Design calculation sheet
Project no: Date: Sheet no.: 1 of 2 Computed by: Eng / Ayman
Subject: Checked by: M.H
Co2 Design System For Electrical Room
Approved by:
Reference : NFPA 12 , Standard on Carbon Dioxide Extinguishing Systems
Total Flooding System
Select Type of Fire 2
1- Surface Fire
2- Deep seated Fire ( Elec.)
Co2 Design Concentration 50 %
Net Zone Volume 8154.30 ft3
Net Zone Volume 231 m3
Volume Factor 0.083 lb.Co2/ft3
Volume Factor 1.33 Kg.Co2/m3
Quantity of Co2 Required 676.81 Ib.Co2
Quantity of Co2 Required 307.23 Kg.Co2
No.of Cylinders (based on 100 Ib each ) 7 Co2 Cylinder
No.of Cylinders (based on 45 Kg each ) 7 Co2 Cylinder
No. of Nozzles for Zone 8 Nozzle
Flow / Nozzle 84.60 Ibs./min
Flow / Nozzle 0.64 Kg./sec
Pipe Sizing at Nozzle Branch 1 Inch