Magnum IEC - Product Specific Information
Magnum IEC - Product Specific Information
• Proven Performance
• Expanded Capabilities
• High Withstand Ratings
A global source for
innovative electrical power distribution solutions
Proven performance …
time and again
For over 70 years, Eaton has
designed, engineered and manu-
factured low voltage circuit
breakers and trip units for the
global market. Our revolutionary product
developments and solutions continue to set the
standard for quality, reliability, and extended
operating life. We are an industry leader in air
circuit breaker technology innovations such as the
first solid-state trip unit, the first microprocessor-
based trip unit, zone selective interlocking, and the
DE-ION® arc extinguisher design, providing
superior arc quenching characteristics.
2
High withstand ratings … in a compact size
Eaton’s innovations meet the needs of today’s modern High withstand ratings
air circuit breakers: Magnum provides high interruption and withstand
• The capability to design more flexible systems that ratings in a small physical size.
can withstand larger available fault currents.
• Better coordination with downstream devices. Through-the-door design
• Reduced size of the switchgear assembly. All controls, indicators, and the trip unit are visible and
• Integrally designed breaker levering mechanism and can be safely accessed without opening the
cassette for drawout breaker with clear indication of compartment door.
connect, test, and disconnect positions.
Common height and depth
Meeting the challenge All three Magnum frame sizes have the same identical
Magnum breakers are engineered specifically for use in height and depth to facilitate standardised designs in
low voltage assemblies applied at nominal voltages of low voltage assemblies.
380, 415, 440, 500 and 690 Vac. Ten continuous ratings
– 800 A through 6300 A – are covered with three frame Complete trip unit family
sizes. Drawout and fixed mounting units are available A full range of Digitrip® programmable and electronic
in 3- or 4-pole designs. trip units has been expanded to offer customers a
Controls and indicators are conveniently grouped on choice of protection, information, and communication
the breaker’s front escutcheon where they can be capabilities to meet specific requirements.
easily viewed and accessed through a cutout door.
3
4
6 5
7 9 8
Rear view of integrally-designed
11 cassette showing generous spacing
for customer bus connections.
10 12
13
14 15
3
A look inside the Magnum
Designed for easy access, inspection, Two-step stored energy mechanism for manually and
and minimal maintenance electrically operated breakers
The stored energy mechanism, control devices, The potential energy is stored in the mechanism to close
accessories, and secondary contacts are easily accessible the breaker in five cycles or less. Sufficient energy to
by removing the front cover, held in place by four captive open the breaker remains available following the closing
screws. For safety, this can only be done when the operation.
breaker is in the disconnect position or removed from the After closing, the charging spring can be recharged to
cell. provide potential energy for reclosing following a fault,
The current sensor viewing window on the rear of the providing high continuity of service. This feature allows
breaker allows for easy identification of the current for the following sequence:
sensor mounted inside.
Charge – Close – Recharge – Open – Close – Open.
A contact wear indicator eliminates the need for
elaborate testing to determine if the contact assembly On manually operated breakers, closing springs are
needs replacing. charged by hand. For electrically operated breakers,
springs are charged by an electric motor but can be
manually charged if no power is available.
1
10
11
2
12
3
13
14
8 9
4
Magnum IEC - Product specific information
1 MW N 5 12 4 V E A 03 MT 6 M C J 2 Y C N M W X
1
Breaker frame Trip unit and protection,
1 I = Standard or double and external control voltage when
required
N = Narrow or double
Poles and neutral Mounting configuration
1 = narrow
K = Special 1100 Vac ACB (facing front of breaker) and load terminals
NN
22
= Non-automatic (no trip unit)
= 520 LI
3 = Three H = Fixed horizontal 52 = 520 LSI
1 Interrupting Icu 4 = Four (neutral left) V = Fixed vertical 5W = 520i LSIG
R = Four (reserved for L = Drawout horizontal M2 = 520M LSI
4 = 40 kV
1 5 = 50 kV
neutral right) MT
MU
= 520M LSI (24–48 Vdc)
= 520M LSI (120 Vac)
6 = 65 kV Nameplate language
MV = 520M LSI (240 Vac)
1 8 = 85 kV E = English
MW = 520Mi LSIG
Z = 100 kV A = Spanish
MJ = 520Mi LSIG (24–48 Vdc)
1 H = 25 kV
(1100 Vac MWK) Sensor and
MK = 520Mi LSIG (120 Vac)
ML = 520Mi LSIG (240 Vac)
rating plug rating
1 Continuous amperes and NN = None 13 = 1250
ME
MC
= 520M LSIA (24–48 Vdc)
= 520M LSIA (120 Vac)
phasing (facing front of 01 = 100 16 = 1600 MF = 520M LSIA (240 Vac)
1 breaker) 02 = 200 20 = 2000 CT = 520MC LSI (24–48 Vdc)
08 = 800 ABC 05 = 250 25 = 2500 CU = 520MC LSI (120 Vac)
1 10
12
= 1000 ABC
= 1250 ABC
03
04
=
=
300
400
30 =
32 =
3000
3200
CV
CE
= 520MC LSI (240 Vac)
= 520MC LSIA (24–48 Vdc)
16 = 1600 ABC 06 = 600 40 = 4000 CC = 520MC LSIA (120 Vac)
1 20 = 2000 ABC 08 = 800 50 = 5000 CF = 520MC LSIA (240 Vac)
25 = 2500 ABC 10 = 1000 63 = 6300 CJ = 520MCi LSIG (24–48 Vdc)
1 32 = 3200 ABC 12 = 1200 CK = 520MCi LSIG (120 Vac)
41 = 4000 ABC (standard CF = 520MCi LSIG (240 Vac)
1 drawout only)
4N = 4000 AABBCC
C1
C2
= 520MC ARMS LSI (24–48 Vdc)
= 520MC ARMS LSI (120 Vac)
5N = 5000 AABBCC C3 = 520MC ARMS LSI (240 Vac)
1 6N = 6300 AABBCC C4 = 520MC ARMS LSIA (24–48 Vdc)
40 = 4000 ABCABC C5 = 520MC ARMS LSIA (120 Vac)
1 50 = 5000 ABCABC
60 = 6300 ABCABC
C6
C7
= 520MC ARMS LSIA (240 Vac)
= 520MC ARMS LSIG (24–48 Vdc)
C8 = 520MC ARMS LSIG (120 Vac)
1 C9 = 520MC ARMS LSIG (240 Vac)
1W = 1150i LSI (24–48 Vdc)
1 1N = 1150i LSI (120 Vac)
1P = 1150i LSI (240 Vac)
1 1R
1S
= 1150i LSIG/A (24–48 Vdc)
= 1150i LSIG/A (120 Vac)
1T = 1150i LSIG/A (240 Vac)
1
1
1
1
1
Table 9. Magnum IEC 60947-2 rated air circuit breakers continued
rms symmetrical current ratings kA
1 Available
current
sensor
and
rating
plugs for
3 With-
stand
digitrip
rms trip
Inter- Inter- Inter- rating With- unit
4 rupting
@ 240
rupting
@ 440
rupting
@ 690
Icw
1-Sec @
stand
rating
Fixed
internal
(estab-
lishes Poles
Frame Breaker Frame Vac Vac Vac 440V/ Icw inst breaker KEMA/ avail-
amperes type type Icu = Ics Icu = Ics Icu = Ics 690V 3-Sec trip In rating) KEUR CCC able
5 2500 MWI-625 Standard 65 65 65 65 n/a 200, 250, X X 3&4
MWI-825 Standard 85 85 85 85 65 300, 400, X X 3&4
1 MWI-C25 Standard 100 100 85 85 65 85
630, 800,
1000, 1250, 3&4
1600, 2000,
1 MWI-H25 Standard 125 125 125 85 65
2500
X X 3&4
1 4000
MWI-H32
MWI-64N
Standard
Double 65 65
125
65 65 n/a 2000, X X
3&4
3&4
2500,
1 MWN-64N Double
Narrow
66 66 66 66 n/a
3200,
X X 3&4
4000
1 MWI-641
MWI-84N
Standard
Double
66
85
66
85
66
85
66
85
n/a
n/a
X
X
X
X
3&4
3&4
1 MWN-84N Double
Narrow
85 85 66 85/66 66 X X 3&4
1 MWI-841
MWI-C4N
Standard
Double
85
100
85
100
85
100
85
100
66
n/a
X
X
X
X
3&4
3&4
1 MWN-C4N Double
Narrow
105 105 66 105/66 66 X X 3&4
1 5000
MWI-C41
MWI-85N
Standard
Double
105
85
105
85
85
85
85
85
n/a
n/a 2500,
X
X
X
X
3&4
3&4
3200,
1 MWI-C5N Double 100 100 100 100 n/a
4000, 5000
X X 3&4
In the withdrawn position, the Finger-proof (IP20) All breakers can be padlocked The drawout breaker can be The breaker spring charging
breaker can be removed from secondary points with easy to secure the breaker in all conveniently racked in or out, handle is designed with
the cell on integral extension access for customer wiring. three positions. An optional stopping at the various sufficient space for operation
rails. key interlock (not shown) can positions with the door closed. even with a gloved hand.
also secure the breaker in
each position.
5
Convenient secondary contact placement facilitates
wiring and maintenance
Secondary wiring points are located in the top front
portion of each cell. A separate door can be used to
cover the contacts so an operator can safely access
■ Connect them without opening the breaker compartment door.
Customer contact points are dedicated to the customer’s
interface, totally free and isolated from factory
connections.
The secondary terminals have standard finger-proof
hinged covers, providing safety by protecting against
accidental contact with live secondary contacts.
Safety is enhanced by the through- ■ Test Covers are hinged for making connections and include a
the-door design that provides for three small access hole for circuit testing using a probe. Each
breaker positions with the door
secondary contact point is dedicated to a specific
closed: connect, test, and disconnect.
function, allowing standardised wiring diagrams and true
electrical interchangeability of common size breakers.
Standard wiring points help improve quality while
reducing maintenance and inspection time for end
■ Disconnect customers.
6
The trip unit family
Protection and information … the digitrip family Programmable trip units
provides choices like no other Digitrip RMS 1150 provides programmability
Ever since introducing the first microprocessor-based for more sophisticated distribution systems
trip unit, Eaton has advanced the technology into a including:
more complete family of Digitrip RMS Electronic and • Increased protection and coordination
Programmable Trip Units designed and engineered capabilities.
exclusively for Magnum breakers. Magnum can also be • Systems monitoring information including power
supplied as a non-automatic switch. factor, voltage current, harmonic distortion,
values, and waveform capture with a three-line
Electronic trip units (8 characters per line) LED display.
• Digitrip RMS 520 LI provides long time and • Two programmable contacts for customer use.
instantaneous protection only. • Time stamping of trip events for improved
• Digitrip RMS 520 LSI / 520i LSIG enables the user as troubleshooting and diagnostics.
many as nine phases and earth current protection • Accuracy of 1% on metered values and 2% on
settings for maximum flexibility in trip-curve shaping energy and power.
and multi-unit coordination, and adds earth fault • Systems diagnostic information.
current protection settings. • INCOM and PowerNet communications.
• Digitrip RMS 520M adds phase, neutral, and • Allows for custom curve shaping or selectable
Earth fault current metering … with a four-character IEC curves.
LCD display window.
• Digitrip RMS 520MC has the same features as the
520Mi, but also includes communications.
7000 7000
4000 4000
1000 1000
60 60
10 10
Time in seconds
Time in seconds
1 1
0.1 0.1
0.01 0.01
0.5 1 2 10 20 50 100 0.05 0.1 0.2 1 2 5 10
Current in multiples Current in multiples
of long delay setting Ir of rating In
7
Trip unit summary table
Magnum Digitrip trip units
The next generation of proven Digitrip RMS
Trip Units is available exclusively on Magnum
Breakers. These true rms sensing trip units
provide accurate coordination with the
conductors and equipment the breaker is
designed to protect.
Trip unit type Digitrip 520 LI Digitrip 520 LSI Digitrip 520M LSI Digitrip 520MC LSI Digitrip 1150i LSI
Digitrip 520i LSIG 3) Digitrip 520Mi LSIG 3) Digitrip 520MCi LSIG 3) Digitrip 1150i LSIG 3)
Ampere range 200 A - 3200 A 200 A - 6300 A 200 A - 6300 A 200 A - 6300 A 200 A - 6300 A
Interrupting rating at 690 V 40 through 100 kA 40 through 100 kA 40 through 100 kA 40 through 100 kA 40 through 100 kA
Rms sensing Yes Yes Yes Yes Yes
Protection and coordination
Protection Ordering options LI LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed rate plug (In) Yes Yes Yes Yes Yes
Overtemperature trip Yes Yes Yes Yes Yes
Long Long delay pickup 0.4 - 1.0 x (In) 0.4 - 1.0 x (In) 0.4 - 1.0 x (In) 0.4 - 1.0 x (In) 0.4 - 1.0 x (In)
delay Long delay time I2t at 6 x Ir 2 - 24 seconds 2 - 24 seconds 2 - 24 seconds 2 - 24 seconds 2 - 24 seconds
protection Long delay time I4t No No No No 1 - 5 seconds
(L) Long delay thermal memory Yes Yes Yes Yes Yes
High load alarm No No No No 0.5 - 1.0 x (Ir)
Short Short delay pickup No 200 - 1000% x (Ir) 200 - 1000% x (Ir) 200 - 1000% x (Ir) 200 - 1000% x (Ir)
delay and M1 and M1 and M1 and M1
protection Short delay time I2t at 8 x Ir No 100 - 500 ms 100 - 500 ms 100 - 500 ms 100 - 500 ms
(S) Short delay time flat No 100 - 500 ms 100 - 500 ms 100 - 500 ms 100 - 500 ms
Short delay time ZSI No Yes Yes Yes Yes
Instantaneous Instantaneous pickup 200 - 1000% x (In) 200 - 1000% x (In) 200 - 1000% x (In) 200 - 1000% x (In) 200 - 1000% x (In)
protection and M1 and M1 and M1 and M1 and M1
(I) Making current release Yes Yes Yes Yes Yes
Off position No Yes Yes Yes Yes
Earth fault Earth fault alarm No No Yes Yes Yes
protection Earth fault pickup No 25 - 100% x (In) 25 - 100% x (In) 25 - 100% x (In) 24 - 100% x (In)
(G) Earth fault delay I2t at .625 x In No 100 - 500 ms 100 - 500 ms 100 - 500 ms 100 - 500 ms
Earth fault delay flat No 100 - 500 ms 100 - 500 ms 100 - 500 ms 100 - 500 ms
Earth fault ZSI No Yes Yes Yes Yes
Earth fault thermal memory No Yes Yes Yes Yes
Neutral protection (N) Yes Model LSI only Model LSI only Model LSI only Model LSI only
System diagnostics
Cause of trip LEDs Yes Yes Yes Yes Yes
Magnitude of trip information No No No Yes Yes
Remote signal contacts No No Yes Yes Yes
Programmable contacts No No No No Yes
System monitoring
Digital display No No 4 char. LCD 4 char. LCD 24 char. LED
Current (%) full scale sensor No No Yes Yes Yes +/- 1%
Voltage (%) L - L No No No No Yes
Power and energy (%) No No No No Yes
Apparent power kVA and demand No No No No Yes
Reactive power kVAR No No No No Yes
Power factor No No No No Yes
Crest factor No No No No Yes
Power quality - harmonics No No No No Yes
% THD No No No No Yes
System communications
Type No No No INCOM/PowerNet INCOM/PowerNet/
Trip Link
Power supply N/A N/A PRM in breaker PRM in breaker PRM in breaker 2)
Additional features
Trip log (3 events) No No No No Yes
Electronic operations counter No No No No Yes
Testing method 1) Test set Test set Test set Test set Integral and test set
Waveform capture No No No No Yes
2) New features will include over and under voltage alarm or trip, over and under frequency alarm or trip, voltage unbalance alarm or trip, and reverse power trip and
phase rotation alarm. Contact Eaton for availability and more details.
3) Only at LSIG with ground fault protection is the "i" of Digitrip required. The Digitrip 1150 will be provided on request.
8
Characteristics table
Magnum characteristics,
dimensions and weights
IP Rating
Door Frame IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20
Cover IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
1) Circuit breakers equipped with integral trip units have a making current release set to trip instantaneously at 25 x In peak current to prevent closing
on a fault current exceeding that magnitude.
2) Magnum ACB’s carry an IT rating at 440 Vac per IEC 60947-2 Annex H. Contact Eaton for 690 Vac IT applications.
3) The Icw 1 sec/3 sec rating is 50/30 kA for 2000 A MWN 50 kA breaker.
4) Standard frame circuit breakers rated 100 kA are equipped with a high instantaneous trip set to protect above 85 kArms. Icu is 100 kA and Ics is 85 kA at 440 Vac.
Icu and Ics are 85 kA at 690 Vac.
5) The approximate weights and dimensions shown are based on horizontal terminals.
6) Non-automatic switches should be applied with a suitable external overcurrent device with very fast instantaneous trip to protect above the published close and latch rating.
If such a device is not used, a selective circuit breaker with trip unit and making current release should be used.
7) The maximum available instantaneous interrupting rating for the standard frame non-automatic switch is 85 kA.
8) Circuit breaker Icm values are equal to Icu times a constant. Value of the constant is either 2.1 or 2.2 as given in IEC 60947-2.
9
Dimensions (mm)
Fixed design
800 - 2000 A narrow frame
318 340
257 133 32
78
352 417
293 391
410 340
257 133 32
78
352 417
414 391
865 340
257 133 32
78
352 417
869 391
10
Withdrawable design
800 - 2000 A narrow frame
86
52
54
511
401
318
477
247
189
173
122
106
19
336 (3-pole) 48
431 (4-pole) 61
474
800 - 3200 A standard frame 458
434
432 411
176 118
129
45
9
432 (3-pole); 559 (4-pole) 434
559 (3-pole); 686 (4-pole)
474
4000 - 6300 A double wide frame 458
434
432
411
176 118
129
45
11
Eaton Corporation is a diversified power management company ranked among the largest Fortune 500
companies. The electrical group is Eaton's largest division and is a global leader in electrical control,
power distribution, power quality, automation, and monitoring products and services. Eaton's global
electrical brands, including Cutler-Hammer®, MGE Office Protection Systems™, Powerware®, Holec®,
MEM®, Santak and Moeller, provide customer-driven PowerChain Management® solutions to serve the
power system needs of the industrial, institutional, government, utility, commercial, residential, IT,
mission critical and OEM markets worldwide.
PowerChain Management solutions help enterprises achieve a competitive advantage through proactive
management of the power system as a strategic, integrated asset throughout its life cycle. With Eaton's
distribution, generation and power quality equipment; full-scale engineering services; and information
management systems, the power system is positioned to deliver powerful results: greater reliability,
operating cost efficiencies, effective use of capital, enhanced safety, and risk mitigation.