c/60c/100c/100e 700~1500%
ABS30c/50c/60c
Max. breaking time
ELCB
EBN50c/60c/100c
EBS30c/50c/60c
Ambient temp. 40 Rated current
Max.
Max.
Operational time
me
Operational tim
Min.
Min.
Sec.
Sec.
Rated current
Rated current
I101
Characteristics curves
Min.
ABL125c
ELCB
EBS125c
EBH50c/125c Max.
Operational time
Min.
Sec.
Rated current
Min.
Max.
Operational time
Ambient temp. 40
Min.
Rated current
Ambient temp. 40
102I
Breaker types Rated current: 100~225A
MCCB
ABN250c, ABS250c
ABH250c, ABL250c
ELCB
Min.
EBN250c, EBS250c
EBH250c
Max.
Operational time
Sec. Min.
Rated current
180
150
150 120
100
80
60
40
Min.
20
100
10
8
6
4
2
50 Max.
0 10 20 30 40 50 1
Operational time
40
Ambient temp. 40
20
10
8
6 Min.
4
150
Sec.
1
0.8
0.6
0.4
Magnetic trip
0.2
range
(960~1440%)
100 0.1
0.08
0.06
0.04
Max. breaking time
0.02
50
0.01
0 10 20 30 40 50 1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
I103
Characteristics curves
Min.
EBN400c, EBS400c, EBH400c, EBL400c
EBN800c, EBS800c, EBL800c
Max.
Operational time
Min.
Sec.
Rated current
240
180
150
120
60
40
Min.
20
100
10
8
6
4
Max.
50 2
0 10 20 30 40 50
1
Ambient temp. 40
Operational time
40
20
10
8
6
Min.
4
150
Sec.
1
0.8
0.6
0.4
0.2
50
0 10 20 30 40 50 0.01
1 1.25 2 3 4 5 6 7 8 9 10 15 20 30 40 50 70 100
104I
Breaker types Rated current: 1000~1200A
MCCB
ABS1000b, ABL1000b
ABS1200b, ABL1200b
ELCB
Min.
EBS1003b, EBS1203b
Max.
Operational time
Compensation curves
Sec.
Rated current
ABS1200bE
Min.
Operational time
Sec.
Rated current
I105
Characteristics curves
Motor Protection type
Min.
MCCB
ABN50cM/60cM/100cM/100dM
ABS30cM/50cM/60cM
Max.
Min.
Operational time
Min. Max.
Operational time
Sec.
Min.
Magnetic trip range
Sec.
Rated current
Max. breaking time
Rated current
16A~32A
rate
compensation
16A~32A
compensation
Min.
current
current
Rated
Max.
Min.
Rated
Operational time
Ambient temp. 40
Ambient temp. 40
Max.
Min.
Operational time
Sec.
rate
rate
Min.
Magnetic trip range
compensation
compensation
45A~90A
Sec.
106I
Rated current
Breaker types Rated current: 16~90A
240
MCCB 180
150
120
100
ABS125cM 80
60
ABH50cM/125cM 40
Min.
20
10
8
6
4
2
Max.
1
40
Operational time
20
10
8
Compensation curves 6
4
Min.
2
Rated current compensation rate (%)
0.8
0.6
16A~32A
0.4
Magnetic trip range
0.2
0.1
45A~90A 0.08
0.06
0.04 Max. breaking time
0.02
0.01
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
Ambient temp. 40
Rated current
Compensation curves
Rated current: 125~225A
Rated current compensation rate (%)
I107
Dimensions
MCCB ABE30b
(mm)
Terminal cover
Insulation barrier Insulation
Terminal cover barrier
Terminal cover
Fixing hole
Terminal cover
Insulation barrier Insulation
Terminal cover barrier
Terminal cover
Fixing hole
DIN-Rail
Terminal cover
Insulation barrier Insulation
Terminal cover barrier DIN-Rail
Terminal cover
Fixing hole
2P 3P
Trip test button Trip test button
Terminal details
(Screw) (Screw)
(Screw) (Screw)
(Screw) (Screw)
(Holder) (Holder)
(Holder) (Holder)
(Holder) (Holder)
3P 3극
108I
MCCB ABN50c ABS30c
ABN60c ABS50c
ABN100c/100e ABS60c
(mm)
25 25 25 56
50
50
50
Ø7.4
50
Ø4.5
22 22 22
115
130
115
130
115
130
50
84
50
84
50
84
19
19
19
13.3 13.3 13.3
58
25 50 25
Trip test button Trip test button Trip test button 60
50 75 75
64
100
68
82
2P 3P 4P
12.5
M5× 14
5
Ø9
5.
Ø
15
7.5
18 24 7 7
M8× 14
7.5
18 24
(≥60A)
110.5
110.5
52
52
52
25 25 52 77 102
2P 3P 4P 2P 3P 4P
I109
Dimensions
(mm)
30 30 30
80
80
80
50
Fixing hole
50
Fixing hole
50
Fixing hole
5
50
8.2
22 22 22
16.5
16.5
16.5
155
155
155
135
100
135
100
135
100
50
50
50
37 37 37
4
8
8
30 60 30 58
10
10
10
2P 3P 4P
9
Ø
16
18 24 8
10
52
52
52
132
30 30 62 92 122
2P 3P 4P 2P 3P 4P
110I
MCCB ABN250c ABS250c ABH250c ABL250c
(mm)
Insulation barrier
Insulation barrier
2,3P 4P
2,3P 4P 2,3P 4P
I111
Dimensions
(mm)
In
Fixing hole Fixing hole Fixing hole
2P 3P 4P
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 or Ø6 M6 or Ø6
Slot "A"
Slot "B"
Slot "C"
142(3p) 142(3p)
187(4p) 187(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P
112I
MCCB ABN630c ABS630c ABL630c
ABN800c ABS800c ABL800c
(mm)
34.5
7
73.5
73.5
73.5
73.5
2P 3P 4P
630AF : 7
800AF : 10
Connecting
Terminal details
Panel
Cover B
Panel
Cover C
212(3P) 212(3P)
282(4P) 282(4P)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P
I113
Dimensions
(mm)
Ø
Ø
Mounting hole Mounting hole
Auxiliary handle
Ø
Ø
Auxiliary handle
3P 4P
or Ø or Ø
3P 4P 3P 4P
114I
MCCB ABS1203bE
(mm)
Ø
Mounting hole
Ø
Mounting hole
Auxiliary handle
Ø
Auxiliary handle
or Ø
I115
Dimensions
(mm)
56
25 Insulation barrier 25 25
Insulation barrier
50
50
7.4
Trip indication Trip indication
by earth fault by earth fault 50
4.5
Residual current Residual current
2.2
(I n) setting (I n) setting
115
130
84
50
130
115
84
50
29.2 29.2
19
68
82
Terminal details Connecting
(≤ 50A)
(≤ 50A) (≥60A)
(≥60A)
M4 or 5 M4 or 5
2, 3P 4P 2P 3P 4P
116I
ELCB EBS125c EBH50c
EBH125c
(mm)
30 30
80
80
50
50
Fixing hole Fixing hole
5
Trip indication Trip indication 50
8.2
22 22 by earth fault
by earth fault
37.8 37.8
Residual current Residual current
(I n) setting
16.5
(I n) setting
16.5
100
100
50
50
155
135
155
135
4.7
4.7
37
2.5
Trip test button
Trip test button for earth fault 4
for earth fault
8
10
8 60
90 90
82
120
3P 4P
M4 or 5 M4 or 5
3P 4P 3P 4P
I117
Dimensions
(mm)
80
Fixing hole Fixing hole
59.4
165
144
126
102
165
144
126
102
50
50
7
7
19.6
19.6
70 105 35
105 140
2, 3P 4P
2, 3P 4P 2, 3P 4P
118I
ELCB EBN400c EBS400c EBH400c EBL400c
(mm)
8
.5
12
41.5
26.5
13
Trip indication Trip indication
8
by earth fault by earth fault
57.9 57.9
48
48
46.9 46.9
16.5 23.9
23.9
257
225
215
150
257
225
215
150
41.4
41.4
48
48
Trip test button 16.5 Trip test button
for earth fault for earth fault
Residual current Residual current
(I n) setting (I n) setting
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 or 6 M6 or 6
Slot "A"
Slot "B"
Slot "C"
142(3p) 142(3p)
187(4p) 187(4p)
2, 3P 4P 2, 3, 4P 3, 4P 3, 4P
I119
Dimensions
(mm)
210
70 34.5 34.5
44 7 10
15
73.5
37
Ø13.5
Ø13.5
8
Ø8
Ø8
56 Earthleakage trip indicator
280
243
280
280
150
96
17
25
23.9
16.5
70 70 95 95
109 109
113 113
145 145
3P
Panel
cover A
Panel
cover B
Panel
cover C
3P
120I
ELCB EBS1000b
EBS1200b
(mm)
Mounting hole
Mounting hole
Auxiliary handle
Reset
Auxiliary handle
Residual current
Reset
(I n) setting
Trip test button
for earth fault
Trip test button
Residual current
(I n) setting
Trip test button
for earth fault
3P
60
3P 3P
I121
Dimensions
Bar type
C C
B
A
A
L L
D
Ø
E E E
MCCB A B C D E
Round type
C
B
A
L
B
C
C
D
Ø
E E E E E E
MCCB A B C D E
122I
Rotary handles
D
E
B
60
104 B A
C
105
43
t1.2~3.2
75
113
51
I123
Dimensions
Rotary handles
t1.2~3.2
2~3.2 2-Ø6
4-Ø5
�
B
D
E
B A
C
E-70U (400AF)
E-80U (800AF)
158.8
243
124I
Remote operation
A3
A1
A2
B2 C2 B4
11.4
B1 C1 B3
A1 A2 A3 B1 B2 B3 B4 C1 C2
I125
Technical Information
Standard accessories
The following accessories for mounting, connection and insulation are standard
items and are packed with Metasol series circuit breakers.
Fixing
screw
2P: 2EA (M4×60) 2P: 2EA (M4×60) 2P: 2EA (M4×55) 2P: 4EA (M6×100) 2P: 4EA (M6×100)
3P: 2EA (M4×60) 3P: 2EA (M4×60) 3P: 2EA (M4×55) 3P: 4EA (M6×100) 3P: 4EA (M6×100)
4P: 4EA (M4×60) 4P: 4EA (M4×60) 4P: 4EA (M4×55) 4P: 4EA (M6×100) 4P: 4EA (M6×100)
3~50A
Terminal 2P: 4EA (M5×14)
bolt 3P: 6EA (M5×14)
2P: 4EA (M8×14) 2P: 4EA (M8×20) 2P: 4EA (M10×30) 2P: 4EA (M12×35)
4P: 8EA (M5×14)
3P: 6EA (M8×14) 3P: 6EA (M8×20) 3P: 6EA (M10×30) 3P: 6EA (M12×35)
60~100A
4P: 8EA (M8×14) 4P: 8EA (M8×20) 4P: 8EA (M10×30) 4P: 8EA (M12×35)
2P: 4EA (M8×14)
3P: 6EA (M8×14)
4P: 8EA (M8×14)
Insulation
barrier
2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA
3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA
4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA
126I
Connection
[3~50A] M5 : 23 ~ 28 [3~50A]
M8 : 55 ~ 75
8.2
M5× 14
8.2
M5× 14 Ø 5.5
Ø 5.5
8.28.2
M5× 14
Ø 5.5 Ø 5.5
M5× 14
Ø 5.5
8.2
18 24 Ø≤5.5 7 Ø 5.5
≤ 11.5 11.5
7.57.5
18 24 7 7
≤ 11.5 ≤ 11.5
18 24 7 7
8.2
18 24 7 7Ø 5.5 ≤Ø11.5
5.5
7.5
18 24 7
100AF
8.2
18 24 Ø 5.5 Ø 5.5 7 7
8.2
M8× 14 Ø9
8.2
M8× 14 Ø9
≤ 11.5Ø 9 ≤ 11.5
8.28.2
Ø9
7.5
18 M8× 14 24 7 7
Ø9 Ø9
M8× 14 Ø9 ≤ 16
8.2
M8× 14 Ø9 7 ≤ 16
Ø 9
8.2
7.5
18 M8× 14 24 Ø≤916 7
7.5
18 24 ≤ 16
7 7 ≤ 16
7.57.5
18 24 ≤ 16
7 7 ≤ 16
18 24 ≤ 16 Ø9
8.2
M8× 14 7 7Ø 9 ≤ 16
7.5
18 24 7
7.5
18 24
Ø9 ≤ 16
8.2
M8× 14 Ø9 7 7
M8 : 55 ~ 75
7.5
18 24
≤ 16 ≤ 16
M8× 14 7 7
M8× 14
7.5
24
88
18
M8× 14 Ø9
Ø9
8 8
M8× 14
Ø9 Ø9
M8× 14
M8× 14 Ø9 Ø9
8
≤ 18
8
18 24 Ø9 Ø9 8 ≤Ø18
9
1010
18 24 Ø≤918 8
18 24 ≤ 18
8 8 ≤ 18
10 10
125AF M8× 14 ≤ 18
18 24 8 8 ≤ 18
8
18 24 ≤ 18 Ø9
8 8Ø 9 ≤ 18
10
18 24 8
10
M8× 14
8
18 24 Ø9 Ø9 ≤ 18
8 8
10
≤ 18 ≤ 18
18 24 8 8
10
M8× 20 Ø9
M8× 20 M8 : 80 ~ 130 Ø9
M8× 20 Ø9 Ø9
M8× 20 Ø9 Ø9
2121
M8× 20 Ø9 Ø9 ≤ 25
M8× 20 10 ≤Ø259
Ø≤ 925 10
21 21
≤ 25 10
28 10 ≤ 25
24 ≤ 25
28 24 10 10
21
≤ 25 ≤ 25
21
28 24 M8× 20 10 10Ø 9 Ø9
≤ 25
10
28 24
28 24
28 24
21
250AF M8× 20 Ø9 Ø9 ≤ 25 10
10
28 24
21
≤ 25 ≤ 25
10 10
28 24
I127
Technical Information
Connection
30 37 .5
30 37 M10× 30 .5 10
M10× 30 10 Ø
Ø
29.5
13
400AF
29.5
13
29
29
12.5
12.5
M12 : 400~500
(Terminal, Busbar)
44 M12× 35 34.5
44 M12× 35 34.5 4
Ø1 4
Ø1
44
29
44
29
800AF
11
11
10.5
10.5
128I
Safety clearance
When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars and
other protection devices installed nearby. These safety clearances are depend on the ultimate breaking capacity
and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the arc chambers
of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing or short-
circuit currents, safety clearances are required.
ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF ABN100e 50 30
ABS30c 30 25
ABS50c 40 30
ABS60c 40 30
ABS125c 50 40
ABH50c 50 40
125AF
ABH125c 100 80
ABL125c 100 80
ABN250c 100 80
ABS250c 100 80
250AF
ABH250c 100 80
ABL250c 100 80
A
ABN400c 100 80
F
ABS400c 100 80
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80
I129
Technical Information
Frame C1 (mm) C
Description
size 460V 250V (mm)
ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF ABN100e 50 30
ABS30c 30 25
ABS50c 40 30
ABS60c 40 30 The dimension of bare conduct + C1
ABS125c 50 40
ABH50c 50 40
125AF
ABH125c 100 80
ABL125c 100 80
ABN250c 100 80
ABS250c 100 80
250AF
ABH250c 100 80
ABL250c 100 80
ABN400c 100 80
C
C
C
C1
C1
C1
ABS400c 100 80
C1
C1
C1
C1
C1
C1
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80
Direct Connection Connection
connection by using a by using a
of cable crimp-type crimp-type
terminal lug terminal lug to
the extended
terminal
130I
Safety clearance
Frame D1 D2 D3 D4
Description
size (mm) (mm) (mm) (mm)
ABN50c 40 40
ABN60c 40 40
ABN100c 50 50
100AF ABN100e 50 50
ABS30c 30 30
ABS50c 40 40
ABS60c 40 40
The dimension of bare conduct + 20
ABS125c 50 50
ABH50c 50 50
125AF
ABH125c 50 50
ABL125c 50 50
ABN250c 50 50
ABS250c 50 50
250AF
ABH250c 50 50
ABL250c 50 50
D4
D3
D1
D2
I131
Technical Information
ABN50c 25 15
ABN60c 25 15
ABN100c 25 15
100AF ABN100e 25 15
ABS30c 20 15
ABS50c 25 15
ABS60c 25 15
ABS125c 25 15
ABH50c 25 15 E E
125AF
ABH125c 50 20
ABL125c 50 20
ABN250c 50 15
ABS250c 50 15
250AF
ABH250c 50 15
ABL250c 50 15
ABN400c 80 40
ABS400c 80 40
400AF
ABH400c 80 40
ABL400c 80 40
ABN800c 80 40
800AF ABS800c 80 40
ABL800c 80 40
132I
Safety clearance
ABN50c 10
ABN60c 10
ABN100c -
100AF ABN100e -
ABS30c 5
ABS50c 10
ABS60c 10
ABS125c -
ABH50c 10
125AF
ABH125c 20
ABL125c
ABN250c -
F
ABS250c -
250AF
ABH250c -
ABL250c
ABN400c 10
ABS400c 10
400AF
ABH400c 10
ABL400c 10
ABN800c 10
800AF ABS800c 10
ABL800c 10
I133
Technical Information
ABN50c 0
ABN60c 0
ABN100c 0
100AF ABN100e 0
ABS30c 0
ABS50c 0
ABS60c 0
ABS125c 0
ABH50c 0
125AF
ABH125c 0
ABL125c 0 G
ABN250c 0
ABS250c 0
250AF
ABH250c 0
ABL250c 0
ABN400c 0
ABS400c 0
400AF
ABH400c 0
ABL400c 0
ABN800c 0
800AF ABS800c 0
ABL800c 0
134I
Insulation Resistance (IR) testing & Withstand voltage testing (For ELCB)
I135
Technical information
Metasol series circuit breakers and auxiliaries comply with the following
international standard:
•IEC 60947-1
Low-voltage switchgear and controlgear - Part 1: General rules
•IEC 60947-2
Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures.
136I
Standard use environment
I137
Technical document
3 3 3 3 3 3 3 3 3
5 5 5 5 5 5 5 5 4
10 10 10 10 10 10 10 9 9
30 ABS30c
15 15 15 15 15 15 15 14 13
20 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 ABN50c, ABS50c
50 50 50 50 50 50 49 47 45
60 60 ABN60c, ABS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 ABN100c, ABN100e
100 100 100 100 100 100 97 94 91
ABH50c, ABS125c,
125 125 125 125 125 125 125 121 116 107
ABH125c, ABL125c
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
ABN250c, ABS250c,
250 200 200 200 200 200 200 193 186 171
ABH250c, ABL250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 ABN400c, ABS400c 300 300 300 300 300 295 291 287
400
350 ABH400c, ABL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
700 ABN800c, ABS800c 700 700 700 700 700 689 679 668
800
800 ABL800c 800 800 800 800 800 788 776 764
138I
Special use environment
15 15 15 15 15 15 15 15 15
30 20 EBS30c 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 EBN50c, EBS50c
50 50 50 50 50 50 49 47 45
60 60 EBN60c, EBS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 EBN100c
100 100 100 100 100 100 97 94 91
125 125 EBH50c, EBS125c, EBH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
EBN250c, EBS250c,
250 200 200 200 200 200 200 193 186 171
EBH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 246 242 238 238
300 EBN400c, EBS400c, 300 300 300 300 295 291 287 287
400
350 EBH400c, EBL400c 350 350 350 350 345 339 332 332
400 400 400 400 400 394 388 381 381
700 EBN800c, EBS800c 700 700 700 700 689 679 668 668
800
800 EBL800c 800 800 800 800 788 776 764 764
I139
Technical document
Impact of altitude
If an MCCB is used in an elevated area higher than 2000m sea level, its operating performance is subject to
dramatic drop in atmospheric pressure and temperature. For example, the air pressure is reduced to 80% of
ordinary pressure at 2,200m and further 50% at 5,500m although the short-circuit performance is not affected. If
it is used in areas of high sea level, you can do correction based on the correction parameter table in high
altitude environment, as described below
[Correction parameter table for altitude]
* Refer to the correction parameter table in high altitude Voltage Current
environment (ANSI C37. 29-1970) Altitude correction correction
1) How to correct voltage: parameter parameter
- If the rated voltage is AC 600V at 4,000m above sea level, 2,000m 1.00 1.00
600V (rated voltage) × 0.82 (correction parameter) = 492V. 3,000m 0.91 0.98
2) How to correct current: 4,000m 0.82 0.96
- If the rated voltage is AC 800A at above 4,000m sea level, 5,000m 0.73 0.94
800A (rated current) × 0.96 (correction parameter) = 768A.
6,000m 0.65 0.92
140I
Environment with vibration and impulse exercised
Vibration
The magnitude of vibration is measured by double amplitude and frequency with the following equation with
accelerator.
αg=0.002×frequency (Hz) ×double amplitude (mm)
* αg: multiple of gravitational acceleration (g=9.8m/sec2)
There are three types of vibration tests including resonance test, vibration endurance test, and malfunction test
as described below.
1) Resonant test
Alter the frequency of sinusoidal wave within the range of 0~55Hz gradually with 0.5~1mm of double
amplitude applied to see if there is any occurrence of vibration on a specific part of MCCB.
2) Vibration endurance test
A sinusoidal wave with double amplitude of 0.5~1mm and frequency of 55Hz (resonant frequency obtained
in previous clause if there is a resonant point) is manually created to check the operational status.
3) Malfunction test
Apply vibration for 10 minutes for each condition of altering double amplitude and frequency to check if there
is any malfunction in MCCB.
Impulse
The magnitude of impulse is denoted by the multiple of gravitational acceleration imposed on the equipment
and part. The test is conducted through a drop impulse test.
I141
Technical document
Top-down Top-down On On
On On
Line Connection
Line Connection Picture 3 Picture34
Picture Picture 4
Status of (1) Non-conduction (On or Off status) Non-conduction (On or Off status)
MCCB (2) Status where rated current is conducted
until the temperature of MCCB becomes
constant and keeps being conducted
Test Judgment ● If it is On, it should not be Off
must be normal
142I
Cerfications
MCCB ELCB
Type Approvals Certificates Type Approvals Certificates Type Approvals Certificates
Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA
ABS52c ● ● ● ABN204c ● ● ●
EBS54c ● ● ●
ABS53c ● ● ● ABS202c ● ● ●
EBN63c ● ● ●
ABS54c ● ● ● ABS203c ● ● ●
ABN62c ABS204c EBS63c ● ● ●
● ● ● ● ● ●
ABN63c ● ● ● ABP202c ● ● ● EBS64c ● ● ●
● ● ● ● ● ●
ELCB 30~250AF
ABN64d ● ● ● ABN603c ● ●
EBH53c ● ● ●
ABS62d ● ● ● ABN604c ● ●
EBH54c ● ● ●
ABS63d ● ● ● ABS602c ● ●
EBS103c ● ● ●
ABS64d ● ● ● ABS603c ● ●
ABN102d ● ● ● ABS604c ● ● EBS104c ● ● ●
ABP103c ● ● ● EBH204c ● ● ●
Note: ● (Completion)
I143
Safety Instructions
•For your safety, please read user's manual thoroughly before operating.
•Contact the nearest authorized service facility for examination, repair, or adjustment.
•Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
•Any maintenance and inspection shall be performed by the personnel having expertise concerned.
2017. 10 ⓒ 2009.10 LSIS Co.,Ltd. All rights reserved. / (22) 2017. 10 Human Power