0% found this document useful (0 votes)
461 views245 pages

UPS5000-E - (50 KVA-125 KVA) User Manual (Integrated UPS 3.0)

Uploaded by

mbaykal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
461 views245 pages

UPS5000-E - (50 KVA-125 KVA) User Manual (Integrated UPS 3.0)

Uploaded by

mbaykal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 245

UPS5000-E-(50 kVA-125 kVA)

User Manual (Integrated UPS


3.0)

Issue 05

Date 2018-09-28

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2018. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: http://e.huawei.com

Issue 05 (2018-09-28) i
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) About This Document

About This Document

Purpose
This document describes the integrated uninterruptible power system UPS5000-E-(50
kVA-125 kVA) in terms of its features, performance, working principles, appearance,
installation, and operation and maintenance (O&M). UPS in this document represents
integrated UPS.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 System engineers
 Hardware installation engineers
 Commissioning engineers
 Data configuration engineers
 Maintenance engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, may result in minor or moderate injury.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. ii


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) About This Document

Symbol Description
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.

Change History
Updates between document issues are cumulative. Therefore, the latest document issue
contains all updates made in previous versions.

Issue 05 (2018-09-28)
Added a new ATS cabinet.

Issue 04 (2018-04-20)
Updated the section "Technical Specifications."

Issue 03 (2018-01-15)
Updated the Monitoring screen image.

Issue 02 (2017-11-27)
Updated the section "Technical Specifications."

Issue 01 (2017-08-30)
This issue is the first official release.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. iii


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) Contents

Contents

About This Document .................................................................................................................... ii


1 Safety Precautions ......................................................................................................................... 1
1.1 General Safety .............................................................................................................................................................. 1
1.2 Electrical Safety ............................................................................................................................................................ 3
1.3 Operating Environment................................................................................................................................................. 6
1.4 Battery Safety ............................................................................................................................................................... 6
1.5 Mechanical Safety ........................................................................................................................................................ 9
1.6 Laying Out Cables ...................................................................................................................................................... 10

2 Overview....................................................................................................................................... 11
2.1 Model Description ...................................................................................................................................................... 11
2.2 Working Principle ....................................................................................................................................................... 12
2.2.1 Conceptual Diagram ................................................................................................................................................ 12
2.2.2 Working Modes........................................................................................................................................................ 13
2.2.2.1 Normal Mode ........................................................................................................................................................ 13
2.2.2.2 Bypass Mode ........................................................................................................................................................ 13
2.2.2.3 Battery Mode ........................................................................................................................................................ 14
2.2.2.4 Maintenance Bypass Mode ................................................................................................................................... 15
2.2.2.5 ECO Mode ............................................................................................................................................................ 16
2.3 Product Introduction ................................................................................................................................................... 17
2.3.1 Product Structure ..................................................................................................................................................... 17
2.3.2 Power Module .......................................................................................................................................................... 20
2.3.3 Bypass Module ........................................................................................................................................................ 22
2.3.4 Control Module ........................................................................................................................................................ 23
2.3.4.1 Overview .............................................................................................................................................................. 23
2.3.4.2 ECM...................................................................................................................................................................... 23
2.3.4.3 Dry Contact Card .................................................................................................................................................. 25
2.3.4.4 Monitoring Interface Card .................................................................................................................................... 26
2.3.5 MDU ........................................................................................................................................................................ 31
2.4 02311FTE-002 and 02311FTC-001 Automatic Transfer Switch (ATS)...................................................................... 33
2.4.1 ATS Appearance....................................................................................................................................................... 33
2.4.2 ATS Controller ......................................................................................................................................................... 35
2.4.3 ATS (8D) Operation Description ............................................................................................................................. 39

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. iv


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) Contents

2.5 02311FTE-004 and 02311FTC-004 Automatic Transfer Switch (ATS)...................................................................... 45


2.5.1 ATS Monitoring Module .......................................................................................................................................... 45
2.5.2 ATS III Segment Manual Operation Description ..................................................................................................... 46
2.6 Optional Components ................................................................................................................................................. 48

3 Installation.................................................................................................................................... 49
3.1 Installation Preparations ............................................................................................................................................. 49
3.1.1 Tools and Instruments .............................................................................................................................................. 49
3.1.2 Site ........................................................................................................................................................................... 51
3.1.2.1 UPS Weight and Dimensions ................................................................................................................................ 51
3.1.2.2 Installation Environment ....................................................................................................................................... 53
3.1.2.3 Installation Clearances .......................................................................................................................................... 53
3.1.3 Preparing Power Cables ........................................................................................................................................... 53
3.1.4 Unpacking and Checking ......................................................................................................................................... 56
3.2 Installing a Single UPS ............................................................................................................................................... 59
3.2.1 Installing the Cabinet ............................................................................................................................................... 59
3.2.2 Installing a Tail Frame ............................................................................................................................................. 63
3.2.3 Installing Batteries ................................................................................................................................................... 69
3.2.4 Routing Cables......................................................................................................................................................... 70
3.2.5 Connecting a Ground Cable ..................................................................................................................................... 73
3.2.6 Connecting AC Input Power Cables ........................................................................................................................ 74
3.2.7 Connecting AC Output Power Cables ...................................................................................................................... 76
3.2.8 Connecting Battery Cables ...................................................................................................................................... 78
3.2.9 Connecting Signal Cables ........................................................................................................................................ 79
3.2.9.1 Connecting a Remote EPO Switch ....................................................................................................................... 79
3.2.9.2 Connecting Communications Cables .................................................................................................................... 80
3.2.9.3 Connecting Fire Protection and Generator Start/Stop Cables (ATS Input Cabinet) .............................................. 81
3.3 (Optional) Combining Cabinets .................................................................................................................................. 82
3.4 Installing a Double-Bus (2N) System ......................................................................................................................... 84
3.4.1 Connecting Power Cables ........................................................................................................................................ 84
3.4.2 Connecting Signal Cables ........................................................................................................................................ 86
3.5 Installation Verification............................................................................................................................................... 86

4 User Interface ............................................................................................................................... 89


4.1 LCD Interface ............................................................................................................................................................. 89
4.1.1 LCD Menu ............................................................................................................................................................... 89
4.1.1.1 Menu Hierarchy .................................................................................................................................................... 89
4.1.1.2 Initial Startup ........................................................................................................................................................ 89
4.1.1.3 Main Menu............................................................................................................................................................ 90
4.1.2 System Info Screen .................................................................................................................................................. 92
4.1.2.1 Module Data Screen.............................................................................................................................................. 92
4.1.2.2 Runn. Info. Screen ................................................................................................................................................ 92
4.1.2.3 Alarms Screen ..................................................................................................................................................... 101

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. v


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) Contents

4.1.2.4 Settings Screen.................................................................................................................................................... 103


4.1.2.5 Maintenance Screen ............................................................................................................................................ 130
4.1.2.6 About Screen ....................................................................................................................................................... 135
4.1.3 System Status Screen ............................................................................................................................................. 136
4.1.4 Common Functions Screen .................................................................................................................................... 136
4.2 WebUI ....................................................................................................................................................................... 137
4.2.1 Login ...................................................................................................................................................................... 137
4.2.2 Monitoring Page .................................................................................................................................................... 140
4.2.2.1 Active Alarms Page ............................................................................................................................................. 141
4.2.2.2 Real-time Data Page ........................................................................................................................................... 142
4.2.2.3 Param. Settings Page........................................................................................................................................... 142
4.2.2.4 Comm. Config. Page ........................................................................................................................................... 143
4.2.2.5 Control Page ....................................................................................................................................................... 143
4.2.3 Query Page ............................................................................................................................................................ 144
4.2.3.1 Historical Alarms Page ....................................................................................................................................... 144
4.2.3.2 Logs Page ........................................................................................................................................................... 144
4.2.4 Config. Page .......................................................................................................................................................... 145
4.2.4.1 User Management ............................................................................................................................................... 145
4.2.4.2 Site Config. page ................................................................................................................................................ 145
4.2.5 Maint. Page ............................................................................................................................................................ 147

5 Operations .................................................................................................................................. 149


5.1 Commissioning the ATS Before Powering On the 02311FTE-002 and 02311FTC-001 Systems ............................ 149
5.1.1 Check before commissioning ................................................................................................................................. 149
5.1.2 ATS Commissioning .............................................................................................................................................. 149
5.2 Powering On and Starting the UPS ........................................................................................................................... 152
5.2.1 Powering On the UPS ............................................................................................................................................ 152
5.2.2 Starting the Inverter ............................................................................................................................................... 152
5.2.2.1 Initial Startup ...................................................................................................................................................... 153
5.2.2.2 Non-initial Startup .............................................................................................................................................. 161
5.2.3 Powering On Loads ............................................................................................................................................... 163
5.3 (Optional) Setting BSC Mode................................................................................................................................... 165
5.4 Shutting Down and Powering Off the UPS .............................................................................................................. 167
5.5 Starting the UPS in Battery Mode ............................................................................................................................ 170
5.6 Transferring to Bypass Mode .................................................................................................................................... 170
5.7 Setting ECO Mode .................................................................................................................................................... 171
5.8 Testing Batteries ....................................................................................................................................................... 173
5.8.1 Forced Equalized Charging Test ............................................................................................................................ 173
5.8.2 Shallow Discharge Test .......................................................................................................................................... 173
5.8.3 Capacity Test.......................................................................................................................................................... 175
5.8.4 Test Data Download ............................................................................................................................................... 176
5.8.4.1 Download over the LCD ..................................................................................................................................... 176

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. vi


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) Contents

5.8.4.2 Download over the WebUI ................................................................................................................................. 177


5.9 Transferring to Maintenance Bypass Mode .............................................................................................................. 177
5.10 Transferring from Maintenance Bypass Mode to Normal Mode ............................................................................ 178
5.11 Performing EPO ...................................................................................................................................................... 179
5.12 Clearing the EPO State ........................................................................................................................................... 179
5.13 Exporting Data ........................................................................................................................................................ 181
5.14 Setting Hibernation Mode ....................................................................................................................................... 182
5.14.1 Settings on the LCD ............................................................................................................................................. 182
5.14.2 WebUI .................................................................................................................................................................. 184
5.15 Setting Intelligent Power Mode .............................................................................................................................. 184
5.15.1 Settings on the LCD ............................................................................................................................................. 185
5.15.2 Settings on the WebUI ......................................................................................................................................... 189
5.15.3 ATS Scenario ....................................................................................................................................................... 192

6 Routine Maintenance ............................................................................................................... 195


6.1 UPS Maintenance ..................................................................................................................................................... 195
6.1.1 Monthly Maintenance ............................................................................................................................................ 195
6.1.2 Quarterly Maintenance .......................................................................................................................................... 196
6.1.3 Annual Maintenance .............................................................................................................................................. 196
6.2 Battery Maintenance ................................................................................................................................................. 197
6.2.1 Precautions for Battery Maintenance ..................................................................................................................... 198
6.2.2 Monthly Maintenance ............................................................................................................................................ 198
6.2.3 Quarterly Maintenance .......................................................................................................................................... 199
6.2.4 Annual Maintenance .............................................................................................................................................. 200
6.3 Power Distribution System Maintenance .................................................................................................................. 201
6.3.1 Monthly Maintenance ............................................................................................................................................ 201
6.3.2 Annual Maintenance .............................................................................................................................................. 201

7 Troubleshooting ........................................................................................................................ 203


8 Parts Replacement ..................................................................................................................... 206
8.1 Replacing a Fuse ....................................................................................................................................................... 206
8.2 Replacing an Indicator .............................................................................................................................................. 208

9 Technical Specification ............................................................................................................ 211


A Menu Hierarchy ....................................................................................................................... 215
A.1 Menus on the LCD ................................................................................................................................................... 215
A.2 Menus on the WebUI ............................................................................................................................................... 217

B PDC Silk Screen Description ................................................................................................. 221


C Alarm List .................................................................................................................................. 222
D Acronyms and Abbreviations................................................................................................ 235

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. vii


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

1 Safety Precautions

1.1 General Safety


This section describes safety precautions to consider before installing, maintaining, and
operating the UPS.

 To minimize the risk of personal injury and damage to equipment, read and follow all the
precautions in this document before performing any operation. The "DANGER",
"WARNING", "CAUTION", and "NOTICE" statements in this document are only
supplemental and do not represent all the safety instructions.
 Only trained and qualified personnel are allowed to install, operate, and maintain Huawei
equipment.

Follow the precautions and special safety instructions provided by Huawei when operating
Huawei products. Huawei will not be liable for any consequences that are caused due to
violations regarding general safety regulations and equipment design, production, and usage
safety standards.

Declaration
Huawei does not take responsibilities for the following situations:
 Operation under severe environments that are not specified in this document.
 Installation or use in environments that are not specified in related international
standards.
 Unauthorized product changes and software code modification.
 Operations not complying with the operation instructions and safety precautions in this
document.
 Damage caused by extreme natural environments.
 Damage caused by using batteries provided by Huawei for non-Huawei UPSs.
 Damage caused by using batteries not provided by Huawei.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 1


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

Power Grid Requirements


A standard UPS can connect to a three-phase, five-wire (L1, L2, L3, N, PE) TT, TN-C, TN-S,
and TN-C-S AC power distribution system (IEC60364-1).

Local Laws and Regulations


Equipment operations must comply with local laws and regulations. The safety instructions in
this document are only supplemental to local safety regulations.

Personal Requirements

Only Huawei engineers or engineers certified by Huawei are allowed to perform UPS
commissioning and maintenance. Otherwise, human injury or equipment damage may occur,
and any resulting UPS faults will be beyond warranty scope.

Personnel who plan to install or maintain Huawei equipment must receive thorough training,
understand all necessary safety precautions, and master the correct operation methods.
Trained and qualified personnel, or personnel certified or authorized by Huawei are:
 Allowed to install, operate, and maintain the equipment.
 Allowed to remove safety facilities and inspect the equipment.
 Allowed to replace or change the devices or components (including software).
 Operation personnel must report faults or errors that might cause serious safety issues to
related owners.
 This product should be installed and used according to the installation and technical,
specification requirements found in this manual. Otherwise, the product may be damaged,
and the resulting product exceptions or component damage will be beyond the warranty
scope.

Grounding Requirements
Devices to be grounded (excluding the energy storage unit) must meet the following
requirements:
 When installing a device, install the ground cable first. When removing a device, remove
the ground cable at the very end.
 Do not damage the ground conductor.
 Do not operate devices if the ground conductor is not installed. Before operating a device,
check the electrical connection of the device to ensure that it is securely grounded.

Personal Safety
 Do not operate the product, or handle cables, during thunderstorms.
 To avoid electric shocks, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 2


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

 Before operating a device, wear electrostatic discharge (ESD) clothes, ESD gloves, and
an ESD wrist strap. Remove any conductors (such as jewelry or watches) before the
operation to avoid electric shocks or burns.
 In the case of fire, leave the building or the equipment room immediately, and turn on the
fire alarm bell or make an emergency call. Never enter the building on fire in any case.
 If the cabinet provides an ESD jack, wear an ESD wrist strap and insert the ground
terminal of the ESD wrist strap into the jack.
 Ensure all switches are turned to OFF during device installation.
 Power on the UPS only after authorized engineers arrive at the site.
 If a C2 UPS is used in residential areas, additional measures must be taken to prevent
radio frequency interferences.
 If the UPS is used for life-supporting medical apparatus and facilities such as lifts where
adequate care has to be taken to ensure personal safety, discuss with the manufacturer in
advance about the applicability, settings, management, and maintenance of the UPS,
which require special considerations during design.

Device Safety
 Before operation, ensure that the device is firmly anchored to the floor or other solid
objects, such as a wall or an installation rack.
 Ensure ventilation vents are unblocked while the system is operating.
 Before powering on the device, ensure that all the screws inside it are securely tightened
and will not fall off during operation.
 After the installation, remove packing materials from the equipment area.
 Replace danger signs that have worn out or are unreadable.
 A UPS can be used to serve resistive-capacitive loads, resistive loads, and
micro-inductive loads. It is recommended that a UPS not be used for pure capacitive
loads, pure inductive loads, and half-wave rectification loads. It does not apply to energy
feedback loads.
 Do not alter the UPS internal structure or installation procedure unless consent from the
manufacturer is given.
 Never use water to clean electrical components inside or outside the UPS.
 Do not drill holes into a cabinet.

1.2 Electrical Safety


High Voltage

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 3


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

 The high voltage power supply provides power for the device operation. Direct or indirect
contact with high voltage power sources may result in fatal injury.
 Non-standard or incorrect high voltage operations may result in fire and electric shocks.
 The personnel who install the AC facility must be qualified to perform high voltage and
AC operations.
 When selecting, connecting, and routing power cables, ensure compliance with local
laws and regulations.
 When operating the AC power supply facility, ensure compliance with local laws and
regulations.
 Before connecting cables to the UPS, ensure that the input power and mains power
distribution switches and output power distribution switch are turned off.
 Use only dedicated tools during high voltage and AC operations.
 If the operation is performed in a damp environment, ensure that the device is dry. When
water is found in the rack or the rack is damp, switch off the power supply immediately.

High Leakage Current

 Ground a device before powering it on. Otherwise, personal injury or device damage may
occur.
 If a "high leakage current" tag is attached to the panel of the device, ground the protective
ground terminal on the device enclosure before connecting the AC power supply to
prevent electric shocks.
 The UPS can generate high leakage currents. Using a circuit breaker that has the leakage
current protection function is not recommended.

Power Cable

Do not install or remove power cables when the device is on. Transient contact between the
core of the power cable and the conductor may generate electric arcs or sparks, which may
cause fire or damage eyesight.
 Before moving or reconnecting the UPS, disconnect the mains and batteries, open the
output power distribution switch, and wait a period of at least 5 minutes after the UPS
completely powers off. Otherwise, electric shocks may occur.
 Before installing or removing the power cable, open the power switch.
 Before connecting a power cable, check that its label is correct.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 4


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

Fuse

If a fuse needs replacing, ensure the new fuse is of the same type and specifications so that the
system runs safely.

Backfeed Protection Dry Contact


The UPS can be configured with a backfeed protection dry contact to work with an external
automatic circuit breaker, preventing the voltage from flowing back to input terminals over
static bypass circuits. If device installation and maintenance personnel do not need to use
backfeed protection, paste labels on the external bypass input circuit breakers informing that
the circuit is connected to the UPS. Disconnect the device from the UPS before performing
operations on the circuit.

Electrostatic Discharge

Static electricity generated by human bodies may damage the electrostatic-sensitive


components on boards, for example, the large-scale integrated (LSI) circuits.
 Wear a pair of ESD gloves or a well-grounded ESD wrist strap when touching the device
or handling boards or application-specific integrated circuits (ASICs).
 When holding a board, hold its edge without touching any components, especially chips.
 Package boards with ESD packaging materials before storing or transporting them.
Figure 1-1 shows how to wear an ESD wrist strap.

Figure 1-1 Wearing an ESD wrist strap

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 5


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

Liquid Prevention
 Do not place the product under areas prone to water leakage, such as near air conditioner
vents, ventilation vents, or feeder windows of the equipment room. Ensure that there is
no condensation inside the product or equipment room. Ensure that no liquid enters the
product. Otherwise, short circuits will occur and may result in serious injury or death.
 If any liquid is detected inside the product, immediately disconnect the power supply and
contact the administrator.

1.3 Operating Environment


The UPS is used for commercial and industrial purposes only. It cannot be used as a power
supply for life support devices.
The TIER4 or TIER3 power supply architecture specified in TIA942, that is, dual power
supply routes, must be used in the power supply systems that are crucial to major economic
interests or order of public places, such as the national computing center, military command
system, emergency command center, railway signal system and control center, civil aviation
air traffic control center, airport command center, financial clearing center, and transaction
center.
The UPS operating environment must meet the requirements for the climate indicator,
mechanically active substance indicator, and chemically active substance indicator in ETSI
EN 300 019-1 class 3.6.

Do not expose the equipment or perform any operations in an environment with flammable or
explosive gas, or smoke.

Any operation on any electrical device in an environment that has flammable air can cause
extreme danger. Strictly obey the operating environmental requirements specified in related
use manuals when using or storing the device.
Do not use the UPS in the following environments:
 Environment containing flammable gases, corrosive gases, abnormal vibrations, and
impacts.
 Non-confined environment near the ocean (0–3.7 km) and indoor or semi-indoor
environment where the temperature and humidity are not controllable, such as a simple
equipment room near the ocean, citizen house, garage, corridor, direct ventilation cabinet,
house with only the roof, railway station platform, gymnasium, aquarium, and so on.

1.4 Battery Safety


This section describes precautions for operating batteries.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 6


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

Before operating batteries, carefully read the safety precautions to ensure correct battery
handling and connection is performed, and personal safety is managed.

 To ensure battery safety and efficient battery management, use the batteries delivered with
the UPS. Huawei shall not be responsible for battery damage caused by using non-Huawei
batteries for Huawei UPSs.
 Ensure lead-acid battery handling is in accordance with local regulations.
 Incorrect handling of batteries may cause hazards. When operating batteries, avoid
battery short circuits and electrolyte overflow or leakage.
 Electrolyte overflow may damage the device by corroding metal parts and circuit boards,
and ultimately damaging the circuit boards.
 Short circuits caused by incorrect operations may cause serious injuries due to high
power of batteries.
 Do not reversely connect positive and negative battery terminals.
 Use batteries of the specified type. Otherwise, the batteries may be damaged.
 Check battery connections periodically to ensure that all screws are securely tightened.
 Install or store batteries in clean, cool, and dry environments.
 Do not decompose, transform, or damage batteries. Otherwise, battery short circuit,
electrolyte leakage, and even personal injury may occur.

Preventative Measures
When installing and maintaining batteries, pay attention to the following points:
 Use dedicated insulated tools.
 Take measures to protect eyes, such as using eye protection devices.
 Avoid skin contact with electrolyte overflow. Wear rubber gloves and protective
clothing.
 When handling a battery, ensure that its electrodes always point upward. Do not tilt or
overturn batteries.
 Switch off the power supply during installation and maintenance.

Short Circuit

Battery short circuits may cause personal injury. The high transient current generated by a
short circuit may release a surge of power and cause a fire.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 7


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

To avoid battery short circuits, do not maintain batteries while they are in use.

Harmful Gas

Do not use unsealed lead-acid batteries. Lead-acid batteries emit flammable gas. Therefore,
place and secure lead-acid batteries horizontally to prevent fire or corrosion.

Store lead-acid batteries in a place with good ventilation, and take fire safety precautions.

Battery Temperature

High temperature may result in battery distortion, damage, and electrolyte overflow.
 Install or store batteries far away from fire sources and heating devices such as
transformers. Never burn batteries.
 If the battery temperature exceeds 60°C, check the battery for electrolyte overflow. If
electrolyte overflows, handle the leakage immediately.

Electrolyte Leakage

In the case of electrolyte leakage, counteract and absorb the leaking electrolyte immediately.

When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte
may harm human bodies. If the electrolyte leaks, use the following substances to counteract
and absorb the leaking electrolyte:
 Sodium bicarbonate (baking soda): NaHCO3
 Sodium carbonate (soda): Na2CO3
When using substances to counteract and absorb electrolytes, strictly follow the guidelines
provided by the battery manufacturer.
If any personnel are exposed to battery electrolyte, wash the exposed area with clean water
immediately and seek medical advice if the situation is serious.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 8


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

1.5 Mechanical Safety


Moving Sharp Objects

Wear protective gloves when moving sharp objects.

Moving Heavy Objects

 Perform operations in accordance with all instructional symbols on the device.


 Take caution to avoid injury when moving heavy objects.
 When moving or lifting a device, hold the handle or bottom of the device.
 When transporting a device using a pallet truck, the forks must be properly positioned to
ensure that the device does not topple. No excessive tilt or jolt is allowed during the
transportation, and the maximum tolerance of the tilting angle during loading and
unloading is 15°. To avoid toppling, secure the device to the pallet truck by using ropes
before moving, and assign persons to watch out the device during movement.
 Move the cabinet with caution. Any bumping or falling may damage the device.

Figure 1-2 Tilting angle of a cabinet

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 9


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 1 Safety Precautions

Handling Fans
Do not insert fingers or boards into the operating fans until the fans are switched off, and have
stopped running.

1.6 Laying Out Cables


Binding Signal Cables

Signal cables must be bound separately from strong-current cables and high-voltage cables.

Laying Out Cables


When the temperature is low, a violent strike or vibrations may damage the cable sheathing.
To ensure cable safety, comply with the following requirements:
 Cables can be laid, or installed, only when the temperature is higher than 0°C (32°F).
Handle cables with caution, especially at lower temperatures.
 Before laying out cables that have been stored in temperatures lower than 0°C (32°F),
move the cables to an environment that is at the requisite ambient temperature. Store
them in this environment for at least 24 hours.
 Do not drop the cables directly from the vehicle.
 As the insulation layer of a cable may age, or be damaged from high temperatures,
ensure a sufficient distance between cables and the DC busbars, shunts, and fuses.
Cables prepared by the customer should be flame resistant. Cables must not be routed
behind the air exhaust vent of the cabinet. The air exhaust vent should not be blocked by
any object.
Before connecting a cable, ensure that the cable and cable label to be used meet the actual
installation requirements.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 10


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

2 Overview

2.1 Model Description


Figure 2-1 UPS model number

Table 2-1 Model number details

No. Item Description


1 Product category UPS
2 UPS family 5000
3 UPS subcategory E
4 Output capacity 50K: 50 kVA
125K: 125 kVA
5 Voltage level H: 380/400/415 V
6 Air conditioner A: air cooled
type
7 Input switch type B: MCCB
S: ATS
8 Output type B: branch power distribution
9 Configuration type S: standard configuration

This document describes the following UPS models:


 UPS5000-E-50K-HABBS

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 11


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

 UPS5000-E-50K-HASBS
 UPS5000-E-125K-HABBS
 UPS5000-E-125K-HASBS

2.2 Working Principle


 indicates an input mode.
 indicates the energy flow direction.

2.2.1 Conceptual Diagram


The UPS5000 is an online product. It uses a modular design, which facilitates maintenance
and capacity expansion. The UPS5000 uses the digital signal processing (DSP) intelligent
control technology. Its power module consists of a rectifier and inverter. The UPS5000
converts inputs into pure, high-quality sine wave outputs by using the high-frequency
switching technology.

Figure 2-2 Conceptual diagram in air cooled scenario

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 12


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

2.2.2 Working Modes


2.2.2.1 Normal Mode
In normal mode, the rectifier converts AC power into DC power, then the inverter converts
DC power into high-precision AC outputs. The conversions protect loads from interference
such as input harmonics, glitches, and voltage transients.

Figure 2-3 UPS conceptual diagram in normal mode

2.2.2.2 Bypass Mode


The UPS automatically transfers to bypass mode upon detecting power module
overtemperature, overload, or other faults that may cause the inverter to shut down. The
bypass power supply is not protected by the UPS which means it may be affected by mains
outage, and incorrect AC voltage or frequency.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 13


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-4 UPS conceptual diagram in bypass mode

2.2.2.3 Battery Mode


If the mains input is abnormal or the rectifier becomes abnormal, the UPS transfers to battery
mode. The power module obtains DC power from batteries, and the power is converted into
AC output by the inverter.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 14


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-5 UPS conceptual diagram in battery mode

2.2.2.4 Maintenance Bypass Mode


When the UPS works in maintenance bypass mode, the current flows through the
maintenance bypass instead of the power module. You can maintain the circuit inside the
cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 15


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-6 UPS conceptual diagram in maintenance bypass mode

2.2.2.5 ECO Mode


The economic control operation (ECO) mode is an economical working mode, which can be
configured on the LCD or web user interface (WebUI). In ECO mode, when the bypass input
is within the ECO voltage and frequency ranges and other ECO power supply conditions are
met, the UPS works in bypass mode and the inverter is in standby state. When the bypass
voltage is outside the ECO voltage range, the UPS transfers from bypass mode to normal
mode. In bypass mode or normal mode, the rectifier keeps working and charges batteries
using a charger. The ECO mode delivers a high efficiency.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 16


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-7 UPS conceptual diagram in ECO mode

Manual startup is required to ensure that the inverter is in standby state and the power flow has reached
the inverter.

2.3 Product Introduction


2.3.1 Product Structure

 The appearance of the UPS5000-E-125K-HABBS (02311FTD-002) is similar to that of the


UPS5000-E-50K-HABBS (02311FTB-001).
 The appearance of the UPS5000-E-125K-HASBS (02311FTE-002) is similar to that of the
UPS5000-E-50K-HASBS (02311FTC-001).
 The appearance of the UPS5000-E-125K-HASBS (02311FTE-004) is similar to that of the
UPS5000-E-50K-HASBS (02311FTC-004).

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 17


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-8 UPS5000-E-50K-HABBS (02311FTB-001) front view

(1) Power input status indicator (2) Input circuit (3) Lighting circuit
breaker breaker
(4) Air conditioner power distribution (5) IT load circuit (6) UPS input circuit
circuit breaker breaker breaker
(7) UPS maintenance bypass circuit (8) Control module (9) Bypass module
breaker
(10) Filler panel (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution monitoring (14) UPS output
board circuit breaker

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 18


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-9 UPS5000-E-125K-HASBS (02311FTE-002) front view

(1) Power input status (2) ATS (3) Lighting circuit


indicator breaker
(4) ATS handle installation (5) Air conditioner power (6) IT load circuit
slot distribution circuit breaker breaker
(7) UPS input circuit (8) UPS maintenance bypass (9) Control module
breaker circuit breaker
(10) Bypass module (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution (14) UPS output circuit breaker
monitoring board

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 19


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-10 UPS5000-E-125K-HASBS (02311FTE-004) front view

(1) Power input (2) ATS drive module (3) ATS monitoring module
status indicator
(4) Lighting circuit (5) Air conditioner power (6) IT load circuit breaker
breaker distribution circuit breaker
(7) UPS input circuit (8) UPS maintenance bypass circuit (9) Control module
breaker breaker
(10) Bypass module (11) Power module (12) ATS transfer switch
(13) ATS handle (14) Monitor display unit (MDU) (15) Power distribution
monitoring board
(16) UPS output
circuit breaker

2.3.2 Power Module


Appearance
Figure 2-11 shows a power module.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 20


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-11 Power module

(1) Positioning lock (2) Run indicator (3) Alarm indicator (4) Fault indicator
(5) Ready switch (6) Output port (7) Input port

Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.

Specifications
 Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
 Weight: < 21 kg
 Rated output capacity: 25 kVA/25 kW
 Power density: 17.2 W/inch3

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 21


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

2.3.3 Bypass Module


Appearance

Figure 2-12 Bypass module

(1) Positioning (2) Battery cold start (3) Run (4) Alarm indicator
lock button indicator
(5) Fault indicator (6) Ready switch (7) Signal port (8) Input and output
ports

Functions
The UPS is set to ECO mode and the bypass voltage is within the specified range.
The power module is overloaded for a period longer than the maximum allowed period.
Both the active and standby ECMs are abnormal.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 22


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

The system fails to run properly and transfers to bypass mode.


A manual operation is performed to transfer to bypass mode.

Specifications
 Dimensions (H x W x D): 130 mm x 442 mm x 500 mm
 Weight < 25 kg
 Maximum output power: 125 kW

2.3.4 Control Module


2.3.4.1 Overview
In a standard configuration, the control module consists of two ECMs, one dry contact card,
and one monitoring interface card (from left to right). The four cards are hot swappable. One
subrack is reserved above the dry contact card. A backfeed protection card or dry contact
extended card can be inserted into this subrack.

Figure 2-13 Signal panel on the control module

(1) Ground terminal (2) Parallel port 1 (3) BSC port (4) Ready switch
1 on ECM 1
(5) Indicators for ECM 1 (6) Parallel port 2 (7) BSC port (8) Ready switch
2 on ECM 2
(9) Indicators for ECM 2 (10) Dry contact card (11) Dry (12) MDU port
contacts
(13) RS485 port (14) Fast Ethernet (FE) (15) COM2 (16) COM1 port
port port
(17) Battery temperature (18) Optional card
sensor port subrack cover

Ports are protected by a security mechanism.

2.3.4.2 ECM
The control module consists of two ECMs that work in active/standby mode. Each card
provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the
lower part.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 23


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-14 ECM

Table 2-2 Ports on the ECM

Silk Screen Description


PARALLEL The PARALLEL port transmits parallel signals.
BSC The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,
ensuring that two buses can switch with each other.
BSC cables are hot-swappable.

Table 2-3 Indicator description

Indicator Color Status Description

NORMAL Green Steady on This ECM is the active ECM.


Blinking at 0.5 This ECM is the standby ECM and it is
Hz ready.
Off This ECM is not ready or the CPLD of
this ECM is being upgraded.
Blinking at 4 Hz The DSP of the ECM is being upgraded or
not configured.
ALM Yellow Steady on The ECM has a minor alarm, but it does
not need to be replaced.
Off The ECM has no minor alarm or the DSP
of the ECM is being upgraded.
FAULT Red Steady on The ECM has a critical alarm.
Off The ECM has no critical alarm or the DSP
of the ECM is being upgraded.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 24


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

2.3.4.3 Dry Contact Card


The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).

Figure 2-15 Dry contact card

Table 2-4 Ports on the dry contact card

Silk Screen Description Status Initial Status


BTG Port for detecting  Connected: battery Disconnected
battery grounding faults grounding fault
 Disconnected: no
0V Port for signal ground
battery grounding
fault
GEN Port for detecting diesel  Connected: D.G. Disconnected
generator (D.G.) mode mode
 Disconnected:
0V Port for signal ground
non-D.G. mode
BCB_OL Port for detecting the  Grounded: BCB box Grounded
BCB box connected
 Disconnected: BCB
box not connected
BCB_STA Port for monitoring the  Connected: battery Disconnected
battery switch switch ON
 Disconnected: battery
switch OFF
BCB_DRV Controls battery circuit  0 V: battery switch 0V
breaker trip. When the not tripped
voltage is +12 V, the  12 V: battery switch
circuit breaker trips. tripped
BCB_0V Port for signal ground
EPO_NO Emergency power-off If the normally open Disconnected
(EPO) port (NO) port is connected to
the EPO_12V port, EPO
EPO_12V +12 V is triggered.
EPO_NC EPO port If the normally closed Connected

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 25


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Silk Screen Description Status Initial Status


EPO_12V +12 V (NC) port is disconnected
from the EPO_12V port,
EPO is triggered.
SWITCH Port for monitoring the  Connected: circuit Connected
STATUS_OUT UPS output circuit breaker ON
breaker  Disconnected: circuit
SWITCH Port for signal ground breaker OFF
STATUS_0V
SWITCH Port for monitoring the  Disconnected: circuit Disconnected
STATUS_MT maintenance circuit breaker ON
breaker  Connected: circuit
SWITCH Port for signal ground breaker OFF
STATUS_0V
SWITCH Port for monitoring the  Connected: circuit Connected
STATUS_BP bypass input circuit breaker ON
breaker  Disconnected: circuit
SWITCH Port for signal ground breaker OFF
STATUS_0V
SPD Port for monitoring the  Connected: SPD Connected
input AC surge enabled
protective device (SPD)  Disconnected: SPD
0V Port for signal ground disabled

 The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
 Set the EPO port to NO or NC as required.
 When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
 Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm2 to 1.5 mm2.

2.3.4.4 Monitoring Interface Card

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 26


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

 The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected and MDU communication fails. Conversely, if
the FE port is mistaken for the RS485 port during cable connection, RS485
communication fails.
 If MDU communication fails, the "Comm. failure" message is displayed on the LCD,
screen switching is disabled, the buzzer buzzes, and the fault indicator is red. Once the
fault is rectified, the LCD recovers, and the alarm is cleared.
 Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
 In a parallel system, ensure that used dry contacts properly connect to each UPS.

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.

Figure 2-16 Monitoring interface card

The maximum voltage and current of ports DO_1 to DO_4 are 30 V DC, 1 A or 60 V DC, 0.5 A
respectively.

Table 2-5 Ports on the monitoring interface card

Port Silk Screen Description

DO_1 NO DO_1 is used to output alarms and indicates critical


alarms by default. It can be set to indicate minor
COM alarms, bypass mode, battery mode, or low battery
voltage.
DO_2 NO DO_2 is used to output alarms and indicates minor
alarms by default. It can be set to indicate critical
COM alarms, bypass mode, battery mode, or low battery
voltage

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 27


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Port Silk Screen Description


DO_3 NO DO_3 is used to output alarms and indicates bypass
mode by default. It can be set to indicate critical
COM alarms, minor alarms, battery mode, or low battery
voltage.
DO_4 NO DO_4 is used to output alarms and indicates battery
mode by default. It can be set to indicate critical
COM alarms, minor alarms, bypass mode, or low battery
voltage.
DB26 MDU Provides FE, RS485, I2C, and CAN signals.
Battery B_TEMP Connects to an indoor battery temperature sensor.
temperature sensor
port
Southbound COM1 Connects to an ambient temperature and humidity
communications sensor over two wires.
port 1
Southbound COM2 Connects to a southbound device.
communications
port 2
Network port FE Connects to the network port on a PC.
Northbound RS485 Connects to a northbound network management
communications device or a third-party network management device
port over two wires.

 Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm2.
 RS485 cables and FE cables must be shielded cables.

Figure 2-17 and Figure 2-18 are recommended wiring methods for DO ports.

Figure 2-17 Wiring method 1

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 28


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-18 Wiring method 2

Figure 2-19 and Table 2-6 describe the COM1 pin definitions.

Figure 2-19 COM1 pins

Table 2-6 COM1 pin definition

Pin Description
1 GND
2 N/A
3 RS485-
4 RS485+
5 N/A
6 12V_PORT

Figure 2-20 and Table 2-7 describe the COM2 pin definitions.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 29


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-20 COM2 pins

Table 2-7 COM2 pin definition


Pin Description

1 RS485+
2 RS485-
3 N/A
4 RS485+
5 RS485-
6 GND
7 CANH0
8 CANL0

Figure 2-21 and Table 2-8 describe the RS485 pin definitions.

Figure 2-21 RS485 pins

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 30


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Table 2-8 RS485 pin definition

Pin Description
1 RS485_T+
2 RS485_T–
3 N/A
4 RS485_R+
5 RS485_R–
6 GND
7 N/A
8 N/A

If cables are prepared onsite, follow the three methods below:


 Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
 Connect pin 4 and pin 5. Pin 4 connects to RS485+ and pin 5 connects to RS485–.
 Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to
RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–.

2.3.5 MDU
Appearance

Figure 2-22 MDU

(1) Status indicator (2) LCD touchscreen

Touch the LCD screen firmly because it is an industrial resistive touchscreen. It is recommended that
you use your fingernails for accurate selection and quick response.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 31


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-23 Touching the LCD

Table 2-9 Status indicator

Status Color Meaning


On Red A critical alarm has been generated, and the buzzer sounds
continuously.
Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Hz.
Green The UPS is running properly or a warning has been generated.
Off N/A The MDU is powered off.

The indicator on the LCD panel is yellow when the bypass supplies power in non-ECO mode.

The ports of the LCD screen are located at the side of the LCD screen.

Figure 2-24 LCD screen ports

Table 2-10 Description of LCD screen ports

No. Port Name Description


1 MUS05A (DB26) Connects to the MDU and monitoring interface card

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 32


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

No. Port Name Description


2 FE Network port for connecting to the web service and for
SNMP networking
3 CAN Reserved
4 RS485_1 Reserved
5 USB Host Connects to a USB flash drive, used for upgrading the LCD
online and upgrading configurations
6 RST Restart switch for the MDU
7 SD Reserved
8 DIP switch Implements specific functions by using the DIP switch and
specific buttons; controls the CAN communication build-out
resistor in a parallel system

Functions
The monitor display unit (MDU) allows for general UPS operations, parameter setting,
viewing of running status and alarms, and so on.

Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm

2.4 02311FTE-002 and 02311FTC-001 Automatic Transfer


Switch (ATS)
2.4.1 ATS Appearance
Figure 2-25 shows an ABB AC transfer switch (ATS). Be familiar with and configure the ATS
before powering on the system. For details about the ATS, see the ATS instructions delivered
with the product.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 33


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-25 ATS

(1) Controller (2) Electric/Manual mode (3) Electric operating


selection handle mechanism
(4) Handle locking latch (5) Manual handle (6) Handle buckle
(7) Position for auxiliary (8) Transfer switch (9) Operating mechanism
contacts
(10) Alarm ID description

 ATS controller
The ATS logic control unit monitors the ATS in real time and configures the ATS system
parameters.
 Electric/Manual mode selection handle
If you flip the electric/manual mode selection handle upwards to the M position, it is
electric mode. If you flip the handle downwards to the Man. position, it is manual mode.

Before you power on the UPS, check that the handle is in the M position.
 ATS handle slot
Before you insert the handle into the ATS handle slot, flip the electric/manual mode
selection handle to the Man. position. After you insert the handle, the ATS controller
starts manual mode.
 Handle locking latch
When the ATS changes from manual mode to electric mode, pull out the ATS handle.
Before you pull out the handle, turn the handle locking latch downwards.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 34


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

After you pull out the handle, flip the electric/manual mode selection handle upwards to
the M position.

2.4.2 ATS Controller


Figure 2-26 shows an ATS controller.

Figure 2-26 ATS controller

(1) Alarm ID description (2) Controller buttons (3) ATS status indicator

Table 2-11 describes the alarm IDs of the ATS controller in detail.

Table 2-11 Alarm ID description

Alarm ID Power Supply Description


Status
1 No voltage The supply voltage is less than 10% of the rated voltage.
2 Undervoltage The supply voltage is less than the undervoltage
threshold.
3 Overvoltage The supply voltage is greater than the overvoltage
threshold.
4 Phase missing A phase of the power supply is open.
5 Voltage The difference between the minimum and maximum
unbalance phase voltages of the power supply exceeds the
percentage of the overvoltage or undervoltage threshold.
6 Incorrect phase The phase sequence of the power supply is incorrect.
sequence

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 35


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Alarm ID Power Supply Description


Status

7 Invalid The supply frequency exceeds the threshold.


frequency

Table 2-12 describes the buttons on the ATS controller.

Table 2-12 Buttons on the ATS controller

Button Name Description

I ON In button control mode, if the ATS is flipped to I, the I switch is


on, and the II switch is off.

II ON In button control mode, if the ATS is flipped to II, the II switch


is on, and the I switch is off.

OFF In button control mode, if the ATS is flipped to OFF, both the I
and II switches are off, and the ATS works in manual mode.

AUTO Sets the ATS controller to the automatic or button control mode
and clears alarms.

ESC Return to the previous step.

Enter Confirm settings.

Up Scroll upwards or go to the previous page.

Down Scroll downwards or go to the next page.

Table 2-13 describes the indicators on the ATS controller.

Table 2-13 Indicators on the ATS controller

Indicator Name Description

Alarm Alarm indicator  On: The ATS generates an alarm, logic switching
fails, switches I and II are ON at the same time, or
the handle is inserted.
 Blinking: The switch logic generates an alarm.
 Off: No alarm is generated.
The alarm status can be cleared using the AUTO
button.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 36


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Indicator Name Description


Auto Control indicator  On: The ATS is in automatic control mode.
 Blinking: The ATS is being tested.
 Off: The ATS is in button control mode.
Power Run indicator  On: The ATS is powered on.
 Blinking: The ATS is in standby mode.
 Off: The ATS is powered off. The controller is in
standby state for at least 1 minute.
Tx/Rx Communication On: The ATS controller is sending data.
indicator

The home screen of the 8D controller displays status for the LN1 and LN2 power supplies,
electric generator, delay, and LLVD.
 Figure 2-27 shows the power status of LN1 and LN2. Table 2-11 describes the power
status alarms.
 Figure 2-28 shows the generator status.
 Figure 2-29 shows the delay status.
 Figure 2-30 shows the LLVD status.

Figure 2-27 Status of the LN1 and LN2 power supplies

(1) LN1 power status (2) LN2 power status


(3) LN1 power alarm ID (4) LN2 power alarm ID

If LN1 and LN2 power indicators are hollow, there is an alarm. Locate the fault based on the alarm ID
and Table 2-11 or the alarm ID description on the 8D controller, and rectify the fault.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 37


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-28 Generator status

 If the screen displays the letter G, the mains-generator mode is in use. If the screen does not display
the letter G, the mains-mains mode is in use.
 If the letter G and an upward arrow are displayed, the generator is working.
 If the letter G and a downward arrow are displayed, the generator is idle.
 If the letter G blinks, an alarm has been generated for the generator.

Figure 2-29 Delay status

(1) Delay name (2) Remaining time


(3) Local control mode (4) Remote control mode

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 38


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-30 LLVD status

(1) OFF (2) ON

Note that the LLVD status (ON/OFF) in the menu is consistent with the input data. For
example: If the input data (DI 11 by default) is active, the LLVD is on. If the input data is
invalid, the LLVD is off.

2.4.3 ATS (8D) Operation Description


The ATS (8D) supports three operation modes, including manual mode, automatic mode, and
button mode. This section describes the operation modes in detail.

 Do not open any cover of the ATS. Even if the power supply is disconnected, hazardous
external control voltage may still exist inside the product.
 Do not adjust the control cable when the ATS or external control cable is electrified.

 Before powering on the ATS, operate the handle to switch on and off the ATS for one to three times.
Ensure that the primary and secondary contacts of the ATS work smoothly.
 Verify that the phase sequences of the two power inputs to the ATS are correct using a phase
sequence table.

Automatic Mode
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Press down the locking latch on the switch panel and pull out the handle.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 39


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-31 Pulling out the handle

If the handle is not pulled out, the automatic mode will be disabled.

Step 4 Flip the Motor/Manual selection lever to the Motor position.

Figure 2-32 Flipping the Motor/Manual selection lever

Step 5 Check whether the Power LED and Auto LED indicators are on, as shown by (1) in Figure
2-33. If the Auto LED indicator is on, the controller is in the automatic operation mode.
Step 6 If the Auto LED indicator is off, press the Auto button once. Then the controller enters the
automatic operation mode, as shown in Figure 2-33.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 40


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-33 Automatic mode

----End

Manual Mode
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Flip the Motor/Manual selection lever to the Man. position.

Figure 2-34 Flipping the Motor/Manual selection lever

Step 4 Insert the handle into the switch panel.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 41


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-35 Inserting the handle

The automatic operation will be disabled after the handle is inserted into the switch panel.

Step 5 The Alarm LED and Power LED indicators go on at the same time when the handle is
inserted.

Figure 2-36 Alarm

After the handle is inserted, the controller automatically switches to the button operation mode. After the
handle is removed, the controller remains in the button operation mode, and the Alarm LED indicator
goes out.

Step 6 Turn the handle to a desired position (I, O, or II).


----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 42


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Button Mode
When the controller is working in the button mode, a user can control the ATS switch using
the I, O, and II buttons on the controller panel. In the button mode, the OMD800 controller
can control the generator.

Do not simultaneously press and hold down any two of the I, II, and O buttons on the
controller panel. Ensure that the interval between two commands is 5s at least. If another
command is issued before the previous one is executed, the protection fuse (F1) under the
motor operation mechanism may be blown.

Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Press down the locking latch on the switch panel and pull out the handle.

Figure 2-37 Pulling out the handle

If the handle is not pulled out, the automatic mode will be disabled.

Step 4 Flip the Motor/Manual selection lever to the Motor position.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 43


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-38 Flipping the Motor/Manual selection lever

Step 5 Check whether the Power LED indicator is on, as shown by (1) in Figure 2-39.
Step 6 Check whether the Auto LED indicator is on.
 If the Auto LED indicator is off, the controller is working in the button mode, as shown
by (3) in Figure 2-39.
 If the Auto LED indicator is on, press the Auto button once. Then the Auto LED
indicator turns off, and the controller enters the button mode, as shown by (2) in Figure
2-39.

Figure 2-39 Button mode

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 44


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

2.5 02311FTE-004 and 02311FTC-004 Automatic Transfer


Switch (ATS)
2.5.1 ATS Monitoring Module
Figure 2-40 ATS monitoring module

Table 2-14 Indicators on the ATS monitoring module

No. Indicator Name Description


1 RUN ATS operating  Steady green: indicates that the ATS is
status indicator operating properly.
 Steady yellow: indicates a warning and minor
alarm.
 Steady red: indicates a critical or major alarm.
2 AUTO ATS working  Steady green: indicates that the ATS works in
mode indicator automatic mode.
 Steady red: indicates that the ATS is in manual
mode and non-firefighting power
disconnection.
3 I I power status  Steady green: indicates that the power supply is
indicator normal.
 Steady red: indicates that the power supply is
abnormal.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 45


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

No. Indicator Name Description


4 NA I power switch  Steady green: indicates that the I power supply
status indicator is switched on.
 Off: indicates that the I power supply is
switched off.
 Steady red: indicates that the I power supply is
abnormally switched on.
5 NA II power switch  Steady green: indicates that the II power supply
status indicator is switched on.
 Off: indicates that the II power supply is
switched off.
 Steady red: indicates that the II power supply is
abnormally switched on.
6 II II power status  Steady green: indicates that the power supply is
indicator normal.
 Steady red: indicates that the power supply is
abnormal.

2.5.2 ATS III Segment Manual Operation Description

 Do not open any cover of the ATS. Even if the power supply is disconnected, hazardous
external control voltage may still exist inside the product.
 Do not adjust the control cable when the ATS or external control cable is electrified.
 Manual operations are forbidden in automatic.
 If you need to switch to the other power supply, turn the switch to both the O (OFF)
position first.

 Before powering on the ATS, operate the handle to switch on and off the ATS for one to three times.
Ensure that the primary and secondary contacts of the ATS work smoothly.
 Verify that the phase sequences of the two power inputs to the ATS are correct using a phase
sequence table.

Both O (OFF) operation


Step 1 Check whether the ATS monitoring module has alarms. If an alarm exists, rectify the fault
first.
Step 2 Insert the handle into the switch panel. Turn the handle gently counterclockwise in the
direction of the arrow until both the I and II signs indicate O (OFF).

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 46


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

Figure 2-41 Inserting and rotating the handle

Step 3 Place the handle back to the original position.


----End

I power supply I (ON) operation


Step 1 Check whether the ATS monitoring module has alarms. If an alarm exists, rectify the fault
first.
Step 2 Insert the handle into the switch panel. Turn the handle clockwise in the direction of the arrow
until the I sign indicates I (ON).

Figure 2-42 Inserting and rotating the handle

Step 3 Place the handle back to the original position.


----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 47


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 2 Overview

II power supply II (ON) operation


Step 1 Check whether the ATS monitoring module has alarms. If an alarm exists, rectify the fault
first.
Step 2 Insert the handle into the switch panel. Press and hold red power button and turn the handle
clockwise in the direction of the arrow until the II sign indicates II (ON).

Figure 2-43 Inserting and rotating the handle

Step 3 Place the handle back to the original position.


----End

2.6 Optional Components


Table 2-15 Optional components

Component Model Function

BSC 5m/10m/15m/60m Transmits bus synchronization signals in a


dual-bus system.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 48


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

3 Installation

3.1 Installation Preparations


3.1.1 Tools and Instruments

Insulate installation tools to prevent electric shocks.

Prepare the following tools and meters indicated in Table 3-1 for installation.

Table 3-1 Tools and meters

Tools and Meters


Electric pallet truck Manual pallet truck Ladder Rubber mallet

Hammer drill and Hand-held electric Alloy hole saw Heat gun
drill bit Φ16 drill

Diagonal pliers Crimping tools Wire stripper Electric hydraulic


pliers

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 49


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Tools and Meters

Clamp meter Multimeter Cable tie Level instrument

Polyvinyl chloride Cotton cloth Label Electrician's knife


(PVC) insulation
tape

Electrostatic Protective gloves Insulated gloves Insulation protective


discharge (ESD) shoes
gloves

Torque screwdriver Cable cutter Brush Flat-head


screwdriver
(2–5 mm)

Phillips screwdriver Insulated torque Heat shrink tubing Insulated adjustable


(M3/M4/M5/M6/M wrench wrench
8) (M6/M8/M12/M16)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 50


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Table 3-1 lists only the common tools for installation and cable connection. For more dedicated tools
required, see the corresponding component manuals. Prepare tools based on site requirements.

3.1.2 Site
3.1.2.1 UPS Weight and Dimensions

Table 3-2 Weight

Model Number of Number of Weight


Modules Redundant
Modules

UPS5000-E-50K-HABBS 2 0 352 kg
UPS5000-E-50K-HASBS 3 1 390 kg
UPS5000-E-125K-HABBS 5 0 435 kg
UPS5000-E-125K-HASBS 6 1 453 kg

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 51


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-1 Dimensions (unit: mm)

(1) Front door (2) Foot (3) Caster (4) Bottom plate
(5) Rear door (6) Base mounting hole (7) Side post (8) Beam

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 52


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

3.1.2.2 Installation Environment


 Do not install the UPS in high temperature, low temperature, or damp environments.
 Install the UPS away from water sources, heat sources, and flammable or explosive
materials. Keep the UPS away from direct sunlight, dust, volatile gases, corrosive
materials, and air dense with salt particles.
 Do not install the UPS in environments with conductive metal scraps in the air.
 The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA
batteries) are 20–30°C. Operating temperatures higher than 30°C shorten the battery
lifespan and operating temperatures lower than 20°C reduce the battery backup time.

3.1.2.3 Installation Clearances


Reserve sufficient space around the cabinet for operation and ventilation:
 Reserve a clearance of at least 800 mm from the front of the cabinet.
 Reserve a clearance of at least 800 mm from the rear of the cabinet.
 Reserve a clearance of at least 500 mm from the top of the cabinet.

Figure 3-2 Reserved clearances (unit: mm)

3.1.3 Preparing Power Cables

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 53


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

The UPS can generate large leakage currents. A circuit breaker equipped with an RCD is not
recommended.

Table 3-3 Recommended cross-sectional areas for power cables

Item UPS5000-E- UPS5000-E- UPS5000-E-50K UPS5000-E-50K


125K (ATS) 125K (ATS) (MCCB)
(MCCB)

Input I Input I current (A) 385 385 184 184


Recommended circuit Three-pole, Three-pole, Three-pole, 250 Three-pole, 250
breaker 400 A 400 A A A
Recommended L1 4 x 185 4 x 185 4 x 95 4 x 95
cross-sectional
area (mm2) L2
L3
N
PE 95 95 50 50
Input II Input II current (A) 385 N/A 184 N/A
Recommended circuit Three-pole, N/A Three-pole, 250 N/A
breaker 400 A A
Recommended L1 4 x 185 N/A 4 x 95 N/A
cross-sectional
area (mm2) L2
L3
N
PE 95 50
Battery Maximum discharge 411 411 164 164
current (A)
Recommended + 2 x 95 2 x 95 95 95
cross-sectional
area (mm2) N 2 x 95 2 x 95 95 95
- 2 x 95 2 x 95 95 95
PE 95 95 50 50

Table 3-4 Recommended cross-sectional areas for output cables

Item Cable Specifications

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 54


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Item Cable Specifications


Air conditioner (40 A) L1 5x6
Recommended L2
cross-sectional area (mm2)
L3
N
PE
Air conditioner (63 A) L1 5 x 10
Recommended L2
cross-sectional area (mm2)
L3
N
PE
Lighting system L 3 x 2.5
Recommended N
cross-sectional area (mm2)
PE
IT load (40 A) L 3x6
Recommended N
cross-sectional area (mm2)
PE
IT load (63 A) L 3 x 10
Recommended N
cross-sectional area (mm2)
PE

When selecting, connecting, and routing power cables, follow local safety regulations and rules.
When the external conditions such as cable layout or ambient temperatures change, perform verification
in accordance with the IEC-60364-5-52 or the local regulations.
The currents listed in the table "Recommended cross-sectional areas for power cables" are measured at a
rated voltage of 380 V; if the rated voltage is 400 V, multiply the currents by 0.95; if the rated voltage is
415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the neutral wires
1.5–1.7 times.
The recommended cables are applicable only when the following requirements are met:
 The cables are routed over a ladder or bracket in a single layer (E or F in IEC60364-5-523).
 The ambient temperature is 30°C.
 The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
 Single- or multi-core 90°C soft power cables with copper conductors are used.
 It is recommended that AC power cables be no longer than 30 m and DC power cables be no longer
than 40 m.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 55


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Table 3-5 Power cable terminal requirements

Port Connection Bolt Bolt Hole Bolt Torque


Description Mode Specifications Diameter Length

AC input Crimped M12 13.5 mm 45 mm 46 N·m


OT/DT
terminals
Battery input Crimped M10 Rivet threaded hole 30 mm 26 N·m
OT/DT diameter
terminals
PE Crimped M12 Rivet threaded hole 45 mm 46 N·m
OT/DT diameter
terminals
Safe grounding Crimped M6 Rivet threaded hole 16 mm 4.5 N·m
OT/DT diameter
terminals

3.1.4 Unpacking and Checking


Context

 Only trained personnel are allowed to move the UPS. Use a pallet truck to transport the
UPS box secured to a wooden support to the installation position.
 Visually inspect the UPS appearance for shipping damage. If it is damaged, notify the
carrier immediately.
 To prevent the UPS from falling over, secure it to a pallet truck using ropes before moving
it.
 To prevent shocks or falls, move the UPS gently. After placing the UPS in the installation
position, unpack it and take care to prevent scratches. Keep the UPS steady during
unpacking.
 Check that the fittings comply with the packing list. If some fittings are missing or do not
comply with the packing list, record the information and contact your local Huawei office
immediately.
 If the UPS installation environment is in poor condition and the UPS will be stored for a
long time after it is unpacked, wrap the UPS with the original plastic coat to prevent dust.

Procedure
Step 1 Use a pallet truck to transport the UPS to the installation position.
Step 2 Remove the UPS outer packing.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 56


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Step 3 After verifying that the UPS is intact, remove the L-shaped brackets securing the cabinet and
the pallet.

Figure 3-3 Removing the L-shaped bracket

Step 4 Insert the two sliding plates under the pallet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 57


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-4 Installing the sliding plates

Step 5 Raise the four anchor bolts to the highest position using an adjustable wrench.

Figure 3-5 Raising the leveling feet

Step 6 Move the UPS over its castors near the installation position.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 58


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

----End

3.2 Installing a Single UPS


3.2.1 Installing the Cabinet
Secured Installation
Step 1 Determine the position for installing the cabinet. Mark mounting holes based on the drawings
or marking-off template.

Figure 3-6 Mounting holes (unit: mm)

Step 2 Use a hammer drill to drill holes for installing expansion bolts and then install expansion bolts
in the holes.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 59


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-7 Expansion bolt composition

(1) M12 bolt (2) Spring washer (3) Flat washer (4) Expansion sleeve

Knock the expansion bolts into the holes until the expansion tube completely fits into the hole.
The expansion sleeves must be completely buried under the ground to facilitate subsequent
installation.

Figure 3-8 Installing expansion bolts (unit: mm)

1. Drill holes in the ground by using a hammer drill. The hole depth is 52 mm to 60 mm.
2. Partially tighten the expansion bolt and vertically insert it into the hole. Knock the
expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the
hole.
3. Partially tighten the expansion bolt.
4. Remove the bolt, spring washer, and flat washer.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 60


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Step 3 Move the UPS over its castors to the installation position.
Step 4 If the castors of the UPS need to be lifted from the ground, perform steps Step 1 to Step 2 in
Non-Secured Installation.
Step 5 Open the front and rear doors.
Step 6 Insert four M12x115 expansion bolts into the expansion bolt holes in the floor, and tighten the
expansion bolts.

Figure 3-9 Tightening expansion bolts

----End

Non-Secured Installation
Step 1 Lower the four anchor bolts at the bottom of the cabinet by using a wrench until all the four
castors at the bottom hang in the air, the anchor bolts bear the whole cabinet weight.

1. Wrench an anchor bolt clockwise to elevate a cabinet, or wrench an anchor bolt


anticlockwise to lower it. The cabinet feet can be adjusted within a range of 0–8 mm.
2. To prevent cabinet tilting, adjust the four anchor bolts instead of one anchor bolt.
3. Use a measuring tape for measurement when leveling the cabinet to ensure that the height
between the cabinet top and the ground is 2000 mm + 3 mm.
4. Do not remove anchor bolts. Otherwise, you need to rework them for use.

Step 2 Check the cabinet levelness using a level. If the cabinet is not leveled, adjust the anchor bolts.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 61


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-10 Adjusting the leveling feet

----End

Installing the UPS on an ESD Floor


A support is required when the UPS is installed on an ESD floor. The support height depends
on the height between the ground and the ESD floor.
Step 1 Lift the cabinet onto the support and align the mounting holes on the cabinet with those on the
support.
Step 2 Level the UPS by adjusting the anchor bolts and using a level.

 Wrench an anchor bolt clockwise to elevate a cabinet, or wrench an anchor bolt


anticlockwise to lower it. The cabinet feet can be adjusted within a range of 0–8 mm.
 To prevent cabinet tilting, adjust the four anchor bolts instead of one anchor bolt.
 Use a measuring tape for measurement when leveling the cabinet to ensure that the height
between the cabinet top and the ground is 2000 mm + 3 mm.
 Do not remove anchor bolts. Otherwise, you need to rework them for use.

Step 3 Insert four M12 bolt assemblies into the mounting holes for the UPS and support. Partially
tighten the bolts.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 62


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-11 Leveling and fixing bolts

(1) Anchor bolt (2) Fixing bolt (3) Level

----End

3.2.2 Installing a Tail Frame


Context
A tail frame is used to increase the depth of a UPS to 1200 mm. Its BOM number is
21242025.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 63


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-12 Installed tail frame

(1) Tail frame

Procedure
Step 1 Use eight M5 tapping screws to secure the tail frame accessories to the tail frame.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 64


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-13 Securing the tail frame accessories

Step 2 Use four M5 tapping screws to secure one upper sealing plate to the tail frame.

There are two upper sealing plates, and the one used in this step has a gap.

Figure 3-14 Upper sealing plate

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 65


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-15 Securing the upper sealing plate

Step 3 Open the UPS rear door, and remove it.

When removing the cabinet rear door, remove the ground cable between the cabinet and the
rear door from the cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 66


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-16 Removing the cabinet rear door

Step 4 Remove the hinges and connecting kits from the UPS rear door and remove the ground cable.

Put aside the hinges and connecting kits as they are needed in follow-up installation
processes.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 67


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-17 Removing the UPS rear door mounting kit

Step 5 Move the tail frame to the cabinet rear door, and adjust the tail frame so that the tail frame top
is flush with the cabinet top.
Step 6 Secure the tail frame to the UPS using eight M5 tapping screws.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 68


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

 Align the upper and lower holes before tightening screws.


 The tail frame side with anchor bolts should face the cabinet bottom.

Figure 3-18 Securing the tail frame

Step 7 Install the hinges and connecting kits removed in Step 4 at the corresponding positions on the
tail frame.
Step 8 Install the UPS rear door on the tail frame.

After installing the UPS rear door, ensure that ground cables are properly connected to the
cabinet and UPS rear door.

----End

3.2.3 Installing Batteries


Context

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 69


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

 Before installing batteries, read through the battery safety precautions, obtain the delivered
battery installation guide, and install batteries as instructed.
 Place the batteries in a correct way to prevent vibrations and shocks.
 Install the batteries from the lower layer to the upper layer to prevent falling over due to
imbalance.

Procedure
Step 1 Install the battery cabinet and batteries.
For details, see the battery installation guide delivered along with the batteries.
----End

3.2.4 Routing Cables

 The basic rule for routing cables is: from inside out and from bottom up.
 When connecting the mains input power cable, strip the outer layer of the 5-wire cable,
wrap each wire in the stripped section using corrugated pipes, and secure the corrugated
pipes using insulation tape to prevent sliding.

Step 1 Remove five rodent-proof meshes and cable hole protection panels from the top of the
cabinet.

You can drill holes in the removed covers as required before reinstalling them on the cabinet.

Figure 3-19 Removing rodent-proof meshes

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 70


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-20 Removing cable hole protection panels

Step 2 Open the rear door, and remove the insulation panels at the rear of the cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 71


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-21 Removing insulation covers

Step 3 Route power cables.


Step 4 Route signal cables. Bind cables to the cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 72


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-22 Routing signal cables

After routing signal cables, reinstall the cable hole protection panels.

----End

3.2.5 Connecting a Ground Cable


Context

 Before connecting cables, check that all UPS input switches are OFF.
 Prepare terminals onsite. The length of the copper wire should be the same as that of the
part of the terminal that covers the conductor.

Procedure
Step 1 Connect a ground cable to the UPS cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 73


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-23 Connecting a ground cable

Step 2 Connect a ground cable to the safety ground of the UPS cabinet.

Figure 3-24 Connect a ground cable to the safety ground of the UPS cabinet

----End

3.2.6 Connecting AC Input Power Cables


02311FTE-002 and 02311FTC-001 Cabinet Input
Step 1 Connect two AC input power cables to input terminals 1L1, 1L2, 1L3, 1N and 2L1, 2L2, 2L3,
2N on the UPS cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 74


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-25 Input terminals

Step 2 Take out PC boards from near the input copper bar, and install them based on the positions of
the positioning holes.

Figure 3-26 Installing PC plates

----End

02311FTE-004 and 02311FTC-004 Cabinet Input


Step 1 Connect two AC input power cables to input terminals 1L1, 1L2, 1L3, 1N and 2L1, 2L2, 2L3,
2N respectively on the UPS cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 75


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-27 Input terminals

----End

02311FTD-002 and 02311FTB-001 Cabinet Input


Step 1 Connect AC input power cables to input terminals L1, L2, L3, and N on the UPS cabinet.

Figure 3-28 Input terminals

----End

3.2.7 Connecting AC Output Power Cables

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 76


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Connect AC output power cables to the UPS from inside out and from top to bottom. Connect
the PE cable, N cable, and L cable in sequence.

The method for connecting AC output power cables is the same for the 50 kVA, and 125 kVA
cabinets. The AC output power cable connection for the UPS5000-E-125K-HASBS cabinet is
used as an example.
Connect output power cables to the customer terminal bars in the UPS cabinet, and connect N
cables and PE cables to the N bar and PE bar on the left and right sides.

Figure 3-29 Connecting output power cables to customer terminals

(1) IT and air conditioner output power cables (2) Lighting output power cables

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 77


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-30 Output N cables and PE cables

(1) Neutral cables (2) PE cables

The number of cables in the figure is only for reference. The actual number of cables depends on the
output loads.

3.2.8 Connecting Battery Cables


Context

 The battery string voltage may cause serious injury. Observe safety precautions when
connecting cables.
 Ensure that cables are correctly connected between battery strings and the battery switch,
and between the battery switch and the UPS.

Procedure
Step 1 Connect battery cables to positive and negative battery terminals and terminal N on the UPS
cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 78


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-31 Battery terminals

Step 2 Route a neutral wire from the middle connection point of positive and negative battery strings.
Take a battery string consisting of 32 batteries as an example. The neutral wire routed from
the middle of positive and negative battery strings, each consisting of 16 batteries.

Figure 3-32 Neutral wire

When connecting the battery cables, wrap cables with corrugated pipes for protection, and
reinstall the removed insulation panels at the rear of the cabinet.

----End

3.2.9 Connecting Signal Cables


3.2.9.1 Connecting a Remote EPO Switch

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 79


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

 Huawei does not provide an EPO switch and cable. Prepare them before installation. The
22 AWG cable is recommended. AWG is short for American wire gauge.
 To prevent problems, equip the EPO switch with a protective cover, and enclose the cable
with a protective tube.

Connect the EPO switch to the dry contact card on the UPS.

When the EPO switch is in the NC state, remove the jumper between EPO_NC and EPO_12V before
connection. When you turn off the EPO switch, EPO is triggered. When the EPO switch is in the NO
state, ensure that the jumper is connected between EPO_NC and EPO_12V. When you turn on the EPO
switch, EPO is triggered.

Figure 3-33 EPO NC connection

Figure 3-34 EPO NO connection

3.2.9.2 Connecting Communications Cables

Procedure
Step 1 Connect one end of the cable to the FE port on the UPS monitoring interface card, and
connect the other end to any PoE port on the smart ETH gateway.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 80


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-35 Connecting Communications Cables

----End

3.2.9.3 Connecting Fire Protection and Generator Start/Stop Cables (ATS


Input Cabinet)

Procedure
Step 1 Connect the fire protection and generator start/stop cables to the terminals on the XT2
terminal block.

Table 3-6 Fire protection and generator start/stop cable connection

Cable Connecting Position in the Device Cable Connecting


Position in the UPS
Fire protection Fire Protection XT2-4
Fire Protection XT2-5
Generator start/stop Generator Start XT2-6
Generator Com XT2-7
Generator Stop XT2-8

Here connecting one of the cables is used as an example. XT2-6 is a normally open contact, XT2-7 is a
common contact, and XT2-8 is a normally closed contact.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 81


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-36 Connecting the fire protection and generator start/stop cables for the UPS

(1) XT2 terminal block

----End

3.3 (Optional) Combining Cabinets


Procedure
Step 1 Open the front and rear doors of the UPS. Wrench the anchor bolts using an wrench to adjust
the UPS height, as shown in Figure 3-37. Use a level to level the UPS.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 82


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-37 Leveling the feet

Step 2 Remove the cabinet connecting kits from the rack, as shown in Figure 3-38.
Step 3 Secure the connecting kits in the connection positions on the front door using screws, as
shown in Figure 3-38.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 83


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-38 Combining UPSs

Step 4 Use the same method to secure the connecting kits in the connection positions on the rear
door.
Step 5 Repeat the procedure to combine other UPSs.

When combining cabinets, ensure that all the upper surfaces of the cabinets are on the same plane.

Step 6 Secure the bolts using a socket wrench.


----End

3.4 Installing a Double-Bus (2N) System


3.4.1 Connecting Power Cables
Procedure
Step 1 Ground each single UPS.
Step 2 Connect AC input and output power cables of each UPS.
Step 3 Connect battery power cables of each UPS.
Step 4 Connect cables to the dual-bus system.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 84


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

Figure 3-39 Conceptual diagram of a dual-bus system

Figure 3-40 Cable connections to a dual-bus system

(1) Input power cables (2) Battery cables (3) Output power cables

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 85


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

3.4.2 Connecting Signal Cables


Procedure
Step 1 Connect signal cables to each single UPS in the dual-bus system by referring to the single
UPS installation method.
Step 2 Connect BSC cables between the master and slave systems of the dual-bus system.

Figure 3-41 Connecting BSC cables

----End

3.5 Installation Verification

Check items 09 and 10 carefully. Otherwise, the UPS may break down.

No. Item Expected Result


01 Consistency between system System configurations, including models and
configurations and delivery number of modules, comply with the contract.
configurations
02 Cable layout Cables are routed properly and meet
engineering requirements.
03 Cable connections Input and output power cables and battery
cables are securely connected and spring
washers are flattened, prevent falling off and
safety accidents. Ensure that there is no
disconnection or potential risk.
04 Serial port connection (security Signal cables are connected properly and
protection mechanism securely.
supported)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 86


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

No. Item Expected Result


05 Cable labels Both ends of each cable are labeled. Labels
are easy to understand.
06 Ground cable connections The ground cable is securely connected to the
equipment room ground bar. Measure the
resistance between the UPS ground cable and
the equipment room ground bar, which must
be less than 0.1 ohm.
07 Distances between cable ties Distances (recommended: 30 cm) between
cable ties are the same, and no burr exists.
08 Cable connections Cables are properly connected according to
wiring diagrams.
09 Live wire and neutral wire The connections are correct. Connect the input
connections 1L1, 1L2, 1L3, 1N, 2L1, 2L2, 2L3, and 2N
wires correctly. Connect the primary and
secondary ATS power cables correctly
10 Input and output live wire phase In single UPS mode, mains and bypass input
sequences and output live wires are connected in a
correct sequence.
11 Battery cable connection Check that the voltages on the positive and
negative battery terminals and battery N are
correct using a multimeter.
12 Operating environment Clean the conductive air and other sundries.
13 Copper busbar short circuit Check that copper busbars are open-circuited
using a multimeter or an insulation resistance
tester.
14 Surge protection switch state The surge protection switch is turned on.
15 Foreign matter cleaning inside The inside and outside of the cabinet, and
the cabinet other operating components, are free from
conductive dust.
1. There is no foreign matter (such as copper
wires and screws) on the top of the cabinet.
2. There is no foreign matter on the copper
bar terminals.
3. There is no foreign matter around switch
terminals.
4. There is no foreign matter on the bottom
plate of the cabinet.
5. There is no foreign matter on the rear
module subrack.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 87


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 3 Installation

 In the scenarios where holes are drilled for routing cables or covers are removed for routing cables,
after routing cables and checking cable connections, use sealing putty to fill in the gap between the
cables and the cabinet.
 After verifying the installation, reinstall all the covers.
 Do not remove the dustproof cover before power-on to prevent dust inside the UPS.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 88


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

4 User Interface

4.1 LCD Interface


4.1.1 LCD Menu
4.1.1.1 Menu Hierarchy

Figure 4-1 Menu hierarchy

4.1.1.2 Initial Startup

User interfaces displayed in this document correspond to the software version


V100R002C43SPC400 and are for reference only.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 89


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

The Settings Wizard screen is displayed when you start the UPS for the first time or when
you restart the UPS after restoring factory settings. You can set Language, Time, Network
Param., and System Param. on the Settings Wizard screen.

Figure 4-2 Settings Wizard

4.1.1.3 Main Menu


The LCD screen is divided into three parts: status bar, alarm bar and information area.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 90


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-3 Main Menu screen

Table 4-1 Main screen description

Number Area Function


1 Status bar Displays the UPS model, capacity, configuration, current date
and time, Universal Serial Bus (USB) flash drive status, and
buzzer status.
2 Alarm bar Displays active alarms in a scrolling list and the number of
active alarms based on severity. Tap the alarm icon area to
open the active alarm page.
3 Informatio Displays the power flow as well as the key information such as
n area load and battery information. Tap the ATS, UPS, PDU-IT,
and PDU-A/C icons to view details.

Table 4-2 Functions of common buttons

Button Function

Returns to the main screen.

Goes to the lower part of a page.

Goes to the upper part of a page.

Returns to the upper-level menu.

Logs out.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 91


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

4.1.2 System Info Screen


On the main screen, tap System Info. The System Info screen is displayed.

Figure 4-4 System Info Screen

4.1.2.1 Module Data Screen


On the System Info, tap the UPS picture. On the Module Data screen, select a module to
view its running data. indicates the selected module.

Figure 4-5 Module Data Screen

4.1.2.2 Runn. Info. Screen


On the System Info. screen, tap to access the Runn Info screen. On this screen, you can
query AC Output, UPS Load, Mains Input, and Bypass Input.
If Cross current monitoring is set to Enable on the System Info > Settings > Advanced
Param. screen and the number of modules in inverter mode is greater than 1, Mod. Cur. Eql.
Data is displayed on the running screen.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 92


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-6 Runn Info screen 1

Figure 4-7 Runn Info screen 2

AC Output

Figure 4-8 AC output

 Phase voltage (V)/Line voltage (V)/Phase current (A)/Frequency (Hz)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 93


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

AC output phase voltage/AC output line voltage/AC output phase current/AC output
frequency.
 Power factor
Proportion of output active power to output apparent power.

UPS Load

Figure 4-9 UPS load

 Active power (kW)


Output active power of each phase on the UPS.
 Apparent power (kVA)
Output apparent power of each phase on the UPS.
 Reactive power (kVAR)
Output reactive power of each phase on the UPS.
 Load ratio (%)
Load ratio of each phase on the UPS, that is, proportion of actual power to rated power.
 Crest factor
Proportion of the peak value of load current to the valid value.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 94


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Mains Input

Figure 4-10 Mains input

 Phase voltage (V)/Line voltage (V)/Phase current (A)/Frequency (Hz)


Mains input phase voltage/Mains input line voltage/Mains input phase current/Mains
input frequency.
 Power factor
Proportion of the mains input active power to the mains input apparent power.

Bypass Input

Figure 4-11 Bypass input

 Phase voltage (V)/Line voltage (V)/Phase current (A)/Frequency (Hz)


Bypass input phase voltage/Bypass input line voltage/Bypass input phase current/Bypass
input frequency.
 Power factor
Proportion of the Bypass input active power to the mains input apparent power.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 95


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Battery Status

Figure 4-12 Battery status

 Battery Status
The value can be Not connected, Equalized Charging, Flt. charging, Hibernating,
discharging, or Not chg. or dis.
 Voltage (V)
Voltage of the battery string.
 Current (A)
Current of the battery string. The current is + when batteries are being charged and -
when discharged.
 Temperature (°C)
Battery operating temperature (A battery sensor is required. If this sensor is not installed,
NA is displayed.)
 Backup time (min)
Battery backup time estimated at the current load.
 Remaining cap. (%)
Remaining battery capacity.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 96


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Total Runtime

Figure 4-13 Total runtime

 Bypass runtime (h)


Time for which the UPS runs in bypass mode.
 Inv. runtime (h)
Time for which the UPS runs in inverter mode.

The value takes an integer. For example:


 If the value is less than 1, the value takes 0.
 If the value is greater than 1 and less than 2, the value takes 1.

Environment Data

Figure 4-14 Environment data

 Ambient temperature (°C)


Temperature measured by the ambient temperature and humidity sensor (Install the
sensor. If this sensor is not installed, NA is displayed.)
 Ambient humid. (%)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 97


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Humidity measured by the ambient temperature and humidity sensor (Install the sensor.
If this sensor is not installed, NA is displayed.)

Mod. Cur. Eql. Data

Mod. Cur. Eql. Data is displayed only when Cross current monitoring is set to Enable and
the number of inverter power modules is greater than 1.

Figure 4-15 Mod. Cur. Eql. data

PDU Data

Figure 4-16 PDU data

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 98


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-17 PDU-IT1

Figure 4-18 PDU-A/C

Figure 4-19 Electricity statistics

 If you want to query the electricity consumed in the current month, set both the start date and end
date to the current month. For example, the current month is March 2016. If you want to query the
electricity consumed in March, set the start date and end date to 2016-03.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 99


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 If you want to query the electricity consumed in a past month, set the start date to the month to be
queried, and set the end date to the next month. For example, if you need to query the electricity
consumed in January 2016, set the start date to 2016-01 and end date to 2016-02. If you set both the
start date and end date to 2016-01, a message will be displayed, indicating wrong query dates.

ATS

Figure 4-20 ATS 1

Figure 4-21 ATS 2

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 100


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Cabinet Input

Figure 4-22 Cabinet input

4.1.2.3 Alarms Screen


On the System Info screen, tap to enter the Alarms screen. On the Alarms screen, you
can view active alarms and historical alarms, clear faults, and control the buzzer.

Figure 4-23 Alarms screen

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 101


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Active Alarms

Figure 4-24 Active Alarms screen

Historical Alarms

Figure 4-25 Historical Alarms screen

Buzzer Off
Two buzzer menus are available, that is, Buzzer On and Buzzer Off.
 If the buzzer is muted, Buzzer On is displayed on the operation screen.
 If the buzzer is enabled, Buzzer Off is displayed on the operation screen.
If you enable the buzzer, the buzzer buzzes when a critical alarm, a minor alarm, or a certain
warning is generated. If you mute the buzzer, it never buzzes.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 102


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-26 Buzzer Off screen

Clear Faults

Figure 4-27 Clear Faults screen

Twinkle
After you tap Twinkle, the UPS reports the address information to the FusionModule APP.
The icon of the corresponding integrated UPS in the device layout diagram on the APP will
blink for 10s.

4.1.2.4 Settings Screen


On the System Info screen, tap . The Settings screen is displayed.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 103


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-28 Settings screen 1

Figure 4-29 Settings screen 2

Figure 4-30 Settings screen 3

Basic Settings

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 104


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Set the date and time correctly. Incorrect time display in running and alarm information would
lead to analysis errors during maintenance or repair.

Figure 4-31 Basic screen 1

Figure 4-32 Basic screen 2

 Language
Twelve languages, including English, Chinese, and Italian, are supported. The default
language is English.
 Password
The preset password is 000001. You can change the password.
 Password complexity check
If the password complexity check is disabled, the user password is required to be a string
of six to eight digits. If the password complexity check is enabled, the password is
required to be a string of 6-20 characters and contain at least two types of characters.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 105


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Communication

Figure 4-33 Communication screen 1

Figure 4-34 Communication screen 2

Figure 4-35 Communication screen 3

 IP address allocation

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 106


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

− If the MDU is directly connected to a computer over a network cable, the IP address
can only be allocated manually. The IP addresses of the MDU and computer must
be in the same network segment, and must be different.
− If the MDU is connected to a computer through a LAN switch or router with the
DHCP function, the IP address can be allocated manually or automatically.
 Manual: Check that their IP addresses are two different values on the same
network segment. Set the UPS IP address to be in the same subnet as the PC IP
address. Perform the bitwise AND operation for the UPS IP address and the
PC IP address with the subnet mask respectively. If the operation results are
the same, the two IP addresses are in the same subnet.
AND operation rule: 1 AND 1 = 1, 1 AND 0 = 0, 0 AND 1 = 0, 0 AND 0 = 0.
That is when the corresponding bits are both 1, the result is 1. In other cases,
the result is 0.

Table 4-3 Bitwise AND operation example

- PC IP address UPS IP address


(182.98.225.125) (182.98.225.112)
PC IP address/UPS IP 10110110.01100010.111000 10110110.01100010.111000
address 01.01111101 01.01110000
Subnet mask 11111111.11111111.111111 11111111.11111111.111111
(255.255.255.192) 11.11000000 11.11000000
Bitwise AND operation 10110110.01100010.111000 10110110.01100010.111000
result 01.01000000 01.01000000

 Automatic: The MDU automatically searches for available IP addresses in the


connected network. Ensure that the MDU and PC are on the same network
segment.

You can set IP address allocation to Manual or Automatic. After you restart the device, IP address
allocation changes back to Manual. IP address is the IP address that you have previously set.
 IP address parameter
Set an Ethernet IP address that ranges from 1.0.0.0 to 223.255.255.255. The default value
is 192.168.0.10.

Ensure that the UPS IP address is unique on the network segment. Otherwise, the WebUI
display function may be abnormal.
 Subnet mask
Set an Ethernet subnet mask that ranges from 0.0.0.0 to 255.255.255.255. The default
value is 255.255.255.0.
 Gateway
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255. The default value
is 192.168.0.1.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 107


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 MAC address
Defines the physical address of network equipment and is not configurable.
 RS485 address/RS485 baud rate
Set an address that ranges from 1 to 254 for this port. RS485 baud rate depends on the
network management conditions.
 Batt. temp. sensors
A maximum of four battery temperature sensors can be cascaded.
 Start addr. of batt. temp. sensor
Set this parameter by using the dual in-line package (DIP) switch on the battery
temperature sensor. The address range is 16-28. Ensure that the address that you set on
the LCD is the same as that set for the DIP switch. Otherwise, communication fails.
 BMUs
BMUs can be cascaded. A maximum of 12 BMUs can be cascaded.
 BMU start address
Set the BMU start address through the DIP switch on the BMU to 112. Ensure that the
address that you set on the LCD is the same as that set for the DIP switch. Otherwise,
communication cannot be implemented.
 Amb. temp & humid sensors/Start addr. of amb. temp. & hum. sensors
An ambient temperature and humidity sensor has the same appearance as a battery
temperature sensor. The two types of sensors (up to four) can be cascaded. The ambient
temperature and humidity sensor address range is 32-44, which is different from the
battery temperature sensor. Therefore, you can use the sensor as an ambient temperature
and humidity sensor or battery temperature sensor by setting the address.
 CIMs
Set this parameter to the number of connected CIMs. A maximum of four CIMs can be
connected.
 CIM start address
Set this parameter to the communications address of the first connected CIM. The
address cannot be changed. The DIP switch should be set to 0000 for the first CIM, and
the DIP switch setting for a later connected CIM should increase by 1 (binary) than that
set for the previous CIM. For details, see the document delivered with the device.
 NTC
The short-distance battery temperature sensor monitors the ambient temperature near
batteries. It ensures that batteries work reliably and securely. The default status is
Disable. If a short-distance battery temperature sensor is configured, set NTC to Enable.
 SSID
When using the mobile app for site setup or inspection, set WiFi SSID after connecting a
WiFi module over a USB port to identify the WiFi device to which the mobile phone is
connected.
 Password
The password for accessing WiFi.

Basic Parameter Settings

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 108


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 Single/Parallel, Output voltage level, and Output frequency must be the same as the
actual values. Otherwise, an alarm may be generated, or other serious faults may occur.
 Battery capacity and Number of cells must be the same as the actual values. Otherwise,
batteries may be damaged, or other serious faults may occur.

Figure 4-36 Basic Parameter Settings

 Single/Parallel
Specifies the UPS running mode. The values include Single and Parallel. The default
value is Single and only Single is supported.
 Output voltage level
Specifies the system output voltage level. The value can be 380 V, 400 V (default), or
415 V. After you change the parameter value, the upper thresholds for the bypass voltage
are restored to the default values. If Output voltage level is 380 V or 400 V, the default
upper threshold is 15% and the default lower threshold is 20%. If Output voltage level
is 415 V, the default upper threshold is 10% and the default lower threshold is 20%. The
parameter is configurable after the inverter shuts down
 Output frequency (Hz)
Specifies the system output frequency level. The value can be 50 Hz (default) or 60 Hz.
 Battery capacity
Specifies the battery string capacity. The value range is 5-3000 Ah, and the default value
is100 Ah.
 Number of cells
Specifies the number of cells. Each 12 V battery consists of six cells. The value range is
180-276, and the default value is 192.

 A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V. The number of cells must be a multiple of 12 (for
example, 180 and 192).
 Cell float voltage, Cell equalized volt, Float volt. temp. comp. coef., and EOD voltage threshold
are set for cells.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 109


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Advanced Parameter Settings

Set System capacity and Power module capacity according to specifications. Incorrect
settings may cause an overload alarm, which affects normal UPS running.

Figure 4-37 Advanced Param. screen 1

Figure 4-38 Advanced Param. screen 2

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 110


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-39 Advanced Param. screen 3

Figure 4-40 Advanced Param. screen 4

 System capacity (kVA)


Rated system capacity, equals to capacity of each power module multiplied by the
number of requisite power modules. The Module quantity mismatch alarm will be
generated if the setting is incorrect.
 Power module capacity (kVA)
Rated power module capacity.
 Requisite modules
Match the system capacity.
 Redundant modules
Set in accordance with loading capacity and redundant requirements.
 Working mode
The value can be Normal mode (default), Converter mode, Self-load mode, or ECO.
 BSC mode
− The value can be Non-BSC (default) or BSC mode. The latter is set when the
system is a dual-bus system.
− A dual-bus system consists of one master and one slave BSC system, which are
specified by the customer. A BSC system cannot be the master and slave at the same
time. Specify master and slave systems during deployment. To change the setting,

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 111


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

you must follow the guidance of maintenance engineers. Set the master and slave
BSC systems to master and slave BSC modes respectively.
− Ensure that the BSC signal cable between the master and slave BSC systems is
properly connected and that BSC-related hardware is properly installed.
 Paral. sys. hibernate
When the customer load is light, set parallel hibernation to alternate modules in
hibernation, which can prolong their service life and improve the system efficiency.
 Module cycle hiber. period (d)
1 to 100 days can be set. The parameter 30 days is set by default.
 Amb. temp. alarm thresh. (°C)
An alarm is generated when the ambient temperature reaches the preset value.
 Top outlet fan
If a top outlet fan is configured, check the fan running status after enabling this
parameter.
 EOD restart
The UPS transfers to battery mode when the mains becomes abnormal. When batteries
reach the EOD threshold and the bypass is disabled and EOD restart is enabled, the
UPS will restart as soon as the mains resumes.
If EOD restart is disabled, clear the alarm manually or enable the function to restart the
UPS.
 EOD restart delay (min)
If EOD restart is set to Enable, the UPS starts working after EOD restart delay when
the mains recovers from an EOD power failure. The value range is 1-1440 min, and the
default value is 10 min.
 Inverter async. alarm
Specifies whether the Inverter async. alarm is displayed when the inverter does not
track the bypass input. The normal power supply is not affected no matter whether you
set the parameter to Enable or Disable.
 Bus overvoltage recovery
Specifies whether to automatically clear the alarm and restart the power module when
the rectifier or inverter shuts down due to a bus overvoltage alarm. If Bus overvoltage
recovery is set to Enable, the bus overvoltage alarm is automatically cleared, and the
rectifier and inverter automatically start when the bus voltage recovers (less than 420 V)
within Bus overvolt. recovery time. When Bus overvoltage recovery is set to Disable,
the bus overvoltage alarm cannot be automatically cleared, and the rectifier and inverter
cannot automatically start. The default value is Enable.
 Bus overvolt. recovery time
If Bus overvoltage recovery is set to Enable, the bus overvoltage alarm is automatically
cleared, and the rectifier and inverter automatically start when the bus voltage recovers
(less than 420 V) within Bus overvolt. recovery time. The default value is 5s.
 Capacitor failure detection
The default value is Enable. When Capacitor failure detection is set to Enable, the
power module performs inverter capacitor fault detection based on the settings of
Capacitor failure detection upper limit and Capacitor failure detection lower limit.
If the power module determines that the inverter capacitor is faulty, it shuts down the
inverter to prevent the fault from expanding.
 Capacitor failure detection upper limit (A)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 112


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

The value range of Capacitor failure detection upper limit is 10–13 A and the default
value is 13 A. When the inverter capacitor current exceeds the current specified by this
parameter, the power module determines that the inverter capacitor is faulty and shuts
down the inverter.
 Capacitor failure detection lower limit (A)
The value range of Capacitor failure detection lower limit is 0–2.5 A and the default
value is 2.5 A. When the inverter capacitor current is lower than the current specified by
this parameter, the power module determines that the inverter capacitor is faulty and
shuts down the inverter. If Capacitor failure detection lower limit is set to 0 A, the
power module does not perform inverter capacitor fault detection.
 Input cur. limiting
This parameter specifies whether the UPS controls input current limiting. When this
parameter is set to Enable, electric generator overload due to excessively large input
current can be prevented. The default value is Disable.
 Input cur. limiting ratio (%)
Limit the input current to protect the electric generator. The value range is 50%-200%,
and the default value is 200%.
 No load output shows zero
When No load output shows zero is Enable, the system changes the value to 0 if there
is no load. The default value is Enable.
 Cross current monitoring
Monitors the relative difference between inter-rack or inter-module currents. If the
parameter is set to Enable, you can view Mod. Cross Cur. and Rack Cross Cur. on the
running screen. The default value is Disable.
 Bus Capa. Life
If Bus Capa. Life is set to Enable, the UPS5000-E detects the bus capacitor lifespan.
 ModbusTCP Encryption
If Modbus TCP is used for communication, communication links do not implement
encryption or implement encryption based on the selected encryption mode.
 Altitude (m)
Set this parameter based on the altitude of the place where the rack is used. The default
value is less than or equal to 1000.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 113


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Input Parameter Settings

Figure 4-41 Input Parameter screen

It is recommended that you retain the default input parameter settings.


 D.G. mode
Enable or disable D.G. mode. Set this parameter when a D.G connects to the input PDC.
Select Enable when a D.G. is detected over dry contacts.
 D.G. power limiting (kVA) and D.G. charger power ratio (%)
Set these two parameters to control the valid input current and limiting input current,
preventing load impact and facilitating cooperation between the UPS and the D.G. The
D.G. power limiting (kVA) setting range is 0-5000 kVA. The D.G. charger power ratio
(%) value range is 0%-100%, and the default value is 0%
 Intra-rack power module startup delay (s)
Control the time interval for each unit to transfer from battery mode to normal mode,
which reduces the impact on the D.G. or power grid. In the case of battery undervoltage,
the system automatically shortens the transfer delay to 1/8 of the normal delay to
accelerate the transfer and prevent battery overdischarge. The value can be 0.5-120
seconds, 5 seconds by default.
 Input adaptability
The value of Input adaptability can be Strong (default) or Weak. Strong input
adaptability applies to the D.G. or input sources whose input current has high frequency
oscillation. In this mode, the total distortion of the input current waveform (THDi) is
poor, but the system is stable. Weak input adaptability is suitable for mains and AC input
sources.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 114


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Output Parameter Settings

Figure 4-42 Output Parameter screen

 Output volt. adjustment (V)


The output voltage can be slightly adjusted based on the onsite power distribution
condition to ensure a minimum difference between the output voltage and the bypass
voltage. This facilitates uninterruptible transfer from normal mode to bypass mode. The
voltage adjustment range is ±5%. The default value is 220.0 when the voltage is 380 V,
230.0 when 400 V, 240.0 when 415 V.
 Output Freq. track rate (Hz/s)
− The value range is 0.1–2.0 Hz/s, and the default value is 0.6 Hz/s.
− This parameter can be adjusted based on site requirements. If Output freq. track
rate (Hz/s) is slow, the inverter frequency is different from the bypass frequency
when the bypass frequency changes. If output is overloaded or the inverter is faulty,
an interruption (less than 20 ms) occurs when the UPS transfers from normal mode
to bypass mode. If Output freq. track rate (Hz/s) is fast, the inverter frequency is
unstable.
 Self-load output cur. ratio (%)
Set the percentage of the output current to the rated output current when the UPS is in
self-load mode. The value can be 20%–100%, 80% by default.
 Output interruption transfer time (ms)
The default value is 0 ms. The transfer from inverter mode to bypass mode takes 1–2 ms,
and the transfer from bypass mode to inverter mode takes 0 to 20 ms.
 Max. BPM transfer times
Cross currents occur during the transfer between bypass mode and normal mode, which
impacts the system. This parameter specifies the number of transfers between bypass
mode and normal mode within 1 hour, which ensures system security. The value can be 1
to 10, 5 by default.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 115


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Bypass Parameter Settings

Figure 4-43 Bypass Parameter screen

 Bypass frequency range (Hz)


When the difference between the bypass input frequency and the rated frequency is
greater than this value, the system determines that the bypass frequency is abnormal and
that the bypass is unavailable.
The bypass frequency range must be greater than the ECO frequency range. The value
range is ±0.5 Hz to ±6 Hz, and the default value is ±2 Hz.
 Maximum bypass voltage
Upper threshold for the bypass voltage. When the difference between the bypass voltage
and the rated voltage exceeds this value, the system determines that the bypass voltage is
abnormal and that the bypass is unavailable.

 When the voltage level is 380 V, the value range is 10%, 15% (default), 20%, and 25%.
 When the voltage level is 400 V, the value range is 10%, 15% (default), and 20%.
 When the voltage level is 415 V, the value range is 10% (default) and 15%.
 Minimum bypass voltage
Lower threshold for the bypass voltage. When the difference between the bypass voltage
and the rated voltage exceeds this value, the system determines that the bypass voltage is
abnormal and that the bypass is unavailable. The value can be –10%, –15%, –20%
(default), –30%, –40%, –50%, or –60%.
 ECO voltage range
In ECO mode, when the difference between the bypass voltage and the rated voltage is
greater than this value, the system determines that the ECO voltage is abnormal and
transfers to normal mode. The values can be ±5% (default), ±6%, ±7%, ±8%, ±9%, or
±10%.
 BPM mode upon BPM overtemp.
This parameter specifies whether to start bypass mode if overtemperature occurs.

Battery Parameter Settings

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 116


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Battery parameter settings have great impact on battery maintenance, battery lifespan, and
UPS discharge time. When you set battery parameters, note the following:
 Retain default settings for Chg. cur. limiting coef. and Cell float voltage. Only
professional maintenance personnel are allowed to change the settings.
 When you set parameters, ensure the following: Chg. cur. limiting coef. >
Transfer-to-equalized charging cur. Coef; Dis. cur. 0.1C EOD ≥ Dis. cur. 0.3C EOD ≥
Dis. cur. 0.5C EOD ≥ Dis. cur. 1.0C EOD.
 Battery type must meet the actual situation. Currently, only VRLA batt. is supported.
 Chg. volt. over range point and Dis. volt. over range point are used to check whether
the batteries in each battery string have the same charge voltage and discharge voltage.
When a value exceeds the specified range, an alarm is generated. The calculation formula
is (Charge/Discharge voltage - Average voltage)/Average voltage x 100%. The
charge/discharge voltage and average voltage are obtained from the BMU. If the BMU is
not configured, you do not need to set these two parameters.

Figure 4-44 Battery Param. screen 1

Figure 4-45 Battery Param. screen 2

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 117


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-46 Battery Param. screen 3

Figure 4-47 Battery Param. screen 4

Figure 4-48 Battery Param. screen 5

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 118


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-49 Battery Param. screen 6

 Installation time
A battery maintenance reminder is displayed when the maintenance time (counted from
the installation time) comes.
 Maintenance period (d)
Interval for reminding users of battery maintenance.
 Battery type
Set the battery type based on actual conditions. Currently, only lead-acid batteries are
supported.
 Chg. cur. limiting coef. (C10)
Charging current limit, which is a multiple of the battery capacity. The value can be
0.05–0.15, 0.1 by default.
 Cell float voltage (V/cell)
Set the float voltage. The value can be 2.23–2.27 V/cell, 2.25 V/cell by default. The
value is configurable in any mode.
 Cell equalized volt. (V/cell)
Set the battery equalized voltage. The value can be 2.30–2.40 V/cell, 2.35 V/cell by
default. The value is configurable in any mode.
 Transfer-to-equalized charging cur. Coef. (C10)
The battery enters equalized charge state when the battery current exceeds this parameter
value. The value range is 0.02–0.08, and the default value is 0.05.
 SOC to start equalized charging (%)
When the SOC is lower than the specified value, batteries enter the equalized charging
mode. The value range is 0–100, and the default value is 70.
 Automatic equalized charging
When the value is Enable, the UPS automatically changes the battery management
status to equalized charging based on the charge current and float charge time.
 Forced equalized charging protection time (h)
When batteries are continuously under float charging or hibernation, you can enable
forced equalized charging. When the forced equalized charging time reaches the value of
this parameter, float charging starts.
 Equalized charging protection interval (d) and Scheduled equalized charging
interval (d)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 119


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

After batteries transfer from equalized charging to float charging, if the batteries do not
discharge, equalized charging starts only after the float charging time reaches Equalized
charging protection interval. After equalized charging is complete, scheduled equalized
charging starts when the non-equalized charging time exceeds Scheduled equalized
charging interval.
 Float volt. temp. comp.
Option to correct the float voltage based on the battery temperature when a battery
temperature sensor is connected. The value is configurable in any mode.
 Float volt. temp. comp. coef. (mV/°C·cell)
Correction coefficient during float voltage temperature compensation.
 Float Chg Temp Comp Center (°C)
Indicates the reference temperature during temperature compensation of the float
charging voltage. The default value is 25.
 Max. batt. dis. time (h)
Set the maximum battery discharge time. When the discharge time reaches the value, the
UPS powers off. The battery discharge time can be set only to 0 hours or a value in the
range 16–48 hours. The default value is 24 hours. If the time is set to 0 hours, battery
discharge protection is not implemented. This parameter cannot be set to a value in the
range 1–15 hours.
 Sched. shallow dis. test
When certain conditions are met, the charger shuts down, and batteries supply power to
loads. The system records the battery discharge data as the reference for battery capacity
and lifespan.
 Sched. shallow dis. test time
The discharge test starts in the specified time period. The value can be 00:00-06:00
(default), 06:00-12:00, 12:00-18:00, or 18:00-24:00. Sched. shallow dis. test time is
displayed when Sched. shallow dis. test is set to Enable.
 Sched. shallow dis. test interval (d)
Set a time interval for shallow discharge tests. The value can be 30-90 days, 60 days by
default. The value is configurable in any mode. Sched. shallow dis. test interval (d) is
displayed when Sched. shallow dis. test is set to Enable.
 Shallow dis. test dis. ratio (%)
Set the proportion of the discharge capacity to the total discharge capacity. The value can
be 10%-50%, 20% by default. The value is configurable in any mode.
 Undertemp. alarm thresh. (°C) and Overtemp. alarm thresh. (°C)
Battery temperatures can be monitored in a timely manner. If a battery overtemperature
alarm is detected, the charging current limit decreases to 0.03 CA. Battery charging stops
if a battery overtemperature protection alarm (when the temperature reaches the high
temperature threshold plus 3°C) is generated. The Undertemp. alarm thresh. can be set
from -20°C to +5°C and the default value is –5°C. The Overtemp. alarm thresh. can be
set from 35°C to 55°C and the default value is 50°C.
 Backup time warning, Remain. cap. warning, Backup time warn. thresh. (min), and
Remain. cap. warn. thresh. (%)
When the first two parameters are set to Enable, an alarm is generated when the backup
time or remaining capacity is less than the alarm threshold. The backup time alarm
threshold is 3–30 min, and the default value is 5 min. The remaining capacity alarm
threshold is 5%–50%, and the default value is 20%.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 120


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 Dis. cur. 0.1C EOD (V/cell), Dis. cur. 0.3C EOD (V/cell), Dis. cur. 0.5C EOD (V/cell),
and Dis. cur. 1.0C EOD (V/cell)
By default, 0.1C EOD (V/cell) is set to 1.80, 0.3C EOD (V/cell) to 1.80, 0.5C EOD
(V/cell) to 1.75, and 1.0C EOD (V/cell) to 1.60. These values are calculated in real time
based on the discharge currents.
 Intelligent hibernation
If this parameter is set to Enable, the intelligent battery hibernation function is enabled.
 Class 1 grid hiber. time (d) and Class 2 grid hiber. time (d)
Set the hibernation time based on the power grid type. In hibernation mode, batteries are
not charged or discharged, which extends the battery lifespan. The Class 1 grid hiber.
time value range is 0–30 days, and the default value is 13 days. The value 0 indicates no
hibernation. The Class 2 grid hiber. time value range is 0–15 days, and the default value
is 6 days. The value 0 indicates no hibernation.
 Single batt. float chg. voltage deviation alarm thres. (%) and Single batt. dis. voltage
deviation alarm thres. (%)
The parameters check whether the batteries in each battery string have the same charge
voltage and discharge voltage. When a value exceeds the specified range, an alarm is
generated.
The calculation formula is (Charge/Discharge voltage - Average voltage)/Average
voltage x 100%.
 Number of battery strings
Number of battery strings connected in parallel.
 Batteries in a single battery string
Number of batteries in a single battery string.

Dry Contact Settings

 Set the dry contacts that you need to use. Otherwise, the UPS may not run properly.
 When you disable a dry contact card, its dry contact signals are disabled.
 After you enable a dry contact card, its dry contact signals can be displayed on the LCD.
 Disable all the dry contacts for a dry contact card that is not connected and all the dry
contacts that are not used to prevent false alarms.
 ( ) encloses a unit, and [ ] encloses silk screen.

Specify dry contact settings on the following cards:


 Dry contact card (MUE05A): provides dry contact signals for the battery grounding
failure detector, D.G., BCB box, and PDCs.
 Backfeed protection board (MUE06A): provides backfeed protection signals. You need
only to enable or disable this board.
 Monitoring interface card (MUS05A): provides four routes of configurable output dry
contact signals.
 Dry contact extended card (MUE07A): provides two routes of input signals and one
route of output signals.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 121


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-50 Dry Contacts screen 1

Figure 4-51 Dry Contacts screen 2

Figure 4-52 Dry Contacts screen 3

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 122


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-53 Dry Contacts screen 4

Figure 4-54 Dry Contacts screen 5

Figure 4-55 Dry Contacts screen 6

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 123


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-56 Dry Contacts screen 7

 MUE05A connection
MUE05A connection status. Independent input signals can be enabled only when this
parameter is set to Enable.
 Batter ground fault [BTG]
Enable or disable the battery grounding failure detection.
 D.G. connection [GEN]
Enable or disable D.G. connection detection.
 BCB connection [OL]
Enable or disable BCB connection detection.
 Batter breaker [STA]
Enable or disable battery circuit breaker monitoring.
 PDC output breaker [OUT]
Enable or disable PDC output circuit breaker monitoring.
 PDC maintenance breaker [MT]
Enable or disable PDC maintenance circuit breaker monitoring.
 BP/SYSMT Switch
If the BP/SYSMT switch is set to Enable, the port has dry contact signal access. How a
user uses the port depends on the status of the BP/SYSMT switch.
 BP/SYSMT switch function
If the BP/SYSMT switch is set to Enable, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU bypass input switch or system maintenance switch.
 SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to Enable, the port has dry contact signal access. How
a user uses the port depends on the status of the SPD/SYSOUT switch.
 SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to Enable, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU input surge protector or system output switch.
 MUE06A connection
If this parameter is enabled, the mains and bypass backfeed protection is enabled.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 124


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 MUS05A DO_1 Action


Control the status of the DO_1 dry contact on the MUS05A dry contact card.
 MUS05A DO_2 Action
Control the status of the DO_2 dry contact on the MUS05A dry contact card.
 MUS05A DO_3 Action
Control the status of the DO_3 dry contact on the MUS05A dry contact card.
 MUS05A DO_4 Action
Control the status of the DO_4 dry contact on the MUS05A dry contact card.
 MUE07A DO_1 Action
Control the status of the DO_1 dry contact on the MUE07 extended dry contact card.
 MUE07A DO_2 Action
Control the status of the DO_2 dry contact on the MUE07 extended dry contact card.
 MUE07A DO_3 Action
Control the status of the DO_3 dry contact on the MUE07 extended dry contact card.
 MUE07A DO_4 Action
Control the status of the DO_4 dry contact on the MUE07 extended dry contact card.
 MUE07A DO_5 Action
Control the status of the DO_5 dry contact on the MUE07 extended dry contact card.
 MUS05A DO_1
Corresponds to signal of the output dry contact DO_1 on the MUS05A.
 MUS05A DO_2
Corresponds to signal of the output dry contact DO_2 on the MUS05A.
 MUS05A DO_3
Corresponds to signal of the output dry contact DO_3 on the MUS05A.
 MUS05A DO_4
Corresponds to signal of the output dry contact DO_4 on the MUS05A.
 MUE07A DO_1
Corresponds to signal of the output dry contact DO_1 on the MUE07A.
 MUE07A DO_2
Corresponds to signal of the output dry contact DO_2 on the MUE07A.
 MUE07A DO_3
Corresponds to signal of the output dry contact DO_3 on the MUE07A.
 MUE07A DO_4
Corresponds to signal of the output dry contact DO_4 on the MUE07A.
 MUE07A DO_5
Corresponds to signal of the output dry contact DO_5 on the MUE07A.
 MUE07A DI_1
Corresponds to signal of the input dry contact DI_1 on the MUE07A.
 MUE07A DI_2
Corresponds to signal of the input dry contact DI_2 on the MUE07A.
 MUE07A DI_3
Corresponds to signal of the input dry contact DI_3 on the MUE07A.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 125


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 MUE07A DI_4
Corresponds to signal of the input dry contact DI_4 on the MUE07A.
 MUE07A DI_5
Corresponds to signal of the input dry contact DI_5 on the MUE07A.

Intelligent Power Supply Settings

Figure 4-57 Intelli. Power screen

The default value of Intelligent power is Disable. If you select Enable, intelligent power
supply parameters are displayed.

Figure 4-58 Intelligent power supply parameters

 Intelligent power
Intelligent power supply mode is applicable when a D.G. is configured, which enables
D.G. power supply when an outage occurs. For details about the installation and
configurations, contact Huawei technical support.
 ATS
Works with the intelligent power supply device.
 D.G startup batt. volt. (V/cell)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 126


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Works with the intelligent power supply device. The value range is 1.80-2.00 V/cell, and
the default value is 1.80 V/cell.

PDU Parameters Settings

Figure 4-59 PDU Parameters screen 1

Figure 4-60 PDU Parameters screen 2

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 127


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-61 PDU Parameters screen 3

Figure 4-62 PDU Parameters screen 4

 Br. cur. shock protect (%)


Branch current shock protection alarm threshold. The value range is 150%-500%, and
the default value is 300%. When the ratio of the branch current to the rated branch
current exceeds the value of Br. cur. shock protect (%), an alarm will be generated.
 X harmonics, Y harmonics, and Z harmonics
The number of three categories of harmonics is displayed. The value range is 2-63. The
default values of X harmonics, Y harmonics, and Z harmonics are 5, 7, and 11,
respectively. The system displays the harmonics settings in Cabinet Input.
 Harmonic alarm enable
Specifies whether harmonic alarming is enabled. It is disabled by default. When
harmonic alarming is enabled, an alarm (voltage or current harmonic alarm) will be
generated if the alarm conditions are met. When harmonic alarming is disabled, no
harmonic alarm will be generated under any condition.
 System overfrequency threshold (Hz)
System over/underfrequency alarm threshold. The value range is 1.0-10 Hz, and the
default value is 1.5 Hz. When the system frequency is higher than the rated frequency
plus the value of this parameter or is lower than the rated frequency minus the value of
this parameter, an alarm is generated.
 Branch breaker open alarm enable

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 128


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

If this parameter is set to Enable, the system generates an alarm when the branch circuit
breaker is open. If this parameter is set to Disable, the system does not generate the
branch circuit breaker open alarm under any condition. The default value is Enable.
 Branch exception alarm enable
If this parameter is set to Enable, the system generates an alarm when the branch circuit
breaker is closed and no load is connected. If this parameter is set to Disable, the system
does not generate the branch exception alarm under any condition. The default value is
Disable.
 Voltage harmonic alarm threshold (%)
When harmonic alarming is enabled and the main route voltage harmonic value exceeds
the alarm threshold specified by this parameter, the system generates an alarm. The value
range is 5.0%–30.0%, and the default value is 30.0%.
 Current harmonic alarm threshold (%)
When harmonic alarming is enabled and the main route current harmonic value exceeds
the alarm threshold specified by this parameter, the system generates an alarm. The value
range is 5.0%–30.0%, and the default value is 30.0%.
 System overvoltage threshold (%)
When the main route voltage is higher than the rated voltage multiplied by the value of
this parameter, the system generates an alarm. The value range is 105.0%–125.0%, and
the default value is 120.0%.
 System undervoltage threshold (%)
When the main route voltage is lower than the rated voltage multiplied by the value of
this parameter, the system generates an alarm. The value range is 75.0%–95.0%, and the
default value is 85.0%.
 Overload threshold (%)
Branch and main route current overload alarm threshold. When the branch current is
lower than the rated branch current multiplied by the value of Br. cur. shock protect (%)
and higher than the rated branch current multiplied by the value of Overload threshold
(%), the system generates a branch overload alarm. When the main route current is
higher than the rated main route current multiplied by the value of Overload threshold
(%), the system generates a main route overload alarm. The value range is
100.0%–120.0%, and the default value is 100.0%.
 Overcurrent threshold (%)
Branch and main route overcurrent threshold. When the main route or branch current is
higher than the rated main route or branch current multiplied by the value of
Overcurrent threshold (%) and lower than the value of rated current multiplied by the
value of Overload threshold (%), the system generates an alarm. The value range is
80.0%–100.0%, and the default value is 80.0%.
 Undercurrent threshold (%)
Branch and main route undercurrent threshold. When the main route or branch current is
higher than the rated main route or branch current multiplied by the value of
Undercurrent threshold (%) and lower than the value of rated current multiplied by the
value of Overcurrent threshold (%), the system generates an alarm. The value range is
30.0%–80.0%, and the default value is 60.0%.
 Three-phase load imbalance
Main route current three-phase load imbalance alarm threshold. The value range is
5.0%–50.0%, and the default value is 25.0%. When the value obtained after the
difference between the maximum and minimum main route three-phase currents is

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 129


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

divided by the minimum current is higher than the value of Three-phase load
imbalance, the system generates an alarm.
 Mains three-phase current imbalance
If this parameter is set to Enable, the system generates an alarm when the main route
three-phase current is imbalanced. If this parameter is set to Disable, the system does not
generate a main route three-phase current alarm under any condition. The default value is
Enable.
 Mains current exceeding lower threshold
If this parameter is set to Enable, the system generates an alarm when the main route
current is lower than the Mains current exceeding lower threshold. If this parameter is
set to Disable, the system does not generate a main route current alarm under any
condition. The default value is Enable.
 Mains current exceeding higher threshold
If this parameter is set to Enable, the system generates an alarm when the main route
current is higher than the Mains current exceeding higher threshold. If this parameter
is set to Disable, the system does not generate a main route current alarm under any
condition. The default value is Enable.
 Branch current exceeding lower threshold
If this parameter is set to Enable, the system generates an alarm when the branch route
current is lower than the Branch current exceeding lower threshold. If this parameter
is set to Disable, the system does not generate a branch route current alarm under any
condition. The default value is Disable.
 Branch current exceeding higher threshold
If this parameter is set to Enable, the system generates an alarm when the branch route
current is higher than the Branch current exceeding higher threshold. If this parameter
is set to Disable, the system does not generate a branch route current alarm under any
condition. The default value is Disable.

4.1.2.5 Maintenance Screen


On the System Info screen, tap . After you log in, the Maintenance screen is displayed.

Figure 4-63 Maintenance screen 1

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 130


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-64 Maintenance screen 2

Battery Maint.

 Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
 A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
 Do not perform battery maintenance when a D.G. is connected.

Perform battery maintenance periodically to increase the battery lifespan and improve the
UPS reliability. Battery maintenance includes Forced Equalized Charging, Shallow Dis.
Test, and Capacity Test. The next maintenance time displayed on the screen reminds you of
the upcoming time to check batteries.

Figure 4-65 Battery Maint. screen

Button is available only when it is in green.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 131


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 Forced Equalized Charging


Perform equalized charging on batteries forcibly.
 Shallow Dis. Test
Discharge partial capacities of batteries.
 Capacity Test
Discharge full capacities of batteries.

USB Operations
The USB Operations screen provides the following functions: Remove USB, Upgrade
Software, Import Config., Export Config., Export Logs, Export E-labels, and Export
Alarms.
This screen allows you to load software online, upgrade software, and download system data.

Figure 4-66 USB Operations screen 1

Figure 4-67 USB Operations screen 2

Inv. ON and Inv. OFF


You can start and shut down the inverter using the LCD. Before the inverter starts, the system
asks for confirmation to prevent misoperation.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 132


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-68 Inv. ON screen

Figure 4-69 Inv. OFF screen

 Inv. ON
The Inv. ON screen allows you to start the inverter manually.
 Inv. OFF
The Inv. OFF screen allows you to shut down the inverter manually.

ECM Switchover

 Only professional personnel are allowed to use this function.


 Perform active/standby switchover (takes about 30 seconds) only after the ECM is inserted,
other configurations are completed, and the ECM starts running properly.

This menu allows you to perform active/standby switchover on the UPS. When you need to
maintain an ECM and it is working, perform active/standby switchover on the ECM. After
switchover, ensure that the ECM stops working (the yellow or red indicator is on, or the green
indicator is blinking) before you maintain it.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 133


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-70 ECM Switchover screen

Screen Calib.
You can calibrate the screen.

Figure 4-71 Screen Calib. screen

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 134


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Bus Capa. Life

Figure 4-72 Bus Capa. Life screen

Reset
After the service life of a capacitor is about to end, you need to manually remove it and
replace it with a new capacitor. After the new capacitor is installed, the power module cannot
detect the replacement, and you need to manually reset the service life of the new capacitor.

Set PDU Address


After you tap this icon, the UPS reallocates a CAN address to the power distribution board
based on the actual address of the board.

4.1.2.6 About Screen


On the System Info screen, tap About on the About screen, you can view the UPS model,
manufacturer name, monitoring version and power version. To view version details, tap
Version Info.

Figure 4-73 About screen

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 135


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

4.1.3 System Status Screen


Figure 4-74 System Status screen

You can click the UPS, PDU-IT, and PDU-A/C icons in the energy flow diagram to view detailed
information about them.

4.1.4 Common Functions Screen


On the main screen, tap Common Functions. On the Common Functions to query the AC
output, load, and mains input information, start or shut down the inverter, control the buzzer,
and query the historical alarms.

Figure 4-75 Common Functions screen 1

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 136


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-76 Common Functions screen 2

4.2 WebUI
4.2.1 Login
Context
Internet Explorer 11 is used as the example browser.

Procedure
Step 1 Open the browser and choose Tools > Internet Options.
Step 2 On the Advanced tab page, ensure that Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2 are
selected and click OK.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 137


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-77 Settings in the Internet Options dialog box

Step 3 Enter https://UPS IP address in the address box of the browser, select a language, set User
name and Password, and click Login. The system supports Internet Explorer 11 and Firefox
31.0.

The preset UPS IP address is 192.168.0.10. You can set the UPS Ethernet IP address on the LCD or
WebUI. The value range is 1.0.0.0–223.255.255.255.

Table 4-4 User description

Default User Preset Password User Rights


admin (system LCD 000001 Performs all operations on the LCD and

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 138


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Default User Preset Password User Rights


administrator) WEB Changeme WebUI, including system running information
browsing, system information (historical
alarms, logs, e-labels, and fault data)
exporting, parameter (system parameters and
battery parameters) setting, system control
(startup, shutdown, troubleshooting, runtime
clearing, and battery management), system
configuration (network parameters, user
management, time and date, and site
information), and system maintenance
(upgrade, calibration, and variables
commissioning).
operator LCD 000001 Only browses the system running information,
(common exports system information (historical alarms,
user) WEB Changeme logs, e-labels, and fault data), starts/shuts
down the inverter, rectifies faults, and
controls the buzzer. Other control and
maintenance functions that may affect system
operation are invisible and parameters cannot
be set.
browser WEB N/A Only browses the system running information.
(browsing
user)

 If an incorrect password is entered three consecutive times, the account will be locked out for 5
minutes.
 After a user logs in to the WebUI, if another user logs in with the same user name, the current
account will be logged out.
 It is advised to change the password after the first login using User Mgmt. on the Config. page to
prevent unauthorized access.

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 139


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

4.2.2 Monitoring Page


Figure 4-78 Monitoring page

Table 4-5 Monitoring function

Number Area Function

1 Running status Displays the power flow and UPS running information.
area
2 Menu bar Displays active alarms and real-time data, sets
parameters, sets communications information, and
provides control commands.
The Active Alarms page is displayed by default.
3 Information area Displays system monitoring information.

You can click the UPS, PDU-IT, and PDU-A/C icons in the energy flow diagram to view
detailed information about them.

You can click to go back to the energy flow diagram page.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 140


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-79 UPS

Figure 4-80 PDU-IT1

Figure 4-81 PDU-A/C

4.2.2.1 Active Alarms Page


The Active Alarms page details active alarms.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 141


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-82 Active Alarms Page

4.2.2.2 Real-time Data Page


You can view the real-time system running data on the Real-time Data page.

Figure 4-83 Real-time Data page

4.2.2.3 Param. Settings Page


Param. Settings page, you can set basic parameters, advanced parameters, input parameters,
output parameters, bypass parameters, battery parameters, and dry contacts. The settings are
the same as those on the LCD.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 142


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-84 Param. Settings page

Calib. output current if no load


Calib. output current if no load can be used only when the UPS output carries no load. If
this parameter is changed from Disable to Enable, the UPS will automatically calibrate the
no-load output current and load rate once. If this parameter is changed from Enable to
Disable, the UPS will not automatically perform calibration and the UPS operation will not be
affected.

4.2.2.4 Comm. Config. Page


Open the Comm. Config. page to set communications information. The settings are the same
as those on the LCD.

Figure 4-85 Comm. Config. page

4.2.2.5 Control Page


Open the Control page to control the system running.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 143


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-86 Control page (single UPS)

4.2.3 Query Page


4.2.3.1 Historical Alarms Page
On the homepage, click the Query tab to open the Historical Alarms page for querying
historical alarms based on severity, generation time, and clear time.

Figure 4-87 Historical Alarms page

4.2.3.2 Logs Page


On the Logs page, you can set Log to Historical logs, Cap. test logs, or Common test logs,
and query or export logs.

Historical logs can be exported but not queried.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 144


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-88 Logs Page

4.2.4 Config. Page


4.2.4.1 User Management
On the home page, choose Config. > User Mgmt.

Figure 4-89 User Management

 On the User Mgmt. page, you can add, modify, delete, lock, or unlock users and change user
passwords.
 The WebUI user name cannot exceed 10 characters and can contain only uppercase and lowercase
letters, digits, and underscores. The password contains 6 to 20 characters and at least two types of
uppercase letters, lowercase letters, digits, and underscores.
 If the LUI password complexity check is disabled, the user password is required to be a string of six
to eight digits. If the password complexity check is enabled, the user password is required to be a
string of 6–20 characters and contain at least two types of characters.

4.2.4.2 Site Config. page


On the home page, choose Config. > Site Config..

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 145


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-90 Site Config. page

 The NTP parameters are used to set the NTP server address, port number, and synchronization
interval.
 The default SNMP version is SNMPv3, and the preset MD5/SHA password is Changeme1, and the
preset DES/AES password is Changeme2. Change the password after your first login, preventing
unauthorized access.
 To obtain the MIB file, choose Config. > Site Config. > SNMP > Download
HUAWEI_UPS_MIB.
 SNMP Trap indicates the IP address of the server configured with network management system
(NMS) software. If SNMP Trap is incorrectly set or not set, system information will be lost or not
reported in time.
 The certificate is used for Secure Sockets Layer (SSL) encryption protection for WebUI login. You
need to apply to a third-party institution for the certificate.
 Configuration Management is used to upload and export configuration parameters in the
monitoring system.
 Multi-brand Management is used to import the brand information of a partner to the corresponding
WebUI.
 Specify Email server IP address, Sender's email, and User account authentication required
when sending a mail and click Test to check whether the test email can be received. Configure
Alarm Notification Server is used to configure a server for receiving alarm emails from the
monitoring system.
 Set Email and Alarm Severity and simulate an alarm. Check that the alarm email can be received.
Configure Alarm Notification Email Address is used to configure the email address for receiving
alarm emails from the monitoring system.
 ModbusTCP Certificate Management: ModbusTCP supports the Transport Layer Security (TLS)
secure protocol for encrypted transmission and implements access authentication through the
bidirectional certificate. Customers can replace the UPS certificate with the certificate trusted by
them.
 ModbusTCP CA Certificate Management: Import a CA certificate to verify the validity of the
Modbus TCP access certificate.
 ModbusTCP Authentication: Verify the identity legitimacy of both parties to ensure data security
for both parties in ModbusTCP communication.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 146


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

 After eUPS certificate management is configured, a certificate can be imported on the WebUI to
replace the preset eUPS certificate.

4.2.5 Maint. Page


On the homepage, click the Maint. tab. The Maint. page provides the Calib.,
Commissioning Var., Upgrade, Download, Bus Capa. Life, and Cur. Equal. Data tabs.

Figure 4-91 Calib.

Figure 4-92 Commissioning Var.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 147


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 4 User Interface

Figure 4-93 Upgrade

Figure 4-94 Download

Figure 4-95 Bus Capa. Life

Figure 4-96 Cur. Equal. Data

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 148


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5 Operations

5.1 Commissioning the ATS Before Powering On the


02311FTE-002 and 02311FTC-001 Systems
5.1.1 Check before commissioning
Before system commissioning, check the power system.

Table 5-1 Check before commissioning

No. Item Result Remarks


1 All circuit breakers are OFF. □ Yes □ No
2 Use a multimeter to check that no short □ Yes □ No
circuit occurs between any two phases of L1,
L2, L3, N, and PE on the AC input side and
that no short circuit occurs between any two
of positive, negative, and N battery
terminals.
3 Positive and negative battery terminals are □ Yes □ No
connected correctly. Check this item by
viewing the color or label of the battery
input cable.
4 The AC input voltage is within the rated □ Yes □ No
input range.
5 The battery input voltage is within the rated □ Yes □ No
range.

5.1.2 ATS Commissioning


Context

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 149


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Perform system commissioning and power-on strictly according to the system manual and
ATS instructions. For any changes in operations and parameters, consult Huawei engineers.
Otherwise, system commissioning or power-on may fail, or even the cabinet is damaged.

Procedure
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 2 Check whether the controller has alarms. If an alarm exists, rectify the fault first.
Step 3 Press the locking latch on the ATS panel, pull out the handle, and insert it into the slot.
Step 4 Check the ATS Motor/Manual selection lever, and flip it to the Motor mode.
Step 5 Check the AC input and configuration status of the ATS.
After the AC input is normal, the ATS controller starts. Check and set ATS parameters based
on the AC input parameters.

 A password is required to log in to the configurations page. Set the password by using the Up, Down,
and Enter buttons. The initial password is 0001.
 Language setting: Default screen > Main Menu > Device Configuration > Language.

 On the default screen, hold down . The main menu screen is displayed. On the

main menu screen, select system configuration and press .


The following table lists the system configuration attributes and values.

Table 5-2 System configuration attributes and values

Item Value Description

Rated operating voltage 110 V/57 V; 115 V/66 V; The default value is 380
120 V/70 V; 208 V/120 V; V/220 V. Set the parameter
220 V/127 V; 230 V/132 V; based on site requirements.
240 V/138 V; 227 V/160 V;
347 V/200 V; 380 V/220 V;
400 V/230 V; 415 V/240 V;
440 V/254 V; 480 V/277 V
Rated frequency 50 Hz; 60 Hz The default value is 50 Hz.
Set the parameter based on
site requirements.
Number of Phases LN1 Single phase; three-phase The default value is
four-wire; three-phase three-phase four-wire.
three-wire

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 150


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Item Value Description


Number of Phases LN2 Single phase; three-phase The default value is
four-wire; three-phase three-phase four-wire.
three-wire
Secondary load Not Used; Opening Only; The default value is Not
Opening And Closing Used.
Generator Usage No Generator; Generator In The default value is No
Use generator. Set the parameter
based on site requirements.
Power supply priority Line 1-Switch I; Line The default value is Line
2-Switch II; No Line 1-Switch I. Set the
Priority parameter based on site
requirements.

 On the main menu screen, select device configuration and press . On the device
configuration screen, you can set thresholds for parameters.
The following table lists the system configuration attributes and values.

Table 5-3 System configuration attributes and values

Item Value Description


Voltage Thresholds Volt Threshold Min –30% to –5% The step increase is
LN1 ±1%. The default
settings are –10%
Volt Threshold Min –30% to –5% for LN1 and LN2.
LN2
Volt Threshold Max +5% to +30% The step increase is
LN1 ±1%. The default
settings are +10%
Volt Threshold Max +5% to +30% for LN1 and LN2.
LN2
Frequency Freq Threshold Min –10% to –1% The step increase is
Thresholds LN1 ±1%. The default
settings are -5% for
Freq Threshold Min –10% to –1% LN1 and LN2.
LN2
Freq Threshold Max +1% to +10% The step increase is
LN1 ±1%. The default
settings are +5% for
Freq Threshold Max +1% to +10% LN1 and LN2.
LN2
Modbus  Modbus address There is no need to
 Local / Remote reset the parameter.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 151


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Item Value Description


Language English; Deutsch; Set the parameter
Francais; Itatiano; based on site
Espanol; Suomi; requirements.
Russian; Chinese

Step 6 Set the ATS controller to auto mode.


----End

5.2 Powering On and Starting the UPS


5.2.1 Powering On the UPS
Prerequisites
Before powering on the UPS, measure the voltage and frequency at the UPS input switch or
the external input switch. Ensure that the phase voltage is within the range of 80–280 V AC
and the frequency is within the range of 40–70 Hz.

Procedure
Step 1 (Skip this step in the case of ATS input.) Turn on the MCCB.
Step 2 Turn on the UPS input circuit breaker QF1.
The UPS is powered by the mains and initialization begins. The LCD displays the Huawei
logo and an initialization progress bar.
----End

5.2.2 Starting the Inverter


Table 5-4 UPS system user list

Default User Preset Password


admin (administrator) LCD 000001
WebUI Changeme
operator (common user) LCD 000001
WebUI Changeme
browser (browsing user) WebUI -

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 152


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.2.2.1 Initial Startup


Step 1 After the MDU starts properly, set the language, time, network parameters, system parameters,
and battery parameters on the Settings Wizard screen.

Figure 5-1 Settings Wizard screen

Table 5-5 Settings Wizard parameters

Menu Parameter Setting


Language N/A Select based on actual conditions.
Time Date format Select based on actual conditions.
YYYY-MM-DD Actual date
Time zone Actual time zone
Time Actual time
Network Param. IP address Automatic
allocation
IP address After IP address allocation is set to Automatic,
IP address, subnet mask, and gateway will be
Subnet mask assigned by the DHCP server (ECC).
Gateway
System Param. 1 Single/Parallel Single
System Param. 2 Output voltage Output voltage level refers to line voltage and
level should be set based on actual conditions.
Output frequency Set based on actual conditions.
(Hz)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 153


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Menu Parameter Setting


Battery capacity Battery capacity = Battery capacity of a battery
string x Number of battery strings connected in
parallel (For example, if the battery capacity of a
battery string is 150 Ah and two battery strings are
connected in parallel to the UPS, set the battery
capacity to 300 Ah.)
Number of cells Indicates the number of 2 V batteries in a battery
string connected to the UPS.
 For a 12 V battery: Number of cells = Number
of batteries x 6 (For example, if a battery string
consists of 40 batteries connected in series, set
Number of cells to 240.)
 For a 2 V battery: Number of cells = Number of
batteries x 1 (For example, if a battery string
consists of 240 batteries connected in series, set
Number of cells to 240.)

Set system parameters with caution because the settings determine whether the UPS can
operate normally.
Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following:
 Set Battery capacity correctly after double check. An incorrect setting affects the
charging power. High or low charging power tends to shorten the battery lifespan, or even
damages batteries. To seek help about how to determine the battery capacity, contact
Huawei technical support.
 Number of cells affects the charge voltage and discharge time. An incorrect setting will
cause a high or low charge voltage, which greatly shortens the battery lifespan. In addition,
the UPS may shut down in advance during discharging, which may result in data backup
failure.

Step 2 After you complete the settings, the Bypass mode and No battery alarms will be displayed
on the LCD and do not need to be cleared. If there are any other alarms, you need to rectify
the faults.

 After you complete the settings, choose System Info. > Settings > Advanced Param., and verify
that the settings of System Capacity, Power module capacity, Requisite modules, and
Redundant modules are consistent with the actual conditions.
 If dry contact signals are connected to the system, choose System Info. > Settings > Dry contacts
and check that the connected dry contacts have been enabled and that the disconnected dry contacts
have been disabled.

Step 3 (02311FTC-004 and 02311FTE-004 cabinets) Set ATS parameters.


1. LCD

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 154


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-2 LCD screen 1

Figure 5-3 LCD screen 2

Figure 5-4 LCD screen 3

Table 5-6 ATS parameter settings

Item Value Description

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 155


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Item Value Description


Control Mode Automatic, Manual The default value is
Automatic.
Power supply combination AC-AC, AC-DG The default value is AC-AC.
Switch mode Auto-switch back, Mutual The default value is
backup, No-switch back Auto-switch back.
Power supply priority Route I first, Route II first The default value is Route I
first.
Disconnect both power Disable, Enable The default value is Disable.
supplies if both are faulty
Route I operating voltage 105–130 The default value is 110.
upper threshold (%)
Route I operating voltage 70–95 The default value is 90.
lower threshold (%)
Route II operating voltage 105–130 The default value is 110.
upper threshold (%)
Route II operating voltage 70–95 The default value is 90.
lower threshold (%)
Route I operating frequency 101–110 The default value is 105.
upper threshold (%)
Route I operating frequency 90–99 The default value is 95.
lower threshold (%)
Route II operating 101–110 The default value is 105.
frequency upper threshold
(%)
Route II operating 90–99 The default value is 95.
frequency lower threshold
(%)
DG Stability delay (s) 1–1800 The default value is 30.
DG stop delay (s) 1–1800 The default value is 10.

2. WebUI

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 156


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-5 WebUI

Step 4 View the system running status diagram on the LCD to check that the UPS is working in
bypass mode.
----End

The Service Expert app can be downloaded from Huawei app store and can run on Android.
User interfaces displayed in this document correspond to the app version V100R001C00B055
and are for reference only.
 For offline startup, enter the barcode and the verification code on the mobile phone app.
The app automatically generates a startup password for the UPS. Then enter the password
on the MDU screen to start the UPS.
 For online startup, activate the startup password on the mobile phone app to start the UPS.
If the initial startup verification passes, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.

Online Startup
Step 1 Insert a WiFi module into the USB port on the MDU.
Step 2 On the MDU, set System Info > Settings > Communication Settings > Password.
Step 3 Enable the mobile phone WLAN, search for the SSID signal, and connect to the WiFi signal.
Step 4 Open the Service Expert app on the mobile phone.
Step 5 On the home screen of the app, tap Startup to access the Set Startup screen.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 157


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-6 Setting startup commissioning

Table 5-7 Parameter description

Item Setting Method

Site Select the site as required.


Device Type Select the device that needs to be connected. Select UPS5000 in this
situation.
Link Enable the connection between the device and the WiFi network.
IP UPS IP address, which can be obtained from the MDU.
Port The port number is 443 by default and can be modified. If the UPS is
managed using the app, the port number must be set to 443.
Username, Same as the user name and password of WebUI accounts. For details about
Password the default system users, preset passwords, and permission, see Table 5-4.

Step 6 Tap Login after setting the parameters.


Step 7 After login, tap Power-on password activation on the screen. A message is displayed,
indicating whether to start the UPS. Tap OK.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 158


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-7 Power-on password activation

----End

Offline Startup
Step 1 Open the Service Expert app on the mobile phone.
Step 2 On the home screen of the app, tap Startup to access the Set Startup screen.
Step 3 Set Site and Device Type as required, and tap Offline Activation.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 159


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-8 Offline activation

Step 4 On the MDU, choose System Info > Maintenance > Inv. ON. You can obtain the Bar code
and Verification code from the screen, as shown in the following figure.

Figure 5-9 Offline startup

The values of the Bar code and Verification code in the figure are for reference only. The actual values
prevail.

Step 5 Enter BarCode and Codes obtained from the MDU on the Offline Activation screen. Tap
Generate PWD to generate a startup password.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 160


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-10 Generating a password

If startup verification fails (the password is not entered within 5 min or the password is incorrect), the
generated password will be invalid for the sake of security. The initial startup verification fails.

Step 6 Enter the generated startup password in Figure 5-9 to start the UPS.
----End

5.2.2.2 Non-initial Startup

Starting the UPS on the MDU


Step 1 Choose Common Functions > Inv. ON.

You can also start the inverter by choosing System Info > Maintenance > Inv. ON.

Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End

Starting the UPS on the WebUI


Step 1 Open a browser (Internet Explorer 11 for example) and choose Tools > Internet Options.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 161


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and then
click OK.

Figure 5-11 Setting the Internet options

Step 3 In the address box of the browser, enter https://UPS IP address.


Step 4 Enter the correct user name and password and click Login.

Figure 5-12 Logging in to the WebUI

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 162


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON, and confirm
the operation to start the inverter.

Figure 5-13 Starting the inverter

If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.

----End

5.2.3 Powering On Loads


Procedure
Step 1 After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears.
Check that the UPS has transferred to normal mode by viewing the system running status
diagram. Check that the UPS three-phase output voltage and frequency are normal by viewing
AC Output on the LCD. Use a multimeter to check that the valid three-phase output voltage
and frequency are normal.

Figure 5-14 Common Functions screen

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 163


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-15 AC Output screen

Step 2 Check that the actual battery capacity and number of cells are consistent with the settings on
the LCD. Use a multimeter to check that the sum of the absolute voltage of the negative
battery string and the voltage of the positive battery string is greater than a certain value (1.6 x
Number of cells) to ensure that the battery strings are connected properly.
Step 3 After confirming that the battery strings are properly connected, turn on the battery string
input switch. If there are multiple battery strings, turn on the switch for each battery string and
then the general switch between battery strings and the UPS. After you turn on the battery
string input switch, the No battery alarm disappears.
Step 4 Turn on the UPS output circuit breaker QF3.

After the UPS is started for the first time, perform a battery capacity test to ensure that battery
parameters are correctly displayed.

Step 5 (Optional) Turn on the lighting output circuit breaker on the integrated UPS and check
whether the PWR indicator on the AC actuator lights up. Press down the lighting button to
power on the light.
Step 6 Turn on the air conditioner circuit breaker on the integrated UPS to power on the air
conditioners.
Step 7 Turn on the IT1 and IT2 output circuit breakers on the integrated UPS, and then turn on the
PDU2000s of the network cabinet and IT cabinet to power on the equipment in the network
cabinet and IT cabinet.

 Do not turn on the reserved circuit breakers.


 When turning on the circuit breakers, observe whether there is any abnormal phenomenon, such as
sparks or unsmooth turning on/off.
 After turning on the IT output circuit breakers, check whether the corresponding branch open alarm
has disappeared from the MDU.
 As for branch open alarms caused by reserved circuit breakers, you can mask these alarms on the
ECC800 WebUI.

Step 8 If a dual-bus system is used, set BSC mode.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 164


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

----End

5.3 (Optional) Setting BSC Mode


 The default value of BSC mode is Non-BSC. Set it to BSC mode when the system is a dual-bus
system.
 The dual-bus system consists of one master and one slave BSC system. You can specify one master
and one slave BSC system during initial startup and change the settings under the guidance of
maintenance engineers. Set the master and slave BSC systems to master and slave BSC modes
respectively.
 Ensure that the BSC signal cable between the master and slave BSC systems is properly connected
and that BSC-related hardware is properly installed.

Settings on the LCD


Step 1 Set the master BSC system. On the main menu of the LCDs of the UPS, choose System
Info > Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set
BSC mode to BSC master mode.

If you have not logged in, enter a user name and password, and tap on the displayed login
screen.

Figure 5-16 BSC master mode

Step 2 Set the slave BSC system. On the main menu of the LCDs of the UPS, choose System Info >
Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set BSC
mode to BSC slave mode.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 165


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-17 BSC slave mode

Step 3 If no alarm is generated after settings, the UPS runs properly.


----End

Settings on the WebUI


Step 1 Set the master BSC system. Log in to the WebUI of each UPS of the master BSC system.
Choose Monitoring > Param. Settings. Under Advanced Param., set BSC mode to BSC
master mode and click Submit.

Figure 5-18 BSC master mode

Step 2 Set the slave BSC system. Log in to the WebUI of each UPS of the master BSC system.
Choose Monitoring > Param. Settings. Under Advanced Param., set BSC mode to BSC
slave mode and click Submit.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 166


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-19 BSC slave mode

Step 3 If no alarm is generated after settings, the UPS runs properly.


----End

5.4 Shutting Down and Powering Off the UPS


Context

After you shut down the inverter, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power. Before you shut down the UPS, ensure
that all loads have shut down.

Procedure
Step 1 Shut down the inverter.
 Using the LCD:
a. On the main screen, tap Common Functions. Tap Inv. OFF.

b. If no user is logged in, enter a user name and password, and tap on the
login screen displayed.
c. In the displayed dialog box, tap Yes to shut down the inverter.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 167


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-20 Inv. OFF screen

To shut down the inverter on the Maintenance screen, tap System Info > Maintenance.
 Method for shutting down the inverter on the WebUI
a. Enter https://UPS IP address in the address box of the browser.
b. Select a language. Enter a user name and password, and click Login to open the
homepage.
c. On the homepage, choose Monitoring > Control, and click Inv. OFF. In the
displayed dialog box, click OK to shut down the inverter.

Figure 5-21 Shutting down the inverter

After the inverter shuts down, if the bypass is normal, the UPS transfers to bypass
mode; if the bypass is not normal, the UPS supplies no power, and the loads shut
down.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 168


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-22 Bypass mode

After the inverter is shut down, the Bypass mode alarm is displayed on the LCD.

Figure 5-23 Abnormal bypass

If the inverter needs to shut down to transfer the UPS to bypass mode, check that the UPS has not
generated an alarm and perform Step 1.

Step 2 After the inverter shuts down, turn off UPS output circuit breaker QF3.
Step 3 Turn off the battery string switch. If there are multiple battery strings, turn off the general
switch between battery strings and the UPS and then the switch for each battery string.
Step 4 Turn off UPS input circuit breaker QF1.
Step 5 Turn off the UPS input circuit breaker (for MCCB input) or disconnect the mains from the
ATS (for ATS input).
----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 169


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.5 Starting the UPS in Battery Mode


Procedure
Step 1 Use a multimeter to check that the sum of the absolute voltage of the negative battery string
and the voltage of the positive battery string is greater than a certain value (1.6 x Number of
cells) to ensure that the batteries are connected properly.
Step 2 Turn off UPS input circuit breaker QF1. Close the battery circuit breaker. If there are multiple
battery strings, close the circuit breaker for each battery string and then the general circuit
breaker between battery strings and the UPS.
Step 3 Use a multimeter to measure the positive and negative battery string voltages at the UPS
battery input terminal. If the sum of the absolute voltage of the negative battery string and the
voltage of the positive battery string is greater than a certain value (1.6 x Number of cells), the
batteries are connected properly.
Step 4 Press and hold down the BATT start button on the bypass module for at least 2 seconds. The
system automatically enters the battery cold start status. The LCD displays the Huawei logo
and an initialization progress bar.

Figure 5-24 Battery startup button

Step 5 After LCD initialization is complete, start the inverter.


----End

5.6 Transferring to Bypass Mode

Before shutting down the inverter, ensure that the bypass is normal. If the bypass is not
normal, after the inverter is shut down, the UPS supplies no power, and the loads shut down.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 170


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Shut down the UPS inverter. Shut down the inverter on the LCD or WebUI, and the UPS
transfers to bypass mode.

If the inverter is shut down when the input voltage or frequency exceeds the specified threshold, the
UPS supplies no power, and the loads shut down.

5.7 Setting ECO Mode


Context
 The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when energy
saving is required.
 When the UPS works in ECO mode, the bypass module takes precedence over the power
module in supplying power to loads. When the bypass module is disconnected, the UPS
switches to the power module. The switchover time is less than 4 ms for typical working
conditions and is no more than 20 ms for harsh working conditions.
 The ECO mode delivers a higher efficiency.
 To avoid frequent transfer between ECO mode and normal mode, do not set the ECO
mode when the bypass input is unstable or is sensitive to load changes.
 ECO mode is not recommended when the load is less than 10%.
 Before transferring the UPS to ECO mode, ensure that the bypass module works
properly.

Procedure
Step 1 Manually shut down the inverter to transfer the UPS to bypass mode.
Step 2 Select a value (±5%, ±6%, ±7%, ±8%, ±9%, or ±10%) from the ECO voltage range
drop-down list box.

Figure 5-25 Setting ECO voltage range

Step 3 Set Working mode to ECO. Information indicating that the UPS works in ECO mode is
displayed on the LCD.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 171


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-26 Setting ECO mode

Step 4 Manually start the inverter.

After the inverter starts, the UPS still works in bypass mode and the inverter is standby. If the
bypass is abnormal, the inverter supplies power immediately. If the inverter is not started, the
UPS may be disconnected.

Figure 5-27 System Status screen

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 172


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.8 Testing Batteries


5.8.1 Forced Equalized Charging Test
Context

Before a forced equalized charging test, ensure that:


 The mains input is normal.
 Batteries are properly connected.
 Batteries are not in the equalized charging state.

Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint.
Step 2 Tap Start next to Forced Equalized Charging to start a forced equalized charging test.

Figure 5-28 Starting a forced equalized charging test

The forced equalized charging test automatically stops in any of the following cases:
 The forced equalized charging test duration reaches the forced equalized charging protection time
(12–24 h, 18 h by default).
 The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
 An alarm is generated.

----End

5.8.2 Shallow Discharge Test

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 173


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Before performing a shallow discharge test, ensure that:


 The UPS works in normal mode with a load ratio fluctuation less than 10%.
 The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
 The mains, batteries, charger, and discharger are normal. No overload alarm is generated.

Automatic Shallow Discharge Test


Step 1 On the home screen of the LCD, choose System Info > Settings > Battery Settings and set
Sched. shallow dis. test to Enable.
Step 2 Set Sched. shallow dis. test time and Sched. shallow dis. test interval as required. After
setting is complete, the system will perform automatic shallow discharge tests based on the
settings.
----End

Manual Shallow Discharge Test


Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint.
Step 2 Tap Start next to Shallow Dis. Test to start a shallow discharge test.

Figure 5-29 Starting a shallow discharge test

When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
 The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
 The discharge voltage reaches the warning threshold (calculated in real time).
 The load ratio fluctuation exceeds 10%.
 An alarm is generated.

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 174


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.8.3 Capacity Test


Context

Before a capacity test, ensure that:


 The UPS is working in normal mode; float charging or hibernation has lasted for 2 hours
after the state of charge (SOC) reaches 100%; and the load ratio fluctuation is less than
10%.
 The UPS has generated no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
 The mains, batteries, charger, and discharger are normal. No overload alarm is generated.

Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint.
Step 2 Tap Start next to Capacity Test to start a capacity test.

Figure 5-30 Starting a capacity test

The capacity test automatically stops in any of the following cases:


 The battery discharge voltage reaches the end of discharge (EOD) voltage plus 0.01 V.
 The load fluctuation exceeds 10%.
 An alarm is generated.
When the battery discharge voltage reaches the EOD voltage plus 0.01 V, the test is complete. The test
data is used as capacity test data. Save the capacity test data record with the largest discharge capacity in
a month as the capacity test data for the month. A maximum of recent 36 capacity test records can be
saved.

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 175


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.8.4 Test Data Download


5.8.4.1 Download over the LCD

Procedure
Step 1 Insert a USB flash drive into the USB port on the MDU.

Step 2 On the main screen of the LCD, choose System Info. Tap . The Maintenance screen is
displayed.
Step 3 Choose USB Operations > Export Logs, and select a log download path.

Figure 5-31 Downloading logs

Step 4 Tap Next. In the displayed dialog box, tap Yes to download data.

Figure 5-32 Confirming the path

----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 176


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.8.4.2 Download over the WebUI

Procedure
Step 1 Log in to the WebUI.
Step 2 Choose Query > Logs, select logs from the Log drop-down list box, then click Export to
export logs.

Figure 5-33 Logs

----End

5.9 Transferring to Maintenance Bypass Mode


Context

 Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
 In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is abnormal, the loads may power off.

Procedure
Step 1 Manually transfer the UPS to bypass mode.
Step 2 Remove the screws using a Phillips screwdriver, remove the barrier chip on the maintenance
bypass switch, and turn on the maintenance bypass switch.
The Maint. breaker closed alarm is displayed in the alarm list.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 177


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-34 Maint. breaker closed alarm

After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode alarms
are displayed on the LCD.

----End

5.10 Transferring from Maintenance Bypass Mode to


Normal Mode
Context

Before you transfer the UPS from maintenance bypass mode to normal mode, ensure that the
bypass input and output are normal.

Procedure
Step 1 Turn off the maintenance bypass switch.
Press down the maintenance bypass switch to turn it off.
The Maint. Breaker closed alarm disappears from the alarm list. Check whether the UPS
works in bypass mode by viewing the system running diagram on the LCD or WebUI.
Step 2 Start the inverters.
----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 178


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

5.11 Performing EPO

 After the EPO button is turned on, the UPS supplies no power and the loads shut down.
 In maintenance bypass mode, the UPS continues to supply power even after the EPO
button is turned on.

Press the external EPO switch that connects to the dry contact card or remove the 4-pin
terminal on the EPO port of the dry contact card of the bypass unit.

Figure 5-35 EPO ports

After you press the EPO button, the EPO and No power supplied alarms are displayed on the
LCD.

5.12 Clearing the EPO State


Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact is not in the
EPO state.
Step 2 Clear the EPO alarm.
 LCD
Choose System Info from the main screen, tap . On the displayed Alarms screen,
tap Clear Faults. In the displayed dialog box, tap Yes, The EPO alarm is cleared
successfully.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 179


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-36 Alarms screen

Figure 5-37 Clearing the alarm

 WebUI
On the homepage, choose Monitoring > Control, and click Clear Fault to clear the
EPO alarm.

Figure 5-38 Clearing the alarm

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 180


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Step 3 View active alarms and ensure that the EPO alarm is cleared. If the input of the system bypass
is normal, the UPS transfers to the bypass mode.
 LCD
Choose System Info from the LCD main screen and tap . The Alarms screen is
displayed. Tap Active Alarms and check whether the EPO alarm is cleared.
 WebUI
Choose Monitoring > Active Alarms to check that the EPO alarm disappears from the
alarm list.
Step 4 Start the inverter.
----End

5.13 Exporting Data


Prerequisites
You have logged in to the WebUI.

Context
The following data can be exported:
 Historical alarms
 Logs
 E-Label
 Fault data

This topic describes how to export historical alarms.

Procedure
Step 1 Choose Query > Historical Alarms, and set Severity, Generated, and Cleared.

Figure 5-39 Querying historical alarms

Step 2 Click Query, and you can see the corresponding historical alarms.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 181


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-40 Exporting historical alarms

Step 3 Click Export and save the displayed webpage.


----End

5.14 Setting Hibernation Mode


When the load power is small and stable, the inverters in some power modules shut down so
that these power modules can enter hibernation state and the other power modules bear all the
load power. This improves the system efficiency, reduces power consumption, and increases
the power module service life. Use the LCD or WebUI to set hibernation mode.

Before starting hibernation mode:


 Ensure that the load power is stable. If the system load power fluctuation is greater than
the rated capacity of half a module (for example, the single-phase load fluctuation is
greater than 4.17 kVA for a 25 kVA module), the UPS may enter and exit from hibernation
mode repeatedly.
 Check that the number of redundant power modules and racks are appropriate. If the
number is insufficient, the UPS may not enter hibernation mode.

5.14.1 Settings on the LCD


Procedure

Step 1 On the main screen, tap System Info and . The Settings screen is displayed.

If you have not logged in, enter a user name and password, and tap on the login screen
displayed.

Step 2 Tap Advanced Param.. Tap or to browse the parameter.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 182


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-41 Hibernation parameters on the LCD

Step 3 On the LCD, set Paral. sys. hibernate to Enable. A confirmation message and security
warning are displayed.

Figure 5-42 Confirmation message

Figure 5-43 Security warning

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 183


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Step 4 Check that the load power is stable (that is, no transient surge results in overload, which may
cause the UPS to transfer to bypass mode), and tap Yes. A message is displayed, indicating
that the hibernation function is set successfully.
Step 5 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
----End

5.14.2 WebUI
Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Param..

Figure 5-44 Hibernation parameters on the WebUI

Step 3 On the WebUI, select Enable from the Paral. sys. hibernate drop-down list box and click
Submit. A message indicating that there is a risk is displayed. Click OK.
Step 4 Set the module cycle hiber. period to an integer ranging from 1 to 100. The default value is
30.

Click Submit after you set the parameter on the WebUI.

----End

5.15 Setting Intelligent Power Mode

Before you connect the D.G. to a UPS system, check that the system is a single UPS system
and that the system is working in non-inverter mode and has connected to batteries.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 184


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

When the UPS is working, the D.G. starts if a mains outage occurs and the battery voltage
reaches the specified threshold. You can set intelligent power mode on the LCD or WebUI.

5.15.1 Settings on the LCD


Procedure

Step 1 On the LCD, choose System Info and tap to access the Settings screen.

If you have not logged in, enter a user name and password, and tap the displayed login screen.

Step 2 On the Settings screen, tap Intelli. Power.

Figure 5-45 Intelligent power supply

Step 3 Select Enable from the Intelligent power drop-down list box. In the displayed dialog box,
tap Yes. Intelligent power supply parameters are displayed.

Figure 5-46 Intelligent power supply parameters

 Intelligent power can be set to Enable and Disable. The intelligent power supply
function can be used only when Intelligent power is set to Enable. It is set to Disable
by default.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 185


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

 ATS can be set to Connected and Not connected. When it is set to Connected, the UPS
works in the ATS scenario. When it is set to Not connected, the UPS works in the reused
scenario. It is set to Connected by default and is available only when Intelligent power
is set to Enable.
 The value range of D.G. startup batt. volt. is 1.80–2.00 V/cell. The default value is 1.80
V/cell. It is available only when Intelligent power is set to Enable.

When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.

Step 4 When Intelligent power is set to Enable, the system will automatically modify some
parameter settings which you can view on the corresponding screen.

Figure 5-47 Parameters associated with intelligent power supply 1

Figure 5-48 Parameters associated with intelligent power supply 2

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 186


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-49 Parameters associated with intelligent power supply 3

Figure 5-50 Parameters associated with intelligent power supply 4

Figure 5-51 Parameters associated with intelligent power supply 5

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 187


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-52 Parameters associated with intelligent power supply 6

Table 5-8 Parameter settings associated with intelligent power supply

Item Automatic Settings Remarks


Working mode ECO N/A
D.G. mode Enable You cannot modify this
parameter if it is set
automatically.
Intra-rack power 5 N/A
module start delay (s)
Input adaptability Strong N/A
Output freq. track rate 0.6 N/A
(Hz/s)
D.G. connection Enable N/A
[GEN]
MUS05A DO_4 D.G. control N/A
ATS Connected N/A
D.G. startup batt. volt. 1.80 N/A
(V/cell)
D.G. power limiting N/A Set this parameter to the actual
(kVA) power of the D.G.
D.G. charger power N/A Set this parameter to the
ratio (%) percentage of the power
provided by the charger for
batteries.

 In battery mode (non-battery test), if the battery voltage reaches the value specified by D.G. startup
batt. volt. or Low battery voltage, the signal for starting the D.G. is triggered.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 188


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

 In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the signal for shutting down the D.G. is triggered.
 If the battery voltage is greater than D.G. startup batt. volt., the UPS exits intelligent power mode
and triggers the D.G. shutdown signal. If the battery voltage is less than D.G. startup batt. volt., a
dialog box is displayed, indicating potential risks. Tap OK to exit intelligent power mode.
 When disconnecting the D.G. from the UPS, set Intelligent power to Disable. Then the system will
automatically modify the following parameters: Working mode is set to Normal mode; Intra-rack
power module start delay (s) is set to 5; Output freq. track rate (Hz/s) is set to 0.6; Input
adaptability is set to Weak; D.G. mode is set to Disable; and D.G. connection [GEN] is set to
Disable. You can modify these parameters as required.

----End

5.15.2 Settings on the WebUI


Procedure
Step 1 On the login page, enter a user name and password, and click Login to access the WebUI of
the UPS.
Step 2 Choose Monitoring > Param. Settings, expand Intelligent Power Settings, and select
Enable from the drop-down list box.

Figure 5-53 Intelligent power supply settings

 Intelligent power can be set to Enable or Disable. The intelligent power supply
function can be used only when Intelligent power is set to Enable. It is set to Disable
by default.
 ATS can be set to Connected or Not connected. When it is set to Connected, the UPS
works in the ATS scenario. When it is set to Not connected, the UPS works in the reused
scenario. It is set to Connected by default and is available only when Intelligent power
is set to Enable.
 The value range of D.G. startup batt. volt. is 1.80–2.00 V/cell. The default value is 1.80
V/cell. It is available only when Intelligent power is set to Enable.

When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 189


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Step 3 When Intelligent power is set to Enable, the system will automatically modify some
parameter settings which you can view on the corresponding page.

Figure 5-54 Parameters associated with intelligent power supply 1

Figure 5-55 Parameters associated with intelligent power supply 2

Figure 5-56 Parameters associated with intelligent power supply 3

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 190


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-57 Parameters associated with intelligent power supply 4

Figure 5-58 Parameters associated with intelligent power supply 5

Figure 5-59 Parameters associated with intelligent power supply 6

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 191


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Table 5-9 Parameter settings associated with intelligent power supply

Item Automatic Settings Remarks


Working mode ECO N/A
D.G. mode Enable You cannot modify this
parameter if it is set
automatically.
Intra-rack power 5 N/A
module start delay (s)
Input adaptability Strong N/A
Output freq. track rate 0.6 N/A
(Hz/s)
D.G. connection Enable N/A
[GEN]
MUS05A DO_4 D.G. control N/A
ATS Connected N/A
D.G. startup batt. volt. 1.80 N/A
(V/cell)
D.G. power limiting N/A Set this parameter to the actual
(kVA) power of the D.G.
D.G. charger power N/A Set this parameter to the
ratio (%) percentage of the power
provided by the charger for
batteries.

 In battery mode (non-battery test), if the battery voltage reaches the value specified by D.G. startup
batt. volt. or Low battery voltage, the signal for starting the D.G. is triggered.
 In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the signal for shutting down the D.G. is triggered.
 If the battery voltage is greater than D.G. startup batt. volt., the UPS exits intelligent power mode
and triggers the D.G. shutdown signal. If the battery voltage is less than D.G. startup batt. volt., a
dialog box is displayed, indicating potential risks. Click OK to exit intelligent power mode.
 When disconnecting the D.G. from the UPS, set Intelligent power to Disable. Then the system will
automatically modify the following parameters: Working mode is set to Normal mode; Intra-rack
power module start delay (s) is set to 5; Output freq. track rate (Hz/s) is set to 0.6; Input
adaptability is set to Weak; D.G. mode is set to Disable; and D.G. connection [GEN] is set to
Disable. You can modify these parameters as required.

----End

5.15.3 ATS Scenario


The D.G. and mains connect to the UPS over an ATS. The MDU obtains the D.G.
startup/shutdown status over the dry contact signals sent from the ATS, and controls D.G.
startup/shutdown over dry contacts.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 192


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-60 ATS scenario

In ATS scenarios, the default parameter settings are used. Working mode can be set based on
the site requirements.
Connect the DO_4 dry contact port on the UPS monitoring interface card to the
startup/shutdown control port on the D.G. The initial status of the DO_4 dry contact is
normally open (NO). When it is closed, the D.G. starts.
The D.G. RUN port of the ATS connects to the dry contact card.

Figure 5-61 Connecting signal cables in the ATS scenario (1)

The AMF port of the ATS connects to the DI_5 port on the dry contact extended card.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 193


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 5 Operations

Figure 5-62 Connecting signal cables in the ATS scenario (2)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 194


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

6 Routine Maintenance

6.1 UPS Maintenance

 Only trained personnel are allowed to perform maintenance. Before performing operations
on the UPS, wear electrostatic discharge (ESD) clothes, ESD gloves, and an ESD wrist
strap. Remove conductive objects such as jewelry or watches during operations to avoid
electric shocks or burns.
 Use insulated tools when maintaining internal devices. Only trained personnel are allowed
to perform maintenance. Customers are not allowed to maintain components behind
protective covers that can be removed only using tools. If the components are to be
maintained, contact Huawei technical support.
 Only maintenance engineers can maintain power modules and bypass modules.
 Maintain UPSs regularly based on the following requirements. Otherwise, the UPSs may
fail to operate properly and the service life may be shortened.

6.1.1 Monthly Maintenance


Table 6-1 Monthly maintenance

Check Item Expected Result Troubleshooting


Operating  Ambient temperature: 0–40°C  If the humidity or temperature
environment  Humidity: 5%–95% RH is abnormal, check the air
(non-condensing) conditioner status.
 Put rodent-proof baffle plates
 Rodent-proof measures have
been taken for the equipment at the door of the UPS
room. equipment room.
 Check that the equipment room
 The equipment room is airtight.
is airtight and not in a direct
ventilation environment.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 195


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

Check Item Expected Result Troubleshooting


Power grid  Input voltage: 380 V AC, 400  If the input voltage is
environment V AC, or 415 V AC (line abnormal, check the power grid
voltage) status and input cable
 Output voltage: 380 V AC, 400 connection.
V AC, or 415 V AC (tolerance  If the output voltage is
±1%, line voltage) abnormal, check the UPS
 Frequency: 40–70 Hz running status and check
whether an alarm is generated.
Information on The status icons on the LCD If an alarm is generated, rectify the
the LCD indicate that all units are operating fault by checking the device status
properly, all operating parameters and parameters.
are within their normal ranges, and
no fault or alarm information is
displayed.

6.1.2 Quarterly Maintenance


Table 6-2 Quarterly maintenance

Check Item Expected Result Troubleshooting


Cleanliness Wipe the cabinet surface using a Remove the dust, especially from
white paper and the paper does not the air filter on the front door, or
turn black. replace the air filter.
Parameter The configuration of the output Reset the parameters.
configuration voltage grade, frequency, number
of batteries, and battery capacity
meets requirements.
Status record Record the three-phase load rate If an exception occurs, check the
and output power factor. load status.
Shallow Conduct a shallow discharge test If an alarm is generated, refer to
discharge test when the UPS is backed up to the alarm list.
(recommended) verify that the batteries can
discharge normally.

6.1.3 Annual Maintenance


Table 6-3 Annual maintenance

Check Item Expected Result Troubleshooting


Grounding Check that the ground Tighten the screws.
cables are connected
securely.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 196


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

Check Item Expected Result Troubleshooting


Power cables and terminals The insulation layer of  Replace the cables.
(between the UPS and the cables is intact and terminals  Secure the output
power distribution cabinet) are free from black marks terminals.
and noticeable sparks.
Cables and circuit breaker The circuit breakers and  Replace the circuit
through-current capacity cables meet load breaker.
requirements.  Replace the cable.
The actual cable
through-current capacity is
greater than the circuit
breaker specifications.

To prevent system failures caused by the deterioration of some key UPS components, you are
advised to check the key components on a regular basis and replace them within the service
life.

Table 6-4 Service life parameters for replaceable components and recommended replacement
intervals

Key Component Design Service Life Recommended


Replacement Interval
Power module 15 years 10 years
Bypass module 15 years 10 years
Fan 15 years 10 years
LCD screen 10 years 8 years

6.2 Battery Maintenance

Before installing batteries, read through the battery user manuals and pay attention to safety
precautions and connection methods provided by battery manufacture.
When installing and maintaining batteries, pay attention to the following points:

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 197


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

 Wrap tools with insulation tape to prevent electric shock.


 Protect your eyes with relevant devices and apply other protective measures.
 Wear insulated gloves and a protective coat in case of electrolyte overflow.
 When moving batteries, avoid handling the battery upside down, handle batteries gently,
and pay attention to personal safety.
 Keep the battery switch off when installing or maintaining the batteries.

6.2.1 Precautions for Battery Maintenance


 Before battery maintenance, get the tools, such as handles, insulated. Do not place other
objects on the top of batteries.
 Never use any organic solvent to clean batteries.
 Never try to remove the safety valve or pour anything into batteries.
 Never smoke or have an open flame around batteries.
 After battery discharge, charge the battery in time to maintain a good service life.
 Only professionals are allowed to perform the maintenance tasks.

6.2.2 Monthly Maintenance


Table 6-5 Monthly maintenance

Item Expected Result Troubleshooting


Battery No battery management alarm is Identify the cause of an alarm
management generated. based on the alarm information.
alarm
Battery 1. The surface is clean and tidy If the battery appearance is
appearance without stains. abnormal, contact Huawei
2. The battery terminals are technical support.
intact.
3. Batteries are free from damage
and cracks.
4. Batteries are free from acid
leakage.
5. Batteries are not deformed or
bulged.
Battery 1. The ambient battery 1. Identify the cause of an
operating temperature is 25±5°C. abnormal battery operating
temperature 2. The battery operating temperature.
temperature is lower than 2. If the fault persists, contact
battery temperature +20°C. Huawei technical support.
3. Battery charge and discharge
conditions meet the
requirements specified in the
battery specifications.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 198


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

Item Expected Result Troubleshooting


Charge voltage  Equalized charging voltage: 1. If the voltage drop between the
of battery string (2.35 V/cell ±1%) x number of battery string output terminals
battery cells and the battery input terminals

at the UPS side is greater than
Float charging voltage: (2.25
1% of the battery string
V/cell ±1%) x number of
voltage, check whether the
battery cells
cable between the battery string
and the UPS is excessively
long, or the cable diameter is
excessively small.
2. Check whether the equalized
charging voltage and float
charging voltage are correctly
set for the UPS.
3. If the fault persists, contact
Huawei technical support.

6.2.3 Quarterly Maintenance


Table 6-6 Quarterly maintenance

Item Expected Result Troubleshooting


Battery temperature The difference between the 1. Install the temperature
sensor measurement temperature measured by the sensor in the correct
accuracy temperature sensor and the position.
temperature displayed on the 2. Replace the battery
MDU is less than 3°C. temperature sensor.
Battery management The settings of battery Set parameters correctly.
parameter settings management parameters meet
the requirements in the user
manual.
Tightness of battery The location of the signs Take photos from multiple
screws marked on battery terminals angles and contact Huawei
indicating tight connections technical support.
does not change.
Cables between batteries No cable deteriorates and the Replace the faulty cable.
insulation layer does not
crack.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 199


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

Item Expected Result Troubleshooting


Battery voltage  Equalized charging 1. Check whether the
voltage: 2.35 V/cell ± equalized charging voltage
0.02 V/cell and float charging voltage

of a battery are normal.
Float charging voltage:
2.25 V/cell ±0.02 V/cell 2. If the charging voltage of a
battery exceeds the
specifications requirement,
perform a complete
forcible equalized charging
for the battery, and check
again whether the voltage
is normal.
3. If the fault persists, contact
Huawei technical support.
Shallow discharge test Conduct a shallow discharge 1. If the batteries cannot
(recommended) test when the UPS is backed discharge normally, locate
up to verify that the batteries the fault (for abnormal
can discharge normally. alarms, see the alarm list).
2. If the fault persists, contact
Huawei technical support.

6.2.4 Annual Maintenance


Table 6-7 Annual maintenance

Item Expected Result Troubleshooting


Capacity Test When the UPS is backed up, 1. Locate the cause when an
discharge a battery to the exception is identified.
undervoltage alarm threshold, to 2. If the fault persists, contact
refresh the capacity of the battery. Huawei technical support.
Battery 1. Each battery terminal is 1. Rectify any abnormal
connection connected reliably. (When connection.
reliability battery strings are powered 2. If the fault persists, contact
off, check the reliability of Huawei technical support.
each terminal in the order
from positive terminals to
negative terminals.)
2. The tightening torque of each
battery screw meets the
requirements of the battery
manufacturer. (A torque
wrench is used for checking
the torque. After checking that
the battery screws meet the
requirements, mark the screws
for later check.)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 200


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

6.3 Power Distribution System Maintenance


O&M Personnel Skill Requirements
O&M personnel must be qualified power distribution system engineers who are familiar with
the data center power supply and distribution system configurations and the operations for
each core component.

6.3.1 Monthly Maintenance


Table 6-8 Monthly maintenance

Item Expected Result Troubleshooting

Power indicator Observe the indicator If the power supply is


luminance, the indicators are normal but an indicator is
on. off or generates dim light,
replace the indicator.

6.3.2 Annual Maintenance


Table 6-9 Annual Maintenance

Item Expected Result Troubleshooting


PDC interior Check whether there is dust If the white paper becomes
on the PDC panels, the dirty, clean the PDC.
white paper that you use to
wipe the PDC panels is
clean.
Bolts between power cables The bolts are secured. Tighten a bolt if it is loose.
and the busbar
Circuit breaker Switch on or off the circuit If the circuit breaker jams,
breaker after powering off maintain or replace it.
the device, the circuit
breaker is switched on and
off smoothly for five times.
PDC air-tightness Check cable holes and PDC If there is a hole or a sealing
sealing plates, there is no plate has shifted, seal the
hole, and sealing plates have cable hole or reinstall the
not shifted. sealing plate.
Cable insulation Measure the insulation If the cable insulation does
resistance, the insulation not meet the requirement,
resistance is greater than or replace the power cable.
equal to 5 megohms.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 201


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 6 Routine Maintenance

Item Expected Result Troubleshooting


PDC insulation Measure the insulation If the insulation does not
resistance, the insulation meet the requirement, check
resistance is greater than or and maintain each
equal to 10 megohms. component.
Insulation resistance of the Measure the insulation If the insulation does not
secondary loop resistance, the insulation meet the requirement, check
resistance is greater than or and maintain each
equal to 2 megohms. component and signal
cables.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 202


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 7 Troubleshooting

7 Troubleshooting

 If the UPS is faulty, alarm information is displayed on the LCD. Clear critical alarms
before powering on the UPS again. Otherwise, the fault scope expands or the UPS is
damaged.
 Do not clear alarms by reseating modules.
 Remove a faulty module after it is confirmed that the module needs replacing. After
removing the module, do not insert it into the UPS again.

 After a UPS finishes troubleshooting and is started, if the LCD continues displaying alarm
information, choose System Info > Alarms > Clear Faults to clear the alarm and then
start the inverter.
 To restore battery discharge after batteries reach EOD, use one of the following methods: 1.
Switch to another battery string. Ensure that each battery has a voltage greater than the
EOD voltage and 11.3 V/cell. 2. Restore the mains power supply to start the inverter.
Close the battery switch and charge batteries until each battery has a voltage greater than
the EOD voltage and 11.3 V/cell.

If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical
support.

Table 7-1 Troubleshooting

Case Symptom Possible Cause Measure


The rectifier is The rectifier is not The mains voltage Check whether the
not normal. working, and the exceeds the upper mains voltage exceeds
bus voltage is not threshold 280 V or is the threshold. If yes,
boosted. less than the lower contact the electric
threshold 80 V. power company.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 203


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 7 Troubleshooting

Case Symptom Possible Cause Measure


PFC soft-startup fails. Replace the power
module.
The power module is Replace the power
faulty. module.
The inverter is The buzzer is The UPS is overloaded Reduce load or rectify
not normal. activated, the Fault or short-circuited. short circuits.
indicator is on, the
inverter is faulty, Inverter Install more air
and the UPS overtemperature conditioners or
transfers to bypass occurs. ventilation devices to
mode. ensure normal
temperatures inside the
equipment room.
The power module is Replace the power
faulty. module.
The charger The buzzer is The charger fails. Replace the power
generates an activated, the Fault module.
alarm. indicator is on, and
the charging The charger Replace the power
function fails. experiences module.
overcurrent.
The charger Check whether the
experiences configured number of
undervoltage. batteries is correct. If the
value is correct but the
alarm persists, replace
the power module.
The UPS works When the mains is Set the UPS working Set the working mode
in bypass mode normal, the UPS mode to ECO mode. correctly.
and does not works in bypass
transfer to mode and does not The bypass transfer Clear the bypass transfer
inverter mode. transfer to inverter times reach the upper times on the LCD.
mode. threshold.

The bypass is The buzzer is The bypass thyristor is Replace the bypass
not normal. activated, and the damaged. module.
Fault indicator is
on. The bypass module Reduce the load, or
experiences improve ventilation.
overtemperature.
The ATS is not After being The input three-phase Power off the ATS and
normal. powered on, the sequence is incorrect. check the phase
ATS automatically sequence.
switches from ON
to OFF or switches
between ON and
OFF repeatedly.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 204


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 7 Troubleshooting

For details about component replacement and maintenance involved in Troubleshooting and Alarm List,
consult Huawei maintenance engineers.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 205


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 8 Parts Replacement

8 Parts Replacement

8.1 Replacing a Fuse


Prerequisites
Spare fuses of the same model are available and functional.

Context
The fuse is located in the right door panel at the rear of the cabinet.
The following tables describe fuses.

Table 8-1 Fuses for models with ATS input

Fuse No. Description

FU1 Fuse of indicator I


FU2 Fuse of indicator II
FU3/4/5 Main route input L1/L2/L3 fuses (AC INPUT VOLT SAMPLE)
FU6/7/8 UPS output U/V/W fuses (IT INPUT VOLT SAMPLE)
FU9/10 Reserved

Table 8-2 Fuses for models with MCCB input

Fuse No. Description


FU1 Fuse of L1 indicator for route I
FU2 Fuse of L2 indicator for route I
FU3/4/5 Main route input L1/L2/L3 fuses (AC INPUT VOLT SAMPLE)
FU6/7/8 UPS output U/V/W fuses (IT INPUT VOLT SAMPLE)
FU9 Fuse of L3 indicator for route I

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 206


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 8 Parts Replacement

Fuse No. Description


FU10 Reserved

Figure 8-1 Fuse

(1) Cover (2) Fuse

Procedure
Step 1 Remove the protective panel.
Step 2 Locate the fuse terminal in the UPS according to the diagram.

Figure 8-2 Fuse positions

(1) Fuse

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 207


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 8 Parts Replacement

Step 3 Open the cover and remove the fuse.


Step 4 Install a new fuse, push the cover, and connect the fuse terminal.
Step 5 Reinstall the protective panel.
----End

8.2 Replacing an Indicator


Prerequisites
 The indicator is faulty.
 Spare indicators of the same model are available and functional.

Tools and Materials


 Phillips screwdriver
 Key to the UPS
 Protective gloves
 Multimeter
 Step ladder
 Spare indicator

Procedure
Step 1 Remove the indicator fuse from the fuse terminal block at the rear of the cabinet to disconnect
the circuit. For the MCCB input, the fuse is connected to #1 fuse base. For the ATS input, the
fuses are connected to #1 and #2 fuse bases.
Step 2 Remove the protective panel.

A cabinet with ATS input is used as an example.

Figure 8-3 Removing the protective panel

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 208


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 8 Parts Replacement

Step 3 Remove the indicator fastener using a Phillips screwdriver.

Figure 8-4 Removing the indicator fastener

Step 4 Replace the indicator if no voltage is detected by using a multimeter.


Step 5 Loosen the screw at the rear of the indicator using a Phillips screwdriver, and remove the
conducting wire.

When removing cables, clearly label the cables with its corresponding terminal ports to prevent incorrect
connections.

Figure 8-5 Replacing an Indicator

Step 6 Remove the retaining ring from the indicator, and remove the indicator from the mounting
hole.
Step 7 Put a new indicator in the mounting hole, secure the retaining ring, and connect the
conducting wire.
Step 8 Install the new indicator in the fastener and reinstall the fastener in the cabinet.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 209


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 8 Parts Replacement

Step 9 Reinstall the fuse so that the circuit is in closed state.


Step 10 Check that the new indicator works properly.
Step 11 Reinstall the protective panel.
----End

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 210


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 9 Technical Specification

9 Technical Specification

Table 9-1 Physical specifications

Item Specifications
Cable routing mode Routed in and out from the top
Protection level IP20
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm
Communication Dry contacts, RS485, and SNMP

Table 9-2 Environmental specifications

Item Specifications

Operating temperature 0°C to 40°C


Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m (When the altitude is greater than 1000 m and less
than 4000 m, the rated power should be derated. For details,
see the IEC62040-3.)

Table 9-3 Safety and EMC

Item Specifications
Safety compliance EN62040-1, 2013
IEC62040-1, 2013

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 211


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 9 Technical Specification

Item Specifications
Electromagnetic EN/IEC62040-2
compatibility (EMC) IEC61000-2-2
IEC61000-4-2
EN61000-4-6: EN/IEC62040-2 2nd Ed (IEC61000-4-6)
EN61000-4-3: EN/IEC62040-2 2nd Ed (IEC61000-4-3)
EN/IEC62040-2 2nd Ed (IEC61000-4-4)
EN/IEC62040-2 2nd Ed (IEC61000-4-5)
IEC61000-4-8
IEC61000-4-11

Table 9-4 Mains Input electrical specifications

Item Specifications

Input system Three-phase, four-wire, and PE


Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
At 0–40°C: The UPS works at full load when the voltage is
176–280 V AC and is linear derated to 40% load when the
voltage is 176–80 V AC.
Input frequency range 40–70 Hz
Input power factor > 0.99 (full load); > 0.98 (half load)
THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear load;
maximum: 5%)

Table 9-5 Bypass Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input frequency range 50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)

Table 9-6 Battery specifications

Item Specifications

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 212


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 9 Technical Specification

Item Specifications
Battery voltage 360–528 V DC (30–44 batteries, 32 by default; derated by 6%
when there are 30 batteries)
Battery management Intelligent battery management
Cold start When a mains outage occurs, batteries can start the UPS to
supply power to loads.
Charging voltage  Equalized charging voltage: 2.3–2.4 V/cell, 2.35 V/cell by
default (30–42 batteries); 2.3–2.35 V/cell, 2.35 V/cell by
default (44 batteries)
 Float charging voltage: 2.23–2.3 V/cell; 2.25 V/cell by
default (30–44 batteries)

Table 9-7 Output electrical specifications

Item Specifications
Output system Three-phase, four-wire, and PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
Output voltage precision ±1% (balanced load)
Output power factor 1
Transfer time  Uninterruptible transfer: 0 ms
 Interruptible transfer: ≤ 20 ms
Output voltage imbalance Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability Inverter overload capability:
 100% < load ≤ 110%: transfer to bypass mode after 60
minutes
 110% < load ≤ 125%: transfer to bypass mode after 10
minutes (tolerance ±0.1 minute)
 125% < load ≤ 150%: transfer to bypass mode after 1
minute
 Load > 150% or a short circuit occurs: run for 200 ms
Derating coefficient of  40 A circuit breaker: 0.75
output circuit breakers  63 A circuit breaker: 0.7

Table 9-8 System electrical specifications

Item Specifications

System efficiency 96% (linear load)

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 213


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) 9 Technical Specification

Item Specifications
Current equalization 5%
specification

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 214


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) A Menu Hierarchy

A Menu Hierarchy

A.1 Menus on the LCD


Level 1 Level 2 Menu Level 3 Menu Level 4 Menu
Menu
System Info Runn Info AC Output N/A
UPS Load N/A
Mains Input N/A
Bypass Input N/A
Battery Status N/A
Module Data N/A
Total Runtime N/A
Environment Data N/A
PDU Data N/A
ATS N/A
Cabinet Input N/A
Mod. Cur. Eql. Data N/A
Alarms Active Alarms N/A
Historical Alarms N/A
Buzzer Off N/A
Clear Faults N/A
Twinkle N/A
Settings Basic N/A
Communication N/A
Basic Param. N/A

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 215


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) A Menu Hierarchy

Level 1 Level 2 Menu Level 3 Menu Level 4 Menu


Menu

Advanced Param. N/A


Input Param. N/A
Output Param. N/A
Bypass Param. N/A
Battery Param. N/A
Dry Contacts N/A
Intelli. Power N/A
Settings Wizard N/A
PDU Param. N/A
ATS Param. N/A
Maintenance Battery Maint. N/A
USB Operations Remove USB
Upgrade Software
Import Config.
Export Config.
Export Logs
Export E-labels
Export Alarms
Multi-brand
Fault Data
Upgrade Software N/A
Inv. ON N/A
Inv. OFF N/A
ECM Switchover N/A
Screen Calib. N/A
Bus Capa. Life N/A
Set PDU address N/A
About Model N/A
Manufacturer N/A
Monitoring Version N/A

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 216


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) A Menu Hierarchy

Level 1 Level 2 Menu Level 3 Menu Level 4 Menu


Menu

Power Version N/A


Version Info N/A
Common AC Output Phase voltage N/A
Functions
Line voltage N/A
Phase current N/A
Frequency N/A
Power factor N/A
UPS Load Active power N/A
Apparent power N/A
Reactive power N/A
Load ratio N/A
Crest factor N/A
Mains Input Phase voltage N/A
Line voltage N/A
Phase current N/A
Frequency N/A
Power factor N/A
Inv. ON N/A N/A
Inv. OFF N/A N/A
Buzzer Off N/A N/A
Historical N/A N/A
Alarms
System Status ATS/MCCB N/A N/A
UPS N/A N/A
PDU-IT1 N/A N/A
PDU-IT2 N/A N/A
PDU-A/C N/A N/A

A.2 Menus on the WebUI


Level 1 Menu Level 2 Menu Level 3 Menu

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 217


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) A Menu Hierarchy

Level 1 Menu Level 2 Menu Level 3 Menu


Monitoring Active Alarms N/A
Real-time Data UPS
Cabinet Input
ATS (available only to a cabinet with the
ATS input)
Module
Power Distribution Branch
Param. Settings Basic Param.
Advanced Param.
Input Param.
Output Param.
Bypass Param.
Battery Param.
Dry Contacts
Intelligent Power Settings
PDU Param.
ATS Param.
Comm. Config. System IP Settings
RS485 Settings
Battery Temperature Sensor Settings
Ambient Temperature and Humidity Sensor
Settings
BMU Settings
CIM Control
NTC Settings
WiFi Settings
Control System Commands and Tests
Query Alarm History Query
Export
Logs Historical log
Cap. test log
Common test log

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 218


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) A Menu Hierarchy

Level 1 Menu Level 2 Menu Level 3 Menu


Config. User Mgmt. New
Modify
Delete
Lock
Unlock
LUI password complexity check
Idle Timeout Logout Allowed timeout
Site Config. Time zone
System Date and Time
System Information
SNMP
SNMP Trap
Certificate Management
Configuration Management
Multi-brand Management
Configure Alarm Notification Server
Configure Alarm Notification Email
Address
ModbusTCP Certificate Management
ModbusTCP CA Certificate Management
ModbusTCP Authentication
eUPS Certificate Management
Maint. Calib Bypass
Module
ECM
Commissioning Var. Bypass
Module
ECM
Upgrade Upgrade UPS Software
Download Download
Bus Capa. Life Bus Capa. Life

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 219


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) A Menu Hierarchy

Level 1 Menu Level 2 Menu Level 3 Menu


Cur. Equal. Data Mod. Cur. Eql. Data

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 220


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) B PDC Silk Screen Description

B PDC Silk Screen Description

The silk screen content is in the format of number of routes+symbol+switch sequence number.
In the single-input scenario, the number of routes is omitted by default. For example, 1QF1
indicates the first switch of input I, 2QF1 indicates the first switch of the second input, and
QF1 indicates the first switch in the single-input scenario.

Table B-1 Symbols

Symbol Name Symbol Name


QF Circuit breaker QFS SPD circuit breaker
FS Surge protective device FU Fuse
(SPD)
ATS Automatic transfer switch MCCB Molded case circuit breaker

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 221


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0001-1 Mains voltage Minor  Cable 1. Check whether cables to


abnormal connections are mains are disconnected,
incorrect. loose, or incorrectly

connected.
The mains is
not normal. 2. If cable connections are
correct, measure the
 The power mains voltage with a
module is multimeter. If the mains
faulty. voltage exceeds 280 V,
the mains input is not
normal; if the mains
voltage is less than 272
V, the sampling circuit of
the power module is not
normal. Replace the
faulty module.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 222


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0001-2  Cable 1. Check whether cables to


connections are mains are disconnected,
incorrect. loose, or incorrectly

connected.
The mains is
not normal. 2. If cable connections are
correct, measure the
 The mains mains voltage with a
input fuse for multimeter. If the mains
the power voltage is less than 80 V,
module is the mains voltage is not
blown. normal; if the mains
voltage exceeds 88 V, the
power module sampling
circuit or fuse may not be
working properly.
Replace the faulty
module.
0001-3 The mains is not Check the mains.
normal.
0004-1 Mains ph. Minor Cable connections Verify the cable connections.
Reversed are incorrect.
0005-1 Mains neutral Minor Cable connections 1. Secure or connect the
absent are incorrect. neutral wire to the cabinet
if it is loose or
disconnected.
2. Check that the neutral
wire to the power
distribution system is
normal.
0006-1 Mains Minor  The mains is Check whether the mains
undervoltage not normal. voltage ranges from 80 V
 The power (excluding 80 V) to 176 V. If
module no, the mains monitoring
sampling circuit for the power module
circuit is not is faulty. Replace the faulty
normal. module.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 223


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0010-1 Abnormal Minor  The bypass 1. Check the bypass input


bypass voltage range is voltage or cable
voltage not correctly connections with a
set. multimeter.
 The bypass 2. Check the voltage system
input voltage is and bypass voltage
not normal. thresholds configured on
the LCD.
0010-2  The bypass 1. Check the bypass input
frequency voltage or cable
range is not connections with a
correctly set. multimeter.
 The bypass 2. Check the bypass input
input frequency frequency. Check the
is not normal. rated frequency and
frequency range
configured on the LCD.
0011-1 Bypass phase Minor The phase Check whether the cable
reversed sequence of the phase sequence is correct
three-phase bypass using a multimeter. If no
input is reversed. multimeter is available,
exchange the positions of
any two cables.
0012-1 Bypass Minor The neutral wire of 1. Secure or connect the
neutral absent bypass input is not neutral wire to the cabinet
installed properly. if it is loose or
disconnected.
2. Check that the neutral
wire to the power
distribution system is
normal.
0020-1 Battery Critical Batteries are not 1. Check whether battery
connected properly installed. polarities are correctly
reversely installed by using a
multimeter. If no, correct
the installation.
2. Check whether the
battery input voltage of
the UPS is normal. If yes,
the battery sampling
circuit of the power
module is faulty. Replace
the power module.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 224


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0021-1 Battery EOD Critical The battery If the BCB box is


voltage reaches the configured, check whether
EOD voltage the BCB box trips. If it trips,
threshold due to close the BCB box switch.
continuous
discharge.
0022-1 No battery Minor  There is no 1. Check that battery cables
battery string. are correctly connected.
 The battery 2. Check that the battery
string is not terminal voltage is
properly normal.
installed. 3. Check that the battery

fuse in the power module
The power
is intact.
module battery
fuse is blown.
0025-1 Battery Minor  The configured 1. Check whether battery
overvoltage number of parameters are correctly
batteries is less set.
than the actual 2. If they are correctly set,
number. certain batteries may be
 The battery faulty.
neutral wire is 3. Check whether the
not installed battery neutral wire is
properly. correctly connected.

0026-1 Low battery Minor  Battery 1. If the low battery voltage


voltage discharge alarm is generated in
results in low battery mode, check
battery voltage. whether the mains

voltage recovers. If yes,
The battery
charge batteries
neutral wire is
immediately.
not installed
properly. 2. Check whether the
battery neutral wire is
 The charger is correctly connected.
faulty.
3. If this alarm is generated
in normal mode, check
whether the battery
switch is ON. If yes, the
charger may be faulty.
Replace the related power
module.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 225


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0530-1 Battery Critical  The battery 1. Check whether the


ground fault string is not positive and negative
properly terminals of the battery
grounded. string are grounded or

have sufficient resistance
The battery
to the ground.
ground
monitoring 2. Check whether the
cable is faulty. battery grounding failure
detector is faulty by
 The dry contact replacing it with a new
board is faulty. one.
3. If no battery grounding
failure detector is
available, check on the
dry contact board
whether the battery
grounding failure detector
is enabled. If yes, disable
it and check whether the
alarm is cleared. If the
alarm persists, the dry
contact board may be
faulty. Replace the board.
0032-1 Battery Critical  The battery 1. Check the battery
overvoltage voltage is voltage.
protection greater than the 2. Check that the configured
upper number of batteries
threshold. matches the actual
 The configured number.
number of 3. Check that the actual
batteries is less number of batteries meets
than the actual requirements.
number.
 The actual
number of
batteries does
not meet
requirements.
0036-2 Battery Warning The time for Maintain the batteries.
maintenance maintenance
reminder arrives.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 226


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0037-1 Battery Critical  The UPS has 1. Check whether the


undervoltage worked in battery voltage is normal.
battery mode 2. Check whether the output
for an extended is overloaded.
amount of time. 3. Check whether any
 The charger is battery is damaged. If
faulty. yes, replace the battery.
4. Check whether any
battery charger generates
an alarm. If yes, replace
the faulty module.
0040-7 Rectifier Critical  The fan for the 1. Check that the air channel
abnormal power module for the module is free
is not from blockage.
functioning 2. Check whether the fans
properly. are functioning properly.
 The air channel Replace the power
for the power module if the fans are
module is faulty.
obstructed.
0043-1 Fan abnormal Critical  The fan for the Replace the faulty power
power module module.
is abnormal.
 The fan
monitoring
cable for the
power module
is not working
properly.
0043-2 The fan is faulty. Check the fan or replace the
bypass module.
0043-3  The fan is 1. Replace the fan.
faulty. 2. Check the fan monitoring
0043-4 cable.
 The fan
monitoring
cable is faulty.
0047-1 Not ready Critical The ready switch Close the ready switch.
is OFF.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 227


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0060-4 Inverter Critical  A load 1. Check load cable


abnormal short-circuit distributions.
occurs. 2. If load cable distributions
 A short circuit are normal, replace the
occurs inside power module.
the module.
(This fault
seldom occurs.)
0061-2 Inverter alarm Minor  The I2C bus is 1. Rectify the fault and
not normal. check whether the alarm

is cleared.
The E2PROM
is faulty. 2. If the alarm is generated
again, replace the power
module.
0061-7 Inverter alarm Minor The bypass  If not all modules
waveform is not generate the alarm, start
normal. the UPS, transfer it to
normal mode, and replace
the faulty module.
 If all modules generate
the alarm, open the
bypass input circuit
breaker. After the inverter
relay is closed, close the
bypass input circuit
breaker 10 seconds later.
0564-1 Overload Critical  The load is 1. Check that there is no
timeout excessive. overload.
 Derating 2. Check that the module
reduces the power is not derated due
rated system to a fan fault.
power. 3. If the alarm persists,

replace the power
The module is
module.
damaged.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 228


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0565-1 Load impact Minor  A large-power 1. Check the load.


transfer-to-by RCD load is 2. If the load is normal,
pass instantly replace the power
connected, or module.
the output load
short-circuits.
 The inverter
bridge
short-circuits.
0566-1 Output Minor  The load is 1. Check that there is no
overload excessive. overload.
 Derating 2. Check that the module
reduces the power is not derated due
rated system to a fan fault.
power. 3. If the alarm persists,

replace the power
The module is
module.
damaged.
0570-4 BPM module Critical  The bypass fan 1. Check the bypass fan and
abnormal is not air channel. If the fan is
functioning faulty, replace it.
properly, or the 2. Check that the ambient
air channel is temperature has not
blocked. exceeded 40°C.
 The ambient 3. Check that there is no
temperature overload.
exceeds the
upper
threshold.
 The load is
excessive.
0583-1 Inter-rack Critical  The inter-rack 1. Check the inter-rack
par. cable parallel system parallel system CAN bus.
abnormal CAN bus is 2. Rectify the disconnection
disconnected or or short-circuit fault.
short-circuited. 3. Replace the ECM.
 Only one rack
works in a
parallel system.
 An ECM is
faulty.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 229


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0583-4 The inter-rack Replace the inter-rack


industrial parallel cable.
frequency
synchronization
cable is broken.
0583-5 The inter-rack
carrier
synchronization
cable is broken.
0583-6  The intra-rack
INVBYP cable
is broken.
 The parallel
CAN bus is
broken.
0584-2 Inter-rack Minor The inter-rack Replace the inter-rack
par. cable parallel cable is parallel cable.
alarm faulty.
0584-4 The inter-rack
industrial
frequency
synchronization
cable is broken.
0085-1 EPO Critical The EPO button is Restore the EPO button
pressed. status. Start the UPS after the
alarm is cleared.
0086-1 Max. number Minor The system Check the load.
of BPM frequently
transfers transfers to bypass
mode due to
overload timeout
or load impact.
0087-1 System Warning The neighboring Check the reason why the
transfer-to-by UPS is not normal, neighboring UPS transfers to
pass and transfers to bypass mode.
bypass mode.
0088-1 Rack address Critical The configured Check the rack address
conflict rack address setting.
conflicts with
another one.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 230


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0089-1 Rack output Minor  The load is  Check the load and
overload excessive. remove some loads or
 The rack expand the UPS power
capacity setting capacity if the UPS is
is not overloaded.
appropriate.  Check that the configured
rack capacity meets
requirements.
0090-1 Dry contact Critical I2C Replace the dry contact
board fault communication board MUE05A.
with the dry
contact board
MUE05A fails.
0090-2 I2C Replace the dry contact
communication board MUE06A.
with the dry
contact board
MUE06A fails.
0356-1 Battery Mode Minor The UPS is The running status is
working in battery displayed. See details about
mode. how to handle other alarms.
0359-1 No power Warning No power is The running status is
supplied supplied. displayed. See details about
how to handle other alarms.
0332-1 Output Minor The output is The running status is
disabled disabled. displayed. See details about
how to handle other alarms.
0334-1 BSC master Warning BSC master The running status is
system system. displayed. No further
measures are required.
0334-2 BSC slave BSC slave system. The running status is
system displayed. No further
measures are required.
0337-1 PDC bypass Critical The bypass input The running status is
input breaker circuit breaker on displayed. No further
open the PDC is OFF. measures are required.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 231


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0338-1 PDC output Critical The output circuit 1. Check that all UPS output
breaker open breaker on the circuit breakers are ON.
PDC is OFF. 2. On the LCD, check that
PDC output breaker
open alarm has
disappeared. If the alarm
persists, tap the Clear
Fault button to clear the
alarm.
0341-1 PDC Maint. Minor The maintenance The running status is
breaker circuit breaker on displayed. No further
closed the PDC is ON. measures are required.
0342-1 Mains input Critical The UPS input The running status is
breaker open circuit breaker is displayed. No further
OFF. measures are required.
0343-1 BPM input Critical The bypass input The running status is
breaker open circuit breaker is displayed. No further
OFF. measures are required.
0340-1 Maint. Minor The UPS The running status is
breaker maintenance displayed. No further
closed circuit breaker is measures are required.
ON.
0335-1 Generator Warning The generator is The running status is
connected connected. displayed. No further
measures are required.
0362-1 BCB off Minor BCB off The running status is
displayed. No further
measures are required.
0594-1 Insufficient Minor  The load is 1. Reduce the load.
redundant excessive. 2. Decrease the configured
racks  The configured number of redundant
number of racks.
redundant racks
is incorrect.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 232


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0095-1 Insuffi. Minor  The load is 1. Reduce the load.


redundancy excessive. 2. Decrease the configured
 The configured number of redundant
number of modules.
redundant
modules is
incorrect.
0096-1 ECO volt. Minor  The ECO 1. Check the bypass input
Abnormal bypass voltage voltage and frequency.
or frequency is 2. Check that the rated
out of the voltage, rated frequency,
preset range. ECO bypass voltage
 The ECO range, and frequency
bypass voltage range are correctly set.
or frequency 3. Check that the bypass
range is cables and circuit
incorrectly set. breakers are correctly

connected.
The bypass
input sequence
is reverse or the
neutral wire is
disconnected.
0098-1 Bypass Minor  The output and 1. Check that the output and
current not input circuit bypass input circuit
shared breakers are breakers on each rack are
OFF. ON.
 The length of 2. Check that bypass input
the bypass and output power cables
input or output on each rack meet the
cables is length requirements.
incorrect. 3. Rectify any bypass SCR

open-circuit.
The bypass
SCR
open-circuits.
0150-1 Inverter Minor  The bypass 1. Check that the bypass
asynchronous frequency output frequency does not
changes fast. change fast.
 The output 2. Check that the Output
frequency track freq. track rate is
rate is properly set.
incorrectly set.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 233


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) C Alarm List

Alarm Alarm Severity Cause Solution


ID Name
(Alar
m
ID-Ca
use
ID)

0101-1 BSC signal Minor  The dual bus 1. Check the dual bus
abnormal connector is connector.
loose. 2. Check the parameter
 Parameters are settings.
set incorrectly.
0102-1 Maint. Critical The user operation 1. Shut down the inverter
breaker is incorrect. and then close the
misoperation maintenance circuit
breaker.
2. After maintenance, open
the maintenance circuit
breaker and then start the
inverter.
0380 In self-check Warning The inverter is in Wait until the inverter
self-check. self-check is complete.

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 234


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) D Acronyms and Abbreviations

D Acronyms and Abbreviations

A
ASIC application-specific integrated circuit
ATS AC transfer switch
AWG American wire gauge

B
BSC bus synchronization controller
BCB-BOX battery circuit breaker box
BBB-BOX battery bus bar box

C
CAN control area network
CE Conformite Europeenne

D
DSP digital signal processing

E
ECO economic control operation
EPO emergency power off
ECM energy control module
EOD end of discharge

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 235


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) D Acronyms and Abbreviations

FE fast Ethernet

I
IEC International Electrotechnical Commission

L
LCD liquid crystal display

M
MDU monitor display unit

N
NC normally closed
NO normally open
NTC negative temperature coefficient

P
PDC power distribution cabinet
PDU power distribution unit
PE protective earthing
PFC power factor correction

R
RS485 Recommend Standard 485

S
SNMP Simple Network Management Protocol
SOC state of charge
SOH state of health
STS static transfer switch

T
THDi total distortion of the input current waveform

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 236


UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0) D Acronyms and Abbreviations

THDv total harmonic distortion of output voltage

U
UPS uninterruptible power system
USB Universal Serial Bus

V
VRLA valve-regulated lead acid battery

Issue 05 (2018-09-28) Copyright © Huawei Technologies Co., Ltd. 237

You might also like