Medium & Low Voltage Distribution

ECOFIT
Modernisation of switchboards
TM

Green is our colour


Catalogue 2015
TM

ECOFIT

Index

1
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage ECOFIT™ solutions

How to find an ECOFIT™ solution?

 1. Select the " generic family ".  2. Select the " Panel type ".  3. Select the " Original device type ".

 1.  2.  3.


Original Brand MV CB or MV Panel MV Panel type Original device type New device type Ref. ECOFIT™ Flyer Page
Contactor or Cradle centre SERED N°
Disconnector to Cradle
USA
Square D ✓ 5-15 kV MC switchgear VAD2-3 Magnum CB 111036EN A-2
West Chester
All brands ✓ All with fixed CB All fixed CB types HVXUW DE Regensburg 111102EN A-3

Alsthom ✓ Alliance FP - GFA FP - GFA FR Macon 111122EN A-4   NEW


LF2 - LF3 - SF1 -
Merlin Gerin ✓ Belledonne B200-B400 DSE22 to DSE78 FR Grenoble 111009EN A-5
Evolis
Merlin Gerin ✓ Belledonne B200G DSE22K-DSE23K LF1 - Evolis FR Grenoble 111010EN A-6
LF1 - R400 - R400D
Merlin Gerin ✓ Belledonne B650 DIS FR Grenoble 111007EN A-7
- Evolis
Merlin Gerin ✓ Belledonne B900 DIS SF1 FR Grenoble 111008EN A-8
AEI,
✓ BVP 17 BVP 17 VMX UK Warrington 111060EN A-9
GEC Alsthom
Cemabloc-
CEM ✓ CB FP FR Mâcon 111026EN A-10
C23mc 15 & 27
Cemabloc-
CEM ✓ CB HVX FR Mâcon 111027EN A-11
C23mc 15 & 27
Cemabloc-
CEM ✓ CS - CX - FPR FPR FR Mâcon 111028EN A-12
C26.0
Nuova Magrini
✓ Composit MG SF1 IT Stezzano* 111048EN A-13
Galileo
VEB
✓ CSIM 1-12 SCI-4 VEIVACUUM F DE Regensburg 111044EN A-14
Otto Buchwitz
VEB
✓ CSIM 3-12 SCI-4 VEIVACUUM F - VA DE Regensburg 111073EN A-15
Otto Buchwitz
AEG ✓ D-12 BAL - VAA - VA VAA - VA DE Regensburg 111075EN A-16

AEG ✓ D-24 BAL - VAA VAA DE Regensburg 111077EN A-17

Alsthom ✓ DNF4-2E FP - GFA FP - HVX - CVX FR Mâcon 111088EN A-18

Alsthom ✓ DNF4 MI&FI FP FP - HVX FR Mâcon 111089EN A-19

Alsthom ✓ DNF5/DNF5-2B FP FP - HVX FR Mâcon 111092EN A-20

Alsthom ✓ DNF6 FP FP - HVX FR Mâcon 111093EN A-21

Alsthom ✓ DNF7 FP FP - HVX-O 2


FR Mâcon 111090EN A-22
Nuova Magrini
✓ Epoclad DHF -F LF1 - LF2 - LF3 - SF1 IT Stezzano* 111049EN A-23
Galileo
Merlin Gerin ✓ Fluair F100-F200 FG1 - FG2 LF2 - LF3 - Evolis FR Grenoble 111012EN A-24

Merlin Gerin ✓ Fluair F100C R400-R400D R400 - R400D FR Grenoble 111013EN A-25

Merlin Gerin ✓ Fluair F300 FG3 SF1 - SF2 FR Grenoble 111101EN A-26

Merlin Gerin ✓ Fluair F400C FC4 SF2 FR Grenoble 111014EN A-27

Merlin Gerin ✓ Fluair F400G FG4 SF1 - SF2 FR Grenoble 111015EN A-28
GEC, GEC
Alstom, Alstom
✓ Fluokit M24 FP FP FR Mâcon 111138EN A-29   NEW
GEC, GEC   NEW
✓ Fluokit M24 + FP FP FR Mâcon 111141EN A-30
Alstom, Alstom
GEC, GEC   NEW
✓ Fluokit M36 FP FP FR Mâcon 111136EN A-31
Alstom, Alstom
Delle Alsthom ✓ FLUOMATIC F540 FR62 FP62 FR Mâcon 111029EN A-32

Delle Alsthom ✓ FLUOMATIC F943 FR62 BLV FR Mâcon 111030EN A-33

AEG ✓ GS-10 GE VA - VAA DE Regensburg 111041EN A-34


HMC 400 - HMC 400 -
GEC Alstom ✓ HMC 400 & HMC 410 UK Warrington 111061EN A-35
HMC 410 HMC 410
GEC Alstom ✓ HMC 1072 HMC 1072 HMC 1072 UK Warrington 111062EN A-36

GEC Alstom ✓ HMC 1172 HMC 1172 HMC 1172 UK Warrington 111063EN A-37

GEC Alstom ✓ HMX 36 HMX 36 HMX36 UK Warrington 111064EN A-38


Concordia
✓ HP HP-W-TW-TM HVX DE Regensburg 111078EN A-39
Sprecher
CEM ✓ KIT 25-PGDt CC FP FR Mâcon 111031EN A-40

CEM ✓ KIT 27.2-PGHt HF4K FP FR Mâcon 111032EN A-41

2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
 1.  2.  3.
Original Brand MV CB or MV Panel MV Panel type Original device type New device type Ref. ECOFIT™ Flyer Page
Contactor or Cradle centre SERED N°
Disconnector to Cradle
AEG ✓ L D-E HVX DE Regensburg 111043EN A-42

Federal Pioneer ✓ Metalclad switchgear DST 2 & 5 DST 2V & 5V CA Toronto* 111067EN A-43

Merlin Gerin ✓ Motorstart P50D C - CD R400 - R400D - CTV1 FR Grenoble 111005EN A-44

Merlin Gerin ✓ Motorstart P500D C1 - CD1 R400 - R400D - CTV1 FR Grenoble 111006EN A-45

GEC Alstom ✓ MX 51 & MX 81 MX 51 - MX 81 MX 51 - MX 81 UK Warrington 111065EN A-46

Delle Alsthom ✓ Normabloc N1347 HL HVX - FPX FR Mâcon 111033EN A-47


GEC, GEC
Alstom, Alstom
✓ Normaclad PX FPX FPX FR Mâcon 111139EN A-48   NEW

Delle Alsthom ✓ Normasept N743 HL FP FR Mâcon 111034EN A-49

Alsthom ✓ PIX 12 - 24 FPX FPX FR Mâcon 111124EN A-50   NEW


GEC, GEC
Alstom, Alstom
✓ PIX SF6 FPX FPX FR Mâcon 111137EN A-51   NEW

AEG ✓ PNX 36 HVX 36 HVX 36 DE Regensburg 111127EN A-52   NEW


IMC - MC - FAL - IFAL
AEG ✓ R - VA - VAA - IVA - BAL VA - VAA - Contactor DE Regensburg 111042EN A-53
- ALF - AL - TG
Ansaldo ✓ Siclad MAG II LF1 - LF2 IT Stezzano* 111050EN A-54
Solenarc DSE Metal- USA
Square D ✓ DSE Magnum CB 111037EN A-55
Clad switchgear West Chester
Nuova Magrini
✓ Venus GI-GL LF1-LF3 IT Stezzano* 111051EN A-56
Galileo
GEC, GEC   NEW
✓ VISAX BLV BLV FR Mâcon 111140EN A-57
Alstom, Alstom
Merlin Gerin ✓ VM6 DM12 FB4 SF1 FR Grenoble 111018EN A-58

Merlin Gerin ✓ VM6 DM22-DM23 FB4 SF1 FR Grenoble 111017EN A-59


GEC, GEC
✓ VMX VMX VMX UK Warrington 111096EN A-60
Alstom, Alstom
AEG ✓ WAK D-E HVX DE Regensburg 111040EN A-61
VA - VAA - ECA - BAL
AEG ✓ WBA VA - VAA - Contactor DE Regensburg 111082EN A-62
- AL
VA - VAA - ECA - BAL
AEG ✓ WBB VA - VAA - Contactor DE Regensburg 111084EN A-63
- AL
AEG ✓ WBD VA - VAA - HVX VA - VAA DE Regensburg 111129EN A-64   NEW

AEG ✓ WK (C/E/B/A) VA - MC - BAL VA - VAA - Contactor DE Regensburg 111086EN A-65


Yorkshire
✓ YSF6 YSF6 YSF6 Evolis UK Warrington 111066EN A-66
Switchgear
AEG ✓ D-12 D-12 panel D-12 panel DE Regensburg 111074EN A-68

AEG ✓ D-24 D-24 panel D-24 panel DE Regensburg 111076EN A-69

Alsthom ✓ DNF7 DNF7 panel DNF7 panel FR Mâcon 111100EN A-70

Merlin Gerin ✓ F100/200 F100/200 panel F100/200 panel FR Grenoble 111071EN A-71

Merlin Gerin ✓ F100C F100C panel F100C panel FR Grenoble 111072EN A-72

AEG ✓ PNX36 PNX36 PANEL PNX36 PANEL DE Regensburg 111126EN A-73   NEW
Alstom ✓ PX 12-24 PX 12-24 panel PX 12-24 panel FR Mâcon 111091EN A-74

AEG ✓ R R panel R panel DE Regensburg 111079EN A-75

GEC Alstom ✓ VISAX VISAX PANEL VISAX PANEL UK Warrington 111123EN A-76   NEW
GEC, GEC
✓ VMX VMX panel VMX panel UK Warrington 111097EN A-77
Alstom, Alstom
AEG ✓ WBA WBA panel WBA panel DE Regensburg 111081EN A-78

AEG ✓ WBB WBB panel WBB panel DE Regensburg 111083EN A-79

AEG ✓ WBD WBD panel WBD panel DE Regensburg 111128EN A-80   NEW
AEG ✓ WK WK panel WK panel DE Regensburg 111085EN A-81

All brands ✓ All All breaker types Evolis MC Cassette FR Grenoble 111105EN A-82

All brands ✓ All All breaker types F400 Cassette FR Grenoble 111106EN A-83

* Not current ECOFIT™ reference centre

3
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage ECOFIT™ solutions

How to find an ECOFIT™ solution?

 1. Select the " generic family ".  2. Select the " Panel type ".  3. Select the " Original device type ".

 1.  2.  3.


Original Brand LV CB or LV Drawer Panel type Original device type New device type Ref. ECOFIT™ centre Flyer Page
Contactor SERED N°

Nuova Magrini
✓ NA B Control Masterpact NW IT Stezzano* 111053EN B-2
Galileo

Merlin Gerin ✓ NA Compact C801-C1251 Compact NS FR Grenoble 111022EN B-3

Merlin Gerin ✓ NA DA Masterpact NW FR Grenoble 111019EN B-4

USA
Square D ✓ NA DS Masterpact NW 111038EN B-5
West Chester

Federal Pioneer ✓ NA H series Masterpact NT - NW CA Toronto* 111068EN B-6

Merlin Gerin ✓ NA Masterpact M Masterpact NW FR Grenoble 111021EN B-7

Square D, USA
✓ NA SE Masterpact NW 111039EN B-8
Westinghouse West Chester

Merlin Gerin ✓ NA Selpact Masterpact NT - NW FR Grenoble 111020EN B-9

Unelec-Areva ✓ Normabloc 660 Unelec CNP Masterpact NW FR Grenoble 111023EN B-10

Merlin Gerin ✓ NA Visucompact CM Masterpact NW FR Grenoble 111024EN B-11

Merlin Gerin ✓ T140 T140 drawers T140 drawers FR Grenoble 111094EN B-13

Merlin Gerin ✓ MB400 MB400 drawers MB400 drawers FR Grenoble 111095EN B-14

* Not current ECOFIT™ reference centre

4
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Protection relays ECOFIT™ solutions

How to find an ECOFIT™ solution?

 1. Select the " generic family ".  2. Select the " Panel type ".  3. Select the " Original device type ".

 1.  2.  3.


Original Brand Protection relay Panel type Original device type New device type Ref. ECOFIT™ centre Flyer Page
SERED N°

GE ✓ CO MiCOM P111/115 CA EAC Canada* 111131EN C-3   NEW


CDG - CAG - CTMM - MiCOM P1x-P2x
Alstom ✓
CTMFM or Vamp 5x
IN EAC India* 111147EN C-4   NEW

ABB ✓ DPU 445 MiCOM P123 CA EAC Canada* 111134EN C-5   NEW

ABB ✓ HCB MiCOM P521 CA EAC Canada* 111133EN C-6   NEW

GE ✓ IAC MiCOM P122 CA EAC Canada* 111132EN C-7   NEW


GEC Alstom,
✓ All KCGG 122 & 142 MiCOM P123R FR Lattes* 111070EN C-8
Areva
M range -
Areva or older ✓ all / draw out MiCOM P120H CA EAC Canada* 111104EN C-9
MCGG 11, 21 & 22
M range relay
Areva or older ✓ all / draw out MiCOM P821MF CA EAC Canada* 111103EN C-10
MCTI 39-40

Alstom ✓ MCGG 62 MiCOM P126 CA EAC Canada* 111135EN C-11   NEW

Merlin Gerin ✓ All Sepam 2000 Sepam 60/80 FR Lattes* 111087EN C-12

Merlin Gerin ✓ RM6+ VIP VIP + ECOFIT™ kit FR Grenoble 111046EN C-13   NEW

Merlin Gerin ✓ Various equipment VIP & Vigirex VIP & Sepam FR Grenoble 111146EN C-14   NEW

* Not current ECOFIT™ reference centre

Substation automation ECOFIT™ solutions

How to find an ECOFIT™ solution?

 1. Select the " generic family ".  2. Select the " Original device type ".

 1.  2.
Original Brand Control System Original device type New device type Ref. ECOFIT™ centre Flyer Page
SERED N°

AREVA or older ✓ Bay Controler BM9x00 MiCOM C624 FR EAC Lattes* 111144EN D-3   NEW
PACIS OI
AREVA or older ✓ PACiS EcoSUI FR EAC Lattes* 113543EN D-4
(V3.x up to V4.6)

AREVA or older ✓ PSCN3020 HMI EcoSUI HMI FR EAC Lattes* 113562EN D-5

Schneider
Electric
✓ Seefox HMI EcoSUI HMI FR EAC Lattes* 111143EN D-6   NEW

* Not current ECOFIT™ reference centre

5
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
PE90457

TM

ECOFIT

Contents

6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
ECOFITTM

Contents

Medium Voltage Distribution A-1

Low Voltage Distribution B-1

Protection relays C-1

Substation automation D-1

7
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
TM

ECOFIT

What does
that mean?

8
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Schneider Electric is helping
you get the most of your
equipment and installations
Schneider Electric helps you
define and implement the best
solution evolvement, increasing
performance and flexibility, while
controlling aging infrastructures
associated costs.

ew
Ren

How do I
renew my Pla
What are n
solution? my options?
Optimize

Asset
Management
How do I Life Cycle How do I
optimize? install and
commission?

How do I
operate and
a ll
st

maintain?
In

Op
e ra
te

ECOFITTM is the economical


complement to maintenance
operations

"Green is our colour" - ECOFIT TM


is the most economical means of reducing your network’s environmental footprint
without buying a whole new system

9
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
TM

ECOFIT

For which
benefits?

10
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Optimisation
with minimal shutdown
COSTS

TM
ECOFIT Local competitors New Equipment

Cost of process downtime

Material cost

Site work cost

• Enhances your process dependability.


• Optimizes your maintenance service costs & limits your investments.
• Maintains compliance with evolving industry standards and legislation.
• E nsures the safety of your personnel and surrounding equipment by using the latest technology.
• Access to Energy Management.

11
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
TM

ECOFIT

ECOFIT ™

reference
centers?

12
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Our main legacies and ECOFIT™
reference centers brand
responsibilities
FRANCE FRANCE GERMANY UK USA ITALY CANADA
BRAND
Grenoble Mâcon Regensburg Warrington West Chester Stezzano* Toronto*

✓ ✓ ✓ ✓

✓ ✓

✓ ✓

Competitors ✓ ✓ ✓ ✓ ✓ ✓ ✓
* not current ECOFIT™ reference centre

ECOFIT™ Reference Centers are in charge of


•D
 esign and development of ECOFIT™ offers using Schneider Offer Creation Process methodology.
• Industrialise, manufacture and optimise
ECOFIT™ offers to answer
the customers’ requests with optimum conditions.

• T est, validation and certification of ECOFIT™ offers using a standard quality directive procedure linked to
international standards.

13
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
TM

ECOFIT EOL

EOL,
the complementary
offer

14
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
End-of-life:
environment in mind!
In complement to ECOFIT™, EOL our high
environmental treatment package: recovery
and recycling for re-use of all medium-voltage
equipment, including SF6 gas.

• 98% of a medium-voltage cubicle can be recovered

•legal SF6
a requirement for the , an

environmental duty

EOL's 1. Collection of medium-voltage equipment from your site.


4 steps
2. Dismantling of the equipment in a Schneider Electric factory. The different
ferrous and non-ferrous materials (copper, aluminium, etc.) are separated and
sent to specialised recycling centres.

3. When applicable, the SF6 is evacuated until the residual pressure is


less than 20 mbar, in accordance with the IEC standard, using adequate
engineered tools. The gas is stored in bottles before being sent for recycling.
The epoxy enclosure is crushed for recovery purposes.

4. A certificate of destruction compliant with the regulations is sent to you.


15
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Benefit from
Schneider Electric’s
image and know-how
Quality certified ISO 9001
PE56733

A major strength
In each of its units, Schneider Electric has an operating organization
whose main role is to verify quality and ensure compliance with
standards. This procedure is:
• uniform for all departments;
• recognized by numerous customers and official organizations.
But, above all, its strict application has made it possible to obtain
the recognition of independent organizations.
The quality system for design and manufacturing is certified in
compliance with the requirements of the ISO 9001 Quality Assurance
model.

Stringent, systematic controls


During its manufacture, each equipment item undergoes systematic
routine tests to verify its quality and compliance:
• measurement of operating capacity and tolerances;
• measurement of losses;
• dielectric testing;
• checks on safety and locking systems;
• checks on low-voltage components;
• verification of compliance with drawings and diagrams.
The results obtained are recorded and initialled by
the Quality Control Department on the specific test certificate
for each device.

Quality & Environment


Schneider Electric undertakes to reduce the
energy bill and CO2 emissions of its customers
by proposing products, solutions and services
which fit in with all levels of the energy value
chain.
At the same time, Schneider Electric strives
to reduce the environmental impact of
its products throughout their entire life-cycle
(from cradle to grave), particularly through eco-
design and eco-production.

16
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Schneider Electric’s policy has always been to provide
Our common values : its customers with very close support in their daily
• Quality activities to enable them to achieve operational
excellence.
• Safety
• Professionalism The experience of
a world leader in Low & Medium
5% of sales Voltage
devoted to R & D Schneider Electric has been manufacturing LV and MV products for
more than 50 years and its installed base amounts to thousand millions

Local support products and devices.


The Schneider Electric brand is known worldwide and recognized
all over the world. by the most demanding customers.
There are always
Schneider Electric people A long history of innovation
close to you:
6200 Services people for a global offer
Based on this experience as world leader, Schneider Electric has
in more than developed a large and comprehensive range of innovative devices.

88 countries!
With one of the world leaders, you take benefit of a global leader
experience and know-how in electric distribution, automation and Power
& Control.

More than All the devices included in this overview have been designed
and manufactured to incorporate the benefits of this extensive

50,000 ECOFIT™ in
experience.

services/delivered Schneider Electric


in various business segments
a brand you can trust
ED equipment obsolescence and unavailability of spare parts
The only solution to extend Electrical Distribution (ED) equipment life cycle is by carrying out an intense maintenance while
planning a modernisation solution thanks to ECOFIT solution.
There are three major phases in the product life cycle:
1. Commercialisation period: The product is launched onto the market and is included in the Schneider Electric catalogue.
2. Full spare parts availability period: The product is withdrawn from the market. Schneider Electric continues to
supply spare parts for a period of time. Generally speaking, the average full spare part supply period after the end of
commercialisation is :
• Medium Voltage equipment: 12 years.
• Low Voltage equipment: 10 years.
When the end of the full spare part supply date is reached, the product is considered have be expired.
3. Modernisation period with ECOFIT™ solution: As of the full spare part supply date, the product is considered
to have expired. Spare part stock and supply are no longer guaranteed after the end of spare part supply date.
Maintennance costs

Corrective, Preventive, Predictive Maintenance


and spare parts guaranteed

Modernisation
Product life

Installation End of End of full End of End of


& commissioning commercialisation spare parts spare parts Services
availability

17
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
PE90457

TM

ECOFIT
Medium
Voltage
Distribution
Medium Voltage Distribution

Contents
MV CB or Contactor or Disconnector MV Panel
5-15 kV MC switchgear A-2 D-12 A-68
All with fixed CB A-3 D-24 A-69
Alliance A-4 DNF7 A-70
Belledonne B200-B400 A-5 F100/200 A-71
Belledonne B200G A-6 F100C A-72
Belledonne B650 A-7 PNX36 A-73
Belledonne B900 A-8 PX 12-24 A-74
BVP 17 A-9 R A-75
Cemabloc-C23mc 15 & 27 A-10 VISAX A-76
Cemabloc-C23mc 15 & 27 A-11 VMX A-77
Cemabloc-C26.0 A-12 WBA A-78
Composit A-13 WBB A-79
CSIM 1-12 A-14 WBD A-80
CSIM 3-12 A-15 WK A-81
D-12 A-16
D-24 A-17 MV Cradle to Cradle
DNF4-2E A-18 All A-82
DNF4 MI&FI A-19 All A-83
DNF5/DNF5-2B A-20
DNF6 A-21
DNF7 A-22
Epoclad A-23
Fluair F100-F200 A-24
Fluair F100C A-25
Fluair F300 A-26
Fluair F400C A-27
Fluair F400G A-28
Fluokit M24 A-29
Fluokit M24+ A-30
Fluokit M36 A-31
FLUOMATIC F540 A-32
FLUOMATIC F943 A-33
GS-10 A-34
HMC 400 & HMC 410 A-35
HMC 1072 A-36
HMC 1172 A-37
HMC 36 A-38
HP A-39
KIT 25-PGDt A-40
KIT 27.2-PGHt A-41
L A-42
Metalclad switchgear A-43
Motorstart P50D A-44
Motorstart P500D A-45
MX 51 & MX 81 A-46
Normabloc N1347 A-47
Normaclad PX A-48
Normasept N743 A-49
PIX 12 - 24 A-50
PIX SF6 A-51
PNX 36 A-52
R A-53
Siclad A-54
Solenarc DSE Metal-Clad switchgear A-55
Venus A-56
VISAX A-57
VM6 DM12 A-58
VM6 DM22-DM23 A-59
VMX A-60
WAK A-61
WBA A-62
WBB A-63
WBD A-64
WK A-65
YSF6 A-66

A-1
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

5 - 15 kV MC switchgear / VAD2 - 3 by MAGNUM


Original brand: Square D

ECOFIT™ proposal
PE90542

PE90543

With ECOFIT™, a true extended life time


< 1985 1995 2004 2006

VAD2-3

Magnum

VAD2-3 ECOFIT™ solution


Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90544

Main technical characteristics


VAD2 VAD3 VAD2 VAD3
Rated current (Ir) 1200 - 3000 A
Magnum Short circuit current (Isc) 29 kA 41 kA 18 - 28 kA 37 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 5 kV 15 kV

Magnum 5SSB Magnum 15SSB Magnum 5SSB Magnum 15SSB

Technology Vacuum Vacuum Rated current Ir (A) 1200 - 3000 1200 - 3000


Rated voltage Ur (kV) 5 15 Short circuit current Isc (kA) 29 - 41 18 - 28

Surge withstand voltage Up (kV) 60 95 Switching sequence O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO


Nominal frequency (Hz) 60 60 Opening time (ms) 60 60

Magnum CB main characteristics


Built with totally new components and tested to ANSI standards, Magnum circuit breakers correctly interface with
the existing breaker compartment components and maintain safety interlocks inherent in the original equipment
design.
• New circuit breakers are installed in existing switchgear.
• Original footprint is left intact, saving time and money.
• Installation expense is a fraction of new equipment costs.
--Less down time for installation.
--Enhanced equipment reliability.
• Manufactured with new components.
• Undergoes complete factory testing.
• Backed by our standard equipment warranty.
• New, easy-to-maintain operating mechanism.
• No bulky arc chutes to handle and maintain.
• Reduced need for difficult to obtain spare parts.

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90542

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

All with fixed CB / All fixed CB types by HVXUW


Original brand: all brands

All breaker
ECOFIT™ proposal
types
Compatible with With ECOFIT™, a true extended life time
all open Air
Insulated
Switchgear legacy This solution consist in fitting a cradle inside an existing panel.
and no legacy - It is particularly adapted for non Schneider Installed Base.
cubicles
with minimum - ECOFIT™ solution with shutters and mechanical interlocks embedded.
inside panel
width ≥ 650 mm - Only the fixed connections (between the cradle and existing busbar) are customized.
- No age condition of the existing equipment.
- Only the width of the existing panel has to be considered.
PE9075

Main technical characteristics


All types
Rated current (Ir) 630 - 2500 A
Withdrawable
HVXUW Short circuit current (Isc) Up to 31.5 kA Up to 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV 24 kV

HVXUW HVXUW

Technology SF6 Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12 - 24

Surge withstand voltage Up (kV) 75 - 125 Closing time (ms) 45 - 63


Nominal frequency (Hz) 50 - 60 Opening time (ms) 35 - 53

Rated current Ir (A) 630 - 2500 Number of switching 10.000


Short circuit current Isc (kA) 16 - 50 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90487

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-3
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

ALLIANCE / FP - GFA by FP - GFA


Original brand: Alsthom

ECOFIT™ proposal
PE90760

With ECOFIT™, a true extended life time


1995 2013 2027

FP - GFA
PE90761

FP - GFA

ECOFIT™ solution

FP -  GFA Commercialisation End of spare parts


Circuit Breaker
PE90761

Main technical characteristics


FP  GFA
Rated current (Ir) 400 - 3150 A 400 A
FP  -  GFA Short circuit current (Isc) 16 - 50 kA 10 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 60 - 75 kV 60 kV

FP GFA FP GFA

Technology SF6 SF6 Switching sequence O-3 min-CO-3 min-CO C/O


CO-15 s-CO
Rated voltage Ur (kV) 7.2  - 12 7.2  O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 60 - 75 60 Closing time (ms) 50 45 - 175
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 70 90 - 120

Rated current Ir (A) 400 - 3150 400 Number of switching 10000 (mechanical) 300000 (mechanical)
Short circuit current Isc (kA) 16 - 50 10 operations

Short circuit duration Tk (s) 1  1  Service temperature (°C) - 25 / + 40 - 25 / + 40


* Class M1: 2000 operations for Isc = 40 kA

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90760

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-4
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Belledonne B200-B400 / DSE22 to DSE78


by LF2 - LF3 - SF1 - Evolis Original brand: Merlin Gerin

ECOFIT™ proposal
With ECOFIT™, a true extended life time
1972 1986 1988 2001
PE90400

DSE22 to DSE78

LF2 - LF3 - SF1 - Evolis

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


DSE22 to DSE78
Circuit Breaker
PE90401

Main technical characteristics


DSE to DSE78
Rated current (Ir) 630 - 3500 A 630 - 3150 A
LF2 - LF3 - SF1 -
Evolis Short circuit current (Isc) 29 - 50 kA 24 - 48 kA 15 - 46 kA 10 - 29 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV 24 kV

LF2 / LF3 LF2 / LF3 SF1 Evolis LF2 LF3 SF1 Evolis

Technology SF6 SF6 SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2 - 12  17.5 24 7.2 - 12 - 17.5 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 - 75 95 125 60 - 75 - 95 Closing time (ms) < 72 < 65 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) < 654 < 50 < 50

Rated current Ir (A) 630 - 3150 630 - 3150 630 - 1250 630 - 2500 Number of switching 10000 10000 10000 10000*
Short circuit current Isc (kA) 29 - 50 29 - 40 10 - 25 40 operations

Short circuit duration Tk (s) 3  3  3  4  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 - 25 / + 40
* class MI: 2000 operations for Isc:40 kA

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90437

Sepam series 10, 20, 40, 60 , 80


PE90415

or
PE90488

MICOMP series 10, 20, 30, 40

A-5
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Belledonne B200G / DSE22K - DSE23K by LF1 - Evolis


Original brand: Merlin Gerin

ECOFIT™ proposal
With ECOFIT™, a true extended life time
1971 1988 1992
PE90403

DSE22K  -  DSE23K
LF1 - Evolis

ECOFIT™ solution

Commercialisation End of commercialisation End of space parts


DSE22K - DSE23K
Circuit Breaker
PE90404

Main technical characteristics


DSE22K - DSE23K
Rated current (Ir) 630 - 1250 A
LF1  - Evolis Short circuit current (Isc) 25 -31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV

LF1 Evolis LF1 Evolis

Technology SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2  7.2  O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 60 Closing time (ms) < 72 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 54 < 50

Rated current Ir (A) 630 - 1250 630 - 1250 Number of switching 10000 2000* - 10.000


Short circuit current Isc (kA) 25 - 31.5 25 - 31.5 operations

Short circuit duration Tk (s) 3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40


* Class M1: 2000 operations for Isc = 40 kA

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90403

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Belledonne B650 / DIS by LF1 - R400 - R400D - EVOLIS


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90396

With ECOFIT™, a true extended life time


1958 1976 1986 1988
PE90397

DIS

LF1 - R400 - R400D - Evolis

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


DIS
Circuit Breaker
PE90398

Main technical characteristics


DIS
Rated current (Ir) 400 - 1250 A
LF1  - R400 - 
R400D - EVOLIS Short circuit current (Isc) 25 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV

LF1 R400 R400D Evolis LF1 R400 R400D Evolis

Technology SF6 SF6 SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2  7.2   7.2   7.2   O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 60 60 60 Closing time (ms) < 72 75 - 155 75 - 155 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) < 54 20 - 50 20 - 50 < 50

Rated current Ir (A) 630 - 1250 80 - 250 80 - 250 630 - 2500 Number of switching 10000 300000 100000 10000
Short circuit current Isc (kA) 31.5 50* 50* 25 - 31.5 operations

Short circuit duration Tk (s) 3  3  3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 - 25 / + 40
* With fuses

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90396

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-7
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Belledonne B900 / DIS by SF1


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90396

With ECOFIT™, a true extended life time


1961 1978 1988 1992
PE90397

DIS

SF1

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


DIS
Circuit Breaker
PE90399

Main technical characteristics


DIS
Rated current (Ir) 400 - 1250 A
SF1 Short circuit current (Isc) 12.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 23 kV

SF1 SF1

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24  O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV)  125 Closing time (ms) < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 50
Rated current Ir (A) 630 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 25 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90396

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-8
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

BVP 17 / BVP 17 by VMX


Original brand: AEI - GEC - GEC Alsthom

ECOFIT™ proposal
PE90604

With ECOFIT™, a true extended life time


1965 1984 2001 2006
PE90605

BVP 17

VMX

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


BVP 17
Circuit Breaker
PE90606

Main technical characteristics


BVP 17
Rated current (Ir) 400 - 1250 A
VMX Short circuit current (Isc) 25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 11 kV

VMX VMX

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 11 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 75 Closing time (ms) < 52
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 61
Rated current Ir (A) 400 - 1250 Number of switching 10.000
Short circuit current Isc (kA) Up to 25 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90604

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-9
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Cemabloc C23mc 15 & 27 / CB by FP


Original brand: CEM

ECOFIT™ proposal
PE90461

With ECOFIT™, a true extended life time


1963 1984 1994 2010
PE90462

CB

FP

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


CB
Circuit Breaker
PE90463

Main technical characteristics


CB
Rated current (Ir) 400 - 1250 A
FP Short circuit current (Isc) 12.5 - 16/25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 23 kV

FP FP

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125 Closing time (ms) 50
Nominal frequency (Hz) 50 - 60 Opening time (ms) 70
Rated current Ir (A) 400 - 3150 Number of switching 10.000
operations
Short circuit current Isc (kA) 12.5 - 40
Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90461

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-10
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Cemabloc C23mc 15 & 27 / CB 6 poles by HVX 6 poles


Original brand: CEM

ECOFIT™ proposal
PE90461

With ECOFIT™, a true extended life time


1963 1984 1994 2010
PE90464

CB 6 poles

HVX 6 poles

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


CB
Circuit Breaker
PE90465

Main technical characteristics


CB
Rated current (Ir) 2500 A
HVX Short circuit current (Isc) 12.5 - 16/25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 23 kV

HVX HVX

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24 CO-15 s-CO
O-0.3 s-CO-15s-CO
Surge withstand voltage Up (kV) 125 Closing time (ms) 35 - 53
Nominal frequency (Hz) 50 - 60 Opening time (ms) 45 - 63
Rated current Ir (A) 630 - 2500 Number of switching 10.000
operations
Short circuit current Isc (kA) 16 - 31.5
Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90461

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-11
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Cemabloc - C26.0 / CS by FPR - C26.1 / CX by FPR - C26.2 /


FPR by FPR Original brand: CEM

ECOFIT™ proposal
PE90466

PE90762

PE90763
With ECOFIT™, a true extended life time
1976 1982 1985 1991
PE90467

CS - CX - FPR

FPR

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


CS
Circuit Breaker
PE90468

Main technical characteristics


CS CX FPR
Rated current (Ir) 400 - 1250 A 400 - 1250 A
FPR Short circuit current (Isc) 14.5 kA 12.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV 24 kV

FPR FPR

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-15 s-CO
Rated voltage Ur (kV) 24

Surge withstand voltage Up (kV) 125 Closing time (ms) 50


Nominal frequency (Hz) 50 - 60 Opening time (ms) 80
Rated current Ir (A) 400 - 1250 Number of switching 10.000
operations
Short circuit current Isc (kA) 12.5
Short circuit duration Tk (s) 1 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90466

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-12
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Composit (860mm width) / MG by SF1


Original brand: Nuova Magrini Galileo

ECOFIT™ proposal
PE90575

With ECOFIT™, a true extended life time


1966 1993 2000 2010
PE90576

MG

SF1

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


MG
Circuit Breaker

Main technical characteristics


PE90232

MG

150-500 150-750 350-750 150-750 350-750


Rated current (Ir) 630 - 1250 A 630 - 1250 A 630 - 1250 A 630 - 1250 A 630 - 1250 A
SF1 Short circuit current (Isc) 8.7 - 28.9 kA 5 - 29 kA 12.5 - 29 kA 3.6 - 24 kA 6.3 - 21.7 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 10 kV 15 kV 17 kV 20 kV 24 kV

SF1 SF1

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 17.5 - 24  O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV)  95 - 125 Closing time (ms) < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 50
Rated current Ir (A) 630 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 25 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90575

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-13
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

CSIM 1-12 / SCI-4 by VEIVACUUM F


Original brand: VEB " Otto Buchwitz "

ECOFIT™ proposal
PE90560

With ECOFIT™, a true extended life time


1975 1991 2006
PE90561

SCI-4

VEIVACUUM F

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


SCI-4
Circuit Breaker
PE90562

Main technical characteristics


SCI-4
Rated current (Ir) 630 - 1250 A
VEIVACUUM F Short circuit current (Isc) 16 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV

VEIVACUUM F VEIVACUUM F

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12

Surge withstand voltage Up (kV) 75 Closing time (ms) 65


Nominal frequency (Hz) 50 - 60 Opening time (ms) 50
Rated current Ir (A) 600 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 25  operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90563

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-14
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

CSIM 3-12 / SCI-4 by VEIVACUUM F - VA


Original brand: VEB " Otto Buchwitz "

ECOFIT™ proposal
PE90640

With ECOFIT™, a true extended life time


1975 1991 2006 2012

SCI-4

VEIVACUUM F - VA
SCI-4
Circuit Breaker ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90641

Main technical characteristics


SCI-4
Rated current (Ir) 630 - 2500 A
VEIVACUUM F - VA Intensity short circuit (Isc) 16 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV

VEIVACUUM F - VA VEIVACUUM F - VA

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12

Surge withstand voltage Up (kV) 75 Closing time (ms) 45 - 65


Nominal frequency (Hz) 50 - 60 Opening time (ms) 45 - 65
Rated current Ir (A) 600 - 3150 Number of switching 10.000
Short circuit current Isc (kA) 25 - 40 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90563

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-15
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

D-12 / BAL - VAA - VA  by VAA - VA


Original brand: AEG

ECOFIT™ proposal
PE90648

With ECOFIT™, a true extended life time


1994 2004

BAL - VAA - VA

VA - VAA 
PE90648

ECOFIT™ solution

BAL - VAA - VA Commercialisation End of commercialisation


Circuit Breaker
PE90650

Main technical characteristics


BAL VAA VA
Rated current (Ir) 200 - 1250 A 200 - 1250 A 1600 A
VAA - VA Intensity short circuit (Isc) 10 - 20 kA 20 - 25 kA 25 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV 12 kV 12 kV

VA - VAA  VA - VAA 

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12 

Surge withstand voltage Up (kV) 95 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 600 - 3150 Number of switching 10.000
Short circuit current Isc (kA) 25 - 31.5 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90649

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-16
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

D-24 / BAL - VAA  by VAA


Original brand: AEG

ECOFIT™ proposal
PE90651

With ECOFIT™, a true extended life time


1994 2004 2013

BAL
PE90651

VAA

VAA

ECOFIT™ solution
BAL - VAA 
Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90650

Main technical characteristics


BAL VAA
Rated current (Ir) 100 - 630 A 630 - 1250 A
VAA  Intensity short circuit (Isc) 10 - 16 kA 16 - 25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV 24 kV

VAA VAA

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 24

Surge withstand voltage Up (kV) 95 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 600 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 10 - 25 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90649

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-17
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

DNF4-2E / FP - GFA by FP - HVX - CVX


Original brand: Alsthom

ECOFIT™ proposal
PE90667

With ECOFIT™, a true extended life time


1983 1997 2007 2009

FP - GFA
PE90668

FP - HVX - CVX

ECOFIT™ solution

FP - GFA Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90669

Main technical characteristics


FP - GFA
Rated current (Ir) 400 - 2000 A
FP  - HVX - CVX Short circuit current (Isc) 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV

FP HVX CVX FP HVX CVX

Technology SF6 Vacuum Vacuum Switching sequence O-3 min-CO-3 min-CO C/O


O-0.3 s-CO-3 min-CO*
Rated voltage Ur (kV) 12 12 12 CO-15s-CO
O-0.3 s-CO-15 s-CO*
O-0.3 s-CO-3min-CO**
Surge withstand voltage Up (kV) 75 75 75 Closing time (ms) 50 35 - 53 40 - 80
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 70 45 - 63 100 - 200

Rated current Ir (A) 400 - 3150 630 - 3150 400 Number of switching 10.000 10.000 300.000 (mech.)
Short circuit current Isc (kA) 12 - 50 16 - 50 4 operations 500.000 (elec.)

Short circuit duration Tk (s) 3  3  1  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40
* HVX only / ** FP only

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90670

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-18
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

DNF4 MI & FI / FP by FP - HVX


Original brand: Alsthom

ECOFIT™ proposal
PE90671

With ECOFIT™, a true extended life time


1983 1997 2007 2010
PE90672

FP 

FP - HVX 

ECOFIT™ solution

FP  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90673

Main technical characteristics


FP 
Rated current (Ir) 400 - 2500 A
FP  - HVX Short circuit current (Isc) 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV

FP HVX FP HVX

Technology SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO


CO-15s-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 12 12 O-0.3 s-CO-3 min-CO CO-15s-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75 75 Closing time (ms) 50 35 - 53
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 70 45 - 63

Rated current Ir (A) 400 - 3150 630 - 3150 Number of switching 10.000 10.000


Short circuit current Isc (kA) 16 - 50 25 - 50 operations

Short circuit duration Tk (s) 3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90671

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-19
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

DNF5 - DNF5-2B / FP by FP - HVX
Original brand: Alsthom

ECOFIT™ proposal
PE90678

With ECOFIT™, a true extended life time


1983 1997 2007 2011
PE90672

FP 

FP - HVX 

ECOFIT™ solution

FP  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90673

Main technical characteristics


FP 
Rated current (Ir) 630 - 2000 A
FP  - HVX Short circuit current (Isc) 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 17.5 kV

FP HVX FP HVX

Technology SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO


CO-15s-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 17.5 17.5 O-0.3 s-CO-3 min-CO CO-15s-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75 75 Closing time (ms) 50 35 - 53
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 70 45 - 63

Rated current Ir (A) 400 - 3150 630 - 3150 Number of switching 10.000 10.000


Short circuit current Isc (kA) 16 - 40 25 - 40 operations

Short circuit duration Tk (s) 3  3 Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90678

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-20
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

DNF6 / FP by FP - HVX
Original brand: Alsthom

ECOFIT™ proposal
PE90679

With ECOFIT™, a true extended life time


1987 1997 2007 2011
PE90680

FP 

FP - HVX 

ECOFIT™ solution

FP  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90673

Main technical characteristics


FP 
Rated current (Ir) 400 - 2000 A
FP  - HVX Short circuit current (Isc) 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

FP HVX FP HVX

Technology SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO


CO-15s-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24 24 O-0.3 s-CO-3 min-CO CO-15s-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75 75 Closing time (ms) 50 35 - 53
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 70 45 - 63

Rated current Ir (A) 400 - 3150 630 - 2500 Number of switching 10.000 10.000


Short circuit current Isc (kA) 16 - 40 25 - 40 operations

Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90679

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-21
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

DNF7 / FP by FP - HVX-O2
Original brand: Alsthom

ECOFIT™ proposal
PE90674

With ECOFIT™, a true extended life time


1983 2013 2024
PE90675

FP

FP - HVX-O2

ECOFIT™ solution

FP 
Circuit Breaker Commercialisation End of commercialisation End of spare parts
PE90676

Main technical characteristics


FP 
Rated current (Ir) 400 - 2000 A
FP - HVX-O2 Intensity short circuit (Isc) 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 36 kV

FP HVX-O2 FP HVX-O2

Technology SF6 Vacuum Switching sequence O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO


O-0.3 s-CO-15s-CO O-3 min-CO-3 min-CO
Rated voltage Ur (kV) 36 40.5 CO-15 s-CO O-0.3 s-CO-15s-CO
O-3 min-CO-3 min-CO CO-15 s-CO
Surge withstand voltage Up (kV) 170 185 Closing time (ms) 50 45 - 53
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 70 45 - 63

Rated current Ir (A) Up to 2500 Up to 2500 Number of switching 5.000 10.000


Short circuit current Isc (kA) 31.5 31.5 operations

Short circuit duration Tk (s) 3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90674

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-22
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Epoclad / DHF & F by LF1 - LF2 - LF3 - SF1


Original brand: Nuova Magrini Galileo

ECOFIT™ proposal
PE90577

With ECOFIT™, a true extended life time


DHF - F
Circuit Breaker 1969 1997 2005 2011

DHF & F

LF1 - LF2 - LF3 - SF1

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90579

Main technical characteristics


DHF & F
6DHF 7F/N 10DHF 7F 15DHF 12F 24DHF 20DHF
LF1 - LF2 - 6DHF/N 250-350 250-750 350-750 350-850 12F/N 350-500 350-750
LF3 - SF1
Circuit Breaker 250-500 350-750 24F
500-750

Rated current (Ir) 630 - 3150 A 630 - 3150 A 630 - 3150 A 630 - 3150 A 630 - 1250 A 630 - 3150 A 630 - 3150 A 630 - 1250 A
Short circuit current (Isc) 20 - 48 kA 29 - 34 kA 12 - 43 kA 18 - 48 kA 13.5 - 32.5 kA 12.5 - 48 kA 9.2 - 14.5 kA 8 - 18 kA /20DHF
12.5 - 18 kA /24F
Rated voltage Un (50/60 Hz) 6 kV 7.2 kV 10 kV 12 kV 15 kV 17 kV 20 kV 24 kV

LF1 LF2 LF3* SF1 LF1 LF2 LF3* SF1

Technology SF6 SF6 SF6 SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2  7.2 - 12  17.5 24 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 60 - 75 95 125 Closing time (ms) < 72 < 72 < 72 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) < 54 < 54 < 54 < 50

Rated current Ir (A) 630 - 1250 2000 /  630 - 3150 630 - 1250 Number of switching 10.000 10.000 10.000 10.000
up to 2000 operations
Short circuit current Isc (kA) 31.5 50 - 40 40 25
Short circuit duration Tk (s) 3  3  3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 - 25 / + 40
* Ur: 7.2 / 12, A: 3150, kA: 50

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90437

Sepam series 10, 20, 40, 60 , 80


PE90577

or
PE90488

MICOMP series 10, 20, 30, 40

A-23
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F100 - F200 / FG1 - FG2 by LF2 - LF3 - Evolis


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90409

With ECOFIT™, a true extended life time


1980 1998 1999 2011

FG1 - FG2

LF2 - LF3 - Evolis

ECOFIT™ solution
FG1 - FG2
Circuit Breaker Commercialisation End of commercialisation End of spare parts
PE90411

Main technical characteristics


FG1 - FG2
Rated current (Ir) 630 - 3150 A 630 - 3150 A 630 - 3150 A
LF2  - LF3 - EVOLIS Short circuit current (Isc) 25 - 50 kA 25 - 50 kA 25 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV

LF2 - LF3 Evolis LF2 - LF3 Evolis

Technology SF6 SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2 - 12 17.5 up to 17.5 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 - 75 95 up to 95 Closing time (ms) < 72 < 72 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) < 54 < 54 < 50

Rated current Ir (A) 630 - 3150 630 - 3150 630 - 2500 Number of switching 10.000 10.000 2000 (Isc =
Short circuit current Isc (kA) 25 - 50 31.5 40 operations 40 kA / M1
class) - 10.000
Short circuit duration Tk (s) 3  3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90409

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-24
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F100C / R400 - R400D by R400 - R400D


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90412

With ECOFIT™, a true extended life time


1980 1998

R400 - R400D

R400 - R400D

ECOFIT™ solution
R400 - R400D
Circuit Breaker Commercialisation End of spare parts
PE90413

R400 - R400D
Circuit Breaker
Main technical characteristics

R400 R400D R400 R400D

Technology SF6 SF6 Switching sequence


Rated voltage Ur (kV) 7.2 7.2

Surge withstand voltage Up (kV) 60 60 Closing time (ms) 75 - 155 75 - 155


Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 20 - 50 20 - 50

Rated current Ir (A) 80 - 250 80 - 250 Number of switching 300.000 100.000


Short circuit current Isc (kA) 50 (with fuses) 50 (with fuses) operations

Short circuit duration Tk (s) 3 3  Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90412

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-25
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F300 / FG3 (1000mm width) by SF1 - SF2


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90742

With ECOFIT™, a true extended life time


1980 1998 1999 2009

FG3

SF1 - SF2

ECOFIT™ solution
FG3
Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90744

Main technical characteristics


FG3
Rated current (Ir) 630 - 2500 A
SF1 - SF2 Short circuit current (Isc) 25 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

SF1 SF2 SF1 SF2

Technology SF6 SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24 24 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125 125 Closing time (ms) < 65 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 50 < 50

Rated current Ir (A) 630 - 1250 1250 - 2500 Number of switching 10.000 10.000


Short circuit current Isc (kA) 25 25 - 31.5 operations

Short circuit duration Tk (s) 3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90409

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-26
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F400C / FC4 by SF2


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90414

With ECOFIT™, a true extended life time


1980 1987 1991 2000

FC4

SF2

FC4 ECOFIT™ solution


Circuit Breaker

Commercialisation End of commercialisation End of spare parts


PE90416

Main technical characteristics


FC4
Rated current (Ir) 1250 - 2500 A
SF2 Short circuit current (Isc) 31.5 - 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 36 kV

SF2 SF2

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 36 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 170 Closing time (ms) < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 50
Rated current Ir (A) 1250 - 2500 Number of switching 10.000
Short circuit current Isc (kA) 31.5 - 40 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90414

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-27
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F400G / FG4 by SF1 - SF2


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90417

With ECOFIT™, a true extended life time


1986 2002 2004 2009

FG4

SF1 - SF2

ECOFIT™ solution
FG4
Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90450

Main technical characteristics


FG4
Rated current (Ir) 1250 - 2500 A 1250 - 2500 A
SF1 - SF2 Short circuit current (Isc) 40 kA 25 - 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV 36 kV

SF1 - SF2 SF1 - SF2

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24 - 36 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125 - 170 Closing time (ms) < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 50
Rated current Ir (A) 1250 - 2500 Number of switching 10.000
Short circuit current Isc (kA) 25 - 40 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90417

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-28
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluokit M24 / FP by FP
Original brand: DELLE ALSTHOM

ECOFIT™ proposal
PE90864

With ECOFIT™, a true extended life time


1987 2007 2011 2014
PE90863

FP 

FP

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


FP
Circuit Breaker
PE90863

Main technical characteristics


FP
Rated current (Ir) 400 - 3150 A 400 - 3150 A
FP Short circuit current (Isc) 16 - 20 - 25 - 31.5 - 40 kA 16 - 20 - 25 - 31.5 - 40 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 12 kV 24 kV

FP FP

Technology SF6 SF6 Switching sequence O-3mn-CO-3mn-CO


CO-15 s-CO
Rated voltage Ur (kV) 12 24 O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75 125 Closing time (ms) 70 
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 50
Rated current Ir (A) 400 - 3150 400 - 3150 Number of switching 10.000
Short circuit current Isc (kA) 16 - 20 - 25 - 31.5 - 40 16 - 20 - 25 - 31.5 - 40 operations

Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90864

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-29
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluokit M24+ / FP by FP
Original brand: DELLE ALSTHOM

ECOFIT™ proposal
PE90862

With ECOFIT™, a true extended life time


2005 2014 2024
PE90863

FP

FP

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


FP
Circuit Breaker
PE90863

Main technical characteristics


FP
Rated current (Ir) 400 - 3150 A 400 - 3150 A
FP Short circuit current (Isc) 16 - 20 - 25 - 31.5 - 40 kA 16 - 20 - 25 - 31.5 - 40 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 12 kV 24 kV

FP FP

Technology SF6 SF6 Switching sequence O-3mn-CO-3mn-CO


CO-15 s-CO
Rated voltage Ur (kV) 12 24 O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75 125 Closing time (ms) 70 
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 50
Rated current Ir (A) 400 - 3150 400 - 3150 Number of switching 10.000
Short circuit current Isc (kA) 16 - 20 - 25 - 31.5 - 40 16 - 20 - 25 - 31.5 - 40 operations

Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90862

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-30
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluokit M36 / FP by FP
Original brand: DELLE ALSTHOM

ECOFIT™ proposal
PE90860

With ECOFIT™, a true extended life time


1987 2014 2024
PE90861

FP

FP

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


FP
Circuit Breaker
PE90861

Main technical characteristics


FP
Rated current (Ir) 400 - 3150 A
FP Short circuit current (Isc) 16 - 20 - 25 - 31.5 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 36 kV

FP FP

Technology SF6 Switching sequence O-3mn-CO-3mn-CO


CO-15 s-CO
Rated voltage Ur (kV) 36 O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 170 Closing time (ms) 70
Nominal frequency (Hz) 50 - 60 Opening time (ms) 50
Rated current Ir (A) 400 - 3150 Number of switching 10.000
Short circuit current Isc (kA) 16 - 20 - 25 - 31.5 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90860

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-31
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluomatic F540 / FR62 by FP62


Original brand: Delle Alsthom

ECOFIT™ proposal
PE90469

With ECOFIT™, a true extended life time


PE90470

1976 1984 1992 1994

FR62

FP62

FR62 ECOFIT™ solution


Circuit Breaker

Commercialisation End of commercialisation End of spare parts


PE90471

Main technical characteristics


FR62
Rated current (Ir) 1250 - 2500 A
FP62 Short circuit current (Isc) 31.5 - 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 36 kV

FP62 FP62

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) 24 CO-15 s-CO
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms) 50
Nominal frequency (Hz) 50 - 60 Opening time (ms) 70
Rated current Ir (A) 400 - 3150 Number of switching 10000
Short circuit current Isc (kA) 16 - 40 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90469

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-32
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluomatic F943 / FR62 by BLV


Original brand: Delle Alsthom

ECOFIT™ proposal
PE90472

With ECOFIT™, a true extended life time


PE90470

1976 1984 1994 1997

FR62 

BLV

FR62 ECOFIT™ solution


Circuit Breaker

Commercialisation End of commercialisation End of spare parts


PE90474

Main technical characteristics


FR62
Rated current (Ir) 400 - 1250 A
BLV Short circuit current (Isc) 16 - 25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

BLV BLV

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) 24 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 125 Closing time (ms) 40
Nominal frequency (Hz) 50 - 60 Opening time (ms) 51
Rated current Ir (A) 400 - 1250 Number of switching 10000 electrical
Short circuit current Isc (kA) 16 - 31.5 operations M2

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90472

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-33
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

GS-10 / GE by VA - VAA
Original brand: AEG

ECOFIT™ proposal
PE90550

With ECOFIT™, a true extended life time


PE90551

1966 1978 2004 2009

GE

VA - VAA 

GE ECOFIT™ solution
Circuit Breaker

Commercialisation End of commercialisation End of spare parts


PE90552

Main technical characteristics


GE
Rated current (Ir) 630 - 3000 A
VA - VAA Short circuit current (Isc) 16 - 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV

VA - VAA  VA - VAA 

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12 

Surge withstand voltage Up (kV)  75  Closing time (ms) 45 - 65


Nominal frequency (Hz) 50 - 60 Opening time (ms) 45 - 65
Rated current Ir (A) 600 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 40 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90553

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-34
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

HMC400 - HMC410 / HMC400 - HMC410 by HMC400 - HMC410


Original brand: GEC Alstom

ECOFIT™ proposal
PE90597

With ECOFIT™, a true extended life time


1960 1970 2015
PE90594

HMC400 - HMC410

HMC400 - HMC410

ECOFIT™ solution
HMC400 - HMC410 
Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90595

Main technical characteristics


HMC400 - HMC410 
Rated current (Ir) 400 A 400 A
HMC400  - HMC410 Short circuit current (Isc) 43.8 kA 26.3 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 3.3 kV 6.6 kV

HMC400 - HMC410  HMC400 - HMC410 

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) Up to 6.6 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 75 Closing time (ms) < 52
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 61
Rated current Ir (A) 400 Number of switching 10.000
Short circuit current Isc (kA) 26.3 - 43.8 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 25 / + 40

Refurbishment
In-house refurbishment, including vacuum contactors and control scheme utlilising
PE90681

Gemstart unit, on site maintenance

A-35
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

HMC1072 /HMC1072 by HMC1072
Original brand: GEC Alstom

ECOFIT™ proposal
PE90599

With ECOFIT™, a true extended life time


1968 1983 1992 2015

HMC1072

HMC1072

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts

Main technical characteristics


HMC1072
Rated current (Ir) 400 A
HMC1072 Short circuit current (Isc) 63 kA rms/1s - 50 kA rms/3s
Rated voltage Un (50/60 Hz) 7.2 kV

HMC1072 HMC1072

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) 7.2 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 75 Closing time (ms) < 52
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 61
Rated current Ir (A) 400 Number of switching 10.000
Short circuit current Isc (kA) 50 - 63 operations

Short circuit duration Tk (s) 3 to 1 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90599

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-36
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

HMC1172 /HMC1172 by HMC1172
Original brand: GEC Alstom

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90600

1980 2006 2008 On-going

HMC1172

HMC1172

ECOFIT™ solution
HMC1172

Commercialisation End of commercialisation End of spare parts

Main technical characteristics


HMC1172
Rated current (Ir) 400 A
Short circuit current (Isc) 63 kA rms/1s - 50 kA rms/3s
Rated voltage Un (50/60 Hz) 7.2 kV

VCB Contactor VCB Contactor

Technology Vacuum Vacuum Switching sequence O-3 min-CO-3 min-CO O/C


Rated voltage Ur (kV) 7.2 7.2 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 63 Closing time (ms) 90 - 120 90 - 120
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 61 < 61
Rated current Ir (A) 1000 - 2000 400 Number of switching 10.000 1.000.000
Short circuit current Isc (kA) 25 - 31.5 9 operations

Short circuit duration Tk (s) 3 1 Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90601

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-37
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

HMX36 /HMX36 by HMX36
Original brand: GEC Alstom

ECOFIT™ proposal
PE90602

With ECOFIT™, a true extended life time


1980 2003 On-going

HMX36

HMX36

ECOFIT™ solution

HMX36
Commercialisation End of commercialisation End of spare parts

Main technical characteristics


HMX36
Rated current (Ir) 400 A
Short circuit current (Isc) 25 kA rms/1s - 31.5 kA rms/3s
Rated voltage Un (50/60 Hz) 36 kV

HMX36 HMX36

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) Up to 36 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 115 Closing time (ms) < 52
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 61
Rated current Ir (A) 400 Number of switching 10.000
Short circuit current Isc (kA) 25 - 31.5 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90602

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-38
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

HP / HP - W - TW - TM by HVX


Original brand: Concordia Sprecher

ECOFIT™ proposal
With ECOFIT™, a true extended life time
1976 2002 2007 2012
PE90653

HP - W - TW - TM

HVX

ECOFIT™ solution

HP - W - TW - TM 
Circuit Breaker Commercialisation End of commercialisation End of spare parts
PE90652

Main technical characteristics


HP - W - TW - TM
Rated current (Ir) 1250 - 3150 A 800 - 1250 A
HVX Short circuit current (Isc) 12.5 - 40 kA 8.4 - 21.7 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 - 12 kV 24 kV

HVX HVX

Technology Vacuum Switching sequence O-0.3 s-CO-3 min-CO


Rated voltage Ur (kV) 12 - 24

Surge withstand voltage Up (kV) 75 - 125 Closing time (ms) 45 - 63


Nominal frequency (Hz) 50 - 60 Opening time (ms) 35 - 53

Rated current Ir (A) 630 - 2500 Number of switching 10.000


Short circuit current Isc (kA) 16 - 31.5 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90654

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-39
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

KIT25-PGDT / CC by FP
Original brand: CEM

ECOFIT™ proposal
PE90475

With ECOFIT™, a true extended life time


1969 1978 1988 1993
PE90476

CC 

FP   End of life

ECOFIT™ solution

CC  Commercialisation End ofcommercialisation End of spare parts


Circuit Breaker
PE90477

Main technical characteristics


CC 
Rated current (Ir) 400  A
FP  Short circuit current (Isc) 12.5 & 14.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

FP FP

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


CO-15 s-CO
Rated voltage Ur (kV) 24 O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms) 50
Nominal frequency (Hz) 50 - 60 Opening time (ms) 70
Rated current Ir (A) 400 - 3150 Number of switching 10.000
operations
Short circuit current Isc (kA) 16 - 40
Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90487

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

KIT 27.2-PGHT / HF4K by FP


Original brand: CEM

ECOFIT™ proposal
PE90478

With ECOFIT™, a true extended life time


1985 1987 1993 1997
PE90479

HF4K

FP FP End of life

ECOFIT™ solution

HF4K  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90480

Main technical characteristics


HF4K 
Rated current (Ir) 400  A
FP  Short circuit current (Isc) 14.5 & 25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

FP FP

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


CO-15 s-CO
Rated voltage Ur (kV) 24 O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms) 50
Nominal frequency (Hz) 50 - 60 Opening time (ms) 70
Rated current Ir (A) 400 - 3150 Number of switching 10.000
operations
Short circuit current Isc (kA) 16 - 40
Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90478

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-41
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

L / D - E by HVX


Original brand: AEG

ECOFIT™ proposal
PE90557

With ECOFIT™, a true extended life time


1965 1972 2003 2004
PE90558

D - E

 HVX 

ECOFIT™ solution
D - E  
Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90559

Main technical characteristics


D - E  
Rated current (Ir) 400 - 2500 A
HVX Short circuit current (Isc) 20 - 50 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 - 12 kV

HVX HVX

Technology Vacuum Switching sequence O-0.3 s-CO-3 min-CO


Rated voltage Ur (kV) 12 - 24

Surge withstand voltage Up (kV) 75 - 125 Closing time (ms) 45 - 63


Nominal frequency (Hz) 50 - 60 Opening time (ms) 35 - 53

Rated current Ir (A) 630 - 2500 Number of switching 10000


Short circuit current Isc (kA) 16 - 40 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90549

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-42
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Metalclad switchgear / DST2 & 5 by DST2V & 5V


Original brand: Federal Pioneer

ECOFIT™ proposal
PE90618-2

With ECOFIT™, a true extended life time


1970 1985 1999 2000
PE90618

DST2 & 5 - DST2

FP DST2V & 5V

ECOFIT™ solution

DST2 & 5  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90619

Main technical characteristics


DST2 & 5 DST2
Rated current (Ir) 1200 - 3000  A 1200 - 3000  A
DST2V & 5V  3-phase MVA rating 250 - 350 MVA 500 - 750 MVA
Circuit Breaker Rated voltage Un 5 kV 15 kV

DST2 V DST5 V DST2 V DST5 V

Technology Vacuum Vacuum Rated current Ir (A) 1200 - 3000 1200 - 3000


Rated voltage Ur (kV) 5 15 3-phase rating (MVA) 350 500 - 750
Surge withstand voltage Up (kV) 60 95

Offer extension
Magnum circuit breakers correctly interface with the Optional capabilities
PE90619

existing breaker compartment components and maintain • Increased fault current interruption rating.
safety interlocks inherent in the original equipment • Relay upgrade, improved accuracy and repeatability,
design. and performance.
• New circuit breakers are installed in existing switchgear. • Power metering, monitoring and communication.
• Original footprint is left intact, saving time and money. • Ground and test devices available for various types of
• Installation expense is a fraction of new equipment costs. switchgear.
• Less down time for installation.
• Enhanced equipment reliability.
• Manufactured with new components.
• Undergoes complete factory testing. Closed Door Electric Racking Mechanism
• Backed by our standard equipment warranty. • Arc flash hazard reduced with remote operation.
• New, easy-to-maintain operating mechanism. • Maintenance shutdown time is significantly reduced.
• No bulky arc chutes to handle and maintain. • No storage space is required for the electrical racking system.
• Reduced need for difficult to obtain spare parts. • Require just a common 120VAC, 15A outlet for power up.

A-43
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Motorstart P50D / C - CD by R400 - R400D - CTV1


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90390

With ECOFIT™, a true extended life time


1960 1980 1988 1992
PE90391

C - CD

R400 - R400D - CTV1

ECOFIT™ solution
C - CD
Circuit Breaker
Commercialisation End of commercialisation End of spare parts
PE90392

Main technical characteristics


C - CD
Rated current (Ir) 80 - 200 A
R400 - R400D - CTV1 Short circuit current (Isc) 50 kA (with fuses)
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV

R400 R400D CTV1 R400 R400D CTV1

Technology SF6 SF6 Vacuum Switching sequence


Rated voltage Ur (kV) 7.2 7.2 7.2

Surge withstand voltage Up (kV) 60  60 60 Closing time (ms) 75 - 155 75 - 155 60 - 80
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 20 - 50 20 - 50 20 - 30

Rated current Ir (A) 80 - 250 80 - 250 80 - 250 Number of switching 300.000 100.000 200.000
Short circuit current Isc (kA) 50 (with fuses) 50 (with fuses) 50 (with fuses) operations
Short circuit duration Tk (s) 3  3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90390

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-44
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Motorstart P500D / C1 - CD1 by R400 - R400D - CTV1


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90393

With ECOFIT™, a true extended life time


1971 1988 1998

C1  -  CD1

R400 - R400D - CTV1

ECOFIT™ solution
C1 - CD1
Circuit Breaker
Commercialisation End of commercialisation End of space parts
PE90395

Main technical characteristics


C1 - CD1
Rated current (Ir) 80 - 250 A
R400 - R400D - CTV1 Short circuit current (Isc) 50 kA (with fuses)
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV

R400 R400D CTV1 R400 R400D CTV1

Technology SF6 SF6 Vacuum Switching sequence


Rated voltage Ur (kV) 7.2 7.2 7.2

Surge withstand voltage Up (kV) 60  60 60 Closing time (ms) 75 - 155 75 - 155 60 - 80
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 20 - 50 20 - 50 20 - 30

Rated current Ir (A) 80 - 250 80 - 250 80 - 250 Number of switching 300.000 100.000 200.000
Short circuit current Isc (kA) 50 (with fuses) 50 (with fuses) 50 (with fuses) operations
Short circuit duration Tk (s) 3  3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90393

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-45
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

MX51 & MX81 by MX51 & MX81


Original brand: GEC Alstom

ECOFIT™ proposal
PE90603

With ECOFIT™, a true extended life time


1974 1981 2012

MX51 & MX81

MX51 & MX81

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


MX51 & MX81

Main technical characteristics


MX51 MX81
Rated current (Ir) 630 - 2000 A 630 - 2000 A 630 - 1250 A 630 - 1250 A
Short circuit current (Isc) 25 - 31.5 kA 25 - 31.5 kA 12.5 - 20 kA 12.5 - 20 kA
Rated voltage Un (50/60 Hz) 3.6 kV 17.5 kV 3.6 kV 17.5 kV

MX51 & MX81 MX51 & MX81

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) Up to 17.5 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 115 Closing time (ms) < 52
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 61
Rated current Ir (A) 630 - 2000 Number of switching 10.000
Short circuit current Isc (kA) Up to 31.5 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90603

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-46
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Normabloc N1347 / HL by HVX -FPX


Original brand: Delle Alsthom

ECOFIT™ proposal
PE90481

With ECOFIT™, a true extended life time


1975 1981 1991 2009
PE90482

HL 

HVX - FPX  

ECOFIT™ solution

HL  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90483

Main technical characteristics


HL 
Rated current (Ir) 630 - 1250  A
HVX - HPX  Short circuit current (Isc) 25 & 40 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 17.5 kV

HVX FPX HVX FPX

Technology Vacuum SF6 Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 17.5 17.5 O-15 s-CO O-0.3 s-CO-15s-CO
O-0.3 s-CO-15s-CO
Surge withstand voltage Up (kV) 95 95 Closing time (ms) 35 - 53 50
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 45 - 63 50

Rated current Ir (A) 630 - 1250 630 - 1250 Number of switching 10000 10000


Short circuit current Isc (kA) 16 - 40 12.5 - 40 operations

Short circuit duration Tk (s) 3 3  Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90481

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-47
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Normaclad PX / FPX by FPX


Original brand: GEC ALSTHOM

ECOFIT™ proposal
PE90765

With ECOFIT™, a true extended life time


1993 1997 2024

FPX
PE90857

FPX

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


FPX
Circuit Breaker
PE90857

Main technical characteristics


FPX
Rated current (Ir) Up to 3150 A Up to 2500 A
FPX Short circuit current (Isc) 40 kA 31.5 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 12 kV 24 kV

FPX FPX

Technology SF6 SF6 Switching sequence O-3mn-CO-3mn-CO


CO-0.3 s-CO-15 s-CO
Rated voltage Ur (kV) 12 24 O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75 125 Closing time (ms) 50 
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 50
Rated current Ir (A) Up to 3150 Up to 2500 Number of switching 10.000
Short circuit current Isc (kA) Up to  40 Up to  31.5 operations

Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90765

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-48
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Normasept N743 / HL by FP
Original brand: Delle Alsthom

ECOFIT™ proposal
PE90484

With ECOFIT™, a true extended life time


1971 1981 1990 1991

HL
PE90485

FP FP

ECOFIT™ solution

HL  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90486

Main technical characteristics


HL 
Rated current (Ir) 400 - 630  A
FP  Short circuit current (Isc) 12.5 - 14.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

FP FP

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


CO-15 s-CO
Rated voltage Ur (kV) 24 O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms) 50
Nominal frequency (Hz) 50 - 60 Opening time (ms) 70
Rated current Ir (A) 400 - 3150 Number of switching 10000
operations
Short circuit current Isc (kA) 16 - 40
Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90487

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-49
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

PX 12 - 24 / FPX by FPX


Original brand: Alstom

ECOFIT™ proposal
PE90765

With ECOFIT™, a true extended life time


1993 1997 1998 2023

FPX
PE90766

FP FPX

ECOFIT™ solution

FPX  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90766

Main technical characteristics


FPX 
Rated current (Ir) 3150 A 2500 A 2500 A
FPX  Short circuit current (Isc) 40 kA/3s 31.5 kA/3s 31.5 kA/3s
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV 17.5 kV 24 kV

FPX FPX

Technology SF6 SF6 SF6 Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) 12 17.5 24 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 100 80 80 Closing time (ms) 50 50 50
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 50 50 50
Rated current Ir (A) 3150 2500 2500 Number of switching 10.000 10.000 10.000
operations
Short circuit current Isc (kA) 40 31.5 31.5
Short circuit duration Tk (s) 3 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90765

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-50
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

PIX SF6 / FPX by FPX


Original brand: ALSTOM

ECOFIT™ proposal
PE90859

With ECOFIT™, a true extended life time


1994 2014 2024

FPX
PE90857

FPX

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


FPX
Circuit Breaker
PE90857

Main technical characteristics


FPX
Rated current (Ir) Up to 3150 A Up to 2500 A Up to 2500 A
FPX Short circuit current (Isc) 40 kA 31.5 kA 31.5 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 12 kV 17.5 kV 24 kV

FPX FPX

Technology SF6 SF6 SF6 Switching sequence O-3mn-CO-3mn-CO


CO-0.3 s-CO-15 s-CO
Rated voltage Ur (kV) 12 17.5 24 O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75 95 125 Closing time (ms) 50 
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 50
Rated current Ir (A) Up to 3150 Up to 2500 Up to 2500 Number of switching 10.000
Short circuit current Isc (kA) Up to  40 Up to  31.5 Up to  31.5 operations

Short circuit duration Tk (s) 3 3 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90859

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-51
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

PNX36 / HVX36  by HVX36


Original brand: AEG

ECOFIT™ proposal
PE90819

With ECOFIT™, a true extended life time


1994 2015
PE90818

HVX36

HVX36 

ECOFIT™ solution

HVX36 Commercialisation End of commercialisation


Circuit Breaker
PE90650

Main technical characteristics


HVX36
Rated current (Ir) 630 - 2500 A
HVX36  Intensity short circuit (Isc) 25 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 36 kV

VAA VAA

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 36

Surge withstand voltage Up (kV) 70 Closing time (ms) 45 - 63


Nominal frequency (Hz) 50 - 60 Opening time (ms) 35 - 53
Rated current Ir (A) 630 - 2500 Number of switching 10.000
Short circuit current Isc (kA) 25 - 31.5 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90819

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-52
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

R / IMC - MC - FAL - IFAL - VA - VAA - IVA - BAL - ALF - AL - TG
by VA - VAA - Contactor Original brand: AEG

ECOFIT™ proposal
PE90554

With ECOFIT™, a true extended life time


1973 1985 1990 1999 2003 2007 2013
PE90555

IMC - MC

FAL - IFAL

BAL - ALF - AL
IMC - MC - FAL - IFAL 
- VA - VAA - IVA - BAL  VA - VAA - IVA  - TG
- ALF - AL - TG
Circuit Breaker End of VA - VAA - Contactor
cialisation
IMC -MC ECOFIT™ solution

Commercialisation End of commercialisation


End of spare parts
PE90556

Main technical characteristics


IMC - MC - FAL - IFAL - VA - VAA - IVA - BAL - ALF - AL - TG
Rated current (Ir) 1250 - 4000 A
VA  - VAA Short circuit current (Isc) 16 - 50 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 - 36 kV

VA - VAA - Contactor VA - VAA - Contactor

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12 - 24

Surge withstand voltage Up (kV)  75 - 125 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 630 - 3550 Number of switching 10.000
Short circuit current Isc (kA) 16 - 50  operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90554

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-53
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Siclad / MAG II by LF1 - LF2


Original brand: Ansaldo

ECOFIT™ proposal
PE90580

With ECOFIT™, a true extended life time


1969 1997 2009
PE90581

MAG II

LF1 - LF2

ECOFIT™ solution
MAG II
Circuit Breaker
Commercialisation End of commercialisation End of spare parts

Main technical characteristics


PE90582

MAG II

MAG II - 6 - 250/400 MAG II - 10 - 500 MAG II - 15 - 6 - 300/350


Rated current (Ir) 630 - 1250 - 2000 A 630 - 1250 - 2000 A 630 - 1250 - 2000 A
LF1 - LF2 Short circuit current (Isc) 20 - 48 kA 20 - 28 kA 12 - 30 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 6 kV 10 kV 15 kV

LF1 LF2* LF1 LF2*

Technology SF6 SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2 - 12 7.2 - 12 - 17.5 O-0.3 s-CO-15 s-CO

Surge withstand voltage Up (kV) 60 - 75 60 - 75 - 95 Closing time (ms) < 72 < 72
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 54 < 54

Rated current Ir (A) 630 - 1250 2000 Number of switching 10.000 10.000


Short circuit current Isc (kA) 31.5 40 operations

Short circuit duration Tk (s) 3  3  Service temperature (°C) - 25 / + 40 - 25 / + 40


* For Siclad panels 730mm & 850mm wide

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90580

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-54
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Solenarc DSE Metal-Clad switchgear / DSE by Magnum CB


Original brand: Square D

ECOFIT™ proposal
PE90539

With ECOFIT™, a true extended life time


<1975 1988 1999 2005
PE90540

DSE

Magnum CB

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


DSE
Circuit Breaker
PE90541

Main technical characteristics


DSE 
Rated current (Ir) 1200 - 3000  A 1200 - 3000  A
Magnum CB
Circuit Breaker 3-phase MVA rating 250 MVA 250 - 1000 MVA
Rated voltage Un 5 kV 15 kV

5MGSB 15MGSB 5MGSB 15MGSB

Technology Vacuum Vacuum Rated current Ir (A) 1200 1200 - 3000


Rated voltage Ur (kV) 5 15 3-phase rating (MVA) 250 250 - 1000
Surge withstand voltage Up (kV) 60 95 Interrupting time (ms) 100 60

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90539

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-55
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Venus / GI - GL by LF1 - LF3


Original brand: Nuova Magrini Galileo

ECOFIT™ proposal
PE90583

GI - GL
With ECOFIT™, a true extended life time
Circuit Breaker
1989 2000 2008 2010
PE90583

GI - GL

LF1 - LF3

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90585

Main technical characteristics


GI GL
Rated current (Ir) 630 - 1250 A 630 - 1250 A 1600 - 3150 A 1600 - 3150 A 1600 - 3150 A 1600 - 3150 A
LF1  - LF3 Short circuit current (Isc) 12.5 - 31.5 kA 12 - 25 kA 50 kA 20 - 40 kA 20 - 40 kA 20 - 31.5 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 7 - 12 kV 17 - 24 - 36 kV 7 kV 12 kV 24 kV 36 kV

LF1 LF3 LF1 LF3

Technology SF6 SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Panel width (mm) 600 900 O-0.3 s-CO-15 s-CO
Rated voltage Ur (kV) 12 17.5
Surge withstand voltage Up (kV) 75 125 Closing time (ms) < 72 < 72
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 54 < 54
Rated current Ir (A) 630 - 1250 1600 - 1250 Number of switching 10.000 10.000
Short circuit current Isc (kA) 31.5 50 operations

Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90583

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-56
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

VISAX / BLV by BLV


Original brand: GEC Alsthom

ECOFIT™ proposal
PE90219

With ECOFIT™, a true extended life time


1996 2015 2025
PE90865

BLV

BLV

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


BLV
Circuit Breaker
PE90865

Main technical characteristics


BLV
Rated current (Ir) 400 - 1250 A 400 - 1250 A 400 - 1250 A 400 - 1250 A
BLV Short circuit current (Isc) 16  - 40 kA 16  - 40 kA 16  - 40 kA 16  - 31.5 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV 24 kV

BLV BLV

Technology SF6 SF6 SF6 SF6 Switching sequence O-3mn-CO-3mn-CO


O-0.3 s-CO-3mn-CO
Rated voltage Ur (kV) 7.2 12 17.5 24 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125 125 125 125 Closing time (ms) 51 
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) 40
Rated current Ir (A) 400 - 1250 400 - 1250 400 - 1250 400 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 16  - 40 16  - 40 16  - 40 16  - 31.5 operations

Short circuit duration Tk (s) 3 3 3 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90219

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-57
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

VM6 DM12 / FB4 by SF1


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90421

With ECOFIT™, a true extended life time


1975 1993 2009 2010
PE90422

FB4

SF1

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


FB4
Circuit Breaker
PE90423

Main technical characteristics


FB4
Rated current (Ir) 400 - 1250 A 400 - 1250 A 400 - 1250 A 400 - 1250 A
SF1 Short circuit current (Isc) 12.5 - 31.5 kA 12.5 - 25 kA 12.5 - 20 kA 12.5 - 20 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV 24 kV

SF1 SF1

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) Up to 24  O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV)  Up to 125 Closing time (ms) < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 50
Rated current Ir (A) 400 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 12.5 - 25 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90421

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-58
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

VM6 DM22 - DM23 / FB4 by SF1


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90419

With ECOFIT™, a true extended life time


1975 1993 2009
PE90565

FB4

SF1

ECOFIT™ solution

FB4 Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90566

Main technical characteristics


FB4
Rated current (Ir) 400 - 630 A
SF1 Short circuit current (Isc) 12.5 - 20 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 24 kV

SF1 SF1

Technology SF6 Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24  O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV)  125 Closing time (ms) < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 50
Rated current Ir (A) 400 - 630 Number of switching 10.000
Short circuit current Isc (kA) 12.5 - 20 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90419

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-59
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

VMX / VMX by VMX


Original brand: GEC Alstom

ECOFIT™ proposal
PE90692

With ECOFIT™, a true extended life time


1987 2004

VMX
PE90764

VMX

ECOFIT™ solution

VMX Commercialisation End of commercialisation


Circuit Breaker
PE90764

Main technical characteristics


VMX
Rated current (Ir) 630 - 2000 A
VMX Short circuit current (Isc) Up to 25 kA/3s
Circuit Breaker Rated voltage Un (50/60 Hz) 11 kV

VMX VMX

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


Rated voltage Ur (kV) 11 O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 95 Closing time (ms) < 52
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 61
Rated current Ir (A) 630 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 25 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90692

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-60
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WAK / D - E - ID - IE by HVX


Original brand: AEG

ECOFIT™ proposal
PE90546

With ECOFIT™, a true extended life time


1965 1972 2003 2004
PE90547

D - E - ID - IE 

 HVX 

ECOFIT™ solution

D - E - ID - IE  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90548

Main technical characteristics


D - E - ID - IE  
Rated current (Ir) 400 - 2500 A
HVX Short circuit current (Isc) Up to 34 kA
Circuit Breaker Rated voltage Un (50/60 Hz) Up to 24 kV

HVX HVX

Technology Vacuum Switching sequence O-0.3 s-CO-3 min-CO


Rated voltage Ur (kV) 12 - 24

Surge withstand voltage Up (kV) 75 - 125 Closing time (ms) 45 - 63


Nominal frequency (Hz) 50 Opening time (ms) 35 - 53

Rated current Ir (A) 630 - 1250 Number of switching 10.000


Short circuit current Isc (kA) 16 - 31.5 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90546

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-61
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WBA / VA - VAA - ECA - BAL - AL by VA - VAA - Contactor


Original brand: AEG

ECOFIT™ proposal
PE90657

With ECOFIT™, a true extended life time


1989 2006
PE90665

VA - VAA - ECA - BAL - AL

VA - VAA - Contactor

ECOFIT™ solution
VA - VAA - ECA - 
BAL - AL Commercialisation
Circuit Breaker
PE90666

Main technical characteristics


BAL - AL VAA ECA VA
Rated current (Ir) 250 A 630 - 1250 A 630 - 2500 A 630 - 2500 A
VA  - VAA Short circuit current (Isc) 20 kA 16 - 25 kA 20 - 50 kA 20 - 50 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 3.6 - 12 kV 12 - 24 kV 12 - 24 kV 12 - 38 kV

VA - VAA - Contactor VA - VAA - Contactor

Technology Vacuum Switching sequence O-0.3 s-CO-3 s-CO


Rated voltage Ur (kV) 12 - 24

Surge withstand voltage Up (kV)  75 - 125 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 630 - 2500 Number of switching 10.000
Short circuit current Isc (kA) 25 - 31.5  operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90658

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-62
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WBB / VA - VAA - ECA - BAL - AL by VA - VAA - Contactor


Original brand: AEG

ECOFIT™ proposal
PE90659

With ECOFIT™, a true extended life time


1994 2004 2013 2014
PE90663

BAL - AL

ECA

VA - VAA

VAA
VA - VAA - ECA - 
BAL - AL
Circuit Breaker ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90664

Main technical characteristics


BAL - AL VAA ECA VA
Rated current (Ir) 250 A 630 - 1250 A 630 - 2500 A 630 - 2500 A
VA  - VAA Short circuit current (Isc) 20 kA 16 - 25 kA 20 - 50 kA 20 - 50 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 3.6 - 12 kV 12 - 24 kV 12 - 24 kV 12 - 38 kV

VA - VAA - Contactor VA - VAA - Contactor

Technology Vacuum Switching sequence O-0.3 s-CO-3 s-CO


Rated voltage Ur (kV) 12 - 15

Surge withstand voltage Up (kV)  75 - 95 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 630 - 2500 Number of switching 10.000
Short circuit current Isc (kA) 25 - 31.5  operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90660

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-63
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WBD / VAA - VA - HVX  by VAA - VA


Original brand: AEG

ECOFIT™ proposal
PE90820

With ECOFIT™, a true extended life time


1992 2015

VA - VAA - HVX
PE90663

VA - VAA  

ECOFIT™ solution

VA - VAA - HVX Commercialisation End of commercialisation


Circuit Breaker
PE90821

Main technical characteristics


VA - VAA - HVX
Rated current (Ir) 630 - 2500 A
VA - VAA  Intensity short circuit (Isc) 25 - 31.5 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 36 kV

VA - VAA VA - VAA

Technology Vacuum Switching sequence O-0.3 s-CO-3min-CO


Rated voltage Ur (kV) 12

Surge withstand voltage Up (kV) 80 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 630 - 3150 Number of switching 10.000
Short circuit current Isc (kA) 25 - 31.5 operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90820

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-64
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WK (C/E/B/A) / VA - MC - BAL by VA - VAA - Contactor


Original brand: AEG

ECOFIT™ proposal
PE90661

With ECOFIT™, a true extended life time


1987 2003 2013
PE90661

MC

BAL

VA 

VA - VAA - Contactor
VA - MC -BAL

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90650

Main technical characteristics


VA - MC - BAL
Rated current (Ir) 630 - 2500 A
VA  - VAA -  Short circuit current (Isc) 31.5 - 50 kA
Contactor Rated voltage Un (50/60 Hz) Up to 24 kV

VA - VAA - Contactor VA - VAA - Contactor

Technology Vacuum Switching sequence O-0.3 s-CO-3 s-CO


Rated voltage Ur (kV) 3.6 - 24 

Surge withstand voltage Up (kV)  60 - 110 Closing time (ms) 20


Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) 400 - 4000 Number of switching 10.000
Short circuit current Isc (kA) 10 - 50  operations

Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90661

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-65
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

YSF6 / YSF6 by YSF6 Evolis


Original brand: Yorkshire Switchgear

ECOFIT™ proposal
PE90607

With ECOFIT™, a true extended life time


1981 2001 2004 2021
PE90608

YSF6

YSF6 Evolis

ECOFIT™ solution

YSF6  Commercialisation End of commercialisation End of spare parts


Circuit Breaker
PE90609

Main technical characteristics


YSF6
Rated current (Ir) 630 - 1250 A
YSF6 EVOLIS Short circuit current (Isc) Up to 25 kA
Circuit Breaker Rated voltage Un (50/60 Hz) 12 kV

YSF6 Evolis YSF6 Evolis

Technology Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 11 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75 Closing time (ms) < 50
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 65
Rated current Ir (A) 630 - 1250 Number of switching 10.000
Short circuit current Isc (kA) 25 operations

Short circuit duration Tk (s) 3  Service temperature (°C) - 25 / + 40

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90607

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-66
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

A-67
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

D-12 panel by D-12 panel


Original brand: AEG

ECOFIT™ proposal
PE90648

With ECOFIT™, a true extended life time


1994 2004

D-12

D-12

ECOFIT™ solution

Commercialisation End of spare parts


D-12

Main technical characteristics


D-12
Rated current (Ir) 1250 A 1600 A
Short circuit current (Isc) 10 - 25 kA 25 - 31.5 kA
Rated voltage Un (50/60 Hz) 12 kV 12 kV

D-12 D-12
Rated insulation level (kV) 12 Rated current of busbar (A) 1250 - 1600 - 2000 - 2500 - 3150*
Rated power frequency 95 Rated short time withstand 25 - 31.5
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 185 Internal Arc Classification PEHLA 31.5 kA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 1200x2400x2500 Ingress Protection degree Standard IP2X
(mm) (IP) On request IP3X, IP4X
* With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90648

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-68
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

D-24 panel by D-24 panel


Original brand: AEG

ECOFIT™ proposal
PE90651

With ECOFIT™, a true extended life time


1994 2004

D-24

D-24

ECOFIT™ solution

D-24
Commercialisation End of spare parts

Main technical characteristics


D-24
Rated current (Ir) 100 - 630 A 630 - 2150 A
Intensity short circuit (Isc) 10 - 16 kA 16 - 25 kA
Rated voltage Un (50/60 Hz) 24 kV 24 kV

D-24 D-24
Rated insulation level (kV) 24 Rated current of busbar (A) 1250 - 1600 - 2000 - 2500 - 3150*
Rated power frequency 95 Rated short time withstand 10 - 16 - 25
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 185 Internal Arc Classification 25
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 1200x2400x2500 Ingress Protection degree Enclosure IP4X, Compartment IP2X
(mm) (IP)
* With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90649

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-69
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

DNF7 panel by DNF7 panel


Original brand: Alsthom

ECOFIT™ proposal
PE90748

With ECOFIT™, a true extended life time


1983 2013 2014

DNF7

DNF7

ECOFIT™ solution

Commercialisation End of commercialisation


DNF7

Main technical characteristics


DNF7
Rated current (Ir) 400 - 2000 A
Intensity short circuit (Isc) 31.5 kA
Rated voltage Un (50/60 Hz) 36 kV

DNF7 DNF7
Rated insulation level (kV) 36 Rated current of busbar (A) 400 - 1250 (2500***)
Rated power frequency 70 Rated short time withstand 16 - 31.5
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 170 Internal Arc Classification 25 kA
voltage (peak value) (kVp) (0.2s) (AFLR)
Overall dimensions (wxhxd) 1300x2250*x2300** Ingress Protection degree Enclosure IP3X
(mm) (IP)
* 2900 mm with busbar compartment - ** 2500 mm with internal arc withstand, 2750 mm with cables voltage compartment - *** With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90748

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-70
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F100-200 panel by Fluair F100-200 panel


Original brand: Merlin Gerin

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90409

1980 1998

F100-200
F100-200

ECOFIT™ solution

Commercialisation End of commercialisation


F100/200

Main technical characteristics


F100 F200
Rated current (Ir) 630 - 3150 A 630 - 3150 A
Short circuit current (Isc) 25 - 50 kA 25 - 50 kA
Rated voltage Un (50/60 Hz) 7.2 kV 12 - 17.5 kV

F100-200 F100-200
Rated insulation level (kV) 7.2 - 12 - 17.5 Rated current of busbar (A) Up to 3150
Rated power frequency 20 - 28 - 38 Rated short time withstand Up to 50
withstand voltage/1mn (kVrms) current (3s) (kA)
Lightning impulse withstand 60 - 75 - 95 Internal Arc Classification
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) ≤1250A: 650x2100x1455/1700 Ingress Protection degree Enclosure IP3X
(mm) 2500 - 3150A: 900x2100x1700 (IP)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90677

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-71
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Fluair F100C panel by Fluair F100C panel


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90644

With ECOFIT™, a true extended life time


1980 1998

F100C
F100C

ECOFIT™ solution

Commercialisation End of commercialisation


F100C

Main technical characteristics


F100C
Rated current (Ir) 630 - 2500 A
Short circuit current (Isc) 8 - 50 kA (with fuses)
Rated voltage Un (50/60 Hz) 7.2 kV

F100C F100C
Rated insulation level (kV) 7.2  Rated current of busbar (A) 630  - 2500
Rated power frequency 20  Rated short time withstand 50
withstand voltage/1mn (kVrms) current (3s) (kA)
Lightning impulse withstand 60 Internal Arc Classification NA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 650x1050x1455 Ingress Protection degree Enclosure IP3X (other: please consult us)
(mm) (IP)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90677

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-72
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

PNX36 panel by PNX36 panel


Original brand: AEG

ECOFIT™ proposal
PE90819

With ECOFIT™, a true extended life time


1994 2015

PNX36
PNX36

ECOFIT™ solution

Commercialisation End of commercialisation

PNX36

Main technical characteristics


PNX36
Rated current (Ir) 630 - 2500 A
Short circuit current (Isc) 10 - 25 kA
Rated voltage Un (50/60 Hz) 36 kV

PNX36 PNX36
Rated insulation level (kV) 36 Rated current of busbar (A) 630 - 2500*
Rated power frequency 70 Rated short time withstand 82
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 170 Internal Arc Classification Arcing due to internal fault according to
voltage (peak value) (kVp) (1s) (AFLR) IEC 60298, 31.5 kA 1s, Type of accessibility A
Overall dimensions (wxhxd) 120x2500x1600 Ingress Protection degree
(mm) (IP)
* With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90819

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-73
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

PX12-24 panel by PX12-24 panel


Original brand: Alstom

ECOFIT™ proposal
PE90677

With ECOFIT™, a true extended life time


1993 1997

PX12-24 
PX12-24

ECOFIT™ solution

Commercialisation End of commercialisation


PX12-24

Main technical characteristics


PX12 PX24
Rated current (Ir) 400 - 3150 A 400 - 2500 A
Short circuit current (Isc) 25 - 40 kA 16 - 25 - 31.5 kA
Rated voltage Un (50/60 Hz) 12 kV 24 kV

PX12 PX24 PX12 PX24


Rated insulation level (kV) 12 24 Rated current of busbar (A) 630 - 3150 630 - 2500
Rated power frequency 28 50 Rated short time withstand 25 - 40 25 - 31.5
withstand voltage/1mn (kVrms) current (3s) (kA)
Lightning impulse withstand 75 125 Internal Arc Classification 25 25
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (mm) <1250A: 650x2135x1320 ≤2000A: 750x2135x1320 Ingress Protection degree Enclosure IP3X Enclosure IP3X
(W x H x D) ≤2000A: 750x2135x1320 >2000A: 900x2335x1570 (IP)
>2000A: 900x2135x1320

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90677

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-74
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

R panel by R panel
Original brand: AEG

ECOFIT™ proposal
PE90655

With ECOFIT™, a true extended life time


1973 1990 1999 2000

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


R

Main technical characteristics


R
Rated current (Ir) 400 - 2500 A 400 - 2500 A
Short circuit current (Isc) Up to 40 kA/3s Up to 25 kA/3s
Rated voltage Un (50/60 Hz) 12 kV 24 kV

R R
Rated insulation level (kV) 12 - 24 Rated current of busbar (A) 630 - 3350
Rated power frequency 28 - 50 Rated short time withstand 40 - 125
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 75 - 125 Internal Arc Classification PEHLA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 700, 800, 1000, 1400, 1600x2330, 2420x1100, Ingress Protection degree Standard IP2X
(mm) 1250, 1300, 1450 (IP) On request IP3X, IP4X

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90655

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-75
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

VISAX panel by VISAX panel


Original brand: GEC Alstom

ECOFIT™ proposal
PE90219

With ECOFIT™, a true extended life time


1996 2015 2029

VISAX

VISAX

ECOFIT™ solution

Commercialisation End of spare parts

VISAX
Main technical characteristics
VISAX
Rated current (Ir) Up to 2500 A Up to 2500 A Up to 2500 A
Short circuit current (Isc) 25 kA/3s 25 kA/3s 25 kA/3s
Rated voltage Un (50/60 Hz) 12 kV 17.5 kV 24 kV

VISAX VISAX
Rated insulation level (kV) 12 17.5 24 Rated current of busbar (A) Up to 2500 Up to 2500 Up to 2500
Rated power frequency 28  38 50 Rated short time withstand 25 25 25
withstand voltage/1mn (kVrms) current (3s) (kA)
Lightning impulse withstand 75 95 125 Internal Arc Classification 25 25 25
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 800 - 1100x2150  - 2650x1250 - 1540 Ingress Protection degree IP3X - IP4X IP3X - IP4X IP3X - IP4X
(mm) (IP)
* With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90219

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-76
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

VMX panel by VMX panel


Original brand: GEC Alstom

ECOFIT™ proposal
PE90692

With ECOFIT™, a true extended life time


1987 2004

VMX

VMX

ECOFIT™ solution

Commercialisation End of commercialisation


VMX
Main technical characteristics
VMX
Rated current (Ir) 630 - 2000 A
Short circuit current (Isc) Up to 25 kA/3s
Rated voltage Un (50/60 Hz) 11 kV

VMX VMX
Rated insulation level (kV) 12 Rated current of busbar (A) Up to 2000
Rated power frequency 28 - 35 Rated short time withstand Up to 26.3
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 75 Internal Arc Classification 25
voltage (peak value) (kVp) (3s) (AFLR)
Overall dimensions (wxhxd) 606 - 540x2000  - 2000x1867 - 1360 Ingress Protection degree IP3X
(mm) (IP)
* With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90692

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-77
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WBA panel by WBA panel


Original brand: AEG

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90657

1989 2006

WBA

WBA

ECOFIT™ solution

WBA Commercialisation End of commercialisation

Main technical characteristics


WBA
Rated current (Ir) 630 - 2500 A 630 - 2500 A
Short circuit current (Isc) 16 - 25 kA & 20 - 50 kA 20 - 50 kA
Rated voltage Un (50/60 Hz) 12  - 24 kV 12  - 38 kV

WBA WBA
Rated insulation level (kV) 12 - 24 Rated current of busbar (A) 630 - 2500
Rated power frequency 28 - 50 Rated short time withstand 63 - 80
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 75 - 125 Internal Arc Classification PEHLA 31.5 kA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 600/800/1000x2330x1250/1300 Ingress Protection degree Standard IP2X
(mm) (IP) On request IP3X, IP4X

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90658

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-78
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WBB panel by WBB panel


Original brand: AEG

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90659

1990 2006

WBB
WBB

ECOFIT™ solution

Commercialisation End of commercialisation


WBB

Main technical characteristics


WBB
Rated current (Ir) 630 - 2500 A
Short circuit current (Isc) 20 - 50 kA
Rated voltage Un (50/60 Hz) 12  - 24 - 38 kV

WBB WBB
Rated insulation level (kV) 12 - 15 Rated current of busbar (A) 630 - 2500
Rated power frequency 28 - 38 Rated short time withstand 63 - 80
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 75 - 95 Internal Arc Classification PEHLA 31.5 kA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 600, 800, 1000x2330x1250, 1500 Ingress Protection degree Standard IP2X
(mm) (IP) On request IP3X, IP4X

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90660

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-79
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WBD panel by WBD panel


Original brand: AEG

ECOFIT™ proposal
PE90820

With ECOFIT™, a true extended life time


1992 2015

WBD

WBD 

ECOFIT™ solution

Commercialisation End of commercialisation


WBD

Main technical characteristics


WBD
Rated current (Ir) 630 - 3150 A
Short circuit current (Isc) 80 kA
Rated voltage Un (50/60 Hz) 12 kV

WBD WBD
Rated insulation level (kV) 12 Rated current of busbar (A) 630 - 3150*
Rated power frequency 28 Rated short time withstand 80
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 80 Internal Arc Classification PEHLA 31.5 kA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 600, 800x3000x1750 Ingress Protection degree IP 2X even for open door and modul in
(mm) (IP) disconnecting position, IP 3X to the busbar,
outside IP 52 possible
* With forced cooling (on request)

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90820

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-80
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

WK panel by WK panel
Original brand: AEG

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90661

1987 2003

WK

WK

ECOFIT™ solution

Commercialisation End of commercialisation


WK

Main technical characteristics


WK
Rated current (Ir) 630 - 2500 A
Short circuit current (Isc) 20 - 50 kA/3s
Rated voltage Un (50/60 Hz) 12  - 24 - 38 kV

WK WK
Rated insulation level (kV) 3.6 - 24 Rated current of busbar (A) 630 - 4000
Rated power frequency 28 - 38 Rated short time withstand 63 - 80
withstand voltage/1mn (kVrms) current (4s) (kA)
Lightning impulse withstand 110 Internal Arc Classification PEHLA 31.5 kA
voltage (peak value) (kVp) (1s) (AFLR)
Overall dimensions (wxhxd) 600/1060x2330x1700/2100 Ingress Protection degree Standard IP2X
(mm) (IP) On request IP3X, IP4X

Offer extension
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
PE90661

PE90437

Sepam series 10, 20, 40, 60 , 80

or
PE90488

MICOMP series 10, 20, 30, 40

A-81
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Cradle to Cradle / All breaker types 


Withdrawable CB by Evolis MC cassette Original brand: All

All breaker
ECOFIT™ proposal
types
Compatible with With ECOFIT™, a true extended life time
all open Air
Insulated
Switchgear legacy This solution consist in fitting a cradle inside an existing panel.
and no legacy - It is particularly adapted for non Schneider Installed Base.
cubicles
with minimum - ECOFIT™ solution with shutters and mechanical interlocks embedded.
inside panel
width ≥ 560 mm - Only the fixed connections (between the cradle and existing busbar) are customized.
- Only the width of the existing panel has to be considered.
PE57994

Main technical characteristics


All types
Rated current (Ir) 630 - 1250 A 630 - 2500 A
Evolis Short circuit current (Isc) Up to 31.5 kA Up to 40 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 7.2 - 12 kV 7.2 - 12 - 17.5 kV

Evolis MC1 MC2 MC3 Evolis MC1 MC2 MC3

Technology Vacuum Vacuum Vacuum Switching sequence O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2 - 12 7.2 - 12 - 17.5 7.2 - 12 - 17.5 O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 - 75 60 - 75 - 95 60 - 75 - 95 Closing time (ms) < 65 < 65 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) < 50 < 50 < 50

Rated current Ir (A) 630 - 1250 630 - 1250 630 - 2500 Number of switching 2.000 (for Isc= 40 kA class M1) - 10.000
Short circuit current Isc (kA) Up to 31.5 Up to 40 Up to 40 operations

Short circuit duration Tk (s) 3  3  1  Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40

240 240 550


DE57194EN

Cassette MC1 MC2 MC3


285
Phase to phase (mm) E 145 185 240
Dimensions (mm) W 556 686 886
H
805
370 H 980 980 980
D 1223 1223 1223
300 Weight (kg) 222 255 326
321 611 100
W D

A-82
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium Voltage Distribution

Cradle to Cradle / All breaker types 


Withdrawable CB by F400 cassette Original brand: All

All breaker
ECOFIT™ proposal
types
Compatible with With ECOFIT™, a true extended life time
all open Air
Insulated
Switchgear legacy This solution consist in fitting a cradle inside an existing panel.
and no legacy - It is particularly adapted for non Schneider Installed Base.
cubicles
with minimum - ECOFIT™ solution with shutters and mechanical interlocks embedded.
inside panel
width ≥ 1105 mm - Only the fixed connections (between the cradle and existing busbar) are customized.
- Only the width of the existing panel has to be considered.
DE57396

Main technical characteristics


All types
Rated current (Ir) 1250 - 2500 A 1250 A
F400 Short circuit current (Isc) Up to 40kA Up to 31.5 kA
Circuit Breaker
Rated voltage Un (50/60 Hz) 24 - 36 kV 40.5 kV

F400 - SF F400 cassette F400 - SF F400 cassette

Technology SF6 SF6 Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO


O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 24 - 36 40.5 O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO

Surge withstand voltage Up (kV) 125 - 170 185 Closing time (ms) < 65 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 50 < 50

Rated current Ir (A) 1250 - 2500 1250 Number of switching 10000 10000


Short circuit current Isc (kA) 25 - 40 31.5 operations

Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40


PE57431

Cassette 1250 A 2500A - 3000 A


Dimensions (mm) A 738 752
B 540 533
C 2030 2030
Weight (kg) 750 850

New panel technical characteristics

A-83
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
PE90457

TM

ECOFIT

Low Voltage
Distribution
Low Voltage Distribution

Contents
LV Circuit Breaker or Contactor
B Control B-2
Compact C801-C1251 B-3
DA B-4
DS B-5
H Series B-6
Masterpact M B-7
SE B-8
Selpact B-9
Unelec CNP B-10
Visucompact CM B-11
Associated offers -
B-12
Energy Management
Associated offers -
B-12
Source-changeover systems

LV Drawer
T140 B-13
MB400 B-14
Offer Extension -
B-15
Drawer components

B-1
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

B Control by Masterpact NT - NW


Original brand: Nuova Magrini Galileo

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90573

1972 1990 2005 2009

B Control (B1-35/B1-50/B3-50/B3-75/B3-90/B4-100)

B Control Masterpact NT - NW


Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90574

Main technical characteristics

B Control Masterpact NT - NW


Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V
Masterpact NW
Circuit Breaker Rated current (A) In 40° C 800 - 4000 A 800 - 4000 A
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 32 - 100 kA 42 - 150 kA

B Control ECOFIT™ solution


The ECOFIT™ B Control solution enables to benefit from all the enhanced features of Masterpact NT
PE90574

or NW circuit breakers and accessories.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

Compact C801 - C1251 by Compact NS800 - NS1250


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90430

PE90572

With ECOFIT™, a true extended life time


1993 2007 2009

Compact C801 - C1251

C801 - C1251 Compact NS800 - NS1251


Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90431

Main technical characteristics

Compact C801 - C1251 Compact NS800 - NS1251

NS801 - NS1251
Rated operational voltage (V AC 50/60 Hz) Ue 690 V 690 V
Circuit Breaker Rated current (A) In 40° C 800 - 1250 A 800 - 1250 A
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 50 - 150 kA 50 - 150 kA

Compact C801 - C1251 ECOFIT™ solutions


Plug & Play
DE90252

The ECOFIT™ ™ Compact Plug & Play solution lets you retrofit the latest generation of Compact NS
circuit breakers in the existing Compact C chassis with very short onsite servicing times.
Solution available for withdrawable type only, 3p & 4p, 800A to 1250A.

Compactkit
1 Removal 2 Replacement
PE90256

PE90257

The ECOFIT™ Compactkit solution enables to benefit from all the enhanced
features of Compact NS circuit breakers and accessories.
It requires total shutdown of the installation to access the busbars.
Solution available for fixed type, 3p & 4p, 800A to 1250A.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-3
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

DA (DSA1 - DNA1 - DSA2 - DNA2 - DRA - DNAH)
by MASTERPACT NW08 -NW63 Original brand: Merlin Gerin

ECOFIT™ proposal
PE90424

With ECOFIT™, a true extended life time


1986 1986 1997 1998

DA (DSA1 - DNA1 - DSA2 - DNA2 - DRA - DNAH)
DA
Circuit Breaker Masterpact NW

ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90427

Main technical characteristics

DA Masterpact NW

Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V


Masterpact NW
Circuit Breaker Rated current (A) In 40° C 630 - 6300 A 800 - 6300 A
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 42 - 100 kA 42 - 150 kA

DA ECOFIT™ solution
The ECOFIT™ DA solution enables to benefit from all the enhanced features of Masterpact NW circuit
PE90427

breakers and accessories.


It requires total shutdown of the installation to access the busbars.
The kit solution (including circuit breaker) is available for fixed and withdrawable types, 3p & 4p,
630 to 6300A.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-4
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

DS by Masterpact NT - NW
Original brand: Square D, Westinghouse

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90537

1983 1998 2007 2013

DS (DS206 - DS416S/H - DS420 - DS308/508/608 - DS516/616/620)

DS Masterpact NT - NW
Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90249

Main technical characteristics

DS Masterpact NT - NW
Rated operational voltage (V AC 50/60 Hz) Ue 600 V 600 V
Masterpact NT - NW
Circuit Breaker Rated current (A) In 40° C 800 - 2000 A 800 - 2000 A
Ultimate breaking capacity (kA rms, 600V AC 50/60Hz) Icu 42 - 65 kA 42 - 65 kA

DS ECOFIT™ solution
The ECOFIT™ DS solutions fixed or draw-out types enable to benefit from all the enhanced features of
PE90249

Masterpact NT or NW circuit breakers and accessories.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-5
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

H Series by Masterpact NT - NW


Original brand: Federal Pioneer

ECOFIT™ proposal
PE90615

With ECOFIT™, a true extended life time


1960 2001 2003 2013

H Series (H3 - HL3 - H2 - HL2 - 1000HF1)

Masterpact NT - NW
H Series
Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90616

Main technical characteristics

H Series Masterpact NT - NW


Rated operational voltage (V AC 50/60 Hz) Ue 600 V 600 V
Masterpact NT - NW
Circuit Breaker Rated current (A) In 40° C 600 - 6000 A 800 - 6000 A
Ultimate breaking capacity (kA rms, 600V AC 50/60Hz) Icu 30 - 200* kA 30 - 200* kA
* with fuse

H Series ECOFIT™ solution


The ECOFIT™ H series solutions fixed or draw-out types enable to benefit from all the enhanced
PE90616

features of Masterpact NT or NW circuit breakers and accessories.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

Masterpact M08 - M63 by Masterpact NW08 -NW63


Original brand: Merlin Gerin

ECOFIT™ proposal
035928

With ECOFIT™, a true extended life time


1986 2003 2004 2013

Masterpact M

Masterpact M Masterpact NW
Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90249

Main technical characteristics

Masterpact M Masterpact NW
Rated operational voltage (V AC 50/60 Hz) Ue 690 V 690 V
Masterpact NW Rated current (A) In 40° C 800 - 6300 A 800 - 6300 A
Circuit Breaker Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 40 - 150 kA 42 - 150 kA

Masterpact M ECOFIT™ solutions


Plug & Play
PE90452

The ECOFIT™ Masterpact Plug & Play solution lets you retrofit the latest generation of Masterpact NW
circuit breakers in the existing Masterpact M chassis.
Solution available for withdrawable type only, 3p & 4p, 800 A to 3200 A.

Masterkit
1 Removal 2 Replacement
PE90453

PE90454

The ECOFIT™ Masterkit solution enables to benefit from all the enhanced
features of Masterpact NW circuit breakers and accessories without
modifying the busbars. It requires total shutdown of the installation to
access the busbars.
Solution available for fixed and withdrawable types, 3p & 4p, 800 A to 6300 A.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-7
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

SE by Masterpact NW
Original brand: Square D

ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90538

1983 2003 2010 2011

SE

SE Masterpact NW
Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90435

Main technical characteristics

SE Masterpact NW
Rated operational voltage (V AC 50/60 Hz) Ue 600 V 600 V
Masterpact NW
Circuit Breaker Rated current (A) In 40° C 1250 - 3000 A 1250 - 3000 A
Ultimate breaking capacity (kA rms, 600V AC 50/60Hz) Icu 100 kA 85 kA

SE ECOFIT™ solution
The ECOFIT™ SE solutions fixed or draw-out types enable to benefit from all the enhanced features
PE90435

of Masterpact NT or NW circuit breakers and accessories.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-8
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

Selpact by Masterpact NT-NW


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90428

With ECOFIT™, a true extended life time


1973 1989 1997 2009

Selpact (DN2 - DS2 - DR2 - DRS2)

Masterpact NT-NW
Selpact
Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90426

Main technical characteristics

Selpact Masterpact NT-NW


Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V
Masterpact NW
Circuit Breaker Rated current (A) In 40° C 630 - 3200 A 800 - 3200 A
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 42 - 100 kA 42 - 100 kA

Selpact ECOFIT™ solution


The ECOFIT™ Selpact solutions enable to benefit from all the enhanced features of Masterpact NT or
PE90426

NW circuit breakers and accessories.

Plug & Play


The Plug&Play solution is available for withdrawable type only, 3p & 4p, 630 to 1600 A.

Kit
The kit solution (including circuit breaker) is available for fixed and withdrawable types, 3p & 4p,
630 to 3200 A.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-9
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

Unelec CNP by Masterpact NW


Original brand: Unelec - Areva

ECOFIT™ proposal
PE90432

With ECOFIT™, a true extended life time


1968 1986 2007 2009

CNP

Masterpact NW
CNP
Circuit Breaker
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90433

Main technical characteristics

CNP Masterpact NW
Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V
Masterpact NW
Circuit Breaker Rated current (A) In 40° C 1250 - 2000 A 1250 - 2000 A
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 36 - 100 kA 42 - 100 kA

CNP ECOFIT™ solution


The ECOFIT™ CNP solution enables to benefit from all the enhanced features of Masterpact NW
PE90433

circuit breakers and accessories.


The solution is suitable for fixed type and only for Normabloc 660 switchboard.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-10
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

Visucompact CM by Masterpact NW
Original brand: Merlin Gerin

ECOFIT™ proposal
PE90434

With ECOFIT™, a true extended life time


1985 2001 2005 2010

Visucompact CM

Masterpact NW
Visu Compact CM
Circuit Breaker ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90435

Main technical characteristics

Visucompact CM Masterpact NW
Rated operational voltage (V AC 50/60 Hz) Ue 440 V 690 V
Masterpact NW
Circuit Breaker Rated current (A) In 40° C 1250 - 2500 A 1250 - 2500 A
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu 70 - 85 kA 42 - 100 kA

Visucompact CM ECOFIT™ solution


The ECOFIT™ Visucompact solution enables to benefit from all the enhanced features of
PE90435

Masterpact NW circuit breakers and accessories.

Active Energy Management™ programme that includes an energy metering system


• Identify the device,
DB402068

PE90571

• Indicate status conditions,


• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.

B-11
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

LV Circuit Breaker & Contactor - Associated offers

Energy Management - Micrologic control units - Measurements and protections

Available for
ECOFIT™ solutions
using Masterpact
NT/NW and
Compact NS

Micrologic 2 5 6 7
Type A-E A-E-P-H A-E-P-H A-P-H
Functions Long time Long time Long time Long time
+ instantaneous + short time + short time + short time
+ instantaneous + instantaneous + instantaneous
+ earth fault + earth leakage up to 3200A

A: Current measurements, fault indications, display and current maximeter.


Specificities: 6.0 provides earth fault protection (residual or Source Ground Return); 7.0 provides earth leakage protection.
E: A + Instantaneous measurement of power and energy without earth leakage protection.
P: A + Calculation of power and energy value, voltage measurement, and programmable protection
H: P + Harmonics

Energy Management - Communication


• Identify the device. 1
• Indicate status conditions.
Available for • Control the device 24 V DC
ECOFIT™ solutions (with the communicating auxiliairies).
using Masterpact • Setting of the protection and alarms functions.
NT/NW and 7
Compact NS 1 Modbus network
2 CCM: Chassis
Communication Module
2
8

3 Breaker Universal Logic 3


Plug (ULP) cord
4 Breaker Communication
Module (BCM)

5 Prefabricated wiring Compact NS


5
6 Micrologic trip unit or Masterpact
NT or NW
7 FDM21 display 4 depending on
the device

8 Line terminator
6

Source-changeover systems
Mechanical interlocking (2 types) Automatic controllers
Available for Using connecting rods or using IVE: Electrical interlocking BA or UA automatic controllers
DA, Selpact and cables
Masterpact M
ECOFIT™ solutions
using Masterpact
NT/NW

B-12
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

T140 drawers by T140 drawers


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90687

With ECOFIT™, a true extended life time


1975 1990 1998

T140 drawers
PE90688

T140 drawers

ECOFIT™ solution
T140 drawers

Commercialisation End of commercialisation End of spare parts


PE90685

Main technical characteristics

T140 drawers T140 drawers


Rated operational voltage (V AC 50/60 Hz) Ue 440 V 440 V
Rated current (A) In 40° C 125 - 625 A 125 - 625 A
T140 drawers
Number of modules 1 to 6 1 to 6

T140 drawers ECOFIT™ solution


The ECOFIT™ T140 drawer solution enables to benefit from all the enhanced features of latest
PE90685

technology devices.
The drawer solutions are suitable for manual or electrical operations.

T140 drawers ECOFIT™ solution - Drawer components


PB103354

• Electrical distribution - Functional units (NSX range with Micrologic).

• Motor control command and protections - Functional units.


102870

102870

102873
LC1D12
106167

• Control command auxiliaries for all types of drawers.


054047

111601

107395
107429

B-13
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

MB400 drawers by MB400 drawers


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90689

With ECOFIT™, a true extended life time


1991 2003 2013

MB400 drawers
PE90688

MB400 drawers

ECOFIT™ solution
MB400 drawers

Commercialisation End of commercialisation End of spare parts


PE90685

Main technical characteristics

MB400 drawers MB400 drawers


Rated operational voltage (V AC 50/60 Hz) Ue 440 V 440 V
Rated current (A) In 40° C 125 - 625 A 125 - 625 A
MB400 drawers
Number of modules 1 to 6 1 to 6

MB400 drawers ECOFIT™ solution


The ECOFIT™ MB400 drawer solution enables to benefit from all the enhanced features of latest
PE90685

technology devices.
The drawer solutions are suitable for manual or electrical operations.

MB400 drawers ECOFIT™ solution - Drawer components


PB103354

• Electrical distribution - Functional units (NSX range with Micrologic).

• Motor control command and protections - Functional units.


102870

102870

102873
LC1D12
106167

• Control command auxiliaries for all types of drawers.


054047

111601

107395
107429

B-14
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Low Voltage Distribution

LV Drawers - Associated offers

Specific spare parts: for any spare parts request for the fixe part, please contact your local correspondant.

Available for
ECOFIT™ solutions
using Masterpact
Drawer components
NT/NW and
Compact NS • Electrical distribution – Functional units (NSX range)

Micrologic 2.2 or 2.3 5.2 or 5.3 6.2 or 6.3


Type A-E A-E
Functions LSI protection LSI protection LSI protection
Ammeter Ammeter
Energy meter Energy meter
A: Current measurements, fault indications, display and current maximeter. Specificities: 6.0 provides earth fault protection
(residual or Source Ground Return); 7.0 provides earth leakage protection.
E: A + Instantaneous measurement of power and energy without earth leakage protection.

• Motor control command and protections – Functional units


1 component motor feeder 2 components motor feeder 3 components motor feeder

Circuit breaker - Thermomagnetic circuit breaker + Thermomagnetic circuit breaker


Contactor combination Contactor or switch-disconnector fuse +
Contactor + Thermal protection

• Control command auxiliaries for all types of drawers


Miniature circuit-breaker
Auxiliary relays
Protection auxiliary circuit

Ground fault protection Push buttons and lights

B-15
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
PE90457

TM

ECOFIT

Protection
relays
MV Protection relay

Contents
Protection relay upgrade benefits C-2
CO C-3
CDG C-4
DPU 445 C-5
HCB C-6
IAC C-7
KCGG 122 & 142 C-8
M range - MCGG 11, 21 & 22 C-9
M range relay - MCTI 39-40 C-10
MCGG 62 C-11
Sepam 2000 C-12
VIP - RM6+ C-13
VIP & Vigirex - Various equipment C-14

C-1
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

Protection upgrade benefits

Improve the performance of your system Why protection upgrade?


with the latest technology in micro-processor
By replacing solid state and older type electromechanical protection relays
based integrated relays.
with technologically advanced multi-function microprocessor-based digital relays,
the performance accuracy and longevity of your system can be significantly improved.
With a number of different protection functions Schneider Electric's range of relays
can provide a range of options to include metering; communication; event capture;
monitoring and control. Units are self-diagnostic to provide enhanced reliability.
It is normally possible to use the existing current and potential transformers
and auxiliary digital relay inputs.
Schneider Electric's application based approach makes it easy to select
the appropriate relay for your needs.

What are the benefits?


Accuracy System protection at the current level reduces unnecessary outages
and minimise stresses to equipment.

Increased accuracy of measurement assists in cost allocation


and understanding power demand requirements.

High reliability from advanced self supervision systems.

Flexibility The integrated functions of the relay allow for communications and control
of the equipment either as a stand-alone unit or as part of networked systems.

All components in the protection chain are referenced and interface rapidly.

No constraints for integration in cubicles due to the compact size of the base unit.

Ease of use Settings and adjustments are entered via the device's keypad
and visually displayed.

Reduced costs The amalgamation of functions into one self-diagnosing meter


reduces expenditure and saves on space.

C-2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

CO by MiCOM P111/115
Original brand: General Electric

ECOFIT™ proposal
PE90866

With ECOFIT™, a true extended life time


2011

CO

CO MiCOM P111/115
Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90867

Main technical characteristics


CO MiCOM P111/115
Case FT-11 or FT 21 Fit FT-11 & FT 21 cutout
MiCOM P111 & 115 Replacement Type - 1 for 3* with minimal rewiring
Protection Relay Type Electromechanical Numerical
Functionality Single phase overcurrent 3 phase + Ground overcurrent
Power supply - 24 VDC - 250 VDC
Communication - IEC 60870-5-103, Modbus RTU
*1 ECOFIT™ P111/115 – CO9 solution could replace 3 single phase CO9 units.

C-3
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

CDG - CAG - CTMM - CTMFM by MiCOM P1x –P2x or Vamp 5x


Original brand: Areva or older

ECOFIT™ proposal
PE90881

With ECOFIT™, a true extended life time

CDG - CAG - CTM range relays


MiCOM or Vamp
CDG type ECOFIT™ solution
Protection Relay

Commercialisation End of commercialisation End of spare parts

Old relay models ECOFIT™ solutions Descrition


Feeder protection relay
CDG - CAG MiCOM P122/P123
(Modbus/IEC103)
Motor protection relay
PE90882

CTMM - CTMFM MiCOM P211


(Modbus/IEC103)
Feeder protection relay
CDG - CAG VAMP 50/52
(IEC 61850)

Main technical characteristics


MiCOM P
Protection Relay CDG - CAG - CTM range relays MiCOM or Vamp
20TE, 4U withdrawal case, mounted
Case Based on 1 or 3 independent units as plug and play solution into the
existing DGC /CAG/ CTM range case
1 withdrawal relay for 3 individual
Replacement Type -
units
Type Electromechanical & induction disk relay type Numerical
Functionality Selective earth & phase fault overcurrent 3 phase & earth overcurrent
Frequency range Calibrated for 50 Hz or 60 Hz only 50 to 60 Hz +/- 20 %
Communication - IEC 60870-5-103, ModBus

C-4
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

DPU 445 by MiCOM P123


Original brand: ABB

ECOFIT™ proposal
PE90872

With ECOFIT™, a true extended life time


2011

DPU 445

DPU 445 MiCOM P123


Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90873

Main technical characteristics


DPU 445 MiCOM P123
Case DPU 445 Fit existing cutout
MiCOM P123 Replacement Type - 1 for 1 with minimal rewiring
Protection Relay Type Digital Numerical
Functionality 3 phase feeder 3 phase + ground feeder overcurrent
Power supply 24 VDC - 125 VDC 24 VDC - 250 VDC
Courier, DNP 3.0, IEC 60870-5-103,
Communication -
ModBus RTU

C-5
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

HCB by MiCOM P521


Original brand: ABB

ECOFIT™ proposal
PE90870

With ECOFIT™, a true extended life time


2009

HCB

HCB MiCOM P521


Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90871

Main technical characteristics


HCB MiCOM P521
Case FT-42 Fit existing cutout
MiCOM P521 Replacement Type - 1 for 1 with minimal rewiring
Protection Relay Type Electromechanical Numerical
Functionality 3 phase differential 3 phase differential
Power supply - 24 VDC - 250 VDC
Communication - IEC 60870-5-103, ModBus RTU

C-6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

IAC by MiCOM P122


Original brand: General Electric

ECOFIT™ proposal
PE90868

With ECOFIT™, a true extended life time


2011

IAC

IAC MiCOM P122


Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90869

Main technical characteristics


IAC MiCOM P122
Case S1, S2, L2 or M1 Fit S1, S2, L2 or M1 cutout
MiCOM P122 Replacement Type - 1 for 3* with minimal rewiring
Protection Relay Type Electromechanical Numerical
Functionality Single phase overcurrent 3 phase + Ground overcurrent
Power supply - 24 VDC - 250 VDC
Courier, DNP3.0, IEC 60870-5-103,
Communication -
ModBus RTU
*1 ECOFIT™ P122 – IAC solution could replace 3 single phase IAC units.

C-7
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

KCGG 122 & 142 by MiCOM P123R


Original brand: Areva

ECOFIT™ proposal
PE90634

With ECOFIT™, a true extended life time


1997 2010 2011 2012

KCGG 122 & 142

KCGG 122 & 142 MiCOM P123R


Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of support


PE90635

Main technical characteristics


MiCOM P123R
Protection Relay
K range relay - KCGG 122 & 142 MiCOM P123R
Case 20TE size flush mounting 20TE size flush mounting
Installation Withdrawable case Withdrawable case
Language English Multilanguage
Communication KBus / Courier KBus / Courier, DNP3, IEC60870-5-103
Power supply 24 V / 125 VDC - 48 V / 250 VDC 24 V / 250 VDC - 48 V / 240 VDC
Digital input supply 48 VDC only According to Power Supply (above)

ECOFIT™ KCGG 122 & 142 upgrades: diagnosis + implementation/installation of a fully industrialised solution
Improve the Full retrofit solution
performance of your Sustainability
■ Replacement of the protection relay and optimised maintenance.
system with the latest ■ Access to spare parts, new communication protocols
technology in micro- and software facilities.
processor based ■ Schneider Electric technical support and guarantee.
Manufacturer expertise
No mechanical or electrical impact on your
integrated relays.
■ Solution developed by our specialist engineers. installation. Implementation and site test within
■ Enhanced performance. a very limited time.
■ Retrofit process optimised. New features enabled:
■ Installation warranted by the manufacturer. ■ Advanced HMI for local control functions.
Consultancy and audit - Engineering solutions &
optimisation ■ Standard communication protocols (Modbus,
Local support & assistance - Maintenance & IEC 60870-5-103, DNP3 or KBUS/Courier).
refurbishment ■ Monitoring & Automation facilities..

C-8
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

M range - MCGG 11, 21 & 22 by MiCOM P120H


Original brand: Areva

ECOFIT™ proposal
PE90752

With ECOFIT™, a true extended life time


< 1984 2010 2012

M range - MCGG 11, 21 & 22

MCGG 22 MiCOM P120H


Protection Relay
ECOFIT™ solution

Commercialisation End of spare parts


PE90635

MiCOM P120H
Protection Relay Main technical characteristics
M range relay - MCGG 11, 21 & 22 MiCOM P120H
Case 20TE size flush mounting 20TE size flush mounting
Installation Withdrawable case Withdrawable case
Language English Multilanguage
Communication KBus / Courier KBus / Courier, DNP3, IEC60870-5-103
Power supply 24 V / 125 VDC - 48 V / 250 VDC 24 V / 250 VDC - 48 V / 240 VDC
Digital input supply 48 VDC only According to Power Supply (above)

C-9
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

M range - MCTI 39-40 by MiCOM P821MF


Original brand: Areva

ECOFIT™ proposal
PE90751

With ECOFIT™, a true extended life time


1984 2010 2012

M range - MCTI 39-40

MCTI 39-40 MiCOM P821MF


Protection Relay
ECOFIT™ solution

Commercialisation End of spare parts


PE90635

Main technical characteristics


MiCOM P821MF
Protection Relay M range relay - MCTI 39-40 MiCOM P821MF
Case 20TE size flush mounting 20TE size flush mounting
Installation Withdrawable case Withdrawable case
Language English Multilanguage
Communication KBus / Courier KBus / Courier, DNP3, IEC60870-5-103
Power supply 24 V / 125 VDC - 48 V / 250 VDC 24 V / 250 VDC - 48 V / 240 VDC
Digital input supply 48 VDC only According to Power Supply (above)

C-10
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

MCGG 62 by MiCOM P126


Original brand: Areva or older

ECOFIT™ proposal
PE90874

With ECOFIT™, a true extended life time


< 1984 2010 2014

MCGG 62

MCGG 62 MiCOM P126


Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90875

Main technical characteristics


MCGG 62 MiCOM P126
Case Size 6 Fit existing cutout
MiCOM P126 Replacement Type - 1 for 1 plug-and-play
Protection Relay Type Static Numerical
Functionality 3 phase overcurrent 3 phase + ground overcurrent
Power supply 24 VDC - 125 VDC 24 VDC - 250 VDC
DNP 3.0, IEC 60870-5-103,
Communication -
ModBus RTU

C-11
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

Sepam 2000 by Sepam 60 - 80 series


Original brand: Merlin Gerin

ECOFIT™ proposal
PE90638

With ECOFIT™, a true extended life time


1993 2006 2012 2015

Sepam 2000

Sepam 2000 Sepam 60 - 80 series


Protection Relay
ECOFIT™ solution

Commercialisation End of commercialisation End of spare parts


PE90639

Main technical characteristics


Sepam Sepam
Sepam 2000
serie 80 serie 60*
M06, M07, M08, M14 X
Motor Application
Sepam 60 - 80 series M02 to M05, M09, M11, M15, M16, M20 to M23 X
Protection Relay
S02, S03, S06 to S09 X
Sub-station Application
S01, S04, S05 X
Bus Bar Application B02, B04, B07, B12 X
B01, B03 X
Transformer Application T01 to T03, T06, T07, T09, T10, T12 to T15, T17 to T19 X
without temp measurement T04, T05, T11, T16 X
Transformer Application T21, T22, T23, T26, T27, T29, T30, T32 to T35, T37 to T39 X
with temp measurement T24, T25, T31, T36 X
Generator Application G01 to G08, G12, G13, G15 to G18 X
C02, C04, C06, C08 X
Capacitor bank Application
C01, C03 X
Transformer
D02, D22 X
Diff. Application
* Sepam serie 80 will be proposed in case of customised Logipam on the original Sepam 2000

ECOFIT™ Sepam 2000 upgrades: diagnosis + implementation/installation of a fully industrialised solution


Improve the 1. Disconnection of existing 2. Presentation of new
performance of your terminal blocks ECOFIT™ S2000
system with the latest
PE90637
PE90637

technology in micro- No mechanical or electrical impact on your


processor based installation. Implementation and site test within
integrated relays. a very limited time.
New features enabled:
■ Advanced HMI for local control functions.
■ Standard communication protocols (Modbus, IEC
61850).
■ Monitoring & advanced graphical interface for
automations and logics.

C-12
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

RM6+ / VIP by VIP + ECOFIT™ kit


Original brand: Merlin Gerin

A true extended life time


PE90567

1987 1998 2008 2012


PE90568

VIP

VIP

VIP
ECOFIT™ solution
Protection relays
Commercialisation End of commercialisation End of spare parts

Proposed substitution
PE90570

RM6+
Phase overcurrent protection IDMT
PE90569

VIP 11R VIP 300LL


(Inverse Definite Minimum Time)
Phase overcurrent protection IDMT
VIP 12R VIP 300LL
(Inverse Definite Minimum Time)
VIP 300LL
Protection relays Phase overcurrent and earth-fault protection
VIP 200 VIP 300LL
IDMT and DT IEC 60255

C-13
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

Various equipment / VIP & Vigirex by VIP & Sepam


Original brand: Merlin Gerin

A true extended life time


PE90835

1987 1998 2005* 2012


PE90568

VIP & Vigirex

VIP & Sepam

VIP
Proposed substitution
Protection relays
Commercialisation End of commercialisation End of spare parts

* Depending on the range

Proposed substitution
Various equipments
Phase overcurrent and Earth-fault protection
VIP 200RMR VIP 300LH
PE90835

IDMT and DT IEC 60255


Sensitive earth-fault protection Vigirex RH110 Sepam series 10
PE90569

Phase overcurrent protection IDMT VIP 13 VIP 30 - VIP 300 - TBC


Phase overcurrent protection DT VIP 17 VIP 37
Phase overcurrent and Earth-fault protection
VIP 300LL
VIP 200 VIP 300
IDMT and DT IEC 60255
Protection relays
Sensitive earth-fault VIP 50 Sepam series 10

C-14
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
MV Protection relay

C-15
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
PE90457

TM

ECOFIT

Substation
automation
Substation Automation

Contents
Control System upgrade benefits D-2
BAY Controler BM9x00 D-3
PACIS OI D-4
PSCN3020 HMI D-5
SEEFOX HMI D-6

D-1
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Substation Automation

Control System upgrade benefits

Improve the performance of your system Why Control Systems upgrade?


with the latest technology in micro-processor
Upgrade solutions intend to improve the performance of your control system with the
based integrated relays.
latest technology in computers. This is also the opportunity to benefit from computer
and OS upgrading to Windows 7 to get enhances performances and advanced features
for the new HMI

Considering the large variety of legacy control systems still in operation with limited
extension and maintenance facilities, these Ecofit solutions provide an opportunity
to benefit of a unique HMI software and standard communication protocol based on
IEC61850.

What are the benefits?


Ready for future Enables smooth and consistent legacy Control System solutions modernization.
extensions
Open, flexible and scalable architecture facilitating aggregation of several systems
at substation level.

Easiness for future extensions.

Ease of use Fast implementing without substation shut down, original control systems can
remain in operation in most of cases

No modification of existing communication network protocol (Modbus TCP or IEC


61850, as well as protective relays communication protocol) . This could be done
step by step in further stages.

Enhance graphical Realtime trends of analog values as tooltip


features
Zoom in/ Zoom out

Monitoring facilities by color bar graph status easy implementation

Costs reduction Cost effective solution providing advanced graphical interface features
and enhanced performances.

Secured migration managed by the manufacturer, thanks to an automatic migration


tool and the use of a standard protocol.

D-2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Substation Automation

Bay Controler BM9x00 by MiCOM C624


Original brand: Areva or older

ECOFIT™ proposal
PE90877

With ECOFIT™, a true extended life time


1994 2009 2014 2018

BM9x00

MiCOM C624

ECOFIT™ solution

Commercialisation End of sales End of maintenance

Main characteristics and performances


BM9x00 MiCOM C624
Communication through legacy EFIP protocol with the Standard communication through IEC61850
SCADA level protocol to SCADA level
Conection with Modbus, IEC870-5-103, IEC 870-5-
Connection with Modbus, IEC103 or KBus
101 Kbus (with K101CVT converter) and IEC61850
communication with protection relay protocol
protocol for downstream relays
No front side communication available for setting files Hardened to match substation cyber security
management requirements.

D-3
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Substation Automation

PACIS OI V3.X UP TO V4.6 by PACIS EcoSUI


Original brand: Areva or older

ECOFIT™ proposal
PE90879

With ECOFIT™, a true extended life time


2003 2005 2013 2014

PACiS OI

PACIS EcoSUI

ECOFIT™ solution

Commercialisation End of Windows® 2000, XP commercialisation End of Microsoft support for Windows® XP

Main characteristics and performances


PACIS OI PACIS EcoSUI
Windows® 7 (32/64bits)
Windows® 2000 or XP
Windows® server 2008 64bits
One Ethernet network management
Multiple IEC61850 client access points
Multi-LAN through IEC/IEC Gateways
Maximum handled dataflow 100 Measured Direct IEC61850 configuration by import of
Values archived /sec / server SCD file
Off-line modification & Time delayed deployment Immediate deployment of database
of database after recompilation modification
Redundancy switch over within 1 mn Hot redundancy seamless switchover
Maximum handled dataflow 100 Measured Handled dataflow up to 3000 MV
Values archived /sec / server archived /sec /server

D-4
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Substation Automation

PSCN3020 HMI by EcoSUI HMI


Original brand: Areva or older

ECOFIT™ proposal
PE90878

With ECOFIT™, a true extended life time


1994 2004 2009 2013

PSCN3020 HMI

EcoSUI HMI

ECOFIT™ solution

Commercialisation End of Microsoft support for Windows® XP Obsolescence status

Main characteristics and performances


PSCN3020 HMI EcoSUI HMI
Windows NT4 OS / 2
®
Windows® 7
Open to Ethernet IEC61850 for all future
One EFIP network management extention and step by step replacement of bay
controllers
Configuration & database generation using Direct IEC61850 configuration by import of
proprietary & obsolete software SCD file for all new extensions
Redundancy switch over within 1 mn Hot redundancy seamless switchover
Handled dataflow up to 3000 MV archived /sec
Handled dataflow limited by EFIP protocol
/server, once fully migrated to IEC61850

D-5
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Substation Automation

Seefox HMI by EcoSUI HMI


Original brand: Schneider Electric

ECOFIT™ proposal
PE90876

With ECOFIT™, a true extended life time


1992 2005 2014 2020

Seefox HMI

EcoSUI HMI

ECOFIT™ solution

End of commercialisation & Windows® XP support

Commercialisation End of Windows® XP commercialisation End of maintenance

Main characteristics and performances


Seefox HMI EcoSUI HMI
Full Schneider Electric HMI and tools design
Windows® XP
operating on Windows® 7
Based on third party HMI limited to Modbus TCP or IEC 61850 native in modeling configuration and
Modbus + communication protocol communication
Configuration tools no more supported or with limited Ready for all standard substation extension using
upgrade facilities IEC61850 standard
Compliant with substation cyber security
requirements

D-6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Substation Automation

D-7
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2015
Medium & Low Voltage Distribution
Modernisation of switchboards

ECOFIT
All over the world
TM

Contact us!
www.schneider-electric.com/electricaldistributionservices

ECOFIT TM = tested, validated and certified by Schneider Electric


©2015 - Schneider Electric - All rights reserved.

The information contained in this document consists of general description of the available technical solutions and are for information purposes only.
Schneider Electric does not make any warranty, representation, guarantee or promise, expressed or implied, about the completeness, accuracy and reliability
of this information. The choice of the technical solutions will be defined in the contractual document and always subject to the proper installation and use
in accordance with the related installation guide, the installation manual and the prevailing standard and/or installation regulations.
The information is provided without liability and is subject to change without notice.

Schneider Electric Industries SAS


35, rue Joseph Monier
CS30323
F - 92505 Rueil-Malmaison cedex (France) This document has been printed on ecological paper

RCS Nanterre 954 503 439


Share capital: €928,298,512 Design: SYNTHESE ECA, Schneider Electric Industries SAS
www.schneider-electric.com Photos: Schneider Electric Industries SAS

SERED111047EN 01-2015