UPS5000-E - (50 KVA-125 KVA) User Manual (Integrated UPS 3.0)
UPS5000-E - (50 KVA-125 KVA) User Manual (Integrated UPS 3.0)
Issue 05
Date 2018-09-28
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Issue 05 (2018-09-28) i
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) About This Document
Purpose
This document describes the integrated uninterruptible power system UPS5000-E-(50
kVA-125 kVA) in terms of its features, performance, working principles, appearance,
installation, and operation and maintenance (O&M). UPS in this document represents
integrated UPS.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
System engineers
Hardware installation engineers
Commissioning engineers
Data configuration engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.
Symbol Description
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.
Change History
Updates between document issues are cumulative. Therefore, the latest document issue
contains all updates made in previous versions.
Issue 05 (2018-09-28)
Added a new ATS cabinet.
Issue 04 (2018-04-20)
Updated the section "Technical Specifications."
Issue 03 (2018-01-15)
Updated the Monitoring screen image.
Issue 02 (2017-11-27)
Updated the section "Technical Specifications."
Issue 01 (2017-08-30)
This issue is the first official release.
Contents
2 Overview....................................................................................................................................... 11
2.1 Model Description ...................................................................................................................................................... 11
2.2 Working Principle ....................................................................................................................................................... 12
2.2.1 Conceptual Diagram ................................................................................................................................................ 12
2.2.2 Working Modes........................................................................................................................................................ 13
2.2.2.1 Normal Mode ........................................................................................................................................................ 13
2.2.2.2 Bypass Mode ........................................................................................................................................................ 13
2.2.2.3 Battery Mode ........................................................................................................................................................ 14
2.2.2.4 Maintenance Bypass Mode ................................................................................................................................... 15
2.2.2.5 ECO Mode ............................................................................................................................................................ 16
2.3 Product Introduction ................................................................................................................................................... 17
2.3.1 Product Structure ..................................................................................................................................................... 17
2.3.2 Power Module .......................................................................................................................................................... 20
2.3.3 Bypass Module ........................................................................................................................................................ 22
2.3.4 Control Module ........................................................................................................................................................ 23
2.3.4.1 Overview .............................................................................................................................................................. 23
2.3.4.2 ECM...................................................................................................................................................................... 23
2.3.4.3 Dry Contact Card .................................................................................................................................................. 25
2.3.4.4 Monitoring Interface Card .................................................................................................................................... 26
2.3.5 MDU ........................................................................................................................................................................ 31
2.4 02311FTE-002 and 02311FTC-001 Automatic Transfer Switch (ATS)...................................................................... 33
2.4.1 ATS Appearance....................................................................................................................................................... 33
2.4.2 ATS Controller ......................................................................................................................................................... 35
2.4.3 ATS (8D) Operation Description ............................................................................................................................. 39
3 Installation.................................................................................................................................... 49
3.1 Installation Preparations ............................................................................................................................................. 49
3.1.1 Tools and Instruments .............................................................................................................................................. 49
3.1.2 Site ........................................................................................................................................................................... 51
3.1.2.1 UPS Weight and Dimensions ................................................................................................................................ 51
3.1.2.2 Installation Environment ....................................................................................................................................... 53
3.1.2.3 Installation Clearances .......................................................................................................................................... 53
3.1.3 Preparing Power Cables ........................................................................................................................................... 53
3.1.4 Unpacking and Checking ......................................................................................................................................... 56
3.2 Installing a Single UPS ............................................................................................................................................... 59
3.2.1 Installing the Cabinet ............................................................................................................................................... 59
3.2.2 Installing a Tail Frame ............................................................................................................................................. 63
3.2.3 Installing Batteries ................................................................................................................................................... 69
3.2.4 Routing Cables......................................................................................................................................................... 70
3.2.5 Connecting a Ground Cable ..................................................................................................................................... 73
3.2.6 Connecting AC Input Power Cables ........................................................................................................................ 74
3.2.7 Connecting AC Output Power Cables ...................................................................................................................... 76
3.2.8 Connecting Battery Cables ...................................................................................................................................... 78
3.2.9 Connecting Signal Cables ........................................................................................................................................ 79
3.2.9.1 Connecting a Remote EPO Switch ....................................................................................................................... 79
3.2.9.2 Connecting Communications Cables .................................................................................................................... 80
3.2.9.3 Connecting Fire Protection and Generator Start/Stop Cables (ATS Input Cabinet) .............................................. 81
3.3 (Optional) Combining Cabinets .................................................................................................................................. 82
3.4 Installing a Double-Bus (2N) System ......................................................................................................................... 84
3.4.1 Connecting Power Cables ........................................................................................................................................ 84
3.4.2 Connecting Signal Cables ........................................................................................................................................ 86
3.5 Installation Verification............................................................................................................................................... 86
1 Safety Precautions
To minimize the risk of personal injury and damage to equipment, read and follow all the
precautions in this document before performing any operation. The "DANGER",
"WARNING", "CAUTION", and "NOTICE" statements in this document are only
supplemental and do not represent all the safety instructions.
Only trained and qualified personnel are allowed to install, operate, and maintain Huawei
equipment.
Follow the precautions and special safety instructions provided by Huawei when operating
Huawei products. Huawei will not be liable for any consequences that are caused due to
violations regarding general safety regulations and equipment design, production, and usage
safety standards.
Declaration
Huawei does not take responsibilities for the following situations:
Operation under severe environments that are not specified in this document.
Installation or use in environments that are not specified in related international
standards.
Unauthorized product changes and software code modification.
Operations not complying with the operation instructions and safety precautions in this
document.
Damage caused by extreme natural environments.
Damage caused by using batteries provided by Huawei for non-Huawei UPSs.
Damage caused by using batteries not provided by Huawei.
Personal Requirements
Only Huawei engineers or engineers certified by Huawei are allowed to perform UPS
commissioning and maintenance. Otherwise, human injury or equipment damage may occur,
and any resulting UPS faults will be beyond warranty scope.
Personnel who plan to install or maintain Huawei equipment must receive thorough training,
understand all necessary safety precautions, and master the correct operation methods.
Trained and qualified personnel, or personnel certified or authorized by Huawei are:
Allowed to install, operate, and maintain the equipment.
Allowed to remove safety facilities and inspect the equipment.
Allowed to replace or change the devices or components (including software).
Operation personnel must report faults or errors that might cause serious safety issues to
related owners.
This product should be installed and used according to the installation and technical,
specification requirements found in this manual. Otherwise, the product may be damaged,
and the resulting product exceptions or component damage will be beyond the warranty
scope.
Grounding Requirements
Devices to be grounded (excluding the energy storage unit) must meet the following
requirements:
When installing a device, install the ground cable first. When removing a device, remove
the ground cable at the very end.
Do not damage the ground conductor.
Do not operate devices if the ground conductor is not installed. Before operating a device,
check the electrical connection of the device to ensure that it is securely grounded.
Personal Safety
Do not operate the product, or handle cables, during thunderstorms.
To avoid electric shocks, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
Before operating a device, wear electrostatic discharge (ESD) clothes, ESD gloves, and
an ESD wrist strap. Remove any conductors (such as jewelry or watches) before the
operation to avoid electric shocks or burns.
In the case of fire, leave the building or the equipment room immediately, and turn on the
fire alarm bell or make an emergency call. Never enter the building on fire in any case.
If the cabinet provides an ESD jack, wear an ESD wrist strap and insert the ground
terminal of the ESD wrist strap into the jack.
Ensure all switches are turned to OFF during device installation.
Power on the UPS only after authorized engineers arrive at the site.
If a C2 UPS is used in residential areas, additional measures must be taken to prevent
radio frequency interferences.
If the UPS is used for life-supporting medical apparatus and facilities such as lifts where
adequate care has to be taken to ensure personal safety, discuss with the manufacturer in
advance about the applicability, settings, management, and maintenance of the UPS,
which require special considerations during design.
Device Safety
Before operation, ensure that the device is firmly anchored to the floor or other solid
objects, such as a wall or an installation rack.
Ensure ventilation vents are unblocked while the system is operating.
Before powering on the device, ensure that all the screws inside it are securely tightened
and will not fall off during operation.
After the installation, remove packing materials from the equipment area.
Replace danger signs that have worn out or are unreadable.
A UPS can be used to serve resistive-capacitive loads, resistive loads, and
micro-inductive loads. It is recommended that a UPS not be used for pure capacitive
loads, pure inductive loads, and half-wave rectification loads. It does not apply to energy
feedback loads.
Do not alter the UPS internal structure or installation procedure unless consent from the
manufacturer is given.
Never use water to clean electrical components inside or outside the UPS.
Do not drill holes into a cabinet.
The high voltage power supply provides power for the device operation. Direct or indirect
contact with high voltage power sources may result in fatal injury.
Non-standard or incorrect high voltage operations may result in fire and electric shocks.
The personnel who install the AC facility must be qualified to perform high voltage and
AC operations.
When selecting, connecting, and routing power cables, ensure compliance with local
laws and regulations.
When operating the AC power supply facility, ensure compliance with local laws and
regulations.
Before connecting cables to the UPS, ensure that the input power and mains power
distribution switches and output power distribution switch are turned off.
Use only dedicated tools during high voltage and AC operations.
If the operation is performed in a damp environment, ensure that the device is dry. When
water is found in the rack or the rack is damp, switch off the power supply immediately.
Ground a device before powering it on. Otherwise, personal injury or device damage may
occur.
If a "high leakage current" tag is attached to the panel of the device, ground the protective
ground terminal on the device enclosure before connecting the AC power supply to
prevent electric shocks.
The UPS can generate high leakage currents. Using a circuit breaker that has the leakage
current protection function is not recommended.
Power Cable
Do not install or remove power cables when the device is on. Transient contact between the
core of the power cable and the conductor may generate electric arcs or sparks, which may
cause fire or damage eyesight.
Before moving or reconnecting the UPS, disconnect the mains and batteries, open the
output power distribution switch, and wait a period of at least 5 minutes after the UPS
completely powers off. Otherwise, electric shocks may occur.
Before installing or removing the power cable, open the power switch.
Before connecting a power cable, check that its label is correct.
Fuse
If a fuse needs replacing, ensure the new fuse is of the same type and specifications so that the
system runs safely.
Electrostatic Discharge
Liquid Prevention
Do not place the product under areas prone to water leakage, such as near air conditioner
vents, ventilation vents, or feeder windows of the equipment room. Ensure that there is
no condensation inside the product or equipment room. Ensure that no liquid enters the
product. Otherwise, short circuits will occur and may result in serious injury or death.
If any liquid is detected inside the product, immediately disconnect the power supply and
contact the administrator.
Do not expose the equipment or perform any operations in an environment with flammable or
explosive gas, or smoke.
Any operation on any electrical device in an environment that has flammable air can cause
extreme danger. Strictly obey the operating environmental requirements specified in related
use manuals when using or storing the device.
Do not use the UPS in the following environments:
Environment containing flammable gases, corrosive gases, abnormal vibrations, and
impacts.
Non-confined environment near the ocean (0–3.7 km) and indoor or semi-indoor
environment where the temperature and humidity are not controllable, such as a simple
equipment room near the ocean, citizen house, garage, corridor, direct ventilation cabinet,
house with only the roof, railway station platform, gymnasium, aquarium, and so on.
Before operating batteries, carefully read the safety precautions to ensure correct battery
handling and connection is performed, and personal safety is managed.
To ensure battery safety and efficient battery management, use the batteries delivered with
the UPS. Huawei shall not be responsible for battery damage caused by using non-Huawei
batteries for Huawei UPSs.
Ensure lead-acid battery handling is in accordance with local regulations.
Incorrect handling of batteries may cause hazards. When operating batteries, avoid
battery short circuits and electrolyte overflow or leakage.
Electrolyte overflow may damage the device by corroding metal parts and circuit boards,
and ultimately damaging the circuit boards.
Short circuits caused by incorrect operations may cause serious injuries due to high
power of batteries.
Do not reversely connect positive and negative battery terminals.
Use batteries of the specified type. Otherwise, the batteries may be damaged.
Check battery connections periodically to ensure that all screws are securely tightened.
Install or store batteries in clean, cool, and dry environments.
Do not decompose, transform, or damage batteries. Otherwise, battery short circuit,
electrolyte leakage, and even personal injury may occur.
Preventative Measures
When installing and maintaining batteries, pay attention to the following points:
Use dedicated insulated tools.
Take measures to protect eyes, such as using eye protection devices.
Avoid skin contact with electrolyte overflow. Wear rubber gloves and protective
clothing.
When handling a battery, ensure that its electrodes always point upward. Do not tilt or
overturn batteries.
Switch off the power supply during installation and maintenance.
Short Circuit
Battery short circuits may cause personal injury. The high transient current generated by a
short circuit may release a surge of power and cause a fire.
To avoid battery short circuits, do not maintain batteries while they are in use.
Harmful Gas
Do not use unsealed lead-acid batteries. Lead-acid batteries emit flammable gas. Therefore,
place and secure lead-acid batteries horizontally to prevent fire or corrosion.
Store lead-acid batteries in a place with good ventilation, and take fire safety precautions.
Battery Temperature
High temperature may result in battery distortion, damage, and electrolyte overflow.
Install or store batteries far away from fire sources and heating devices such as
transformers. Never burn batteries.
If the battery temperature exceeds 60°C, check the battery for electrolyte overflow. If
electrolyte overflows, handle the leakage immediately.
Electrolyte Leakage
In the case of electrolyte leakage, counteract and absorb the leaking electrolyte immediately.
When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte
may harm human bodies. If the electrolyte leaks, use the following substances to counteract
and absorb the leaking electrolyte:
Sodium bicarbonate (baking soda): NaHCO3
Sodium carbonate (soda): Na2CO3
When using substances to counteract and absorb electrolytes, strictly follow the guidelines
provided by the battery manufacturer.
If any personnel are exposed to battery electrolyte, wash the exposed area with clean water
immediately and seek medical advice if the situation is serious.
Handling Fans
Do not insert fingers or boards into the operating fans until the fans are switched off, and have
stopped running.
Signal cables must be bound separately from strong-current cables and high-voltage cables.
2 Overview
UPS5000-E-50K-HASBS
UPS5000-E-125K-HABBS
UPS5000-E-125K-HASBS
Manual startup is required to ensure that the inverter is in standby state and the power flow has reached
the inverter.
(1) Power input status indicator (2) Input circuit (3) Lighting circuit
breaker breaker
(4) Air conditioner power distribution (5) IT load circuit (6) UPS input circuit
circuit breaker breaker breaker
(7) UPS maintenance bypass circuit (8) Control module (9) Bypass module
breaker
(10) Filler panel (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution monitoring (14) UPS output
board circuit breaker
(1) Power input (2) ATS drive module (3) ATS monitoring module
status indicator
(4) Lighting circuit (5) Air conditioner power (6) IT load circuit breaker
breaker distribution circuit breaker
(7) UPS input circuit (8) UPS maintenance bypass circuit (9) Control module
breaker breaker
(10) Bypass module (11) Power module (12) ATS transfer switch
(13) ATS handle (14) Monitor display unit (MDU) (15) Power distribution
monitoring board
(16) UPS output
circuit breaker
(1) Positioning lock (2) Run indicator (3) Alarm indicator (4) Fault indicator
(5) Ready switch (6) Output port (7) Input port
Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.
Specifications
Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
Weight: < 21 kg
Rated output capacity: 25 kVA/25 kW
Power density: 17.2 W/inch3
(1) Positioning (2) Battery cold start (3) Run (4) Alarm indicator
lock button indicator
(5) Fault indicator (6) Ready switch (7) Signal port (8) Input and output
ports
Functions
The UPS is set to ECO mode and the bypass voltage is within the specified range.
The power module is overloaded for a period longer than the maximum allowed period.
Both the active and standby ECMs are abnormal.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 500 mm
Weight < 25 kg
Maximum output power: 125 kW
(1) Ground terminal (2) Parallel port 1 (3) BSC port (4) Ready switch
1 on ECM 1
(5) Indicators for ECM 1 (6) Parallel port 2 (7) BSC port (8) Ready switch
2 on ECM 2
(9) Indicators for ECM 2 (10) Dry contact card (11) Dry (12) MDU port
contacts
(13) RS485 port (14) Fast Ethernet (FE) (15) COM2 (16) COM1 port
port port
(17) Battery temperature (18) Optional card
sensor port subrack cover
2.3.4.2 ECM
The control module consists of two ECMs that work in active/standby mode. Each card
provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the
lower part.
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm2 to 1.5 mm2.
The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected and MDU communication fails. Conversely, if
the FE port is mistaken for the RS485 port during cable connection, RS485
communication fails.
If MDU communication fails, the "Comm. failure" message is displayed on the LCD,
screen switching is disabled, the buzzer buzzes, and the fault indicator is red. Once the
fault is rectified, the LCD recovers, and the alarm is cleared.
Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
In a parallel system, ensure that used dry contacts properly connect to each UPS.
The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.
The maximum voltage and current of ports DO_1 to DO_4 are 30 V DC, 1 A or 60 V DC, 0.5 A
respectively.
Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm2.
RS485 cables and FE cables must be shielded cables.
Figure 2-17 and Figure 2-18 are recommended wiring methods for DO ports.
Figure 2-19 and Table 2-6 describe the COM1 pin definitions.
Pin Description
1 GND
2 N/A
3 RS485-
4 RS485+
5 N/A
6 12V_PORT
Figure 2-20 and Table 2-7 describe the COM2 pin definitions.
1 RS485+
2 RS485-
3 N/A
4 RS485+
5 RS485-
6 GND
7 CANH0
8 CANL0
Figure 2-21 and Table 2-8 describe the RS485 pin definitions.
Pin Description
1 RS485_T+
2 RS485_T–
3 N/A
4 RS485_R+
5 RS485_R–
6 GND
7 N/A
8 N/A
2.3.5 MDU
Appearance
Touch the LCD screen firmly because it is an industrial resistive touchscreen. It is recommended that
you use your fingernails for accurate selection and quick response.
The indicator on the LCD panel is yellow when the bypass supplies power in non-ECO mode.
The ports of the LCD screen are located at the side of the LCD screen.
Functions
The monitor display unit (MDU) allows for general UPS operations, parameter setting,
viewing of running status and alarms, and so on.
Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm
ATS controller
The ATS logic control unit monitors the ATS in real time and configures the ATS system
parameters.
Electric/Manual mode selection handle
If you flip the electric/manual mode selection handle upwards to the M position, it is
electric mode. If you flip the handle downwards to the Man. position, it is manual mode.
Before you power on the UPS, check that the handle is in the M position.
ATS handle slot
Before you insert the handle into the ATS handle slot, flip the electric/manual mode
selection handle to the Man. position. After you insert the handle, the ATS controller
starts manual mode.
Handle locking latch
When the ATS changes from manual mode to electric mode, pull out the ATS handle.
Before you pull out the handle, turn the handle locking latch downwards.
After you pull out the handle, flip the electric/manual mode selection handle upwards to
the M position.
(1) Alarm ID description (2) Controller buttons (3) ATS status indicator
Table 2-11 describes the alarm IDs of the ATS controller in detail.
OFF In button control mode, if the ATS is flipped to OFF, both the I
and II switches are off, and the ATS works in manual mode.
AUTO Sets the ATS controller to the automatic or button control mode
and clears alarms.
Alarm Alarm indicator On: The ATS generates an alarm, logic switching
fails, switches I and II are ON at the same time, or
the handle is inserted.
Blinking: The switch logic generates an alarm.
Off: No alarm is generated.
The alarm status can be cleared using the AUTO
button.
The home screen of the 8D controller displays status for the LN1 and LN2 power supplies,
electric generator, delay, and LLVD.
Figure 2-27 shows the power status of LN1 and LN2. Table 2-11 describes the power
status alarms.
Figure 2-28 shows the generator status.
Figure 2-29 shows the delay status.
Figure 2-30 shows the LLVD status.
If LN1 and LN2 power indicators are hollow, there is an alarm. Locate the fault based on the alarm ID
and Table 2-11 or the alarm ID description on the 8D controller, and rectify the fault.
If the screen displays the letter G, the mains-generator mode is in use. If the screen does not display
the letter G, the mains-mains mode is in use.
If the letter G and an upward arrow are displayed, the generator is working.
If the letter G and a downward arrow are displayed, the generator is idle.
If the letter G blinks, an alarm has been generated for the generator.
Note that the LLVD status (ON/OFF) in the menu is consistent with the input data. For
example: If the input data (DI 11 by default) is active, the LLVD is on. If the input data is
invalid, the LLVD is off.
Do not open any cover of the ATS. Even if the power supply is disconnected, hazardous
external control voltage may still exist inside the product.
Do not adjust the control cable when the ATS or external control cable is electrified.
Before powering on the ATS, operate the handle to switch on and off the ATS for one to three times.
Ensure that the primary and secondary contacts of the ATS work smoothly.
Verify that the phase sequences of the two power inputs to the ATS are correct using a phase
sequence table.
Automatic Mode
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Press down the locking latch on the switch panel and pull out the handle.
If the handle is not pulled out, the automatic mode will be disabled.
Step 5 Check whether the Power LED and Auto LED indicators are on, as shown by (1) in Figure
2-33. If the Auto LED indicator is on, the controller is in the automatic operation mode.
Step 6 If the Auto LED indicator is off, press the Auto button once. Then the controller enters the
automatic operation mode, as shown in Figure 2-33.
----End
Manual Mode
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Flip the Motor/Manual selection lever to the Man. position.
The automatic operation will be disabled after the handle is inserted into the switch panel.
Step 5 The Alarm LED and Power LED indicators go on at the same time when the handle is
inserted.
After the handle is inserted, the controller automatically switches to the button operation mode. After the
handle is removed, the controller remains in the button operation mode, and the Alarm LED indicator
goes out.
Button Mode
When the controller is working in the button mode, a user can control the ATS switch using
the I, O, and II buttons on the controller panel. In the button mode, the OMD800 controller
can control the generator.
Do not simultaneously press and hold down any two of the I, II, and O buttons on the
controller panel. Ensure that the interval between two commands is 5s at least. If another
command is issued before the previous one is executed, the protection fuse (F1) under the
motor operation mechanism may be blown.
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Press down the locking latch on the switch panel and pull out the handle.
If the handle is not pulled out, the automatic mode will be disabled.
Step 5 Check whether the Power LED indicator is on, as shown by (1) in Figure 2-39.
Step 6 Check whether the Auto LED indicator is on.
If the Auto LED indicator is off, the controller is working in the button mode, as shown
by (3) in Figure 2-39.
If the Auto LED indicator is on, press the Auto button once. Then the Auto LED
indicator turns off, and the controller enters the button mode, as shown by (2) in Figure
2-39.
----End
Do not open any cover of the ATS. Even if the power supply is disconnected, hazardous
external control voltage may still exist inside the product.
Do not adjust the control cable when the ATS or external control cable is electrified.
Manual operations are forbidden in automatic.
If you need to switch to the other power supply, turn the switch to both the O (OFF)
position first.
Before powering on the ATS, operate the handle to switch on and off the ATS for one to three times.
Ensure that the primary and secondary contacts of the ATS work smoothly.
Verify that the phase sequences of the two power inputs to the ATS are correct using a phase
sequence table.
3 Installation
Prepare the following tools and meters indicated in Table 3-1 for installation.
Hammer drill and Hand-held electric Alloy hole saw Heat gun
drill bit Φ16 drill
Table 3-1 lists only the common tools for installation and cable connection. For more dedicated tools
required, see the corresponding component manuals. Prepare tools based on site requirements.
3.1.2 Site
3.1.2.1 UPS Weight and Dimensions
UPS5000-E-50K-HABBS 2 0 352 kg
UPS5000-E-50K-HASBS 3 1 390 kg
UPS5000-E-125K-HABBS 5 0 435 kg
UPS5000-E-125K-HASBS 6 1 453 kg
(1) Front door (2) Foot (3) Caster (4) Bottom plate
(5) Rear door (6) Base mounting hole (7) Side post (8) Beam
The UPS can generate large leakage currents. A circuit breaker equipped with an RCD is not
recommended.
When selecting, connecting, and routing power cables, follow local safety regulations and rules.
When the external conditions such as cable layout or ambient temperatures change, perform verification
in accordance with the IEC-60364-5-52 or the local regulations.
The currents listed in the table "Recommended cross-sectional areas for power cables" are measured at a
rated voltage of 380 V; if the rated voltage is 400 V, multiply the currents by 0.95; if the rated voltage is
415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the neutral wires
1.5–1.7 times.
The recommended cables are applicable only when the following requirements are met:
The cables are routed over a ladder or bracket in a single layer (E or F in IEC60364-5-523).
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
Single- or multi-core 90°C soft power cables with copper conductors are used.
It is recommended that AC power cables be no longer than 30 m and DC power cables be no longer
than 40 m.
Only trained personnel are allowed to move the UPS. Use a pallet truck to transport the
UPS box secured to a wooden support to the installation position.
Visually inspect the UPS appearance for shipping damage. If it is damaged, notify the
carrier immediately.
To prevent the UPS from falling over, secure it to a pallet truck using ropes before moving
it.
To prevent shocks or falls, move the UPS gently. After placing the UPS in the installation
position, unpack it and take care to prevent scratches. Keep the UPS steady during
unpacking.
Check that the fittings comply with the packing list. If some fittings are missing or do not
comply with the packing list, record the information and contact your local Huawei office
immediately.
If the UPS installation environment is in poor condition and the UPS will be stored for a
long time after it is unpacked, wrap the UPS with the original plastic coat to prevent dust.
Procedure
Step 1 Use a pallet truck to transport the UPS to the installation position.
Step 2 Remove the UPS outer packing.
Step 3 After verifying that the UPS is intact, remove the L-shaped brackets securing the cabinet and
the pallet.
Step 5 Raise the four anchor bolts to the highest position using an adjustable wrench.
Step 6 Move the UPS over its castors near the installation position.
----End
Step 2 Use a hammer drill to drill holes for installing expansion bolts and then install expansion bolts
in the holes.
(1) M12 bolt (2) Spring washer (3) Flat washer (4) Expansion sleeve
Knock the expansion bolts into the holes until the expansion tube completely fits into the hole.
The expansion sleeves must be completely buried under the ground to facilitate subsequent
installation.
1. Drill holes in the ground by using a hammer drill. The hole depth is 52 mm to 60 mm.
2. Partially tighten the expansion bolt and vertically insert it into the hole. Knock the
expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the
hole.
3. Partially tighten the expansion bolt.
4. Remove the bolt, spring washer, and flat washer.
Step 3 Move the UPS over its castors to the installation position.
Step 4 If the castors of the UPS need to be lifted from the ground, perform steps Step 1 to Step 2 in
Non-Secured Installation.
Step 5 Open the front and rear doors.
Step 6 Insert four M12x115 expansion bolts into the expansion bolt holes in the floor, and tighten the
expansion bolts.
----End
Non-Secured Installation
Step 1 Lower the four anchor bolts at the bottom of the cabinet by using a wrench until all the four
castors at the bottom hang in the air, the anchor bolts bear the whole cabinet weight.
Step 2 Check the cabinet levelness using a level. If the cabinet is not leveled, adjust the anchor bolts.
----End
Step 3 Insert four M12 bolt assemblies into the mounting holes for the UPS and support. Partially
tighten the bolts.
----End
Procedure
Step 1 Use eight M5 tapping screws to secure the tail frame accessories to the tail frame.
Step 2 Use four M5 tapping screws to secure one upper sealing plate to the tail frame.
There are two upper sealing plates, and the one used in this step has a gap.
When removing the cabinet rear door, remove the ground cable between the cabinet and the
rear door from the cabinet.
Step 4 Remove the hinges and connecting kits from the UPS rear door and remove the ground cable.
Put aside the hinges and connecting kits as they are needed in follow-up installation
processes.
Step 5 Move the tail frame to the cabinet rear door, and adjust the tail frame so that the tail frame top
is flush with the cabinet top.
Step 6 Secure the tail frame to the UPS using eight M5 tapping screws.
Step 7 Install the hinges and connecting kits removed in Step 4 at the corresponding positions on the
tail frame.
Step 8 Install the UPS rear door on the tail frame.
After installing the UPS rear door, ensure that ground cables are properly connected to the
cabinet and UPS rear door.
----End
Before installing batteries, read through the battery safety precautions, obtain the delivered
battery installation guide, and install batteries as instructed.
Place the batteries in a correct way to prevent vibrations and shocks.
Install the batteries from the lower layer to the upper layer to prevent falling over due to
imbalance.
Procedure
Step 1 Install the battery cabinet and batteries.
For details, see the battery installation guide delivered along with the batteries.
----End
The basic rule for routing cables is: from inside out and from bottom up.
When connecting the mains input power cable, strip the outer layer of the 5-wire cable,
wrap each wire in the stripped section using corrugated pipes, and secure the corrugated
pipes using insulation tape to prevent sliding.
Step 1 Remove five rodent-proof meshes and cable hole protection panels from the top of the
cabinet.
You can drill holes in the removed covers as required before reinstalling them on the cabinet.
Step 2 Open the rear door, and remove the insulation panels at the rear of the cabinet.
After routing signal cables, reinstall the cable hole protection panels.
----End
Before connecting cables, check that all UPS input switches are OFF.
Prepare terminals onsite. The length of the copper wire should be the same as that of the
part of the terminal that covers the conductor.
Procedure
Step 1 Connect a ground cable to the UPS cabinet.
Step 2 Connect a ground cable to the safety ground of the UPS cabinet.
Figure 3-24 Connect a ground cable to the safety ground of the UPS cabinet
----End
Step 2 Take out PC boards from near the input copper bar, and install them based on the positions of
the positioning holes.
----End
----End
----End
Connect AC output power cables to the UPS from inside out and from top to bottom. Connect
the PE cable, N cable, and L cable in sequence.
The method for connecting AC output power cables is the same for the 50 kVA, and 125 kVA
cabinets. The AC output power cable connection for the UPS5000-E-125K-HASBS cabinet is
used as an example.
Connect output power cables to the customer terminal bars in the UPS cabinet, and connect N
cables and PE cables to the N bar and PE bar on the left and right sides.
(1) IT and air conditioner output power cables (2) Lighting output power cables
The number of cables in the figure is only for reference. The actual number of cables depends on the
output loads.
The battery string voltage may cause serious injury. Observe safety precautions when
connecting cables.
Ensure that cables are correctly connected between battery strings and the battery switch,
and between the battery switch and the UPS.
Procedure
Step 1 Connect battery cables to positive and negative battery terminals and terminal N on the UPS
cabinet.
Step 2 Route a neutral wire from the middle connection point of positive and negative battery strings.
Take a battery string consisting of 32 batteries as an example. The neutral wire routed from
the middle of positive and negative battery strings, each consisting of 16 batteries.
When connecting the battery cables, wrap cables with corrugated pipes for protection, and
reinstall the removed insulation panels at the rear of the cabinet.
----End
Huawei does not provide an EPO switch and cable. Prepare them before installation. The
22 AWG cable is recommended. AWG is short for American wire gauge.
To prevent problems, equip the EPO switch with a protective cover, and enclose the cable
with a protective tube.
Connect the EPO switch to the dry contact card on the UPS.
When the EPO switch is in the NC state, remove the jumper between EPO_NC and EPO_12V before
connection. When you turn off the EPO switch, EPO is triggered. When the EPO switch is in the NO
state, ensure that the jumper is connected between EPO_NC and EPO_12V. When you turn on the EPO
switch, EPO is triggered.
Procedure
Step 1 Connect one end of the cable to the FE port on the UPS monitoring interface card, and
connect the other end to any PoE port on the smart ETH gateway.
----End
Procedure
Step 1 Connect the fire protection and generator start/stop cables to the terminals on the XT2
terminal block.
Here connecting one of the cables is used as an example. XT2-6 is a normally open contact, XT2-7 is a
common contact, and XT2-8 is a normally closed contact.
Figure 3-36 Connecting the fire protection and generator start/stop cables for the UPS
----End
Step 2 Remove the cabinet connecting kits from the rack, as shown in Figure 3-38.
Step 3 Secure the connecting kits in the connection positions on the front door using screws, as
shown in Figure 3-38.
Step 4 Use the same method to secure the connecting kits in the connection positions on the rear
door.
Step 5 Repeat the procedure to combine other UPSs.
When combining cabinets, ensure that all the upper surfaces of the cabinets are on the same plane.
(1) Input power cables (2) Battery cables (3) Output power cables
----End
----End
Check items 09 and 10 carefully. Otherwise, the UPS may break down.
In the scenarios where holes are drilled for routing cables or covers are removed for routing cables,
after routing cables and checking cable connections, use sealing putty to fill in the gap between the
cables and the cabinet.
After verifying the installation, reinstall all the covers.
Do not remove the dustproof cover before power-on to prevent dust inside the UPS.
4 User Interface
The Settings Wizard screen is displayed when you start the UPS for the first time or when
you restart the UPS after restoring factory settings. You can set Language, Time, Network
Param., and System Param. on the Settings Wizard screen.
Button Function
Logs out.
AC Output
AC output phase voltage/AC output line voltage/AC output phase current/AC output
frequency.
Power factor
Proportion of output active power to output apparent power.
UPS Load
Mains Input
Bypass Input
Battery Status
Battery Status
The value can be Not connected, Equalized Charging, Flt. charging, Hibernating,
discharging, or Not chg. or dis.
Voltage (V)
Voltage of the battery string.
Current (A)
Current of the battery string. The current is + when batteries are being charged and -
when discharged.
Temperature (°C)
Battery operating temperature (A battery sensor is required. If this sensor is not installed,
NA is displayed.)
Backup time (min)
Battery backup time estimated at the current load.
Remaining cap. (%)
Remaining battery capacity.
Total Runtime
Environment Data
Humidity measured by the ambient temperature and humidity sensor (Install the sensor.
If this sensor is not installed, NA is displayed.)
Mod. Cur. Eql. Data is displayed only when Cross current monitoring is set to Enable and
the number of inverter power modules is greater than 1.
PDU Data
If you want to query the electricity consumed in the current month, set both the start date and end
date to the current month. For example, the current month is March 2016. If you want to query the
electricity consumed in March, set the start date and end date to 2016-03.
If you want to query the electricity consumed in a past month, set the start date to the month to be
queried, and set the end date to the next month. For example, if you need to query the electricity
consumed in January 2016, set the start date to 2016-01 and end date to 2016-02. If you set both the
start date and end date to 2016-01, a message will be displayed, indicating wrong query dates.
ATS
Cabinet Input
Active Alarms
Historical Alarms
Buzzer Off
Two buzzer menus are available, that is, Buzzer On and Buzzer Off.
If the buzzer is muted, Buzzer On is displayed on the operation screen.
If the buzzer is enabled, Buzzer Off is displayed on the operation screen.
If you enable the buzzer, the buzzer buzzes when a critical alarm, a minor alarm, or a certain
warning is generated. If you mute the buzzer, it never buzzes.
Clear Faults
Twinkle
After you tap Twinkle, the UPS reports the address information to the FusionModule APP.
The icon of the corresponding integrated UPS in the device layout diagram on the APP will
blink for 10s.
Basic Settings
Set the date and time correctly. Incorrect time display in running and alarm information would
lead to analysis errors during maintenance or repair.
Language
Twelve languages, including English, Chinese, and Italian, are supported. The default
language is English.
Password
The preset password is 000001. You can change the password.
Password complexity check
If the password complexity check is disabled, the user password is required to be a string
of six to eight digits. If the password complexity check is enabled, the password is
required to be a string of 6-20 characters and contain at least two types of characters.
Communication
IP address allocation
− If the MDU is directly connected to a computer over a network cable, the IP address
can only be allocated manually. The IP addresses of the MDU and computer must
be in the same network segment, and must be different.
− If the MDU is connected to a computer through a LAN switch or router with the
DHCP function, the IP address can be allocated manually or automatically.
Manual: Check that their IP addresses are two different values on the same
network segment. Set the UPS IP address to be in the same subnet as the PC IP
address. Perform the bitwise AND operation for the UPS IP address and the
PC IP address with the subnet mask respectively. If the operation results are
the same, the two IP addresses are in the same subnet.
AND operation rule: 1 AND 1 = 1, 1 AND 0 = 0, 0 AND 1 = 0, 0 AND 0 = 0.
That is when the corresponding bits are both 1, the result is 1. In other cases,
the result is 0.
You can set IP address allocation to Manual or Automatic. After you restart the device, IP address
allocation changes back to Manual. IP address is the IP address that you have previously set.
IP address parameter
Set an Ethernet IP address that ranges from 1.0.0.0 to 223.255.255.255. The default value
is 192.168.0.10.
Ensure that the UPS IP address is unique on the network segment. Otherwise, the WebUI
display function may be abnormal.
Subnet mask
Set an Ethernet subnet mask that ranges from 0.0.0.0 to 255.255.255.255. The default
value is 255.255.255.0.
Gateway
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255. The default value
is 192.168.0.1.
MAC address
Defines the physical address of network equipment and is not configurable.
RS485 address/RS485 baud rate
Set an address that ranges from 1 to 254 for this port. RS485 baud rate depends on the
network management conditions.
Batt. temp. sensors
A maximum of four battery temperature sensors can be cascaded.
Start addr. of batt. temp. sensor
Set this parameter by using the dual in-line package (DIP) switch on the battery
temperature sensor. The address range is 16-28. Ensure that the address that you set on
the LCD is the same as that set for the DIP switch. Otherwise, communication fails.
BMUs
BMUs can be cascaded. A maximum of 12 BMUs can be cascaded.
BMU start address
Set the BMU start address through the DIP switch on the BMU to 112. Ensure that the
address that you set on the LCD is the same as that set for the DIP switch. Otherwise,
communication cannot be implemented.
Amb. temp & humid sensors/Start addr. of amb. temp. & hum. sensors
An ambient temperature and humidity sensor has the same appearance as a battery
temperature sensor. The two types of sensors (up to four) can be cascaded. The ambient
temperature and humidity sensor address range is 32-44, which is different from the
battery temperature sensor. Therefore, you can use the sensor as an ambient temperature
and humidity sensor or battery temperature sensor by setting the address.
CIMs
Set this parameter to the number of connected CIMs. A maximum of four CIMs can be
connected.
CIM start address
Set this parameter to the communications address of the first connected CIM. The
address cannot be changed. The DIP switch should be set to 0000 for the first CIM, and
the DIP switch setting for a later connected CIM should increase by 1 (binary) than that
set for the previous CIM. For details, see the document delivered with the device.
NTC
The short-distance battery temperature sensor monitors the ambient temperature near
batteries. It ensures that batteries work reliably and securely. The default status is
Disable. If a short-distance battery temperature sensor is configured, set NTC to Enable.
SSID
When using the mobile app for site setup or inspection, set WiFi SSID after connecting a
WiFi module over a USB port to identify the WiFi device to which the mobile phone is
connected.
Password
The password for accessing WiFi.
Single/Parallel, Output voltage level, and Output frequency must be the same as the
actual values. Otherwise, an alarm may be generated, or other serious faults may occur.
Battery capacity and Number of cells must be the same as the actual values. Otherwise,
batteries may be damaged, or other serious faults may occur.
Single/Parallel
Specifies the UPS running mode. The values include Single and Parallel. The default
value is Single and only Single is supported.
Output voltage level
Specifies the system output voltage level. The value can be 380 V, 400 V (default), or
415 V. After you change the parameter value, the upper thresholds for the bypass voltage
are restored to the default values. If Output voltage level is 380 V or 400 V, the default
upper threshold is 15% and the default lower threshold is 20%. If Output voltage level
is 415 V, the default upper threshold is 10% and the default lower threshold is 20%. The
parameter is configurable after the inverter shuts down
Output frequency (Hz)
Specifies the system output frequency level. The value can be 50 Hz (default) or 60 Hz.
Battery capacity
Specifies the battery string capacity. The value range is 5-3000 Ah, and the default value
is100 Ah.
Number of cells
Specifies the number of cells. Each 12 V battery consists of six cells. The value range is
180-276, and the default value is 192.
A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V. The number of cells must be a multiple of 12 (for
example, 180 and 192).
Cell float voltage, Cell equalized volt, Float volt. temp. comp. coef., and EOD voltage threshold
are set for cells.
Set System capacity and Power module capacity according to specifications. Incorrect
settings may cause an overload alarm, which affects normal UPS running.
you must follow the guidance of maintenance engineers. Set the master and slave
BSC systems to master and slave BSC modes respectively.
− Ensure that the BSC signal cable between the master and slave BSC systems is
properly connected and that BSC-related hardware is properly installed.
Paral. sys. hibernate
When the customer load is light, set parallel hibernation to alternate modules in
hibernation, which can prolong their service life and improve the system efficiency.
Module cycle hiber. period (d)
1 to 100 days can be set. The parameter 30 days is set by default.
Amb. temp. alarm thresh. (°C)
An alarm is generated when the ambient temperature reaches the preset value.
Top outlet fan
If a top outlet fan is configured, check the fan running status after enabling this
parameter.
EOD restart
The UPS transfers to battery mode when the mains becomes abnormal. When batteries
reach the EOD threshold and the bypass is disabled and EOD restart is enabled, the
UPS will restart as soon as the mains resumes.
If EOD restart is disabled, clear the alarm manually or enable the function to restart the
UPS.
EOD restart delay (min)
If EOD restart is set to Enable, the UPS starts working after EOD restart delay when
the mains recovers from an EOD power failure. The value range is 1-1440 min, and the
default value is 10 min.
Inverter async. alarm
Specifies whether the Inverter async. alarm is displayed when the inverter does not
track the bypass input. The normal power supply is not affected no matter whether you
set the parameter to Enable or Disable.
Bus overvoltage recovery
Specifies whether to automatically clear the alarm and restart the power module when
the rectifier or inverter shuts down due to a bus overvoltage alarm. If Bus overvoltage
recovery is set to Enable, the bus overvoltage alarm is automatically cleared, and the
rectifier and inverter automatically start when the bus voltage recovers (less than 420 V)
within Bus overvolt. recovery time. When Bus overvoltage recovery is set to Disable,
the bus overvoltage alarm cannot be automatically cleared, and the rectifier and inverter
cannot automatically start. The default value is Enable.
Bus overvolt. recovery time
If Bus overvoltage recovery is set to Enable, the bus overvoltage alarm is automatically
cleared, and the rectifier and inverter automatically start when the bus voltage recovers
(less than 420 V) within Bus overvolt. recovery time. The default value is 5s.
Capacitor failure detection
The default value is Enable. When Capacitor failure detection is set to Enable, the
power module performs inverter capacitor fault detection based on the settings of
Capacitor failure detection upper limit and Capacitor failure detection lower limit.
If the power module determines that the inverter capacitor is faulty, it shuts down the
inverter to prevent the fault from expanding.
Capacitor failure detection upper limit (A)
The value range of Capacitor failure detection upper limit is 10–13 A and the default
value is 13 A. When the inverter capacitor current exceeds the current specified by this
parameter, the power module determines that the inverter capacitor is faulty and shuts
down the inverter.
Capacitor failure detection lower limit (A)
The value range of Capacitor failure detection lower limit is 0–2.5 A and the default
value is 2.5 A. When the inverter capacitor current is lower than the current specified by
this parameter, the power module determines that the inverter capacitor is faulty and
shuts down the inverter. If Capacitor failure detection lower limit is set to 0 A, the
power module does not perform inverter capacitor fault detection.
Input cur. limiting
This parameter specifies whether the UPS controls input current limiting. When this
parameter is set to Enable, electric generator overload due to excessively large input
current can be prevented. The default value is Disable.
Input cur. limiting ratio (%)
Limit the input current to protect the electric generator. The value range is 50%-200%,
and the default value is 200%.
No load output shows zero
When No load output shows zero is Enable, the system changes the value to 0 if there
is no load. The default value is Enable.
Cross current monitoring
Monitors the relative difference between inter-rack or inter-module currents. If the
parameter is set to Enable, you can view Mod. Cross Cur. and Rack Cross Cur. on the
running screen. The default value is Disable.
Bus Capa. Life
If Bus Capa. Life is set to Enable, the UPS5000-E detects the bus capacitor lifespan.
ModbusTCP Encryption
If Modbus TCP is used for communication, communication links do not implement
encryption or implement encryption based on the selected encryption mode.
Altitude (m)
Set this parameter based on the altitude of the place where the rack is used. The default
value is less than or equal to 1000.
When the voltage level is 380 V, the value range is 10%, 15% (default), 20%, and 25%.
When the voltage level is 400 V, the value range is 10%, 15% (default), and 20%.
When the voltage level is 415 V, the value range is 10% (default) and 15%.
Minimum bypass voltage
Lower threshold for the bypass voltage. When the difference between the bypass voltage
and the rated voltage exceeds this value, the system determines that the bypass voltage is
abnormal and that the bypass is unavailable. The value can be –10%, –15%, –20%
(default), –30%, –40%, –50%, or –60%.
ECO voltage range
In ECO mode, when the difference between the bypass voltage and the rated voltage is
greater than this value, the system determines that the ECO voltage is abnormal and
transfers to normal mode. The values can be ±5% (default), ±6%, ±7%, ±8%, ±9%, or
±10%.
BPM mode upon BPM overtemp.
This parameter specifies whether to start bypass mode if overtemperature occurs.
Battery parameter settings have great impact on battery maintenance, battery lifespan, and
UPS discharge time. When you set battery parameters, note the following:
Retain default settings for Chg. cur. limiting coef. and Cell float voltage. Only
professional maintenance personnel are allowed to change the settings.
When you set parameters, ensure the following: Chg. cur. limiting coef. >
Transfer-to-equalized charging cur. Coef; Dis. cur. 0.1C EOD ≥ Dis. cur. 0.3C EOD ≥
Dis. cur. 0.5C EOD ≥ Dis. cur. 1.0C EOD.
Battery type must meet the actual situation. Currently, only VRLA batt. is supported.
Chg. volt. over range point and Dis. volt. over range point are used to check whether
the batteries in each battery string have the same charge voltage and discharge voltage.
When a value exceeds the specified range, an alarm is generated. The calculation formula
is (Charge/Discharge voltage - Average voltage)/Average voltage x 100%. The
charge/discharge voltage and average voltage are obtained from the BMU. If the BMU is
not configured, you do not need to set these two parameters.
Installation time
A battery maintenance reminder is displayed when the maintenance time (counted from
the installation time) comes.
Maintenance period (d)
Interval for reminding users of battery maintenance.
Battery type
Set the battery type based on actual conditions. Currently, only lead-acid batteries are
supported.
Chg. cur. limiting coef. (C10)
Charging current limit, which is a multiple of the battery capacity. The value can be
0.05–0.15, 0.1 by default.
Cell float voltage (V/cell)
Set the float voltage. The value can be 2.23–2.27 V/cell, 2.25 V/cell by default. The
value is configurable in any mode.
Cell equalized volt. (V/cell)
Set the battery equalized voltage. The value can be 2.30–2.40 V/cell, 2.35 V/cell by
default. The value is configurable in any mode.
Transfer-to-equalized charging cur. Coef. (C10)
The battery enters equalized charge state when the battery current exceeds this parameter
value. The value range is 0.02–0.08, and the default value is 0.05.
SOC to start equalized charging (%)
When the SOC is lower than the specified value, batteries enter the equalized charging
mode. The value range is 0–100, and the default value is 70.
Automatic equalized charging
When the value is Enable, the UPS automatically changes the battery management
status to equalized charging based on the charge current and float charge time.
Forced equalized charging protection time (h)
When batteries are continuously under float charging or hibernation, you can enable
forced equalized charging. When the forced equalized charging time reaches the value of
this parameter, float charging starts.
Equalized charging protection interval (d) and Scheduled equalized charging
interval (d)
After batteries transfer from equalized charging to float charging, if the batteries do not
discharge, equalized charging starts only after the float charging time reaches Equalized
charging protection interval. After equalized charging is complete, scheduled equalized
charging starts when the non-equalized charging time exceeds Scheduled equalized
charging interval.
Float volt. temp. comp.
Option to correct the float voltage based on the battery temperature when a battery
temperature sensor is connected. The value is configurable in any mode.
Float volt. temp. comp. coef. (mV/°C·cell)
Correction coefficient during float voltage temperature compensation.
Float Chg Temp Comp Center (°C)
Indicates the reference temperature during temperature compensation of the float
charging voltage. The default value is 25.
Max. batt. dis. time (h)
Set the maximum battery discharge time. When the discharge time reaches the value, the
UPS powers off. The battery discharge time can be set only to 0 hours or a value in the
range 16–48 hours. The default value is 24 hours. If the time is set to 0 hours, battery
discharge protection is not implemented. This parameter cannot be set to a value in the
range 1–15 hours.
Sched. shallow dis. test
When certain conditions are met, the charger shuts down, and batteries supply power to
loads. The system records the battery discharge data as the reference for battery capacity
and lifespan.
Sched. shallow dis. test time
The discharge test starts in the specified time period. The value can be 00:00-06:00
(default), 06:00-12:00, 12:00-18:00, or 18:00-24:00. Sched. shallow dis. test time is
displayed when Sched. shallow dis. test is set to Enable.
Sched. shallow dis. test interval (d)
Set a time interval for shallow discharge tests. The value can be 30-90 days, 60 days by
default. The value is configurable in any mode. Sched. shallow dis. test interval (d) is
displayed when Sched. shallow dis. test is set to Enable.
Shallow dis. test dis. ratio (%)
Set the proportion of the discharge capacity to the total discharge capacity. The value can
be 10%-50%, 20% by default. The value is configurable in any mode.
Undertemp. alarm thresh. (°C) and Overtemp. alarm thresh. (°C)
Battery temperatures can be monitored in a timely manner. If a battery overtemperature
alarm is detected, the charging current limit decreases to 0.03 CA. Battery charging stops
if a battery overtemperature protection alarm (when the temperature reaches the high
temperature threshold plus 3°C) is generated. The Undertemp. alarm thresh. can be set
from -20°C to +5°C and the default value is –5°C. The Overtemp. alarm thresh. can be
set from 35°C to 55°C and the default value is 50°C.
Backup time warning, Remain. cap. warning, Backup time warn. thresh. (min), and
Remain. cap. warn. thresh. (%)
When the first two parameters are set to Enable, an alarm is generated when the backup
time or remaining capacity is less than the alarm threshold. The backup time alarm
threshold is 3–30 min, and the default value is 5 min. The remaining capacity alarm
threshold is 5%–50%, and the default value is 20%.
Dis. cur. 0.1C EOD (V/cell), Dis. cur. 0.3C EOD (V/cell), Dis. cur. 0.5C EOD (V/cell),
and Dis. cur. 1.0C EOD (V/cell)
By default, 0.1C EOD (V/cell) is set to 1.80, 0.3C EOD (V/cell) to 1.80, 0.5C EOD
(V/cell) to 1.75, and 1.0C EOD (V/cell) to 1.60. These values are calculated in real time
based on the discharge currents.
Intelligent hibernation
If this parameter is set to Enable, the intelligent battery hibernation function is enabled.
Class 1 grid hiber. time (d) and Class 2 grid hiber. time (d)
Set the hibernation time based on the power grid type. In hibernation mode, batteries are
not charged or discharged, which extends the battery lifespan. The Class 1 grid hiber.
time value range is 0–30 days, and the default value is 13 days. The value 0 indicates no
hibernation. The Class 2 grid hiber. time value range is 0–15 days, and the default value
is 6 days. The value 0 indicates no hibernation.
Single batt. float chg. voltage deviation alarm thres. (%) and Single batt. dis. voltage
deviation alarm thres. (%)
The parameters check whether the batteries in each battery string have the same charge
voltage and discharge voltage. When a value exceeds the specified range, an alarm is
generated.
The calculation formula is (Charge/Discharge voltage - Average voltage)/Average
voltage x 100%.
Number of battery strings
Number of battery strings connected in parallel.
Batteries in a single battery string
Number of batteries in a single battery string.
Set the dry contacts that you need to use. Otherwise, the UPS may not run properly.
When you disable a dry contact card, its dry contact signals are disabled.
After you enable a dry contact card, its dry contact signals can be displayed on the LCD.
Disable all the dry contacts for a dry contact card that is not connected and all the dry
contacts that are not used to prevent false alarms.
( ) encloses a unit, and [ ] encloses silk screen.
MUE05A connection
MUE05A connection status. Independent input signals can be enabled only when this
parameter is set to Enable.
Batter ground fault [BTG]
Enable or disable the battery grounding failure detection.
D.G. connection [GEN]
Enable or disable D.G. connection detection.
BCB connection [OL]
Enable or disable BCB connection detection.
Batter breaker [STA]
Enable or disable battery circuit breaker monitoring.
PDC output breaker [OUT]
Enable or disable PDC output circuit breaker monitoring.
PDC maintenance breaker [MT]
Enable or disable PDC maintenance circuit breaker monitoring.
BP/SYSMT Switch
If the BP/SYSMT switch is set to Enable, the port has dry contact signal access. How a
user uses the port depends on the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to Enable, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU bypass input switch or system maintenance switch.
SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to Enable, the port has dry contact signal access. How
a user uses the port depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to Enable, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU input surge protector or system output switch.
MUE06A connection
If this parameter is enabled, the mains and bypass backfeed protection is enabled.
MUE07A DI_4
Corresponds to signal of the input dry contact DI_4 on the MUE07A.
MUE07A DI_5
Corresponds to signal of the input dry contact DI_5 on the MUE07A.
The default value of Intelligent power is Disable. If you select Enable, intelligent power
supply parameters are displayed.
Intelligent power
Intelligent power supply mode is applicable when a D.G. is configured, which enables
D.G. power supply when an outage occurs. For details about the installation and
configurations, contact Huawei technical support.
ATS
Works with the intelligent power supply device.
D.G startup batt. volt. (V/cell)
Works with the intelligent power supply device. The value range is 1.80-2.00 V/cell, and
the default value is 1.80 V/cell.
If this parameter is set to Enable, the system generates an alarm when the branch circuit
breaker is open. If this parameter is set to Disable, the system does not generate the
branch circuit breaker open alarm under any condition. The default value is Enable.
Branch exception alarm enable
If this parameter is set to Enable, the system generates an alarm when the branch circuit
breaker is closed and no load is connected. If this parameter is set to Disable, the system
does not generate the branch exception alarm under any condition. The default value is
Disable.
Voltage harmonic alarm threshold (%)
When harmonic alarming is enabled and the main route voltage harmonic value exceeds
the alarm threshold specified by this parameter, the system generates an alarm. The value
range is 5.0%–30.0%, and the default value is 30.0%.
Current harmonic alarm threshold (%)
When harmonic alarming is enabled and the main route current harmonic value exceeds
the alarm threshold specified by this parameter, the system generates an alarm. The value
range is 5.0%–30.0%, and the default value is 30.0%.
System overvoltage threshold (%)
When the main route voltage is higher than the rated voltage multiplied by the value of
this parameter, the system generates an alarm. The value range is 105.0%–125.0%, and
the default value is 120.0%.
System undervoltage threshold (%)
When the main route voltage is lower than the rated voltage multiplied by the value of
this parameter, the system generates an alarm. The value range is 75.0%–95.0%, and the
default value is 85.0%.
Overload threshold (%)
Branch and main route current overload alarm threshold. When the branch current is
lower than the rated branch current multiplied by the value of Br. cur. shock protect (%)
and higher than the rated branch current multiplied by the value of Overload threshold
(%), the system generates a branch overload alarm. When the main route current is
higher than the rated main route current multiplied by the value of Overload threshold
(%), the system generates a main route overload alarm. The value range is
100.0%–120.0%, and the default value is 100.0%.
Overcurrent threshold (%)
Branch and main route overcurrent threshold. When the main route or branch current is
higher than the rated main route or branch current multiplied by the value of
Overcurrent threshold (%) and lower than the value of rated current multiplied by the
value of Overload threshold (%), the system generates an alarm. The value range is
80.0%–100.0%, and the default value is 80.0%.
Undercurrent threshold (%)
Branch and main route undercurrent threshold. When the main route or branch current is
higher than the rated main route or branch current multiplied by the value of
Undercurrent threshold (%) and lower than the value of rated current multiplied by the
value of Overcurrent threshold (%), the system generates an alarm. The value range is
30.0%–80.0%, and the default value is 60.0%.
Three-phase load imbalance
Main route current three-phase load imbalance alarm threshold. The value range is
5.0%–50.0%, and the default value is 25.0%. When the value obtained after the
difference between the maximum and minimum main route three-phase currents is
divided by the minimum current is higher than the value of Three-phase load
imbalance, the system generates an alarm.
Mains three-phase current imbalance
If this parameter is set to Enable, the system generates an alarm when the main route
three-phase current is imbalanced. If this parameter is set to Disable, the system does not
generate a main route three-phase current alarm under any condition. The default value is
Enable.
Mains current exceeding lower threshold
If this parameter is set to Enable, the system generates an alarm when the main route
current is lower than the Mains current exceeding lower threshold. If this parameter is
set to Disable, the system does not generate a main route current alarm under any
condition. The default value is Enable.
Mains current exceeding higher threshold
If this parameter is set to Enable, the system generates an alarm when the main route
current is higher than the Mains current exceeding higher threshold. If this parameter
is set to Disable, the system does not generate a main route current alarm under any
condition. The default value is Enable.
Branch current exceeding lower threshold
If this parameter is set to Enable, the system generates an alarm when the branch route
current is lower than the Branch current exceeding lower threshold. If this parameter
is set to Disable, the system does not generate a branch route current alarm under any
condition. The default value is Disable.
Branch current exceeding higher threshold
If this parameter is set to Enable, the system generates an alarm when the branch route
current is higher than the Branch current exceeding higher threshold. If this parameter
is set to Disable, the system does not generate a branch route current alarm under any
condition. The default value is Disable.
Battery Maint.
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.
Perform battery maintenance periodically to increase the battery lifespan and improve the
UPS reliability. Battery maintenance includes Forced Equalized Charging, Shallow Dis.
Test, and Capacity Test. The next maintenance time displayed on the screen reminds you of
the upcoming time to check batteries.
USB Operations
The USB Operations screen provides the following functions: Remove USB, Upgrade
Software, Import Config., Export Config., Export Logs, Export E-labels, and Export
Alarms.
This screen allows you to load software online, upgrade software, and download system data.
Inv. ON
The Inv. ON screen allows you to start the inverter manually.
Inv. OFF
The Inv. OFF screen allows you to shut down the inverter manually.
ECM Switchover
This menu allows you to perform active/standby switchover on the UPS. When you need to
maintain an ECM and it is working, perform active/standby switchover on the ECM. After
switchover, ensure that the ECM stops working (the yellow or red indicator is on, or the green
indicator is blinking) before you maintain it.
Screen Calib.
You can calibrate the screen.
Reset
After the service life of a capacitor is about to end, you need to manually remove it and
replace it with a new capacitor. After the new capacitor is installed, the power module cannot
detect the replacement, and you need to manually reset the service life of the new capacitor.
You can click the UPS, PDU-IT, and PDU-A/C icons in the energy flow diagram to view detailed
information about them.
4.2 WebUI
4.2.1 Login
Context
Internet Explorer 11 is used as the example browser.
Procedure
Step 1 Open the browser and choose Tools > Internet Options.
Step 2 On the Advanced tab page, ensure that Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2 are
selected and click OK.
Step 3 Enter https://UPS IP address in the address box of the browser, select a language, set User
name and Password, and click Login. The system supports Internet Explorer 11 and Firefox
31.0.
The preset UPS IP address is 192.168.0.10. You can set the UPS Ethernet IP address on the LCD or
WebUI. The value range is 1.0.0.0–223.255.255.255.
If an incorrect password is entered three consecutive times, the account will be locked out for 5
minutes.
After a user logs in to the WebUI, if another user logs in with the same user name, the current
account will be logged out.
It is advised to change the password after the first login using User Mgmt. on the Config. page to
prevent unauthorized access.
----End
1 Running status Displays the power flow and UPS running information.
area
2 Menu bar Displays active alarms and real-time data, sets
parameters, sets communications information, and
provides control commands.
The Active Alarms page is displayed by default.
3 Information area Displays system monitoring information.
You can click the UPS, PDU-IT, and PDU-A/C icons in the energy flow diagram to view
detailed information about them.
On the User Mgmt. page, you can add, modify, delete, lock, or unlock users and change user
passwords.
The WebUI user name cannot exceed 10 characters and can contain only uppercase and lowercase
letters, digits, and underscores. The password contains 6 to 20 characters and at least two types of
uppercase letters, lowercase letters, digits, and underscores.
If the LUI password complexity check is disabled, the user password is required to be a string of six
to eight digits. If the password complexity check is enabled, the user password is required to be a
string of 6–20 characters and contain at least two types of characters.
The NTP parameters are used to set the NTP server address, port number, and synchronization
interval.
The default SNMP version is SNMPv3, and the preset MD5/SHA password is Changeme1, and the
preset DES/AES password is Changeme2. Change the password after your first login, preventing
unauthorized access.
To obtain the MIB file, choose Config. > Site Config. > SNMP > Download
HUAWEI_UPS_MIB.
SNMP Trap indicates the IP address of the server configured with network management system
(NMS) software. If SNMP Trap is incorrectly set or not set, system information will be lost or not
reported in time.
The certificate is used for Secure Sockets Layer (SSL) encryption protection for WebUI login. You
need to apply to a third-party institution for the certificate.
Configuration Management is used to upload and export configuration parameters in the
monitoring system.
Multi-brand Management is used to import the brand information of a partner to the corresponding
WebUI.
Specify Email server IP address, Sender's email, and User account authentication required
when sending a mail and click Test to check whether the test email can be received. Configure
Alarm Notification Server is used to configure a server for receiving alarm emails from the
monitoring system.
Set Email and Alarm Severity and simulate an alarm. Check that the alarm email can be received.
Configure Alarm Notification Email Address is used to configure the email address for receiving
alarm emails from the monitoring system.
ModbusTCP Certificate Management: ModbusTCP supports the Transport Layer Security (TLS)
secure protocol for encrypted transmission and implements access authentication through the
bidirectional certificate. Customers can replace the UPS certificate with the certificate trusted by
them.
ModbusTCP CA Certificate Management: Import a CA certificate to verify the validity of the
Modbus TCP access certificate.
ModbusTCP Authentication: Verify the identity legitimacy of both parties to ensure data security
for both parties in ModbusTCP communication.
After eUPS certificate management is configured, a certificate can be imported on the WebUI to
replace the preset eUPS certificate.
5 Operations
Perform system commissioning and power-on strictly according to the system manual and
ATS instructions. For any changes in operations and parameters, consult Huawei engineers.
Otherwise, system commissioning or power-on may fail, or even the cabinet is damaged.
Procedure
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Press the locking latch on the ATS panel, pull out the handle, and insert it into the slot.
Step 4 Check the ATS Motor/Manual selection lever, and flip it to the Motor mode.
Step 5 Check the AC input and configuration status of the ATS.
After the AC input is normal, the ATS controller starts. Check and set ATS parameters based
on the AC input parameters.
A password is required to log in to the configurations page. Set the password by using the Up, Down,
and Enter buttons. The initial password is 0001.
Language setting: Default screen > Main Menu > Device Configuration > Language.
On the default screen, hold down . The main menu screen is displayed. On the
Rated operating voltage 110 V/57 V; 115 V/66 V; The default value is 380
120 V/70 V; 208 V/120 V; V/220 V. Set the parameter
220 V/127 V; 230 V/132 V; based on site requirements.
240 V/138 V; 227 V/160 V;
347 V/200 V; 380 V/220 V;
400 V/230 V; 415 V/240 V;
440 V/254 V; 480 V/277 V
Rated frequency 50 Hz; 60 Hz The default value is 50 Hz.
Set the parameter based on
site requirements.
Number of Phases LN1 Single phase; three-phase The default value is
four-wire; three-phase three-phase four-wire.
three-wire
On the main menu screen, select device configuration and press . On the device
configuration screen, you can set thresholds for parameters.
The following table lists the system configuration attributes and values.
Procedure
Step 1 (Skip this step in the case of ATS input.) Turn on the MCCB.
Step 2 Turn on the UPS input circuit breaker QF1.
The UPS is powered by the mains and initialization begins. The LCD displays the Huawei
logo and an initialization progress bar.
----End
Set system parameters with caution because the settings determine whether the UPS can
operate normally.
Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following:
Set Battery capacity correctly after double check. An incorrect setting affects the
charging power. High or low charging power tends to shorten the battery lifespan, or even
damages batteries. To seek help about how to determine the battery capacity, contact
Huawei technical support.
Number of cells affects the charge voltage and discharge time. An incorrect setting will
cause a high or low charge voltage, which greatly shortens the battery lifespan. In addition,
the UPS may shut down in advance during discharging, which may result in data backup
failure.
Step 2 After you complete the settings, the Bypass mode and No battery alarms will be displayed
on the LCD and do not need to be cleared. If there are any other alarms, you need to rectify
the faults.
After you complete the settings, choose System Info. > Settings > Advanced Param., and verify
that the settings of System Capacity, Power module capacity, Requisite modules, and
Redundant modules are consistent with the actual conditions.
If dry contact signals are connected to the system, choose System Info. > Settings > Dry contacts
and check that the connected dry contacts have been enabled and that the disconnected dry contacts
have been disabled.
2. WebUI
Step 4 View the system running status diagram on the LCD to check that the UPS is working in
bypass mode.
----End
The Service Expert app can be downloaded from Huawei app store and can run on Android.
User interfaces displayed in this document correspond to the app version V100R001C00B055
and are for reference only.
For offline startup, enter the barcode and the verification code on the mobile phone app.
The app automatically generates a startup password for the UPS. Then enter the password
on the MDU screen to start the UPS.
For online startup, activate the startup password on the mobile phone app to start the UPS.
If the initial startup verification passes, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.
Online Startup
Step 1 Insert a WiFi module into the USB port on the MDU.
Step 2 On the MDU, set System Info > Settings > Communication Settings > Password.
Step 3 Enable the mobile phone WLAN, search for the SSID signal, and connect to the WiFi signal.
Step 4 Open the Service Expert app on the mobile phone.
Step 5 On the home screen of the app, tap Startup to access the Set Startup screen.
----End
Offline Startup
Step 1 Open the Service Expert app on the mobile phone.
Step 2 On the home screen of the app, tap Startup to access the Set Startup screen.
Step 3 Set Site and Device Type as required, and tap Offline Activation.
Step 4 On the MDU, choose System Info > Maintenance > Inv. ON. You can obtain the Bar code
and Verification code from the screen, as shown in the following figure.
The values of the Bar code and Verification code in the figure are for reference only. The actual values
prevail.
Step 5 Enter BarCode and Codes obtained from the MDU on the Offline Activation screen. Tap
Generate PWD to generate a startup password.
If startup verification fails (the password is not entered within 5 min or the password is incorrect), the
generated password will be invalid for the sake of security. The initial startup verification fails.
Step 6 Enter the generated startup password in Figure 5-9 to start the UPS.
----End
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.
Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and then
click OK.
Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON, and confirm
the operation to start the inverter.
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
----End
Step 2 Check that the actual battery capacity and number of cells are consistent with the settings on
the LCD. Use a multimeter to check that the sum of the absolute voltage of the negative
battery string and the voltage of the positive battery string is greater than a certain value (1.6 x
Number of cells) to ensure that the battery strings are connected properly.
Step 3 After confirming that the battery strings are properly connected, turn on the battery string
input switch. If there are multiple battery strings, turn on the switch for each battery string and
then the general switch between battery strings and the UPS. After you turn on the battery
string input switch, the No battery alarm disappears.
Step 4 Turn on the UPS output circuit breaker QF3.
After the UPS is started for the first time, perform a battery capacity test to ensure that battery
parameters are correctly displayed.
Step 5 (Optional) Turn on the lighting output circuit breaker on the integrated UPS and check
whether the PWR indicator on the AC actuator lights up. Press down the lighting button to
power on the light.
Step 6 Turn on the air conditioner circuit breaker on the integrated UPS to power on the air
conditioners.
Step 7 Turn on the IT1 and IT2 output circuit breakers on the integrated UPS, and then turn on the
PDU2000s of the network cabinet and IT cabinet to power on the equipment in the network
cabinet and IT cabinet.
----End
If you have not logged in, enter a user name and password, and tap on the displayed login
screen.
Step 2 Set the slave BSC system. On the main menu of the LCDs of the UPS, choose System Info >
Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set BSC
mode to BSC slave mode.
Step 2 Set the slave BSC system. Log in to the WebUI of each UPS of the master BSC system.
Choose Monitoring > Param. Settings. Under Advanced Param., set BSC mode to BSC
slave mode and click Submit.
After you shut down the inverter, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power. Before you shut down the UPS, ensure
that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
Using the LCD:
a. On the main screen, tap Common Functions. Tap Inv. OFF.
b. If no user is logged in, enter a user name and password, and tap on the
login screen displayed.
c. In the displayed dialog box, tap Yes to shut down the inverter.
To shut down the inverter on the Maintenance screen, tap System Info > Maintenance.
Method for shutting down the inverter on the WebUI
a. Enter https://UPS IP address in the address box of the browser.
b. Select a language. Enter a user name and password, and click Login to open the
homepage.
c. On the homepage, choose Monitoring > Control, and click Inv. OFF. In the
displayed dialog box, click OK to shut down the inverter.
After the inverter shuts down, if the bypass is normal, the UPS transfers to bypass
mode; if the bypass is not normal, the UPS supplies no power, and the loads shut
down.
After the inverter is shut down, the Bypass mode alarm is displayed on the LCD.
If the inverter needs to shut down to transfer the UPS to bypass mode, check that the UPS has not
generated an alarm and perform Step 1.
Step 2 After the inverter shuts down, turn off UPS output circuit breaker QF3.
Step 3 Turn off the battery string switch. If there are multiple battery strings, turn off the general
switch between battery strings and the UPS and then the switch for each battery string.
Step 4 Turn off UPS input circuit breaker QF1.
Step 5 Turn off the UPS input circuit breaker (for MCCB input) or disconnect the mains from the
ATS (for ATS input).
----End
Before shutting down the inverter, ensure that the bypass is normal. If the bypass is not
normal, after the inverter is shut down, the UPS supplies no power, and the loads shut down.
Shut down the UPS inverter. Shut down the inverter on the LCD or WebUI, and the UPS
transfers to bypass mode.
If the inverter is shut down when the input voltage or frequency exceeds the specified threshold, the
UPS supplies no power, and the loads shut down.
Procedure
Step 1 Manually shut down the inverter to transfer the UPS to bypass mode.
Step 2 Select a value (±5%, ±6%, ±7%, ±8%, ±9%, or ±10%) from the ECO voltage range
drop-down list box.
Step 3 Set Working mode to ECO. Information indicating that the UPS works in ECO mode is
displayed on the LCD.
After the inverter starts, the UPS still works in bypass mode and the inverter is standby. If the
bypass is abnormal, the inverter supplies power immediately. If the inverter is not started, the
UPS may be disconnected.
----End
Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint.
Step 2 Tap Start next to Forced Equalized Charging to start a forced equalized charging test.
The forced equalized charging test automatically stops in any of the following cases:
The forced equalized charging test duration reaches the forced equalized charging protection time
(12–24 h, 18 h by default).
The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
An alarm is generated.
----End
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).
The load ratio fluctuation exceeds 10%.
An alarm is generated.
----End
Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint.
Step 2 Tap Start next to Capacity Test to start a capacity test.
----End
Procedure
Step 1 Insert a USB flash drive into the USB port on the MDU.
Step 2 On the main screen of the LCD, choose System Info. Tap . The Maintenance screen is
displayed.
Step 3 Choose USB Operations > Export Logs, and select a log download path.
Step 4 Tap Next. In the displayed dialog box, tap Yes to download data.
----End
Procedure
Step 1 Log in to the WebUI.
Step 2 Choose Query > Logs, select logs from the Log drop-down list box, then click Export to
export logs.
----End
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is abnormal, the loads may power off.
Procedure
Step 1 Manually transfer the UPS to bypass mode.
Step 2 Remove the screws using a Phillips screwdriver, remove the barrier chip on the maintenance
bypass switch, and turn on the maintenance bypass switch.
The Maint. breaker closed alarm is displayed in the alarm list.
After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode alarms
are displayed on the LCD.
----End
Before you transfer the UPS from maintenance bypass mode to normal mode, ensure that the
bypass input and output are normal.
Procedure
Step 1 Turn off the maintenance bypass switch.
Press down the maintenance bypass switch to turn it off.
The Maint. Breaker closed alarm disappears from the alarm list. Check whether the UPS
works in bypass mode by viewing the system running diagram on the LCD or WebUI.
Step 2 Start the inverters.
----End
After the EPO button is turned on, the UPS supplies no power and the loads shut down.
In maintenance bypass mode, the UPS continues to supply power even after the EPO
button is turned on.
Press the external EPO switch that connects to the dry contact card or remove the 4-pin
terminal on the EPO port of the dry contact card of the bypass unit.
After you press the EPO button, the EPO and No power supplied alarms are displayed on the
LCD.
WebUI
On the homepage, choose Monitoring > Control, and click Clear Fault to clear the
EPO alarm.
Step 3 View active alarms and ensure that the EPO alarm is cleared. If the input of the system bypass
is normal, the UPS transfers to the bypass mode.
LCD
Choose System Info from the LCD main screen and tap . The Alarms screen is
displayed. Tap Active Alarms and check whether the EPO alarm is cleared.
WebUI
Choose Monitoring > Active Alarms to check that the EPO alarm disappears from the
alarm list.
Step 4 Start the inverter.
----End
Context
The following data can be exported:
Historical alarms
Logs
E-Label
Fault data
Procedure
Step 1 Choose Query > Historical Alarms, and set Severity, Generated, and Cleared.
Step 2 Click Query, and you can see the corresponding historical alarms.
Step 1 On the main screen, tap System Info and . The Settings screen is displayed.
If you have not logged in, enter a user name and password, and tap on the login screen
displayed.
Step 3 On the LCD, set Paral. sys. hibernate to Enable. A confirmation message and security
warning are displayed.
Step 4 Check that the load power is stable (that is, no transient surge results in overload, which may
cause the UPS to transfer to bypass mode), and tap Yes. A message is displayed, indicating
that the hibernation function is set successfully.
Step 5 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
----End
5.14.2 WebUI
Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Param..
Step 3 On the WebUI, select Enable from the Paral. sys. hibernate drop-down list box and click
Submit. A message indicating that there is a risk is displayed. Click OK.
Step 4 Set the module cycle hiber. period to an integer ranging from 1 to 100. The default value is
30.
----End
Before you connect the D.G. to a UPS system, check that the system is a single UPS system
and that the system is working in non-inverter mode and has connected to batteries.
When the UPS is working, the D.G. starts if a mains outage occurs and the battery voltage
reaches the specified threshold. You can set intelligent power mode on the LCD or WebUI.
Step 1 On the LCD, choose System Info and tap to access the Settings screen.
If you have not logged in, enter a user name and password, and tap the displayed login screen.
Step 3 Select Enable from the Intelligent power drop-down list box. In the displayed dialog box,
tap Yes. Intelligent power supply parameters are displayed.
Intelligent power can be set to Enable and Disable. The intelligent power supply
function can be used only when Intelligent power is set to Enable. It is set to Disable
by default.
ATS can be set to Connected and Not connected. When it is set to Connected, the UPS
works in the ATS scenario. When it is set to Not connected, the UPS works in the reused
scenario. It is set to Connected by default and is available only when Intelligent power
is set to Enable.
The value range of D.G. startup batt. volt. is 1.80–2.00 V/cell. The default value is 1.80
V/cell. It is available only when Intelligent power is set to Enable.
When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.
Step 4 When Intelligent power is set to Enable, the system will automatically modify some
parameter settings which you can view on the corresponding screen.
In battery mode (non-battery test), if the battery voltage reaches the value specified by D.G. startup
batt. volt. or Low battery voltage, the signal for starting the D.G. is triggered.
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the signal for shutting down the D.G. is triggered.
If the battery voltage is greater than D.G. startup batt. volt., the UPS exits intelligent power mode
and triggers the D.G. shutdown signal. If the battery voltage is less than D.G. startup batt. volt., a
dialog box is displayed, indicating potential risks. Tap OK to exit intelligent power mode.
When disconnecting the D.G. from the UPS, set Intelligent power to Disable. Then the system will
automatically modify the following parameters: Working mode is set to Normal mode; Intra-rack
power module start delay (s) is set to 5; Output freq. track rate (Hz/s) is set to 0.6; Input
adaptability is set to Weak; D.G. mode is set to Disable; and D.G. connection [GEN] is set to
Disable. You can modify these parameters as required.
----End
Intelligent power can be set to Enable or Disable. The intelligent power supply
function can be used only when Intelligent power is set to Enable. It is set to Disable
by default.
ATS can be set to Connected or Not connected. When it is set to Connected, the UPS
works in the ATS scenario. When it is set to Not connected, the UPS works in the reused
scenario. It is set to Connected by default and is available only when Intelligent power
is set to Enable.
The value range of D.G. startup batt. volt. is 1.80–2.00 V/cell. The default value is 1.80
V/cell. It is available only when Intelligent power is set to Enable.
When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.
Step 3 When Intelligent power is set to Enable, the system will automatically modify some
parameter settings which you can view on the corresponding page.
In battery mode (non-battery test), if the battery voltage reaches the value specified by D.G. startup
batt. volt. or Low battery voltage, the signal for starting the D.G. is triggered.
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the signal for shutting down the D.G. is triggered.
If the battery voltage is greater than D.G. startup batt. volt., the UPS exits intelligent power mode
and triggers the D.G. shutdown signal. If the battery voltage is less than D.G. startup batt. volt., a
dialog box is displayed, indicating potential risks. Click OK to exit intelligent power mode.
When disconnecting the D.G. from the UPS, set Intelligent power to Disable. Then the system will
automatically modify the following parameters: Working mode is set to Normal mode; Intra-rack
power module start delay (s) is set to 5; Output freq. track rate (Hz/s) is set to 0.6; Input
adaptability is set to Weak; D.G. mode is set to Disable; and D.G. connection [GEN] is set to
Disable. You can modify these parameters as required.
----End
In ATS scenarios, the default parameter settings are used. Working mode can be set based on
the site requirements.
Connect the DO_4 dry contact port on the UPS monitoring interface card to the
startup/shutdown control port on the D.G. The initial status of the DO_4 dry contact is
normally open (NO). When it is closed, the D.G. starts.
The D.G. RUN port of the ATS connects to the dry contact card.
The AMF port of the ATS connects to the DI_5 port on the dry contact extended card.
6 Routine Maintenance
Only trained personnel are allowed to perform maintenance. Before performing operations
on the UPS, wear electrostatic discharge (ESD) clothes, ESD gloves, and an ESD wrist
strap. Remove conductive objects such as jewelry or watches during operations to avoid
electric shocks or burns.
Use insulated tools when maintaining internal devices. Only trained personnel are allowed
to perform maintenance. Customers are not allowed to maintain components behind
protective covers that can be removed only using tools. If the components are to be
maintained, contact Huawei technical support.
Only maintenance engineers can maintain power modules and bypass modules.
Maintain UPSs regularly based on the following requirements. Otherwise, the UPSs may
fail to operate properly and the service life may be shortened.
To prevent system failures caused by the deterioration of some key UPS components, you are
advised to check the key components on a regular basis and replace them within the service
life.
Table 6-4 Service life parameters for replaceable components and recommended replacement
intervals
Before installing batteries, read through the battery user manuals and pay attention to safety
precautions and connection methods provided by battery manufacture.
When installing and maintaining batteries, pay attention to the following points:
7 Troubleshooting
If the UPS is faulty, alarm information is displayed on the LCD. Clear critical alarms
before powering on the UPS again. Otherwise, the fault scope expands or the UPS is
damaged.
Do not clear alarms by reseating modules.
Remove a faulty module after it is confirmed that the module needs replacing. After
removing the module, do not insert it into the UPS again.
After a UPS finishes troubleshooting and is started, if the LCD continues displaying alarm
information, choose System Info > Alarms > Clear Faults to clear the alarm and then
start the inverter.
To restore battery discharge after batteries reach EOD, use one of the following methods: 1.
Switch to another battery string. Ensure that each battery has a voltage greater than the
EOD voltage and 11.3 V/cell. 2. Restore the mains power supply to start the inverter.
Close the battery switch and charge batteries until each battery has a voltage greater than
the EOD voltage and 11.3 V/cell.
If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical
support.
The bypass is The buzzer is The bypass thyristor is Replace the bypass
not normal. activated, and the damaged. module.
Fault indicator is
on. The bypass module Reduce the load, or
experiences improve ventilation.
overtemperature.
The ATS is not After being The input three-phase Power off the ATS and
normal. powered on, the sequence is incorrect. check the phase
ATS automatically sequence.
switches from ON
to OFF or switches
between ON and
OFF repeatedly.
For details about component replacement and maintenance involved in Troubleshooting and Alarm List,
consult Huawei maintenance engineers.
8 Parts Replacement
Context
The fuse is located in the right door panel at the rear of the cabinet.
The following tables describe fuses.
Procedure
Step 1 Remove the protective panel.
Step 2 Locate the fuse terminal in the UPS according to the diagram.
(1) Fuse
Procedure
Step 1 Remove the indicator fuse from the fuse terminal block at the rear of the cabinet to disconnect
the circuit. For the MCCB input, the fuse is connected to #1 fuse base. For the ATS input, the
fuses are connected to #1 and #2 fuse bases.
Step 2 Remove the protective panel.
When removing cables, clearly label the cables with its corresponding terminal ports to prevent incorrect
connections.
Step 6 Remove the retaining ring from the indicator, and remove the indicator from the mounting
hole.
Step 7 Put a new indicator in the mounting hole, secure the retaining ring, and connect the
conducting wire.
Step 8 Install the new indicator in the fastener and reinstall the fastener in the cabinet.
9 Technical Specification
Item Specifications
Cable routing mode Routed in and out from the top
Protection level IP20
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm
Communication Dry contacts, RS485, and SNMP
Item Specifications
Item Specifications
Safety compliance EN62040-1, 2013
IEC62040-1, 2013
Item Specifications
Electromagnetic EN/IEC62040-2
compatibility (EMC) IEC61000-2-2
IEC61000-4-2
EN61000-4-6: EN/IEC62040-2 2nd Ed (IEC61000-4-6)
EN61000-4-3: EN/IEC62040-2 2nd Ed (IEC61000-4-3)
EN/IEC62040-2 2nd Ed (IEC61000-4-4)
EN/IEC62040-2 2nd Ed (IEC61000-4-5)
IEC61000-4-8
IEC61000-4-11
Item Specifications
Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input frequency range 50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)
Item Specifications
Item Specifications
Battery voltage 360–528 V DC (30–44 batteries, 32 by default; derated by 6%
when there are 30 batteries)
Battery management Intelligent battery management
Cold start When a mains outage occurs, batteries can start the UPS to
supply power to loads.
Charging voltage Equalized charging voltage: 2.3–2.4 V/cell, 2.35 V/cell by
default (30–42 batteries); 2.3–2.35 V/cell, 2.35 V/cell by
default (44 batteries)
Float charging voltage: 2.23–2.3 V/cell; 2.25 V/cell by
default (30–44 batteries)
Item Specifications
Output system Three-phase, four-wire, and PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
Output voltage precision ±1% (balanced load)
Output power factor 1
Transfer time Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Output voltage imbalance Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60
minutes
110% < load ≤ 125%: transfer to bypass mode after 10
minutes (tolerance ±0.1 minute)
125% < load ≤ 150%: transfer to bypass mode after 1
minute
Load > 150% or a short circuit occurs: run for 200 ms
Derating coefficient of 40 A circuit breaker: 0.75
output circuit breakers 63 A circuit breaker: 0.7
Item Specifications
Item Specifications
Current equalization 5%
specification
A Menu Hierarchy
The silk screen content is in the format of number of routes+symbol+switch sequence number.
In the single-input scenario, the number of routes is omitted by default. For example, 1QF1
indicates the first switch of input I, 2QF1 indicates the first switch of the second input, and
QF1 indicates the first switch in the single-input scenario.
C Alarm List
0089-1 Rack output Minor The load is Check the load and
overload excessive. remove some loads or
The rack expand the UPS power
capacity setting capacity if the UPS is
is not overloaded.
appropriate. Check that the configured
rack capacity meets
requirements.
0090-1 Dry contact Critical I2C Replace the dry contact
board fault communication board MUE05A.
with the dry
contact board
MUE05A fails.
0090-2 I2C Replace the dry contact
communication board MUE06A.
with the dry
contact board
MUE06A fails.
0356-1 Battery Mode Minor The UPS is The running status is
working in battery displayed. See details about
mode. how to handle other alarms.
0359-1 No power Warning No power is The running status is
supplied supplied. displayed. See details about
how to handle other alarms.
0332-1 Output Minor The output is The running status is
disabled disabled. displayed. See details about
how to handle other alarms.
0334-1 BSC master Warning BSC master The running status is
system system. displayed. No further
measures are required.
0334-2 BSC slave BSC slave system. The running status is
system displayed. No further
measures are required.
0337-1 PDC bypass Critical The bypass input The running status is
input breaker circuit breaker on displayed. No further
open the PDC is OFF. measures are required.
0338-1 PDC output Critical The output circuit 1. Check that all UPS output
breaker open breaker on the circuit breakers are ON.
PDC is OFF. 2. On the LCD, check that
PDC output breaker
open alarm has
disappeared. If the alarm
persists, tap the Clear
Fault button to clear the
alarm.
0341-1 PDC Maint. Minor The maintenance The running status is
breaker circuit breaker on displayed. No further
closed the PDC is ON. measures are required.
0342-1 Mains input Critical The UPS input The running status is
breaker open circuit breaker is displayed. No further
OFF. measures are required.
0343-1 BPM input Critical The bypass input The running status is
breaker open circuit breaker is displayed. No further
OFF. measures are required.
0340-1 Maint. Minor The UPS The running status is
breaker maintenance displayed. No further
closed circuit breaker is measures are required.
ON.
0335-1 Generator Warning The generator is The running status is
connected connected. displayed. No further
measures are required.
0362-1 BCB off Minor BCB off The running status is
displayed. No further
measures are required.
0594-1 Insufficient Minor The load is 1. Reduce the load.
redundant excessive. 2. Decrease the configured
racks The configured number of redundant
number of racks.
redundant racks
is incorrect.
0101-1 BSC signal Minor The dual bus 1. Check the dual bus
abnormal connector is connector.
loose. 2. Check the parameter
Parameters are settings.
set incorrectly.
0102-1 Maint. Critical The user operation 1. Shut down the inverter
breaker is incorrect. and then close the
misoperation maintenance circuit
breaker.
2. After maintenance, open
the maintenance circuit
breaker and then start the
inverter.
0380 In self-check Warning The inverter is in Wait until the inverter
self-check. self-check is complete.
A
ASIC application-specific integrated circuit
ATS AC transfer switch
AWG American wire gauge
B
BSC bus synchronization controller
BCB-BOX battery circuit breaker box
BBB-BOX battery bus bar box
C
CAN control area network
CE Conformite Europeenne
D
DSP digital signal processing
E
ECO economic control operation
EPO emergency power off
ECM energy control module
EOD end of discharge
FE fast Ethernet
I
IEC International Electrotechnical Commission
L
LCD liquid crystal display
M
MDU monitor display unit
N
NC normally closed
NO normally open
NTC negative temperature coefficient
P
PDC power distribution cabinet
PDU power distribution unit
PE protective earthing
PFC power factor correction
R
RS485 Recommend Standard 485
S
SNMP Simple Network Management Protocol
SOC state of charge
SOH state of health
STS static transfer switch
T
THDi total distortion of the input current waveform
U
UPS uninterruptible power system
USB Universal Serial Bus
V
VRLA valve-regulated lead acid battery