86 Lockout Auxiliary Relay Site Test Report: Mechanical Checks & Visual Inspection

This document summarizes test results for an 86 Lockout Auxiliary Relay. Mechanical checks found no defects. Electrical tests of pick-up voltage, time, and burden were within specified limits. Contact status checks for 12 normally open and 6 normally closed auxiliary contacts all showed proper operation. Testing equipment and calibration dates are also listed.

Uploaded by

Jaikaran Dan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
301 views2 pages

86 Lockout Auxiliary Relay Site Test Report: Mechanical Checks & Visual Inspection

This document summarizes test results for an 86 Lockout Auxiliary Relay. Mechanical checks found no defects. Electrical tests of pick-up voltage, time, and burden were within specified limits. Contact status checks for 12 normally open and 6 normally closed auxiliary contacts all showed proper operation. Testing equipment and calibration dates are also listed.

Uploaded by

Jaikaran Dan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

86 Lockout Auxiliary Relay

Site Test Report

Customer: SAMSUNG SS / SWG: 11 / 304


Location: PKG-4,GOSP-1 Sheet No.: Page 1 of 2
General Data & Information:
Manufacture: G.E Type: Series 95
Panel No.: 103- INC-1 Designation: F18 (86-51-1)
Description: LOCKOUT RELAY HAND RESET Aux. Supply: 125V DC
Serial No. 003116516 CAT NO: 957803E

Mechanical Checks & Visual Inspection:


No. Descriptions Remarks
1 Inspects for any physical damage or defects. Ok
2 Verify connection as per approval drawing Ok
3 Check the tightness of all connection. Ok
4 Indications checks Ok

Electrical Test:
Pick- Up Test:

Pick- Up DC Voltage Limits Pick-Up


Injected Terminals
(V) DC Voltage (V) Current (mA)
B–G >33 19.39 367

Pick- Up Time Test at Rated Voltage:

Applied DC Voltage Pick- Up Time Limits Pick- Up Time


Injected Terminals
(V) (mSec) (mSec)
B–G 125.00 ≅ 8.2 8.00

Relay Burden Test at Rated Voltage:

Applied DC Voltage Measured Current Rated Burden Coil Resistance at Ambient Temp.
(V) (A) (A) (Ω)
125.00 1.383 3.0 52.7

Contacts Check: (All Contact Status in Un - Energized Mode)


Remarks Date
31/07/2013
Tested By Witnessed By
Company Testing Engineer Sign Company Witness Sign
Al Fanar K.K ARAMCO
86 Lockout Auxiliary Relay
Site Test Report

Customer: SAMSUNG SS / SWG: 11 / 304


Location: PKG-4,GOSP-1 Sheet No.: Page 2 of 2
General Data & Information:
Manufacture: G.E Type: Series 95
Panel No.: 103- INC-1 Designation: F18 (86-51-1)
Description: LOCKOUT RELAY HAND RESET Aux. Supply: 125V DC
Serial No. 003116516 CAT NO: 957803E

Number of Auxiliary Contacts: NO: 6 NC: 6

Contact No. Contact Status Result Contact No. Contact Status Result
12-18 NO OK 11-13 NC OK
14-16 NO OK 15-17 NC OK
22-28 NO OK 21-23 NC OK
24-26 NO OK 25-27 NC OK
32-38 NO OK 31-33 NC OK
34-36 NO OK 35-37 NC OK

Testing Equipment Used:

ITEM Test Equipment Serial Number Calibration date Calibration due date

1 SVERKER780 1100363 04 NOV 2012 04 NOV 2013

2 MULTIMETER 18970173 04 NOV 2013 04 NOV 2014

Remarks Date
31/07/2013
Tested By Witnessed By
Company Testing Engineer Sign Company Witness Sign
Al Fanar K.K ARAMCO