0% found this document useful (0 votes)
127 views1 page

Total Flooding System: Drwazah Engineering Consultant & Safety

This 3 sentence summary provides the key details from the document: The document is a design calculation sheet for a CO2 fire suppression system for an electrical room, which specifies a total flooding system using 50% CO2 concentration to protect against deep seated electrical fires, and determines that 7 CO2 cylinders each containing 100 lbs or 45 kg would be needed, along with 8 nozzles sized at 1 inch to discharge the required 676.81 lbs or 307.23 kg of CO2 into the net zone volume of 8,154.30 ft3 or 231 m3.

Uploaded by

aakoglanis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
127 views1 page

Total Flooding System: Drwazah Engineering Consultant & Safety

This 3 sentence summary provides the key details from the document: The document is a design calculation sheet for a CO2 fire suppression system for an electrical room, which specifies a total flooding system using 50% CO2 concentration to protect against deep seated electrical fires, and determines that 7 CO2 cylinders each containing 100 lbs or 45 kg would be needed, along with 8 nozzles sized at 1 inch to discharge the required 676.81 lbs or 307.23 kg of CO2 into the net zone volume of 8,154.30 ft3 or 231 m3.

Uploaded by

aakoglanis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Drwazah Engineering Consultant & Safety

Design calculation sheet


Project no: Date: Sheet no.: 1 of 2 Computed by: Eng / Ayman
Subject: Checked by: M.H
Co2 Design System For Electrical Room
Approved by:

Reference : NFPA 12 , Standard on Carbon Dioxide Extinguishing Systems

Total Flooding System

Select Type of Fire 2

1- Surface Fire

2- Deep seated Fire ( Elec.)

Co2 Design Concentration 50 %

Net Zone Volume 8154.30 ft3

Net Zone Volume 231 m3

Volume Factor 0.083 lb.Co2/ft3

Volume Factor 1.33 Kg.Co2/m3

Quantity of Co2 Required 676.81 Ib.Co2

Quantity of Co2 Required 307.23 Kg.Co2

No.of Cylinders (based on 100 Ib each ) 7 Co2 Cylinder

No.of Cylinders (based on 45 Kg each ) 7 Co2 Cylinder

No. of Nozzles for Zone 8 Nozzle

Flow / Nozzle 84.60 Ibs./min

Flow / Nozzle 0.64 Kg./sec

Pipe Sizing at Nozzle Branch 1 Inch