- This document provides an electrical design analysis for a two-story, two-bedroom residential house for Hernan and Grace Guillena. - It calculates branch circuit loads and sizes conductors accordingly, sizes the main distribution panel board and protective equipment, calculates short circuit currents and voltage drops. - The main findings are that a 80A, 250V, 10kA circuit breaker is required for the main service equipment, and the voltage drop is within acceptable limits of less than 5% at the farthest load point.

Uploaded by

harold de guzman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
989 views5 pages

Electrical System Design Analysis: Hernan / Grace Guillena Lot 2, Blk. 8, Southside Subdivision, Sum-Ag, Bacolod City

- This document provides an electrical design analysis for a two-story, two-bedroom residential house for Hernan and Grace Guillena. - It calculates branch circuit loads and sizes conductors accordingly, sizes the main distribution panel board and protective equipment, calculates short circuit currents and voltage drops. - The main findings are that a 80A, 250V, 10kA circuit breaker is required for the main service equipment, and the voltage drop is within acceptable limits of less than 5% at the farthest load point.

Uploaded by

harold de guzman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

ELECTRICAL SYSTEM DESIGN ANALYSIS

HERNAN / GRACE GUILLENA


Lot 2, Blk. 8, Southside Subdivision, Sum-ag, Bacolod City

---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
PROJECT NAME : TWO (2) STOREY, TWO (2) BEDROOM RESIDENCE

OWNER : Hernan / Grace Guillena

LOCATION : Lot 2, Blk. 8, Southside Subdivision, Brgy. Sum-ag, Bacolod City

SUBJECT : Electrical Design Analysis in compliance with the requirements of


Section 1301 of the National Building Code and DPWH
Memorandum Circular No. 2 Series of 2015

OBJECTIVES :
● To provide design load analysis & establish proper
size/capacity of feeder and service entrance conductors
and equipment.
● Identify fault (short circuit) level at each bus for proper
sizing of the interrupting capacity of circuit breakers.
● Evaluate loading & feeder conductor sizes to ensure that
the voltage drop is within tolerable level thereby ensuring
good quality of power delivered to circuit loads.

REFERENCES : Philippine Electrical Code (latest edition)


Electrical Pllan Review (Cooper)

PARAMETERS :
● Allowable Voltage drop at the farthest load point- <5%
● Supply Transformer is 1- 50KVA, 7620/120/240V, Z = 1.50%
● Nominal Voltage is 230V, at 80% power factor

BRANCH CIRCUIT CALCULATIONS:

Circuit No. 1 : 17 Lighting Outlet


It = 1700*(1.25)/230
= 9.24 Amps.
Use: 2 No. 3.5mm2 THHN copper conductor inside a 15 mm dia. uPVC pipe
With 1-20A, 250V, 10kAic, molded case circuit breaker

Circuit No. 2 : 14 Lighting Outlets


It = 1400*(1.25)/230
= 7.61 amps.
Use: 2 No. 3.5mm2 THHN copper conductor inside a 15 mm dia. uPVC pipe
With 1-20A, 250V, 10kAic, molded case circuit breaker

Circuit No. 3 : 6 Convenience Outlet


It = 1080*(1.25)/230
= 5.87 amps.
Use: 2 No. 3.5mm2 THHN copper conductor inside a 15 mm dia. uPVC pipe
With 1-30A, 250V, 10kAic, molded case circuit breaker
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
Circuit No. 4 : 9 Convenience Outlet
It = 1620*(1.25)/230
= 8.80 amps.
Use: 2 No. 3.5mm2 THHN copper conductor inside a 15 mm dia. uPVC pipe
With 1-30A, 250V, 10kAic, molded case circuit breaker

Circuit No. 5 : 2 Air Con Outlets


It = 2000*(1.25)/230
= 10.81 amps.
Use: 2 No. 5.5mm2 THHN as phase conductor and 1-2.0mm2 THHN as ground
conductor inside a 20 mm dia. uPVC pipe
With 1-30A, 250V, 10kAic, molded case circuit breaker

Circuit No. 6 : 3 Water pump Outlet


It = 1800*(1.25)/230
= 9.78 amps.
Use: 2 No. 5.5mm2 THHN as phase conductor and 1-2.0mm2 THHN as ground
conductor inside a 20 mm dia. uPVC pipe
With 1-30A, 250V, 10kAic, molded case circuit breaker

Circuit No. 7 : 1 Spare Circuit


It = 1800*(1.25)/230
= 9.78 amps.
Use: 2 No. 5.5mm2 THHN as phase conductor and 1-2.0mm2 THHN as ground
conductor inside a 20 mm dia. uPVC pipe
With 1-30A, 250V, 10kAic, molded case circuit breaker

Circuit No. 8 : 1 Spare Circuit


It = 1800*(1.25)/230
= 9.78 amps.
Use: 2 No. 5.5mm2 THHN as phase conductor and 1-2.0mm2 THHN as ground
conductor inside a 20 mm dia. uPVC pipe
With 1-30A, 250V, 10kAic, molded case circuit breaker

MAIN DISTRIBUTION PANEL BOARD CONDUCTOR & PROTECTIVE EQUIPMENT:

Total Computed Current,

Lighting and Small Appliance Load = 75 m2 * 24va/m2


= 1,800 volt-ampere
Water Pump loads = 1,800 volt-ampere
Air-Con Load = 2,000 volt-ampere
-------------------------------
Total Computed Load = 5,600 volt-ampere

It = (5,600 + 0.25*2000)/230
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
= 26.52 amps

Service Entrance Conductor:

Considering future loads and spare circuit,


Use 2 -22mm2 THHN as main service drop wire
+ 1- 8.0mm2 THW wire as Grounding Electrode Conductor in
25 mm dia. RSC pipe

Main Service Equipment:

It = 30 + (3600/230)
= 45.65 amps

1 - 80A, 250v, 10 kAIC, Molded Case Circuit Breaker

SHORT CIRCUIT CALCULATION :

Transformer Ifull load = (50)*(1000)/(230)


= 217.39 amperes

Transformer Multiplier = 100/1.5


= 66.66

Let-through Short circuit current


ISCA = (217.39)*(66.66)
= 14,489 amperes

f(transformer) = (2)*(30)*(14,489)/[2425 * 1 * 230]


= 1.5587

Multiplier = 1/(1+1.5587)
= 0.3908

Short circuit current at the Load Side of the Main Distribution Panel

ISC-transformer = (14,489)*(0.3908)
= 5,662.3 amperes

Therefore:
Considering fault impedance, the Main Circuit Breaker shall have a
minimum kAIC rating of 10 kA.
All downstream circuit breakers shall have a kAIC rating of 10kA.

---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA
VOLTAGE DROP CALCULATION:

Voltage at Transformer Secondary = 240 volts

Voltage Drop at the Terminal of Main Circuit Breaker

V.D. (Main CB) = (30)*(26.52)*(860)/1000000


= 0.6842 volts

Voltage Drop at the farthest Panel Board ( Circuit No. 5)

Circuit No. 5 (load = 8.70 Amp)

V.D. (@ Last L.O.) = (40)*(8.70)*(1995)/1000000


= 0.6943 volts

Total Voltage Drop from source to the farthest load of the system.

Voltage Droptotal = 0.6842 + 0.6943


= 1.3785 volts

Percent Voltage Drop = (1.3785)(100)/230


= 0.599%

Since the %V.D. < 5%, therefore the conductors are adequately sized.

Prepared by :

NOEL P. GARBO
Professional Electrical Engineer
PRC No. 2881 – 2021
PTR No. 7542223 dated January 11, 2019

---------------------------------------------------------------------------------------------------------------------------------------------------------------------
This Design Analysis is prepared for the residential house of HERNAN / GRACE GUILLENA