Power System Stability
Power System Stability
E
o Restrict the bus voltages close to their nominal values
jXgI
o Ensure phase angles between two buses are not too
Ut
large
o check for overloading of the power equipment and IZline
transmission lines. U
Steady-state stability is assessed by load flow studies
I
Transient Stability involves the study of the power
system following a major disturbance e.g. system faults, E U 0
I
sudden load changes, loss of generating units, line Z
switching etc E( ) U
Following a large disturbance, the synchronous Z Z
machine power (load) angle changes due to sudden Apparent power at the infinite bus S U I *
acceleration of the rotor shaft. Real power P ReU I *
3 6
1
Observations
U . E( ) U 2 1. It is not necessarily desirable to have total line
P Re
Z Z
compensation – series capacitor
2. Power can only be transferred if the line has some
U . E cos( ) U cos
2
reactance P = 0 for X = 0
Z Z Z
X
Let = 90 - For a lossless line (R = 0 and = 90)
U . E cos(90 ) U cos 90
2
R U . E sin
P P Power transferred to the infinite bus
Z Z X
The steady-state stability limit is given by
U . E sin( ) U sin
2
U .E
Z Z Pmax
X
Maximum power transfer occurs when + = 90 or If the load increases beyond Pmax, increases but P
= 90 - where depends on the line impedance decreases
The system is stable only if increases when P increases
i.e. dP/d is positive -90 < < 90
77 10
U . E U 2 sin
Pmax ……………………….… (1)
Z Z
R
sin and Z R2 X 2 …………………… (2)
Z
88 1111
Under no-load condition, I = 0, E = U = 0 the Pmax can be increased by increasing E and/or U and
rotor and the stator fluxes are coincident reducing X
Higher excitation voltages and fast response excitation
When the machine is loaded, the rotor flux leads the
stator flux by systems substantially increase the steady-state limit
Higher line voltage – increases transmission system
On no-load
capability
U2 U 2 .R 1 R Methods of reducing the reactance
Pmax U2 2 2 1. Use of double-circuit line
R X
2 2 R2 X 2 R2 X 2 R X
2. Use of bundled conductors
The optimum value of X is obtained from dPmax/dX = 0 3. Series compensation of the line reactance – optimum
value X = 3.R
X = 3.R
4. Use of synchronous phase modifiers – installed in
intermediate substations to increase power limit
5. Use machines with low impedance
9 1212
2
Transient stability Assumptions made in transient stability studies
If one string is suddenly cut, this will result in transient 1. The swing equation/curve method
oscillations in the coupled strings and all the weights will The variation of load angle with time is considered
wobble after an occurrence of a disturbance
The coupled system may settle down to a new steady state When a disturbance occurs, the machine will accelerate
or one or more additional strings may cut, resulting in a or decelerate depending on whether Pe < Pm or Pe > Pm
chain reaction in which more strings may break forcing a
This involves changing the load angle from 0 to 1 as
system collapse
shown below
In a similar way, in an interconnected power network, the Stability will depend on whether will continue to
tripping of a transmission line may cause a catastrophic increase or decrease or whether it will stabilize at a new
failure in which a large number of generators are lost value after some oscillations
forcing a blackout in a large area.
14 17
15 1818
3
Derivation of the swing equation If is the angular position of the rotor in electrical radians
w.r.t. a synchronously rotating reference and 0 is its value
Under steady state conditions, Te = Tm and Ta=0 the
at t = 0,
machine runs at synchronous speed Ns rpm
= rt - 0t + 0 (electrical radians)
However, when there is an imbalance between the torques So that
acting on the rotor, there is a net torque Ta that causes the
d
rotor to accelerate or decelerate r 0 r (electrical rad/s)
dt
Ta = Tm – Te ……………………………….… (3) d 2 dr d r
(electrical rad/s2)
Where dt 2 dt dt
Tm Prime mover torque less mechanical losses in Nm dr ( pu ) d r ( pu )
0 0
Te electromagnetic torque developed in Nm dt dt
Tm is assumed to be constant because the action of the Equation (7) can be re-written as
governor is ignored 2 H d 2
Tm Te Per unit swing equation
0 dt 2
19 2222
Quantity
Substituting (5) for J in (4) gives
2H dm
VA Tm Te Length
02m base dt
Mass
Re-arranging
d m T T Velocity
m e …………………….… (6)
dt 0 m VAbase 0 m
2H
Acceleration
2121 2424
4
2. Equal area criterion
The principle of the method involves comparison of Consider the energy injected during acceleration
energies injected into the system during acceleration and 1
1 1
W1 Ta d
a
the energy absorbed during deceleration P d
If the two balance, then stability is assumed 0 0
W1 K1 A1
25 28
The generating unit is initially operating in steady state at During deceleration, the energy absorbed is given by
Pe = Pm = Pm0 and = 0 2
1 2
If Pm is increased from Pm0 to Pm1, the machine will W2 Ta d Pa d
1
1
accelerate (since Pm > Pe) towards a new steady state load
where Pa Pe Pm1
angle
However, due to the inertia of the machine, it will W2 K1 A2
overshoot this new angle If the system is to remain stable, the W1 = W2 A1 = A2
When = 1, Pe = Pm1, and the acceleration is zero, 2
26 29
stabilise at 1 2 2 …………...…(2)
dt dt
But
dt dt
If exceeds 3, Pm > Pe and the rotor accelerates again
Substituting (2) in (1) gives
causing further increase in and the system looses
H d d d
2
stability Pa ………………………(3)
0 dt dt dt
Pm > Pe for 0 < < 1 and the rotor accelerates whereas
Pm < Pe for 1 < < 2 and the rotor decelerates Multiplying (3) by dt gives and integrating from 0 to
A1 is the accelerating area and A2 is the decelerating area 2
d H d
2
H
0 dt
d dt Pa d
Equal-area criterion states that A1 = A2 0 dt 0
0 0
27 30
5
At = 0, d/dt = 0; at = 2, d/dt = 0
2
A2
Pa d 0
0
where Pa Pm Pe
1 2
A1
Pm Pe d Pm Pe d 0
0 1
1 2
P
0
m Pe d Pe Pm d
1 1 0
A1 = Pm Pe 2 d Pm ( 1 0 )
0
In power systems, sudden changes in mechanical power
2 2
EU sin
A 2 = Pe 3 Pm d
are unusual Pm d
1
Sudden changes in electrical power do occur e.g. system 1
Xe3
faults, line switching 2
EU sin
For stability Pm ( 1 0 ) Pm d
1
31 X
34 e 3
X X U0
X X
EU sin X X
where X e1 X g 1 2
Pe1 X1 X 2
X e1 X‘1
Pe2 = 0
E
After the fault U0 E U0
X‘2 X3Y X'3 X‘2 X‘3
U . E sin where X e 3 X g X1
Pe 3
Xe3
33 36
6
After the fault
U . E sin where X e 3 X g X1
Pe 3 For any system, there is a maximum allowable clearing
Xe3
angle if stability is to be maintained
1 1
EU sin
A1 = Pm Pe 2 d Pm d This angle is called the critical clearing angle (CCA)
0 0
X e 2
The time corresponding to critical clearing angle is called
2 2
EU sin the critical clearing time (CCT) i.e. this is the longest fault
A 2 = Pe 3 Pm d Pm d duration allowable for stability to be maintained after a
1
1
Xe3
fault
The CCT is determined from the swing curve
For stability
1 2 Under certain circumstances, it is possible to determine
EU sin EU sin
Pm X e 2 d X e 3 Pm d the CCT power-angle characteristics of the system
0 1
CCT can also be evaluated using the equal area criterion
method in which 1 = cr and 2 = max
37 40
EU
At = 0, Pm = Pe1(max)sin0 where Pe1(max)
X e1
A2
A1 P
0 sin 1 m
Pe1(max)
38 41
cr can be evaluated from the above equation since it is the only
unknown.
39 42
7
Calculation of critical clearing time Solution
j0.4
Infinite bus
CCT can only be calculated from power transfer curves X X
j0.2
if there is no power transfer during a fault (Pe2 = 0 and Pa j0.4
= Pm – Pe2 = constant - irrespective of the load angle) X'd = j0.2
X X 1.00
Under any other operating condition, the CCT can only 3- fault
be obtained from the swing curves (Pe2 0 and Pa = Pm –
Pe2 constant; Pa = f())
For the case when Pe2 = 0
Xe1 = j(0.2+0.2+0.4//0.4) = j0.6 pu
43 46
Pre-fault power
EU sin 1.0 1.44
Integrating (1) gives Pe1 sin 2.4sin
X e1 0.6
d 0t
…………………..…(2)
dt 0 2 H m
P dt 0 Pm t At = 0, Pe1 = Pm = 1.0 pu
2H
Pe1 2.4sin 0 1.0
Further integration of (2) yields 0 24.6 0.43 rad
0 Pm t 2
0 During the fault
4H
j0.4 j0.4
Pt 2
At = cr, t = tcr cr 0 0 m cr
j0.1 j0.1
4H
tcr
cr 0 4H E
U0
0 Pm j0.2 j0.05 j0.2
44 47
Example 1 j1.6
j1.6
j0.4
A generator is connected to an infinite bus through a j0.1 j0.1
8
Read on the following sub-topics
cr cr
A1 = Pm Pe 2 d 1.0 0.9sin d Role of automatic voltage regulator in
0 0.43 improving stability
= cr 0.9cos cr 1.25 Effect of grounding on stability
max 2.55
prevention of steady state pull out
A2 =
P e3 Pm d 1.8sin 1.0d
1
cr
= cr 1.8cos cr 1.06
For stability A1 = A2
cr 0.9cos cr 1.25 cr 1.8cos cr 1.06
cr 1.78 rad 102
49 52
50