Three Phase Transformer
Three Phase Transformer
Three phase transformers are used to step-up or step-down the high voltages in
various stages of power transmission system. The power generated at various
generating stations is in three phase nature and the voltages are in the range of
13.2KV or 22KV. In order to reduce the power loss to the distribution end, the
power is transmitted at somewhat higher voltages like 132 or 400KV. Hence, for
transmission of the power at higher voltages, three phase step-up transformer is
used to increase the voltage. Also at the end of the transmission or distribution,
these high voltages are step-down to levels of 6600, 400, 230 volts, etc. For this, a
three phase step down transformer is used.
A three phase transformer can be built in two ways; a bank of three single
phase transformers or single unit of three phase transformer.
Instead of using three single phase transformers, a three phase bank can be
constructed with a single three phase transformer consisting of six windings on a
common multi-legged core. Due to this single unit, weight as well as the cost is
reduced as compared to three units of the same rating and also windings, the
amount of iron in the core and insulation materials are saved. Space required to
install a single unit is less compared with three unit bank. But the only
disadvantage with single unit three phase transformer is if the fault occurs in any
one of the phase, then entire unit must be removed from the service.
A three phase transformer can be constructed by using common magnetic core for
both primary and secondary windings. As we discussed in the case of single phase
transformers, construction can be core type or shell type. So for a bank of three
phase core type transformer, three core type single phase transformers are
combined. Similarly, a bank of three phase shell type transformer is get by
properly combining three shell type single phase transformers. In a shell type
transformer, EI laminated core surrounds the coils whereas in core type coil
surrounds the core.
In core type three phase transformer, core is made up of three limbs or legs and
two yokes. The magnetic path is formed between these yokes and limbs. On each
limb both primary and secondary windings are wounded concentrically. Circular
cylindrical coils are used as the windings for this type of transformer. The primary
and secondary windings of one phase are wounded on one leg. Under balanced
condition, the magnetic flux in each phase of the leg adds up to zero. Therefore,
under normal conditions, no return leg is needed. But in case of unbalanced loads,
high circulating current flows and hence it may be best to use three single phase
transformers.
Shell Type Construction
In shell type, three phases are more independent because each phase has
independent magnetic circuit compared with core type transformer. The
construction is similar to the single phase shell type transformer built on top of
another. The magnetic circuits of this type of transformer are in parallel. Due to
this, the saturation effects in common magnetic paths are neglected. However,
shell type constructed transformers are rarely used in practice.
Consider the below figure in which the primary of the transformer is connected in
star fashion on the cores. For simplicity, only primary winding is shown in the
figure which is connected across the three phase AC supply. The three cores are
arranged at an angle of 120 degrees to each other. The empty leg of each core is
combined in such that they form center leg as shown in figure.
When the primary is excited with the three phase supply source, the currents IR, IY
and IB are starts flowing through individual phase windings. These currents
produce the magnetic fluxes ΦR, ΦY and ΦB in the respective cores. Since the
center leg is common for all the cores, the sum of all three fluxes are carried by it.
In three phase system, at any instant the vector sum of all the currents is zero. In
turn, at the instant the sum of all the fluxes is same. Hence, the center leg doesn’t
carry any flux at any instant. So even if the center leg is removed it makes no
difference in other conditions of the transformer.
Likewise, in three phase system where any two conductors acts as return for the
current in third conductor, any two legs acts as a return path of the flux for the
third leg if the center leg is removed in case of three phase transformer. Therefore,
while designing the three phase transformer, this principle is used.
These fluxes induce the secondary EMFs in respective phase such that they
maintain their phase angle between them. These EMFs drives the currents in the
secondary and hence to the load. Depends on the type of connection used and
number of turns on each phase, the voltage induced will be varied for obtaining
step-up or step-down of voltages.
Star-delta
Delta-star
Delta-delta
Star-star
Star – Delta Connection
Delta-delta
This type of connection is used when the supply source is delta connected
and the secondary load needs single voltage with high current. This is
generally employed for three phase power loads (like three phase motor).
In this, both primary and secondary windings are connected in delta fashion.
The voltage across the load is equal to the secondary voltage and voltage
across the primary winding is equal to source voltage. In this, the current
flow through the load will be 1.732 times the secondary current and the
feeder current will equal to the 1.732 times current through the primary
winding. Due to these high supply and load currents, it is recommended to
place transformer much closer to both source and load circuits.
In this, there exists no phase difference between the primary and secondary
voltages.
The three phase voltages remains constant even with unbalanced load, thus
allows unbalanced loading.
The main advantage of this connection is if the one transformer is defective
or removed for service (open delta connection), then remaining two
transformers continue to deliver thee phase power at reduced load capacity.
Star – Star Connection
In this, both primary and secondary windings are connected in star fashion
and also there exist no phase difference between the primary and secondary
voltages.
In this, current flowing through both primary and secondary windings are
equal to the currents of the lines to which they are connected (supply source
and load). And voltages between line phases on either end equal to 1.732
times respective winding voltages.
Due to neutral availability, it is well suited for three phase four wire system.
This type connection satisfactorily works if the load is balanced. But if the
load is unbalanced, the neutral point shift causes unequal phase voltages.
Large third harmonic voltages would appear in both primary and secondary
windings without the neutral tie. This may lead to the insulation failures.
This connection considerably generates interference with communication
lines and hence with this connection configuration, telephone lines cannot
be run in parallel.
Due to these disadvantages, the star-star connection is rarely used and not
employed in practice.
In case of fault or loss of one phase results to the complete unit shut down. This is
because in three phase transformer, a common core is shared for all three units. If
one unit is defective, the core of this defective unit would immediately saturate
because the absence of an opposing magnetic field. This causes the greater escape
of magnetic flux to the metal enclosures from the core. This further raises the
heating of the metallic parts and in some cases this heat would enough to cause to
fires. Therefore, a three phase transformer (or entire unit) must be shut down if any
one phase is defective.