Electrical System Design Analysis: Hernan / Grace Guillena Lot 2, Blk. 8, Southside Subdivision, Sum-Ag, Bacolod City
Electrical System Design Analysis: Hernan / Grace Guillena Lot 2, Blk. 8, Southside Subdivision, Sum-Ag, Bacolod City
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
PROJECT NAME : TWO (2) STOREY, TWO (2) BEDROOM RESIDENCE
OBJECTIVES :
● To provide design load analysis & establish proper
size/capacity of feeder and service entrance conductors
and equipment.
● Identify fault (short circuit) level at each bus for proper
sizing of the interrupting capacity of circuit breakers.
● Evaluate loading & feeder conductor sizes to ensure that
the voltage drop is within tolerable level thereby ensuring
good quality of power delivered to circuit loads.
PARAMETERS :
● Allowable Voltage drop at the farthest load point- <5%
● Supply Transformer is 1- 50KVA, 7620/120/240V, Z = 1.50%
● Nominal Voltage is 230V, at 80% power factor
It = (5,600 + 0.25*2000)/230
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
= 26.52 amps
It = 30 + (3600/230)
= 45.65 amps
Multiplier = 1/(1+1.5587)
= 0.3908
Short circuit current at the Load Side of the Main Distribution Panel
ISC-transformer = (14,489)*(0.3908)
= 5,662.3 amperes
Therefore:
Considering fault impedance, the Main Circuit Breaker shall have a
minimum kAIC rating of 10 kA.
All downstream circuit breakers shall have a kAIC rating of 10kA.
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
VOLTAGE DROP CALCULATION:
Total Voltage Drop from source to the farthest load of the system.
Since the %V.D. < 5%, therefore the conductors are adequately sized.
Prepared by :
NOEL P. GARBO
Professional Electrical Engineer
PRC No. 2881 – 2021
PTR No. 7542223 dated January 11, 2019
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA