Unit-4 Sewer Appurtenances - Only Introduction (4 Hours) R2
Unit-4 Sewer Appurtenances - Only Introduction (4 Hours) R2
Introduction
Sewer appurtenances are those structures of sewerage system which are constructed at
suitable interval and other locations along a sewer line, to assist in efficient operation and
maintenance of the system.
The important appurtenances of sewer are as follows:
1) Manholes
2) Drop manholes
3) Lamp holes
4) Street inlets
5) Catch basins
6) Flushing devices (Flushing tanks)
7) Inverted siphon
8) Grease and oil trap
9) Storm regulators
10) Ventilating shaft
11) Water closet
12) Trap
13) Clean outs
4.1. Necessity of sewer appurtenances
The sewer appurtenances are necessary due to following two reasons:
Sewer appurtenances are necessary for proper functioning and maintenances of sewer.
For cleaning of sewers when choked up and for periodic cleaning.
4.2. Construction of sewer appurtenances- (location, function and construction)
The location, function and
construction of all appurtenances
has been described as follows:
4.2.1. Manhole
A masonry or RCC chamber
constructed along the sewer to
provide access for inspection,
testing, cleaning, and removal of
obstructions from the sewer line
is called manhole.
It may be circular or square in
shape and has a suitable cover
(generally of CI) on the top.
Object of providing manhole
1) To provide manual excess for
inspection, cleaning, testing etc.
in sewer.
2) To allow joining of sewer lines
in case of changing in direction or at level or both. Fig-4.1 Manhole (Source: PN Modi, 2001)
3) To lay sewer in convenient length and
4) To achieve the ventilation of sewers.
Location of Manhole
It is generally provided directly over the centerline of the sewer and at every
bend, junctions, and every change of gradient, direction and size and at
other convenient locations.
Spacing of manhole
Spacing of manhole depends upon size of sewer, bends and junctions, every variation of
size and gradient etc. but normal spacing with respect to dia. is shown in table 4.1 below:
Diameter (m) < 0.3 > 0.3 to 0.6 > 0.6 to 0.9 > 0.9 to 1.2 >1.2 to 1.5 > 1.5
Spacing (m) 45 75 90 120 250 300
Construction of manhole
A manhole has following
components:
(Refer figure 4.1) ⟹
a) Top cover and frame:
Depth of frame is 20 to 25 cm
and width is 10 cm.
The clear cover of opening
should be at least 50 cm.
Weight of top cover with
frame = 90 to 270 kg
b) Access shaft:
The upper portion of manhole
is called access shaft which
provides an access to the
working chamber.
Its size is 0.6m x 0.75m for
rectangular and for circular
manhole its diameter is 0.6m
to 0.75m.
Classification of manhole
Manholes are classified based on depth as follows:
a) Shallow manhole:
When the depth of manhole is 0.75 m to 0.90 m it is called shallow
manhole.
It is constructed at the start of branch sewer with light CI cover and also
called inspection chamber.
Lamp holes:
A lamp hole is a small opening provided on
sewers as shown below in figure 4.3 mainly to
permit the insertion of lamp into the sewer for the
purpose of inspection of sewer and detecting the
presence of any obstructions in the sewer from
two adjacent manholes upstream and
downstream.
It is useful, if there is slight curve and change in
gradient of sewer and have limited space to
provide manhole in narrow lanes.
Fig-4.3: Lamp hole
(Source: Birdie & Birdie 2001)
a) Curb inlet:
It consists of a vertical opening with CI or steel
bar gratings on (kerb).
It is more suitable because it allows entering a
very less quantity of suspended matters.
So it is common (Refer to figure 4.5)
Fig-4.5: Curb inlet
b) Gutter inlet: (Source: Birdie & Birdie 2001)
It consists of a horizontal opening with CI or
steel bar gratings directly on the gutter to catch
large quantity of water.
It allows entering a large quantity of suspended
matters than curb inlet (refer to figure 4.6).
It is suitable for roads having steep slopes and
no problem of suspended matters.
Sewer outlet:
Figure 4.13
4.2.9. Trap:
In plumbing, a trap is a U-shaped pipe, S-shaped pipe, or J-shaped pipe located below or
within a plumbing fixture.
Because of its shape, the trap retains a small amount of water (the depth of water seal is
about 25 mm to 75 mm) after the fixture's use. This water in the trap creates a seal that
prevents sewer gas from passing from the drain pipes back into the occupied space of the
building.
Essentially all plumbing fixtures including sinks, bathtubs, and toilets must be equipped with
either an internal or external trap.
Most traps can either be disassembled for cleaning or they provide some sort of cleanout
feature.
Classification of traps
Traps are classified as follows:
(a) Classification according to the shape (Fig. 4.18)
(i) P-Trap (refer Fig. 4.18 a)
(ii) Q-Trap or half S-trap (refer Fig.4.18 b)
(iii) S-Trap (refer Fig.4.18 c)
The development of all these traps has been shown in Fig.4.19 (d).
Fig. – 4.22)
Fig. – 4.22).
Examples of traps