Module 3: Sequence Components and Fault Analysis: Sequence Modeling (Tutorial)
Module 3: Sequence Components and Fault Analysis: Sequence Modeling (Tutorial)
Objectives
In this lecture we will solve tutorial problems on fault analysis in sequence domain
Fig 13.1 shows the single line diagram of a 13.8kV system connected to a 480V bus through a
1.
13.8kV/480V
transformer. Two motor loads of 400hp and 600hp are connected to the bus through three parallel three
core copper cables. If a 3 phase bolted fault occurs at , compute the fault currents. Repeat the
calculations for fault at .
Ans: Let us take base power as 1000kVA and base voltage as 480V.
Base impedance
ratio = 15
or
1. i.e.
Ans:
Cable Modeling
Length of cable ,
Resistance of one conductor per km = 0.178
Reactance of one conductor per km = 0.108
Since, three conductors are in parallel, equivalent resistance and reactance for 500m length is given by,
in pu
= 0.129
in pu
Cable
1. Ans:
Modeling
Length of cable
Resistance of one conductor per km is given as 0.181 and reactance / km is given as 0.124 . Since,
three conductors are in parallel, equivalent resistance and reactance for 300m cable is given by,
Converting into pu
in pu pu
in pu pu
Motors
Note that 1hp = 746watts; if we assume a
motor power factor of 0.746, then
equivalent motor kVA will be unity. Hence,
we will assume that 1hp is equivalent to
1kVA.
Subtransient reactance = 25%
Ratio = 6
pu
pu
For motor 2
pu
pu
in pu = 0.069 + j0.416
The equivalent circuit of the system used to calculate the Thevenin's equivalent at node A is shown in fig
13.2. The dotted lines indicate the ground potential.
1. Ans: Fault at
We now desire to compute Thevenin's
impedance at node A.
For fault at , the network as shown in fig
13.2 can be reduced to network as shown
in fig 13.3. Hence, Thevenin's impedance,
is given by,
Therefore, three phase fault current at fault F1
Fault at
1. Ans: F
2
1. Ans:
i.e.,
Fig 13.5 shows the single line diagram of a 3 bus system. The sequence data for transmission lines and
2.
generators
are given in table 1. If a bolted single line to ground fault occurs at F, calculate the fault current. If the
fault impedance is j0.1 pu; what will be the fault current?
Sequence Data in pu
Description
Zero Positive Negative
Generator - A j0.03 j0.25 j0.15
Generator - B j0.02 j0.20 j0.12
Transmission Line 1 j0.14 j0.08 j0.08
Transmission Line 2 j0.17 j0.13 j0.13
Transmission Line 3 j0.10 j0.06 j0.06
Transmission Line 4 j0.12 j0.06 j0.06
2. Ans: Zero Sequence Impedance
For calculating Z 0 , the circuit shown in fig 13.5 is reduced as shown in fig 13.6.
2. Ans: Positive Sequence Impedance
Similarly, positive sequence impedance Z 1 can be found out by reducing the circuit as shown in fig 13.7.
i.e. Z 1 , positive sequence impedance = j0.01 + j0.124
= j0.134 pu
Review Questions
Recap