¥mm] | PROJECTS & DEVELOPMENT INDIA LIMITED Document No Rov | Talcher
[DIL | TE Fertilizers}
SECTION : VI - 3.2.1
FIRE FIGHTING SYSTEM
PLANT _ : ELECTRICAL DISTRIBUTION SYSTEM
PROJECT: INTEGRATED COAL BASED FERTILISER COMPLEX,
AT TALCHER, ANGUL DISTRICT, ODISHA (INDIA)
° | 260321
25.08.23
Issued for Enquiry
aks
AMAR,
AMAR
nev |_REVOATE
EFF DATE
PURPOSE
PREPD
REWWO
‘PPD
FORM No: 02-0000-0021F1 REVS
Al rights reservedELECTRICAL DISTRIBUTION SYSTEM | “roreaemmnaseanaa1 |
TALCHER FERTILIZERS LIMTED tie
Document No. | Rev
FIRE FIGHTING SYSTEM ss Fertlzers |
‘TABLE OF CONTENTS
NUMBER DESCRIPTION SHEET NUMBER
35 :
13.0 Safety Items. 7
Manual Call Points
augue DescrIron nayaet oF
FORM NO, 02.0000.0021 FS REVS Al igh reservesge
ara
PDIL
ELECTRICAL DISTRIBUTION SYSTEM | powsseamascomaz [0
‘TALGHER FERTILIZERS LIMITED tilther
Document No. | Rev
FIRE FIGHTING SYSTEM [sheet ore | Fettilzers_ |
Shi
10
2.0
3.0
34
32
33
34
35
36
a7
3.8
FORM NO, 02.0000.0021 FS REVS
PURPOSE
The purpose of this document is to establish the design basis of the complete fire fighting
system.
DEFINITIONS
PESO - Petroleum And Explosives Safety Organization
CCE- Chief Controller of Explosives
NFPA- National Fire Protection Association
IS- Indian Standards
NBC- National Building Code (India)
TAC — Tariff Advisory Committee
SCOPE
This specification covers design basis and execution requirements for fire protection
system to be provided by CONTRACTOR as per statutory regulations and NFPA codes.
The design and construction of the fire detection and protection equipment shall be of
internationally accepted standards and in compliance with the regulations of the Tariff
‘Advisory Committee (TAC), National Building Code (NBC) - 2016 and other relevant
statutory requirements for Electrical Distribution System. Any other Standard which are
not mentioned in the technical specification but are found necessary to meet the
requirement of TAC and standard engineering practices for safe and sound operation of
the System are to be included at no extra cost to the Owner.
‘A comprehensive fire protection system shall be designed for the whole of the proposed
Electrical Distribution System to provide @ high degree of protection for plant, tanks,
equipment and buildings and employees. Interfacing with other systems (e.g. fuel and air
handling plants, ventilation systems, etc.) will be required
‘Taping/s with the fire water mains shall be provided at plant battery limit (adjacent to the
proposed plant location) as per requirement. The same (tie-in location/s) shall be decided
during the detail engineering
‘The CONTRACTOR'S design and engineering activities listed in this specification are the
minimum requirements to be complied with preparation of detailed design basis,
specifications, standards and list of codes for each system based on guidelines given in
subsequent clauses of scope of work.
‘The term ‘Fire Fighting System’ referred here generally covers various equipments and
facilities being provided for controlling fires. These include faciities such as fire water
network accessories and fire water piping network together with hydrants, monitors,
various kinds of portable fire extinguishers like Dry Chemical Powder type, etc., as well as
sand and water buckets and sign boards.
The Fire Fighting System shall be designed to provide adequate facilities for extinguishing
any fire in the entire area of Electrical Distribution System and associated facilities of the
proposed Scope of work. The system shall be designed and installed as per TAC / NFPA
API/ ISIPESO/NBC standards and also as per latest applicable standards/ codes. The
rights reservedELECTRICAL DISTRIBUTION SYSTEM PCTRSEMDOESECVIOZA
TALCHER FERTRIZERS UMTED ae
PDIL) | FIRE FIGHTING SYSTEM Siesta af Fertilizers |
system shall be complete in all respects essential for proper installation operation and
maintenance, irrespective of whether such systems are specifically mentioned in this
specification or not.
3.9 Hydraulic analysis of fire water ring main network including line size, flow and pressure at
various section of the system shall be submitted for Owner/Consultant’s approval
3.10 The detail design shall take into consideration of all stipulations, practices followed by
Statutory Regulations/Authoriies for al types of jobs of this package.
3.11 Preparation of PFD/ P&ID's and equipment data sheets. Preparation of material take-off,
material requisitions and purchase requisition of bought out items. Design calculations for
the respective fire protection system, Installation, drawings and documents, Operating,
maintenance and spare parts manuals wherever applicable.
3.12 Taking approval from statutory authorities.
40 FIRE PROTECTION PHILOSOPHY
The Fire Protection Philosophy is based on Loss Preventive and Control, The importance
of adequate fire protection facilities need not be emphasized as no plant is absolutely
safe because of the inherent hazard it carries. A fire in one partsection of the plant can
endanger other sections of plant as well. If fire breaks out, it must be controlled /
extinguished as quickly as possible to minimize the loss to life and property and to
prevent further spread of fire.
50 GENERAL CONSIDERATIONS
The following fire protection facilities shall be provided depending upon the nature or the
installation and risk involved
+ Fire Water System
+ Gas Flooding ( proven equivalent ) System
‘+ Carbon Dioxide Flooding System
+ Dry Chemical Extinguishing System
+ Portable fire fighting equipment
60 FIRE WATER SYSTEM
Fire Water System shall be designed as per NEPA Code and complied with Local Law!
Indian Standards/ Civil Defense requirements / National Building Code- 2016.
6.1 Fire Fighting System
1) Fire Hydrant shall be provided in a ring round the facilities of the plant and storage
area in the contractor scope.
2) Fire Fighting System design and layout is subject to review and approval by Local
Statutory Authorities. Documentation & obtaining approval of the fire fighting system
from local fire service authority shall be in scope of contractor.
3) Contractor shall calculate the fire water requirement and tie-in for scope shall be
taken from the OSBL fire water network. Offsite fire water network (OSBL scope)
shall be available around the unit. Contractor shall take the required tappings from
this Offsite header with an isolation valve for each tapings,
4) Valves on fire water mains shall be of Gate type with rising stem, only, Valves on fire
water lines shall be located in RCC valve chamber provided with top cover to
FORM NO. 02.0000-0021 FS REVS rights reservedAL) ELECTRICAL DISTRIBUTION SYSTEM] pormencoaeovaz ]
TALHER FERTILIZERS UNITED eee LO Bhar
PDIL) | FIRE FIGHTING SYSTEM Sea bare Fertlzers |
facilitate easy operation/ maintenance of valves. The top of chamber shall be 80 mm
above ground level.
5) Fire Protection system's detailed location map to be displayed at Fire Station & Plant
Control Rooms.
70 FIRE WATER DISTRIBUTION SYSTEM
7.1 General
i) Fire hydrant ring from battery limit tapping point with isolation Gate valve, hydrants,
monitors and deluge valve system and accessories to be provided.
ii) Indoors hydrants for plant and non-plant buildings shall be provided as required.
i) Single headed hydrant for inside the buildings and double headed hydrants for
outside building shall be used.
iv) For process units, external ring header with hydrants and an internal distribution with
monitors and hose reels shall be installed
¥)_ Along the network, a number of block (gate type) valves shall be located in such a
way that the various areas of the plant can be fed with fire water even during
maintenance operations on part of the fire water network, Gate valve shall be
provided at every 300m and at crossings (Junctions) to ensure easy maintenance
and uninterrupted water supply in case of break down and shall be planned in such a
way that outage of any section of fire water line should not affect other section
Vi) Fire water shall not be used for any other purpose.
vil) Extension of hydrants/monitors for spill fire (as required by TAC) shall also to be
provided.
vill) Diesel oil storage tank areas shall be surrounded by hydrants & water cum foam
monitors (SS304 body & nozzle, fixed stand post type, manual operation, 500-750
USGPM variable type flow, self inducting foam induction mechanism) along with
portable type foam cans (each 200 Litres capacity).
ix) Cast Iron as MOG for piping items in the fire fighting system shall not be used
72 Hydrant
The hydrants shall be wet barrel type, self-standing, 4” size with 2 separate hydrant
valves (material of construction SS304) on each stand post & hose connection 2-1/2" with
gate type isolation valves at vertical portion of hydrant.
73 Fire Box
Each Fire Box shall consist of two fire hoses having 2-1/2" diameter and 30 M length, one
adjustable flow nozzle(material of construction SS304) and hose coupler (material of
construction $8304). Fire boxes shall be installed so that each fire box can be reached
from two hydrants, Hose boxes shall be made of M.S, material and painted red with
dimensions 18 SWG thick M.S. sheet, size 750 mm x 600 mm x 250 mm.
7.4 Monitor
Monitor, fixed type, UL listed, material of construction $$304, shall be installed for the
protection of high columns and process structures. Monitors capacity shall be 2580 LPM
Higher capacity may be achieved with higher pressure. Monitor shall be manually
FORM NO. 02.0000-0021 FS REVS rights reserveda ELECTRICAL DISTRIBUTION SYSTEM | pcreeuooaseonaa1 ]
TAL CHER FERTILIZERS LMIED eee LO Bhar
PDIL) | FIRE FIGHTING SYSTEM a Fertlzers |
operated. The monitors shall be suitable for combination of straight and fog jet; the
straight jetto-fog change is obtained manually. Water Monitor shall be BIS marked IS:
8442, However to meet the jet-fog combination as specified UL listed monitor with 750
GPM shall be considered
7.5 Fixed Water Spray System
Automatic fixed water spray system, designed in accordance with NFPA 15, with
automatically pneumatically operated deluge valve having manual by-pass valve system
& detectors, shall be installed to the following locations:
+ Each Cable Cellar shall be fire protected by CO2/DCP type fire extinguisher of suitable
capacity,
+ Both High Velocity Water Spray (HVWS) System and Nitrogen Injection Fire Prevention
and Extinguishing System (NIFPES) shall be provided for transformers fire protection of
capacity more then 60 MVA.
* Nitrogen Injection Fire Prevention and Extinguishing System (NIFPES) shall be provided
for transformers fire protection of capacity more the 20MVA.
+ Both High Velocity Water Spray (HVWS) System shall be provided for transformers fire
protection having oil capacity more than 2000 Liters,
Other fre protection systems including Fire hydrants, monitors and Fire Extinguishers etc.
shall be provided for transformer having oil capacity upto 2000 Liters.
7.6 Hose Reel
Hose reel, connected to fire water network, preferably shall be provided in sufficient
numbers at various required locations. Each hose reel shall be equipped with a valve 1-
1/2" size, 30 meters of fire hose and water branch pipe.
7.7 Hose Box (Indoor Hydrant)
Hose reel, connected to fire water network, preferably shall be located in the warehouses
and process units. Each hose box shall be equipped with a hose cabinet, valve (1-1/2"
size), 20 meters fire hose and water branch pipe
7.8 Standpipe and Hose System
Standpipes with hose stations for Class III (NFPA 14) service are preferred, having one 2-
1/2 inch valve hose connection and 1-1/2" valve hose connection with 30 m lengths of 1-
41/2" fire hose and 1-1/2" water branch pipe, for the protection of selected buildings
79 Sprinkler System
‘The sprinkler system, wet type, shall be designed according to NFPA 13, Sprinklers
system shall be installed in the hall and rooms, as applicable.
8.0 GAS FLOODING SYSTEM
81 GAS/ CLEAN AGENT FLOODING FIRE EXTINGUISHING SYSTEM
Clean Agent (Inergen or Argonite) System shalll be provided to
Rack Room, Panel room, Computer rack room and Control Room, as applicable.
FORM NO. 02.0000-0021 FS REVS rights reservedante
PDIL) |
ELECTRICAL DISTRIBUTION SYSTEM | poveacmnonSconaa1 ]
TALCHER FERTILIZERS LIMITED tier
Document No. Rev
FIRE FIGHTING SYSTEM Shoot 7 ofS Fertilizers |
82
9.0
10.0
10
12.0
13.0
CARBON DIOXIDE GAS FLOODING FIRE EXTINGUISHING SYSTEM
Carbon dioxide gas flooding fire extinguishing system shall be provided for
+ Electrical panels at substations & other locations.
PORTABLE FIRE EXTINGUISHERS
Portable fire extinguisher shall be provided for all plant buildings. Wheeled type (40 kg
charge) and portable type (6 kg charge) dry powder extinguishers, suitable for class ABC
fire, shall be provided as per NFPA requirements. Portable type (6 kg charge) and
wheeled (30kg charge) Carbon Dioxide extinguishers shall be provided for fire fighting in
the electrical substation and control rooms and other agreed locations as per NFPA
requirements. Contractor shall specify the numbers and location for Owner's review and
approval
DCP Units of 50 Kg and 75 Kg for areas like large oil consoles, substations, flammable
gas etc, as applicable.
FIRE PROTECTION FOR DIESEL TANK
‘Adequate fire protection requirements shall be provided by bidder for Diesel tank as per
NFPA and PESO.
BREATHING APPARATUS SET
Breathing apparatus set (UL listed) with shouldered type compressed air cylinders shall
be provided, minimum 3 nos. in each control room & each substation, for emergency use,
(Online air mask (UL listed) shall be provided along with each Breathing apparatus set.
SAFETY ITEMS.
Bidder shall provide safety items as per hazard requirements, in accordance with NBC-
2016/TACINFPA. Safety shower shall be provided, as applicable
EXECUTION, INSPECTION AND TESTING
If the system packager/manufacturer is collaborating with any foreign party for basic
engineering, design, etc, he should provide certificate of collaboration and first
submission of design and detailed drawing shall be approved by the Collaborator.
The Contractor shall supply recommended spares for first 24 months of operation and
maintenance and subsequent requirements,
All execution, inspection and testing for completion of fire protection system shall be
carried out based on Codes, standards and specifications. Contractor shall develop a
detail inspection, and testing procedures based on codes, standards and specifications.
Following minimum tests but not limited to, shall be carried out after completion of the
system testing Fire water network piping
‘* Demonstration test for system capacity requirements.
‘© Demonstration test for water spray & sprinkler systems,
‘+ Demonstration test for gas flooding system,
‘The Contractor shall meet all requirements for inspection and testing of the system,
FORM NO. 02.0000-0021 FS REVS rights reservedTL | ELECTRICAL DISTRIBUTION SYSTEM | ~pereasoaseoneaa ]
a TALGNER FERTEIZERS MITED | her
PDIL) | FIRE FIGHTING SYSTEM a Fertlzers |
14,0 DOCUMENTATION
Drawings and documents shall be prepared as required by approval authorities in all
respects and submitted by the Contractor. The Contractor shall make arrangement for
inspection and testing for statutory authorities at various stages of the work.
FORM NO. 02.0000-0021 FS REVS rights reserved