Instrument Transformers 1
Instrument Transformers 1
1. The parameters of Instrument are grouped just as is in other types of transformer but
differ slightly when described with their inherent parameters. Exciting branch of
potential transformers are usually ignored but not in current transformers.
2. The term "burden" is used to express the load of instruments transformers which is
the impedance connected to its secondary. Burden is simply the volt-amperes delivered
to the load. Thus, when an instrument transformer delivers 5amps to a resistive load of
0.1 ohm the burden is 2.5VA at 5amps (P= I2 x R)
Current Transformers
Phase relationship in sensed current in the primary of instrument transformers may not
always be in phase with the load current, however they can be configured to shift the
angle by as much as 30o.
Proper study of Instrument Transformers is in order, external PDF files included in this
section will give you quick access to valuable information you might need.
Current transformers are chosen according to its type and they are:
- The Bushing Type (Window or Donut) used in low to medium voltage switchgears and
circuit breakers.
- Wound Type, which is called the "Choicest CT". It is the preferred CT for low voltage
application up to 600Volts, because of its excellent performance under a wide variety of
operating conditions.
The burden of CTs are not computed cumulatively but individually since a single phase
to ground fault will involve only one CT to trip a breaker. For a three phase fault,
however, all three CTs will pick up the fault current and the resistance of all device
leads must be considered in the calculations.
CT burden is now quantified in terms of impedance of the load (lead wires) with its
corresponding resistance and reactance components, since this is more accurate. CT
burden must be distributed, equally as much as possible, between all the three phases
of the system. Add all the burden of of the CT in series in the secondary of the CT; In
case smaller wires will increase the burden of the CT as they cannot be made as short
as possible, use larger wire size.
At very high current occurring during a fault, the magnetic circuits of CTs starts to
saturate and the impedance of the burden decreases as the secondary increases. For
this reason, the performance of CTs below C100 rating must be thoroughly evaluated. It
may be essential for you to perform calculations for the CT's burden for every value of
secondary current to determine the CT’s actual accuracy.
Current Transformer Accuracy
Ratio Correction Factor (RCF) is the term used to identify the accuracy of a current
transformer. The Accuracy Class of current transformer for a particular application must
be determined using ANSI C57.13-1993 or latest that is available, which shows a table
of standard percent error, standard metering burdens at 60Hz at 90% lagging power
factor. To determine the minimum to maximum range the CT will operate under normal
condition, the accuracy of the CT must be determined at 10% and 100% load current.
Proper study of CTs is in order, PDF files included in this section gives you quick
access to valuable CT selection information that simply cannot all be explained in this
space.
Voltage Transformers
- Voltage Transformer (VT) or Potential Transformer (PT) have both a primary and
secondary winding. Voltage transformers are connected to phases in either line-to-line
or line to ground as dictated by the system requirements of a power supply. VT or PT is
similar to the conventional transformers.
Safety Considerations
Safety and continuity of service of any electrical installation is the electrical engineer's
primordial concern. To achieve safety and continuity of service, however the protective
relays must also be well coordinated. The term “coordination” simply mean the proper
calibration of protective relays, both in their tripping time and the current magnitude to
which they should actuate and trip corresponding circuit breaker/s in either the
upstream or downstream level of the power supply system.
A caveat, safety and coordination are one, they simply cannot be treated as separate
items: safety is compromised without proper coordination. To achieve this, the electrical
engineer must be comfortable employing the symmetrical components, which is the
great tool for any power protection specialist to guarantee the appropriate functioning of
all systems and sub-systems. His familiarity with applicable standards and
manufacturer’s device/s documentations is likewise of equal importance, too.
Voltage transformers or potential transformers (PTs) carry very small current under
normal operating parameters, thus they have small magnetic core cross-sectional area
and wound with very fine wire. The primary of voltage transformers must be fused since
they are prone to damage by transients than a power transformer. Select a fuse sized at
300% of the potential transformer primary full-load current, if it is not available, select
the next standard larger size. Relay application dictates the voltage transformer's
connection configuration that is, wye-wye or wye-delta. The ratio and phase angle
inaccuracies of voltage transformers can be neglected since they are not within
significant values if the burden is not within its thermal volt-rating danger point, i.e. so
long as its thermal volts-ampere rating is not exceeded.
7.2kV Ring Main Unit PTs and CTs including the protection relays for the system are
shown in this partial image capture. The RMU also have two panels for interconnecting
adjacent light railway transit system RMUs for emergency power supply in case of
supply outage in one of the adjacent stations.
View clear image here
Protective relaying is an art, with the cost of protection always being balanced with
system reliability and safety. How the protection system is configured and set up all
depends on you?
34.5 kV Switchgear
34.5kV switchgear partial image. It supplies 1500KVA 34.5kV/6.6kV Auxiliary
Transformer and 2-2150KVA 34.5kV/6.6kV Rectifier Transformers. The partial SLD
image also show the CTs and PTs including the protection relays for the system. The
switchgear also has a metering cubicle for incoming 34.5kV feeder.
Electromechanical relays can be affected since they are not hermetically sealed,
or with weakened or defective seals as age sets in. This happened to one 50MW
unit of geothermal plant complex. The 50MW turbine generator blew up sending a
heavy turbine component flying and tearing off the roof and landing more than 50
meters away from the power house.
A team, to which I was a member, was formed to investigate the cause. The Team
found that a fault occurred just after the GCB that failed to trip causing the power cables
between the generator and the GCB including the GCB contacts itself to instantly melt
and weld. With the generator/turbine suddenly losing its load as the circuit opened due
to the disintegration of the power cables, the generator/turbine spun at a very high
speed because the emergency steam vent failed to work, too. Operations personnel
tried to open it manually, to no avail; and ran as fast as they could as the whole power
house started shaking violently. Luckily no one was injured in the incident.
The Sequence of Events Recorder indicated the GCB protection relay actuated, but
failed to establish a connection, since its contacts, after investigations were conducted,
revealed a contaminated contact points caused by H 2S gas. The steam emergency vent
did not open, too, and manual operation did not work because of heavy corrosion
caused by the same gas
Assume a 1MVA load, a 4.16kV feeder protected by a 5kV circuit breaker with a 50/5
CT ratio:
138/10 = 13.8Amps. This is the current that the CT delivers to the relay. The relay must
be programmed according to your calculations. If your calculations say it must act at 10
times its minimum closing current, select a relay tap of: 13.8Amps/10 = 1.38. Choose
the relay tap closest to 1.38.
@5X the minimum relay closing current:
13.8Amps/5 = 2.76. Choose the relay tap closest to 2.76. Electromechanical relay taps
ranges from 0.5 to 2, 1.5 to 6, and 4 to 16 Amps. This is indicated in the CT nameplate.
Note:
- Programmable solid state relay taps may need different computations from the "basic"
computation above as may be recommended by its manufacturer.
- Solid State relays use smaller lead wires due to the small current used by its electronic
circuitry. Always use the current transformer manufacturer's recommendation to
determine the size of the CT based on your calculated CT burdens.
Cost-wise, digital relays are much affordable than electromechanical relays. Old
protection specialists who trudged the long and rigorous path to bring us the present
state of advanced protective relaying technique consider employment of affordable
digital relay devices is not the primary concern, but how the "art of protective relaying" is
preserved with the entry of programmable microprocessor-based relays.
Microprocessor-based relays are considered a big leap for a great number of protection
specialists in big or small engineering firms. It is a big leap too, most especially for
digital relay manufacturers, since the massive investment in precision equipment
needed to build electromechanical relay components, such precision balance beams,
polarizing coils, induction disks, is no longer a big concern. All these complicated
components have all been replaced by a simple easy to manufacture printed boards
that can be mass-produced with minimum time. The advent of the digital relay has one
big disadvantage: a big number of engineers now almost always ignore symmetrical
component theory and application.
Probably the most onerous practice today is A/E firms' passing the responsibility of
short-circuit calculations and system protection to electrical contractors or testing
specialist freelance which is creating a legal liability environment. Only the protection
specialist employed or maintained by A/E firms MUST perform all the complex
calculations for the protection system.
AC Protective Devices
Device #1 - Master Element. The initiating device, such as a control
switch, etc., that serves, either directly or through such permissive
devices as protective and time-delay relays, to place equipment in or out
of operation.
Typical uses: For providing a time-delay for re-transfer back to the normal source in an
automatic transfer scheme
Device #10 - Unit Sequence Switch. A switch that is used to change the
sequence in which units may be placed in and out of service in multiple-
unit equipment.
NOTE: If only two relatively important functions are performed by the device, it is
preferred that both function numbers be used.
NOTE: This excludes devices that perform such shunting operations as may be
necessary in the process of starting a machine by devices 6 or 42 (or their equivalent)
and also excludes device function 73 that serves for the switching of resistors.
Typical uses: Used to transfer a reduced voltage starter from starting to running.
Device #21 - Distance Relay. A device which functions when the circuit
admittance, impedance or reactance increases or decreases beyond
predetermined limits. It has three (3) zones of protection, Zone-1, Zone-2
and Zone-3.
Device #24 - Volts per Hertz Relay. A relay that functions when the ratio
of voltage to frequency exceeds a preset value. The relay may have an
instantaneous or a time characteristic.
Typical uses: In a closed transition breaker transfer, a device #25 relay is used to
ensure two-sources are synchronized before paralleling. Use for feeder protection.
Typical uses: Used to initiate an automatic transfer when a primary source of power is
lost.
Device #28 - Flame Detector. A device that monitors the presence of the
pilot or main flame in such apparatus as a gas turbine or a steam boiler.
Typical uses: Used to remotely indicate that a protective relay has functioned, or that a
circuit breaker has tripped. Typically, a mechanical “drop” type annunciator panel is
used.
Typical uses: Used to prevent reverse power from feeding an upstream fault. Often
used when primary backup generation is utilized in a facility.
Typical uses: Used to indicate the position of a draw out circuit breaker (TOC switch).
Device #44 - Unit Sequence Starting Relay. A relay that functions to start
the next available unit in multiple-unit equipment upon the failure or
non-availability of the normally preceding unit.
Typical uses: Use for tripping circuit breakers instantaneously during a high-level short
circuit. Can trip on phase - phase (50), phase-neutral (50N), phase-ground (50G) faults.
Typical uses:
- For tripping a circuit breaker after a time delay during a sustained overcurrent. - For
tripping a circuit breaker instantaneously during a high-level short circuit.
Typical uses: A term applied typically to high and medium voltage circuit breakers or
low voltage power circuit breakers.
Device #52a - AC circuit breaker position (contact open when circuit
breaker open)
Device #55 - Power Factor Relay. A relay that operates when the power
factor in an AC circuit rises above or below a predetermined value.
Device #59 - Over Voltage Relay. A relay that functions on a given value
of overvoltage.
Typical uses: Used to trip a circuit breaker, protecting downstream equipment from
sustained over voltages.
Typical uses: Used in conjunction with a 27 device to delay tripping of a circuit breaker
during a brief loss of primary voltage, to prevent nuisance tripping.
Typical uses: Use to protect a transformer during a rapid pressure rise during a short
circuit. This device will typically act to open the protective devices above and below the
transformer. Typically used with a 63-X auxiliary relay to trip the circuit breaker.
Note: This function is not applied to a device connected in the secondary circuit of
current transformers in a normally grounded power system, where other device
numbers with the suffix G or N should be used; that is, 51N for an AC time overcurrent
relay connected in the secondary neutral of the current transformers.
Typical uses: Used to detect and act on a ground-fault condition. In a pulsing high
resistance grounding system, a device #64 will initiate the alarm.
Device #68 - Blocking Relay. A relay that initiates a pilot signal for
blocking of tripping on external faults in a transmission line or in other
apparatus under predetermined conditions or that cooperates with other
devices to block tripping or to block reclosing on an out-of-step
condition or on power swings.
Device #69 - Permissive Control Device. A device that is generally a two-
position manually operated switch that in one position permits the
closing of a circuit breaker or the placing of equipment into operation,
and in the other position prevents the circuit breaker to the equipment
from being operated.
Typical uses: Used to indicate a low liquid level within a transformer tank in order to
save transformers from loss-of-insulation failure. An alarm contact is available as a
standard option on a liquid level gauge. It is set to close before an unsafe condition
actually occurs.
Typical uses: Used to automatically reclose a circuit breaker after a trip, assuming the
fault has been cleared after the power was removed from the circuit. The recloser will
lock-out after a predetermined amount of failed attempts to reclose.
Typical uses: Use to protect static equipment, such as cable, bus, transformers by
measuring the current differential between two points. Typically the upstream and/or
downstream circuit breaker will be incorporated into the “zone of protection”.
Device #91 - Voltage Directional Relay. A relay that operates when the
voltage across an open circuit breaker or contactor exceeds a given
value in a given direction.
Device #92 - Voltage and Power Directional Relay. A relay that permits or
causes the connection of two circuits when the voltage difference
between them exceeds a given value in a predetermined direction and
causes these two circuits to be disconnected from each other when the
power flowing between them exceeds a given value in the opposite
direction.
DC Protective Devices
Device #53 - Exciter or DC Generator Relay. A relay that forces the dc
machine field excitation to build up during starting or that functions
when the machine voltage has built up to a given value.
Acronyms Description
AFD - Arc Flash Detector
HST – Historian
Suffixes Description
_1 - Positive-Sequence
_2 - Negative-Sequence
AC - Alternating Current
AN - Anode
BF - Breaker Failure
BK - Brake
BL - Block (Valve)
BP - Bypass
BT - Bus Tie
BU - Backup
CA - Cathode
CH - Check (Valve)
D - Discharge (Valve)
DC - Direct Current
DD - Disturbance Detector
E - Exciter
G - Ground or Generator
GC - Ground Check
H - Heater or Housing
L - Line or Logic
M - Motor or Metering
N - Neutral or Network
O - Over
P - Phase or Pump
PC - Phase Comparison
T - Transformer or Thyratron
TD - Time Delay
TM - Telemeter
U - Under or Unit
X - Auxiliary
Z – Impedance
The fuse voltage is a function of its capability to interrupt the flow of overload current in
the event of a fault. Generally, fuse voltage rating should be higher than the circuit
where they are used. but never lower, since the fuse voltage rating is a function of its
capability to interrupt the overload current in the event of a fault. If the voltage rating of
the fuse is much lower, say 50%, than the system voltage, the arc quenching effect of
the fuse might be impaired when the fuse element melts. A basic example: A 750mA
5kV microwave oven high voltage fuse tube has a diameter no bigger than fuses we
find in electronic circuits, but with a much longer length. The considerably longer length
enables the fuse to quench the arc when the fuse opens.
For low voltage system, fuses with 600Volts fuse rating will perform well in a 230V to
480V system. Always check the time current characteristic curve of the fuse
manufacturer since you might assume that a time delay fuse (Class K5) of a lower
ampere rating offers better protection than a higher rated non-time delay fuse (Class K1
or class J). This is a false assumption. In general, the rating of the fuse is an asymptotic
value e.g: the equation y=1/x curve: The increasing value of x towards infinity will make
the value of y getting nearer and nearer to zero and gets closer and closer to the x-axis
but never touching it). This equates to a condition where the minimum fuse melting
threshold is not met and the fuse does not open; inasmuch as the overcurrent is below
or just slightly below the fuse's melting threshold.
The Current Limiting Fuse's peak let-through is the CLF's instantaneous value. The
I2t average let-through value is the thermal energy produced during the fuse element's
opening. The equation I2t is the square of the current multiplied by the time. It is
proportional to the energy and magnetizing forces cause by a fault, generating heat and
opening the fuse element. The I2t information of a fuse is provided by manufacturer's
data sheet for coordinating the upstream and downstream of an electrical network.
To minimize the damage to electrical equipment during a fault, use a CLF with lower let-
through current than the available short circuit current of the system.
CFLs in Series
Current Limiting Fuses limits the very high fault current to a lesser value (let-through
current) in areas where there is a substantial increase in available short circuit current
due to the addition of new reactive loads. This condition renders the circuit breaker's
interrupting rating become marginally low for the system. Instead of replacing the circuit
breaker, which entails a major investment cost, the Current Limiting Fuse is used and
installed before and in series with the circuit breaker.
Available short circuit current increases through the years due to addition of motor or
other reactive loads in the facility that was not foreseen earlier. Another contributing
factor is the increased available short circuit at the utility side due to new industrial
facilities connected to them.
Another factor is the high available short circuit in the area during the design stage of a
substation or switching facility. The designer opts to use CLF instead of resorting to
impedance grounding or using expensive breakers with high interrupting ratings.
CFLs are usually applied in the incoming feeder to raise the circuit breaker's interrupting
rating; or used in conjunction with Load Break Switches or Automatic Transfer Switches
since a properly sized current limiting fuse limits the short-circuit current to within the
withstand rating of the switch contacts.
Using CFLs do not mean no damage to some electrical auxiliaries, i.e. contacts,
bimetals or other minor parts, unless they have been designed as a combo unit, rated
and tested accordingly by the manufacturer.
Fuses have different operating time. A standard fuse may require to reach 2X its rated
value to open the protected circuit in about 1 sec., while the fastblow fuse at twice its
rated value, will open the circuit in about 0.1 sec or less. Fastblow blow fuses are the
commonly used fuses. They are used in circuitry where a delay in the opening of a
protected circuit during a fault can cause considerable damage to costly electrical or
electronic equipment.
110kV, 50hz oil circuit breaker MKP-110 for 110kV/3.3kV DC Traction Substation,
Toliatti City Railway, Russia. Courtesy of Wikimedia OS Author: Vivan755 - March 2011
Slow blow fuses, or time delay fuses or anti-surge fuses, on the other hand, are
commonly used in combination with motors. Motors have high starting current; and
motors that have loads when started have starting current that can approach the "locked
rotor" current in its time-current characteristic curve.
Non-time delay fuses are referred by NEC as single element fuses. This fuse type will
not open under normal conditions as long as the inrush current of the motor (eg.,
starting current) will not exceed the fuse's rating. They are sized 300% of the Ifl of the
motor per NEC Table 450-152 with exception #2 of Art. 430-52 allowing a 400% I fl.
Low Voltage Dual Element Fuses
Low voltage dual element fuses have two series connected elements enclosed in a
single tube to provide instantaneous short circuit protection with the other providing time
delay function under normal load. The disadvantage of this fuse is the downtime that is
loss to replace it. Its advantage is it provides the motivation by operations personnel to
determine the exact cause of the fault. The type of the fuse's enclosure including
ambient temperature should also be taken into account.
Fuse overload conditions have maximum operating times defined in accordance with
industry standards in terms of its time delay characteristic at a certain percentage of
overload. Lab testing of fuses establishes parameters and data that are used to
construct the fuse's time-current curves based on RMS current at 0.1 second or more. It
also establishes the fuse element's average minimum melting time to clear an overload
condition.
Fuses have different operating time. A standard fuse may require to reach 2X its rated
value to open the protected circuit in about 1 sec. while fast blow fuse, at twice its rated
value will open the circuit in about 0.1 sec or less. Fast blow fuses are the commonly
used fuses in circuits where a delay in the opening of a protected circuit during a fault
can cause considerable damage to costly electrical equipment.
Slow blow fuses, or time delay fuses or anti-surge fuses, on the other hand, are
commonly used in combination with motors. Motors have high starting current especially
those that have loads when started where starting current can approach the locked rotor
current of a motor during starting.
Temperature Derating
Class CC
Class CC fuses are rated to interrupt a minimum of 200,000 amps and are rated for
600 volts . These small branch circuit fuses have overall dimensions of 13/32” x 1-1/2”.
They are available from 1/10 amp through 30 amps.
Class G
Class G fuses are rated for 480 volts and are rated to interrupt a minimum of 100,000
amps. The fuse diameter is 13/32” while the length varies from 1-5/16” to 2- 1/2”. These
are available in ratings from 1 amp through 60 amps.
Class H
Class H fuses are rated to interrupt a minimum of 10,000 amps. The voltage ranges
from 250 and 600 volts. These fuses can be either renewable or non-renewable. These
are available in amp ratings of 1 amp through 600 amps.
Class J
Class J fuses are labeled “Current-Limiting” and are not interchangeable with other
classes. Voltage rating is 600 volts and rated to interrupt a minimum of 200,000 amps
Summary of Protective Devices and Their Ratings Reference: Electric Power System
Protection and Coordination by: Michael Anthony - University of Michigan.
Class K
Class K fuses are current limiting fuses. They have interrupting ratings of 50,000,
100,000, or 200,000 amps. The fuses are listed as K-1, K-5, or K-9 fuses. Each
subclass has designated I2t and Ip maximums. They have the same dimensions as
Class H fuses. They are "current-limiting" fuses but they are not marked as so.
Class L
Labeled "Current-Limiting" Class L fuses are rated 600 volts AC. These fuses are rated
for 600A to 6,000A with interrupting capacity of 200,000 amperes AC. They are bolt
mounted.
Class R
Class R fuses have 250Volts to 600Volts rating and are marked "Current-Limiting."
These fuses have a minimum of 200,000Amps interrupting rating. They have similar
dimension as the Class H fuse but fuses with lower interrupting capacity cannot be
mounted on the Class R mounting clips.
Class T
Class T fuses have a time-lag characteristic, fast acting and with an interrupting rating
of 200,000Amps RMS. These are small fuses suited for limited spaces. They are rated
300Volts to 600Volts RMS (Root-Mean-Square).
These fuses interrupt current ranges from their minimum breaking current to their rated
breaking capacity as specified by the manufacturer.
These fuses will interrupt all currents from rated breaking capacity down to marginally
small but continuous overcurrent that accumulates enough heat within an hour to melt
the fuse element.
Interrupts any current below rated breaking capacity by total melting of the fuse
element.
These fuses have several series arcs and longer element strips to interrupt the high
voltage arching when the fuse element opens. The element strip for this fuse could be
as long as 1 meter and is wound around a star-shaped ceramic core with the distance
of each turn carefully taken into consideration to mitigate possible flash over between
them. The wound ceramic core is then then fitted to fuse cartridge long enough to
accommodate it.
↑Top
Non-Current Limiting Fuses
High voltage fuses have two classes classified under international standards. They
are:
1. Expulsion fuses - These fuses are for outdoor applications - only - for the protection
of high voltage transmission and distribution system. This fuse has a thin element in
series with a flexible braid in the fuse cartridge. The fuse is mechanically designed so
that the braid is under constant spring tension. When the fuse element melts under
heavy fault current, the braid is released activating a latch that will cause the fuse to
disengage and fall downward. This mechanical action causes the arc to fully extinguish
effectively preventing a restrike.
2. Liquid Fuse Link - The strip element of these fuses is fitted in a fuse cartridge filled
with high dielectric liquid with a spring or a strain wire that secures the element under
tension. The spring provides immediate separation when the fuse element melts. The
high dielectric liquid provides the immediate quenching action. These fuses are the
early type of non-current limiting fuses
1. Oil Circuit Breakers - Arching between the contacts of the circuit breaker is
quenched by mineral oil. Arc chambers are use to quench the arc at the shortest time
possible. Arc duration last from 0.02 - 0.05 sec.
2. Vacuum Circuit Breakers - The contacts of this circuit breaker are hermetically
sealed in a vacuum container with contacts separated by bellows. The arc is produced
by metallic vapor boiled from the electrodes and extinguished when the vapor particles
condense on solid surfaces.
3.Sulfur hexafluoride or SF6 Gas Circuit Breakers - Circuit breaker technology has
greatly changed from 1950's to current time. The SF 6 circuit breaker contacts are
separated by the SF6 gas. Arc caused by contact separation is interrupted and cooled
by the gas. The SF6 gas in the envelop should have the correct pressure in order to
achieve this. It is for this reason that SF 6 gas in the envelop should be constantly
monitored for correct pressure. Ring Main Units are good example of medium voltage
SF6 switchgears.
Circuit Breaker Interrupting Rating and Interrupting Capacity
Interrupting Rating
It is the circuit breaker’s maximum short circuit current that can be safely interrupted
under test conditions. Under test conditions simply mean it is the breaker’s tested
condition.
Properly selecting the interrupting rating of a circuit breaker can bring so many
concerns to one specifying it, since there are so many current values to evaluate and
consider. However, knowing the RMS (root mean square) symmetrical rating of the
system together with percent power factor (%pf) or, alternately X/R ratio and the circuit
breaker’s interrupting rating will suffice. Asymmetrical RMS, peak asymmetrical currents
are reliant on %pf or X/R ratio and thus can be neglected.
For more information please see Determining Power Circuit Breaker Interrupting
Ratings - Eaton
Interrupting Capacity
Typical installation of Capacitor Trip Device. Source: Time Mark Capacitor Trip
Devices .pdf
Our topic on circuit breakers would be incomplete without mentioning Capacitor Trip
Devices (CTDs), which are DC voltage storage devices used to trip a medium
voltage circuit breaker when the control transformer, such as 34.5kV/240V or
4.16kV/240V, etc., connected to the AC primary power supply is loss during a fault,
unavailable, or may become lower than the normal voltage level needed to effect
tripping of the circuit breaker. CTDs provide a good alternative, since circuit breaker
tripping elements are impulse loads that require only a brief electrical pulse for it to
actuate. A CTD is composed of series resistors and half-wave rectifier diodes
connected to the secondary of a control transformer to the capacitor with the resistors
acting as charging current limiters. Capacitor type used is electrolytic type.
The voltage stored in the capacitor is maintained at about 300VDC when connected to a
220VAC secondary of a control transformer, and discharges slowly when the AC power
supply is loss. When a tripping signal is received at this stage, the capacitor stored
voltage is discharged to the circuit breaker tripping elements. To accomplish this, CTD
design must still have sufficient capacity when control voltage falls to its minimum
voltage range as defined in ANSI C37.06, and must be capable of effecting a trip 2
seconds after the power supply is removed. CTD manufacturers exceeds this
requirement by a good margin by testing their CTDs from 2 to 10 seconds. Some CTDs
now have backup batteries. CTDs are also used to actuate the breaker lockout relay
Device #86 that's also supplied by the control transformer. This, however would require
two CTDs, one for tripping the circuit breaker, and one for locking-out the circuit
breaker, since CTDs do not allow multiple loads.
The advantages of CTDs include economy of installation for small MV/LV substations in
isolated or remotely located areas where the battery becomes a costly option in terms of
initial cost and maintenance and its suitability for outdoor installation. Its disadvantages
are: no breaker status indicating lights, no DC power supply for communication
equipment; uneconomical for use in large substations; and uses limited life electrolytic
capacitors that changes in value over time. For this reason, CTD’s must be checked
from time to time, with care, by discharging the capacitor using 500ohms 5 to10 watt
resistor across its terminals.