RS Calibration Isotech-3610D
RS Calibration Isotech-3610D
(Switching mode)
82IP-3610DMB
Ei
SAFETY TERMS AND SYMBOLS
These terms may appear in this manual or on the product:
Ei
FOR UNITED KINGDOM ONLY
NOTE As the colours of the wires in main leads may not correspond with the colours marking
This lead/appliance must only identified in your plug/appliance, proceed as follows:
be wired by competent persons
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked
WARNING
with the letter E or by the earth symbol or coloured Green or Green & Yellow.
THIS APPLIANCE MUST BE
EARTHED
The wire which is coloured Blue must be connected to the terminal which is marked with the
IMPORTANT Letter N or coloured Blue or Black.
The wires in this lead are
coloured in accordance with The wire which is coloured Brown must be connected to the terminal marked with the letter L
the following code: or P or coloured Brown or Red.
Green/ If in doubt, consult the instructions provided with the equipment or contact the supplier.
Yellow: Earth
Blue : Neutral This cable/appliance should be protected by a suitably rated and approved HBC mains fuse;
Brown: Live (Phase) refer to the rating information on the equipment and/or user instructions for details. As a guide,
cable of 0.75mm ² should be protected by a 3A or 5A fuse. Larger conductors would normally
require 13A types, depending on the connection method used.
Any moulded mains connector that requires removal/replacement must be destroyed by removal
of any fuse & fuse carrier and disposed of immediately, as a plug with bared wires is hazardous
if a engaged in live socket. Any re-wiring must be carried out in accordance with the information
detailed on this label.
Eii
Statement of Compliance
EN 61326-1: Electrical equipment for measurement, control and laboratory use—EMC requirements (1997+A1:1998 )
Conducted Emission EN 55022 Class A Electrostatic Discharge EN 61000-4-2 (1995)
Radiated Emission (1994)+A1(1995)+A2(1997) Radiated Immunity EN 61000-4-3 (1996)
Current Harmonic EN61000-3-2 Class A Electrical Fast Transients EN 61000-4-4 (1995)
(1995)/A12(1996)/A13(1997)/A1(1998)/A2(1998)/prA14(2000) Surge Immunity EN 61000-4-5 (1995)
Conducted RF Immunity EN 61000-4-6 (1996)
Voltage Fluctuation EN61000-3-3 (1995) Voltage Dip/Interruption EN 61000-4-11 (1994)
Eiii
CONTENTS
SECTION PAGE
1. INTRODUCTION…………………………………………………………………………….……………………… 1
2. SPECIFICATIONS…………………………………………………………………………………………………… 2
2-1 General…………………………………………………………………………………….……………………. 2
2-2 Constant Voltage Operation…………………………………………………………………………………… 3
2-3 Constant Current Operation…………………………………………………………………………………... 3
2-4 Indicator Meter…………………………………………………………………………………………………. 3
2-5 Insulation………………………………………………………………………………………………………... 3
3. PRECAUTIONS BEFORE OPERATION………………………………………………………………………….. 4
3-1 Unpacking the Switching Power Supply……………………………………………………………………… 4
3-2 Checking the line voltage………………………………………………………………………………………. 4
3-3 Environment……………………………………………………………………………………………………. 5
3-4 Equipment installation and operation………………………………………………………………………… 5
4. THEORY OF OPERATION………………………………………………………………………………………… 6
5. PANEL CONTROLS AND INDICATORS………………………………………………………………………… 9
5-1 Front Panel……………………………………………………………………………………………………… 9
5-2 Real Panel………………………………………………………………………………….……………………. 9
6. OPERATION INSTRUCTIONS……………………………………………………………………………………. 12
6-1 Precaution………………………………………………………………………………….……………………. 12
6-2 Setting Current Limit…………………………………………………………………………………………... 12
6-3 Constant Voltage/Constant Current Characteristic…………………………………………………………. 13
6-4 Operation Mode………………………………………………………………………………………………… 14
7. MAINTENANCE…………………………………………………………………………………………………… 15
7-1 Fuse Replacement………………………………………………………………………………………………. 15
7-2 Line voltage Conversion………………………………………………………………………………………... 15
7-3 Adjustment……………………………………………………………………………………………………… 16
7-4 Cleaning…………………………………………………………………………………………………………. 18
Eiv
1. INTRODUCTION
This series of switched mode power supplies have removed the inconvenience of big volumes and heavyweight
associated with traditional power supplies.
The output voltage and current are controlled by two variable resistors with coarse and fine regulation for simple and
precise adjustment.
Features:
l Wide input voltage range— 97V~133V (for 115V) and 195V~265V (for 230V).
l With high frequency operation the size of power the transformer is reduced
l With small size, light weight and high power density.
l Entire efficiency rate up to 70%.
l Constant current and constant voltage modes.
l Zero adjustment for the voltage and current output.
E1
2.SPECIFICATION
2-1. General
Mains supply : 115V/230V±15% 50/60Hz(Switch selectable).
Rating, dimension and weight : See Table 2-1.
Table 2-1
MAX. RATING INPUT RATING FUSE STYLE & RATING WEIGHT
Model
Voltage Current Watts VA 115V 230V kg
IPS-1820D 18V 20A 500 900 T 10A 250V T 6.3A 250V 3.3
IPS-3610D 36V 10A 500 900 T 10A 250V T 6.3A 250V 3.3
IPS-606D 60V 6A 500 900 T 10A 250V T 6.3A 250V 3.3
Dimensions:128(W) × 145(H) × 285(D) mm.
WARNING: Voltage over 60V DC is a lethal shock hazard to the user. Be careful when
connecting power supplies in series to achieve voltage higher than 60V DC totally or 60V
DC between any connection and earth ground.
E2
2-2.Constant Voltage Operation
(1) Output Voltage ranges from 0 to rated voltage with continuous adjustment.
(2) Voltage regulation
line regulation≦5mV.
load regulation≦5mV.
(3) Recovery time≦500µs(50% Load change, minimum load 0.5A).
(4) Ripple & Noise≦5mVrms, 100mVp-p (tested by 20MHz oscilloscope.)
(5) Temperature coefficient≦100ppm/℃.
2-3.Constant Current Operation
(1) Output current ranges from 0 to rated current with continuous adjustment.
(2) Current regulation
line regulation≦3mA.
load regulation≦3mA.
(3) Ripple & Noise≦3mArms (IPS-606D).
≦5mArms (IPS-3610D).
≦10mArms (IPS-1820D).
2-4.Indicator Meter
1)Voltage:
Display : 3 1/2 Digits 0.39” Green LED display.
Accuracy : ±(0.5% of reading + 2 digits).
2)Current:
Display : 3 1/2 Digits 0.39” Red LED display.
Accuracy : ±(0.5% of reading + 2 digits).
2-5.Over Voltage Protection
(1) Over Voltage Protection ranges from 5% rating to rating +5.5%.
(2) OVP Accuracy ±(Vset 1%+0.6V)
2-6.Insulation
Between Chassis and Output Terminal : ≧20MΩ (DC500V).
Between Chassis and AC Cord : ≧30MΩ (DC500V).
E3
3. PRECAUTIONS BEFORE OPERATION
3.1 Unpacking the Switched ModePower Supply
The instrument has been fully inspected and tested before shipping from the factory. Upon receiving the instrument,
please unpack and inspect it to check if there is any damages caused during transportation. If any sign of damage is
found, notify the bearer and/or the dealer immediately.
WARNING: To avoid electrical shock the power cord protective grounding conductor must be
connected to ground.
When line voltages are changed, replace the required fuses shown below.
Line voltage Range Fuse Line voltage Range Fuse
115V 97-133V T 10A 250V 230V 195-265V T 6.3A 250V
WARNING: To avoid personal injury, disconnect the power cord before removing the fuse
holder.
E4
3.3 Environment
The normal ambient temperature range of this instrument is from 0° to 40°C (32° to 104°F). Operation of the
instrument above this temperature range may cause damage to the circuits.
Do not use the instrument in a place where strong magnetic or electric fields exist as they may disturb the
measurement.
WARNING: This is a Class A product. In a domestic environment this product may cause
radio interference in which case the user may be required to take adequate measures.
E5
4.THEORY OF OPERATION
E6
l Description of Circuit Theory
1) +10V Voltage reference circuit:
Start up the circuits of R306 and D302 to ensure the output voltage of OPA U301, PIN 1 is in positive status when power is on.
At this moment, the output voltage of PIN 1 will pass through R307 to maintain the voltage of both ends of ZENER DIODE
ZD301(6.2V) to 6.2V. As OPA has the character of false short circuit, so U301 PIN3=6.2V, refer to the following formula:
VR301 + R304 + R305 VR301 + 4.99k + 10k
Vref = 6.2 = 6.2 @ 10V
R305 10k
Therefore, the OPA’s output voltage can be changed by adjusting the VR301 as shown in the following formula:
Vref=10V→VR301=1.14kΩ
E7
l Figure 1: Block Diagram
E8
5.PANEL CONTROLS AND INDICATORS
E9
Fig. 4-1 Front Panel
E10
Fig. 4-2 Rear Panel
E11
6.OPERATION INSTRUCTIONS
6-1.Precaution
(1)AC input
AC input should be within the range of line voltage±15% 50/60Hz.
WARNING: To avoid electrical shock, the power cord protective grounding conductor must be
connected to ground.
(2)Installation
Avoid using the power supply in a place where ambient temperature exceeds 40℃. The heat sink located at rear of
the power supply must have sufficient space for radiation.
CAUTION: To avoid damaging the power supply, don’t use it in a place where ambient
temperature exceeds 40℃.
E12
6-3.Constant Voltage / Constant Current Crossover Characteristic
The working characteristic of this series is called a constant voltage/constant current automatic crossover type. This permits
continuous transition from constant current to constant voltage modes in response to the load change. The intersection of
constant voltage and constant current modes is called the crossover point. Fig.5-1 shows the relationship between this
crossover point and the load.
For example, if the load is such that the power supply is operating in the constant voltage mode, a regulated output voltage
is provided. The output voltage remains constant as the load increases, up until the point where the preset current limit is
reached. At that point, the output current becomes constant and the output voltage drop is proportioned to further increases
in load. The crossover point is indicated by the front panel LED indicators. The crossover point is reached when the CV
indicator goes out and the CC indicator is on.
E13
Similarly, crossover from the constant current to the constant voltage mode automatically occurs from a decrease in
load, a good example of this would be seen when charging a 12 volt battery. Initially, the open circuit voltage of the
power supply may be preset for 13.8 volts. A low battery will place a heavy load on the supply and it will operate in the
constant current mode, which may be adjusted for a 1 amp charging rate. As the battery becomes charged, and its
voltage approaches 13.8 volts, its load decreases to the point where it no longer demands the full 1 amp charging rate.
This is the crossover point where the power supply goes into the constant voltage mode.
E14
7. MAINTENANCE
WARNING
The following instructions are used by qualified personnel only. To avoid electrical shock, do not perform any servicing
other than the operating instructions of the manual unless you are qualified to do so.
7-1.Fuse Replacement
If the fuse blown, the CV or CC indicators will not light and the power supply will not operate. The fuse should not
normally blow unless a problem has developed in the unit. Try to determine and correct cause of the blown fuse, then
replace only with a fuse of the correct rating and type.
The fuse is located on the rear panel (see Fig. 4-2).
WARNING: For continued fire protection. Replace with 250V fuse of the specified type and rating,
and disconnect the power cord before replacing fuse.
E15
7-3.Internal adjustments
The unit was accurately adjusted at the factory before shipment. So, readjustment is suggested only when the accuracy
of circuit is affected by the repair, or when you have the reason to believe that the unit is out of accuracy. The
recommended calibration device is a multimeter with an accuracy of ±0.1% dcv or better.
If readjustment is required, proceed the following procedure. Locations of the adjustments are shown in Fig. 6-1 and
Fig.6-2.
(1) Adjustment of the Rating Voltage
A. Connect an accurate (±0.1%) external multimeter to measure the dc voltage at output terminals of the power
supply.
B. Set the COARSE and FINE VOLTAGE controls to maximum (fully clockwise).
C. Adjust trimmer VR301 for a reading on the multimeter to be 18.50V for IPS-1820D, 36.50V for IPS-3610D, and
60.50V for IPS-606D.
D. Adjust trimmer pot VR2 to set the reading value of voltmeter as same as the one shown on the multimeter..
E16
E17
7-4 Cleaning
To clean the power supply, use a soft cloth dampened in a solution of mild detergent and water. Do not spray cleaner
directly onto the instrument, since it may leak into the cabinet and cause damage. Do not use chemicals containing
benzine, benzene, toluene, xylene, acetone, or similar solvents. Do not use abrasive cleaners on any portion of the
instrument.
RS Components UK
PO Box 99, Corby
Northants, NN17 9RS
Tel: 01536 201234
Fax: 01536 405678
E18