Supply Fan Control For Constant Air Volume Air Handling Units
Supply Fan Control For Constant Air Volume Air Handling Units
Supply Fan Control for Constant Air Volume Air Handling Units
1
Table of Contents
Building and Facility information Figure 2 shows a schematic diagram for the
section plan of Building III. Each AHU serves each
The applied building complex, located in Omaha, floor. There is no terminal box and modulating damper.
Nebraska, was built in the late 1960s and composed of Each zone has reheat coils to maintain room air
building III, II and I. The 12-story building III, 8-story temperature for unequal loading. The AHU schematic
building II and 4-story building I are used as an office diagram is shown in Figure 3.
building complex with total area of 489,000 square
feet, which is served by AHUs with VFD. Each system Return Mechanic
Air
is a typical multi-zone CV system without terminal box. room
AHU 8
AHU 14A AHU 7A retrofit effort. The following is the procedure for the
AHU 14B AHU 7B optimal supply fan speed.
Building II
AHU 2A AHU 3A Interior zone
Interior zone load profile in an office building is
AHU 4A
AHU 4B
AHU 3B
AHU 2B normally not too variable because there is no influence
AHU 3C
AHU 2C on the outside air conditions and similar heat gains.
Building I Cooling load for interior zones considers total sensible
AHU 1A
cooling load due to heat gains by people, lighting and
office equipment conditioned spaces.
The supply fan speed for interior zone is typically
AHU 1B
optimized to be the following:
Figure 1. AHUs serving area layout
! Identify the maximum load ratio for the AHU
To identify the building load ratio for an AHU,
Relief Fan Relief air
room air temperature, supply air temperature and
H H H H
discharge air temperature should be measured daily.
LEVEL 11
After measuring room conditions of each floor, choose
H H H H
LEVEL 10 the highest (zone B) and lowest load zone (zone A) of
LEVEL 9
H H H H
each zone as shown in Figure 4. The building load ratio
H H H H can be calculated by the following equation:
LEVEL 8
Tr − TDA
LEVEL 7
H H H H
α= (1)
LEVEL 6
H H H H Tr − TSA
Return air shaft
H H H H 80
LEVEL 5
Tr (zone A )
H H H H 75
LEVEL 4
Temperature (F)
Tr (zone B)
H H H H 70
LEVEL 3
TDA (zone A)
H H H H 65
LEVEL 2
H H H H 60
LEVEL 1 TDA (zone B)
H H H H
55
PLAZA
LEVEL TSA
50
LOWER AHU 7B Return AHU 8
AHU 6 AHU 7A
LEVEL air 8:00 9:30 11:00 12:30 14:00 15:30 17:00
Time
Figure 2. Section plan of the East of Building III
Figure 4. Measured data for building load ratio
2
Table of Contents
0.6
temperatures from 40°F to 100°F. During heating
period, the fan speed has minimum fan speed like
0.4
terminal box minimum airflow ratio.
If the system works continuously 24 hours and 7
0.2
Minimum load ratio (zone A) days, the fan speed will have 3 different modes:
0.0
occupied hours at weekday daytime, unoccupied hours
8:00 9:30 11:00 12:30 14:00 15:30 17:00 at weekend daytime and unoccupied hours at weekday
Time night time. VFD speed was modulated to maintain the
Figure 5. Calculated zone load ratio graph supply fan speed at its set point. Figure 7 shows the
determined supply fan speed ratio with 3 different
! Develop/implement the optimal fan speed modes.
100
Develop the supply fan speed set point based on
the previous maximum load ratio and modulate the 80
Supply fan speed(%)
speed
0.4
! Implement the optimal fan speed
0.2 Implement the supply fan speed set point based
on the pervious determined set point. Also, measure
0.0 the room air condition to verify this control. Figure 8
8:00 9:30 11:00 12:30 14:00 15:30 17:00
shows the trending data for the supply fan speed and
Time
outside air temperature.
Figure 6. Determined fan speed ratio
3
Table of Contents
100 75.0
90
72.5 PLF
Supply fan speed(%)
80 2F
70 70.0
Temperature(F)
3F
60 67.5 4F
50 5F
40 65.0
6F
30 62.5 7F
20 8F
10 60.0
10F
0 57.5 11F
50 60 70 80 90 100
Outside air temperature(F) 55.0
6:00 8:00 10:00 12:00 14:00 16:00 18:00
Figure 8. Supply fan speed and outside air temperature Time
trend
Figure 10. Discharge temperature graph of optimal
supply fan control
Results and discussions
After applying the optimal supply fan control The reheat energy savings can be considered as the
sequence in real buildings, the energy consumption and reheat energy consumption required to heat the reduced
room conditions were measured and analyzed. airflow from the discharge air temperature to the room
temperature. The reheating coil energy consumption
Energy consumption in the actual system can be estimated based on the equation (2).
! Interior zone
Room, supply and discharge air temperature were •
measured with a data-logger to compare the thermal ∆E rh = m⋅ C p ⋅ (α fixed − α dynamic ) ⋅ (TDA − Tr ) (2)
energy consumption. The results show room and
supply air temperature are similar but discharge air From previous measured room condition data, the
temperature is different for each area served. Figures 9 reheat energy consumption is 6,947,892 Btu/hr when
and 10 show the discharge air temperature graphs of there is fixed VFD speed, as shown in Table 1 and
existing and optimal supply fan control. Two figures Figure 11. On the other hand, the energy consumption
show each floor has a similar trend but different is 3,896,493 Btu/hr when there is dynamic VFD speed.
discharge temperature to maintain room air The thermal energy consumption of dynamic VFD
temperature by adjusting reheating coil. Each floor speed is less than that of the fixed VFD speed by 44 %.
discharge temperature shows that there is unnecessary Therefore, when the supply fan speed control is
reheat energy from supply air condition to maintain optimized, thermal energy can be reduced.
room air temperature, even the 8th floor, and also
wastes a fan power energy. After implementing a Table 1. Comparison data of thermal energy
dynamic VFD speed, the discharge air temperature has consumption
Fixed VFD Dynamic VFD Energy
a lower than fixed VFD speed as shown in Figure 9 Floor
speed (Btu/hr) speed (Btu/hr) saving (%)
and 10. The discharge air temperature is reduced and
reheating energy should also be saved by dynamic PLF 784,891 502,611 36.0
VFD speed. 2nd 680,100 350,993 48.4
75.0 rd
3 527,329 163,780 68.9
72.5 PLF
4th 799,420 551,056 31.1
2F
70.0 5th 693,341 344,032 50.4
Temperature(F)
3F
67.5 4F th
5F
6 720,195 467,998 35.0
65.0 6F th
7 624,738 429,354 31.3
62.5 7F
th
8F 8 458,972 81,093 82.3
60.0
10F
10th 822,660 599,766 27.1
57.5 11F
55.0
11th 836,246 405,810 51.5
6:00 8:00 10:00 12:00 14:00 16:00 18:00 Total 6,947,892 3,896,493 43.9
Time
Figure 9. Discharge temperature graph of existing
supply fan control
4
Table of Contents
! Exterior zone
In the exterior zone, before installing VFD, the
supply fan power was 5796.0 kWh per week. After
installing VFD on the supply fan, the supply fan speed
set point was 90%(21.0 kW) of the design speed. The
supply fan power was 3528.0 kWh per week. After
implementing optimal speed, the supply fan power was
1426.1 kWh per week. Figure 13 shows the trend data
for supply fan speed and fan power after
implementation of the new control sequence for the
exterior zone. The fan power savings is 39% after
installing VFD and 75% after dynamic VFD speed. In
addition, the discharge air temperature and airflow are
reduced and then reheating energy should also be saved
Figure 11. Comparison graph of the thermal energy by dynamic VFD speed.
consumption
90 100
fan speed is reset based on the maximum zone load. Figure 13. Supply fan speed and power trend graph for
Figure 12 shows the trended data for the supply fan exterior zone
speed for the interior zone. The supply fan power was
1013.6 kWh per week. The supply fan speed was Evaluation of thermal performance
reduced significantly. The decrease of fan speed results To verify the interior zone condition, select the
in major fan power and zone reheating coil energy furthest zone (11th floor) from AHU and highest load
savings. The fan power savings is 29% after installing zone (8th floor). Exterior zone chooses the furthest zone
VFD and 60% after dynamic VFD speed. The system (11th floor). The range of the room air temperatures is
can be operated continuously without frequent speed 72.4°F ~ 73.8°F during occupied hour, as shown in
adjustment by the building operator. Figure 14. After implementing dynamic VFD speed,
the room air temperature is able to maintain the set
90.0 90.0 point and did not result in comfort issues. Therefore, it
80.0
Supply fan speed
(Dynamic speed )
80.0 is assumed that there is proper and stable room air
70.0 70.0
temperature control.
Measurement of CO2 in occupied spaces has
Supply fan power(kW)
Supply fan speed(%)
60.0 60.0
Fan power
been widely used to evaluate the amount of outdoor air
50.0 50.0
(Without VFD)
: 36.2 kW
supplied to indoor spaces. The average CO2 level on
40.0
Fan power (With VFD)
40.0 each floor was in the range of 400 ~ 500 ppm when the
30.0
: 25.7 kW
30.0 average outdoor air concentration was 320 ppm.
Fan power
20.0
(Dynamic speed )
20.0
According to ASHRAE Standard 62, comfort criteria
are likely to be satisfied if the ventilation results in
10.0 10.0
indoor CO2 concentrations less than 700 ppm above the
0.0 0.0
Mon.
8-7-06 8-8-06
Tue. Wed. Thr. Fri. Sat. Sun.
8-9-06 8-10-06 8-11-06 8-12-06 8-13-06 8-14-06
outdoor air concentration, which is representative of
0:00 0:00 0:00 0:00 0:00 0:00 0:00 0:00 delivery rates of outside air. Therefore, it is judged that
Time
any IAQ problems due to reduction of the airflow will
Figure 12. Supply fan speed and power trend graph for not happen.
interior zone
5
Table of Contents
75.0
[2] ASHRAE, 1992, ASHRAE Standard 55-1992,
Thermal environmental conditions for human
74.5
occupancy.
Interior zone (11th FL)
Temperature (F)
Conclusions
NOMENCLATURE
c p - specific heat capacity, Btu/lbm °F
•
m - mass flow rate, lbm/hr
Tr - room dry bulb temperature, °F
TSA - supply dry bulb temperature, °F
TDA - Discharge dry bulb temperature, °F
α - Building load ratio, %
α fixed - fixed airflow
α dynamic - dynamic airflow
References