CG Power and Industrial Solutions Limited: LT Motors Division Ahmednagar
The document provides technical specifications for a 3 phase induction motor including its frame size, rated output, voltage, speed, cooling method, enclosure type, efficiency, power factor, temperature rise, insulation class, torque values, method of starting, winding connections, terminal information, bearing types, shaft and body materials, weight, applicable standards, and accessories.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
204 views
CG Power and Industrial Solutions Limited: LT Motors Division Ahmednagar
The document provides technical specifications for a 3 phase induction motor including its frame size, rated output, voltage, speed, cooling method, enclosure type, efficiency, power factor, temperature rise, insulation class, torque values, method of starting, winding connections, terminal information, bearing types, shaft and body materials, weight, applicable standards, and accessories.
Voltage (V) 415 +-10% Rated Current (A) 97.00 Rated Speed (RPM) 1480 No of poles 4 Frequency (Hz) 50 +-5% Duty S1 Method of Cooling IC411 Degree of Protection IP55 Gas Group Not applicable Mounting B3 Temp Class NO Enclosure TEFC Safe Area
Load 100% Load 75% Load 50% Load
Efficiency IE2 - 93.5 % 93.5 % 93 % Power factor 0.84 0.79 0.72 AMB. Temp/Temp rise 50°C/70°C (By Resistance Method) Insulation class F (Temp. rise limited to class ‘B’) Rated Torque (kg-m) 36.20 Locked rotor current % FLC 700 Starting torque % FLT 225 Pull out torque % FLT 275
Method of starting Variable Voltage / Frequency
Winding connections Delta No of terminals 6 Direction of rotation Bidirectional
Motor GD Sq. (kg-m²) 6.28
Load GD Sq. (kg-m²) 6.28 Starting time @100% V (Sec) 0.9 Locked rotor Withstand time hot (Sec.) 15 Locked rotor Withstand time cold (Sec.) 30 Stator Thermal / Cooling time constant 60 / 120 (min) Terminal box position RHS From DE Cable size 2 * 3C,95-MM² Bearing DE/ODE 6318-C3 / 6318-C3-I Type of lubrication Unirex-N3 Shaft Material EN8 OR C40 Stator Body Material Cast Iron
Net Weight (Approx.) kg 600
Paint shade RAL7034 Applicable standards IS:1231,IS:12075,IS:12065,IS:325, Space heaters SPACE HEATER 60WX2 (CE280/315) Voltage: 220-240V Accessories Rod Type Btd Reqd(1/Brg),Insulated Bearing At Nde,3Wire Type Rtd Pt100-3Nos Reqd,
Customer specific requirement if any:
All performance data is subject to tolerance as per IEC 60034
All performance shall be measured on sinusoidal supply Temp rise test shall be carried at rated kW & voltage for 1 hour other than S1 duty Max 5 % THD allowed for voltage and Temperature rise is limited to class F, unless otherwise specified Inverter driven motors, voltage spikes are allowed maximum 1600 V with min. rise time of 0.1 microsecond, cable size to be selected accordingly. Customer specific paint shade and paint thickness will not be applicable on powder coated components. Issued By : Vinoth Kumar M Date : 02/11/2019 LT Motors Division, Ahmadnagar