100% found this document useful (1 vote)
729 views

TM3 Monitoring Unit: Installation and Users Manual

This document provides a 3-sentence summary of the TM3 monitoring unit installation and users manual: The manual describes how to install the TM3 monitoring unit, including connecting various sensors to monitor temperature, flood detection, dry contacts and 4-20mA sensors. It also covers initial configuration of the unit through the web interface or SMS to set up sensor thresholds, alarm profiles and contact details. The document provides instructions for viewing sensor data and alarms through the unit's LCD display, web interface and alarm log to monitor environmental conditions.

Uploaded by

Andres Soto R
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
729 views

TM3 Monitoring Unit: Installation and Users Manual

This document provides a 3-sentence summary of the TM3 monitoring unit installation and users manual: The manual describes how to install the TM3 monitoring unit, including connecting various sensors to monitor temperature, flood detection, dry contacts and 4-20mA sensors. It also covers initial configuration of the unit through the web interface or SMS to set up sensor thresholds, alarm profiles and contact details. The document provides instructions for viewing sensor data and alarms through the unit's LCD display, web interface and alarm log to monitor environmental conditions.

Uploaded by

Andres Soto R
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 60

TM3 monitoring

unit installation and


users manual
contents
introduction 2 analogue names 25
product description 2 configuration page 26
document overview 3 4-20mA sensor configuration page 27
product certification 3 self test configuration page 29
related documents 3 temperature sensor configuration page 30
disabled alarms configuration page 32
physical description 4 uncleared alarms configuration page 33
inventory 7 general configuration page 34
additional parts 8 camera configuration page 35
SNMP configuration page 36
installation 9 security configuration page 37
install the TM3 unit 9 log out page 38
power cord, network cable
and GSM antenna connections 10 front panel functions 39
sensor connection 11 temp 39
temperature sensors 11 self test 40
flood sensors 11 disable/enable all alarms 41

dry contacts 11 clock 41

4-20mA sensors 12 enter 41

relay connection 12 GSM sms data access 42


initial configuration 13 view data 45
before the unit is used operationally the following home page 46
minimum configuration is required 13 alarm log 47
set the time and date 13 graph view 48
connecting laptop to TM3 14 camera view 49
GSM configuration 15 SNMP 50
ethernet/internet configuration (first time) 17
maintenance 51
configuration 19
contact configuration page 20
trouble shooting 52
alarm profile configuration page 21 clean the TM3 monitoring unit 53
dry contact alarm configuration page 22
disposal 53
analogue alarms configuration page 24
transmission selection 24 specifications 54

1
introduction
product description
The TM3 Monitoring Unit is a generic environmental monitoring system, capable of interfacing to various

sensors and communicating sensor status on Ethernet (web based), GSM and SNMP. Sensors which can be

connected include NTC temperature sensors, flood sensors, dry contacts and third party 4-20mA sensors.

The unit can be configured through the web interface and by SMS. Temperature Thresholds can also

be configured on the front panel keypad interface. Sensor levels and thresholds, alarm descriptions,

alarm profiles, contact details and communication data are configurable on the unit.

The TM3 Unit is capable of logging alarms and analogue sampled data which can be viewed from the

web interface. Images from a network enabled camera can be viewed on the web interface. Two

onboard relays for controlling external devices and a 12Vdc and 18Vdc power supplies are available on

the unit. The unit has battery backup capability during mains power failure. Onboard SD card saves all

programmed information. In the event of a unit failing the SD card is removed from the faulty unit and

inserted into a new unit and the TM3 is ready to monitor.

2
document overview
The TM3 Unit Installation and Users Manual describes how to install a TM3 Monitoring Unit, how sensors are connected and configuration
of the sensor inputs is performed. It also describes maintenance and fault finding. After performing the installation and configuration
procedures as set out in this document, the TM3 Unit is ready for installation specific configuration and operational environmental
monitoring.

product certification
The TM3 Unit CE certification is pending. The following IEC specifications are applicable to the TM3 Monitoring Unit:
n Electrical Fast Transients (EFT) IEC 61000-4-4
n Electrostatic Discharge (ESD) IEC 61000-4-2
n Surges IEC 61000-4-5
n Radiated Susceptibility IEC 801-3
n Voltage Dips and Interruptions IEC 61000-4-11
n Conducted Susceptibility IEC 61000-4-6
n Emissions and Harmonics IEC 61000-3-3 and IEC 61000-3-2
n General Products Safety Directive 2001/95/EC
n RoHS Compliance 2002/95/EC

related documents
Unless otherwise noted, the following documentation and software is available on the CD provided with the device or on the applicable
product page on the RT Systems website www.rtsystems.co.za
n Installation and Users Manual
n ICASA Approval Certificate
n GSM Module Certification Data
n IP Set Software
n IOD’s
n TM3 Base Station Programming Software.
Refer to the software help file for installation and users instructions.
n SD card default configuration files
n SNMP mib file

3
physical description
front panel

1 2 3 4 5

6 7 8 9 10 11

item description
GSM Transmit Indicator
1 TRM
This is a red LED and will light up during GSM transmission and reception.
Temperature setup select key
2 TEMP The temperature sensor thresholds and calibration settings are configured when selecting the TEMP key.
Press twice in succession to calibrate the sensors.
Down key
3 The down key is used to scroll through menus and decrement numerical values during system configuration
and setup.
Right key
4
The right key is used to move the cursor to the right during system configuration and setup.
Enter key
5 ENTER Press Enter to enter the telemetry menu where raw input data can be viewed. The Enter key is also used to
save setup data.

4
item description
Liquid Crystal Display
6 LCD
The LCD displays all the system data.
GSM Status Indicator
7 GSM n Flashing once every second – Initialising, not registered on the GSM network.
n Flashing once every three seconds – Registered on GSM network.
Self test select key
8 SELF TEST
By selecting the Self Test key the unit performs a sequence of tests to determine its own health status.
Up key
9 The up key is used to scroll through menus and increment numerical values during system configuration
and setup
Left key/Clock/Cancel
This is a multifunction key. Press to set up the time and date of the unit. When in a setup menu this key
10
can be used to move the cursor to the left. This key is also used to cancel menu selections when in a menu
select mode.
DISABLE Disable All Alarms
11 ALL By selecting this key all alarms will be disabled. To enable alarms select key or unit enables alarms after
ALARMS one hour. This will be indicated on the LCD and on the Web interface.

5
back panel

1 2 3 4 5 6 7 8 9

10 11 12 13

item description
GSM Antenna
1 SMA connector for GSM antenna connection.
Connector

2 VOLTAGE OUTPUT Provides one 18V dc, 50mA voltage output for sensor supply voltage.

3 4-20mA Inputs Three 4-20mA inputs available for connecting third party sensors.
Temperature
4 Four inputs available to connect NTC temperature sensors.
Sensor Inputs
FLOOD SENSOR
5 Two inputs available for multiple flood sensors in series terminated with a 10kΩ end of line resistor.
INPUTS
6 Voltage Output Provide two 12V dc, 200mA voltage outputs for sensor supply voltage.
DRY CONTACT
7 Eight dry contacts available for dry contacts.
INPUTS
DRY CONTACT
8 Seven dry contacts available for dry contacts.
INPUTS
9 RELAY OUTPUTS Used for relay controlled external devices.
10/100 Base-T
10 Provides for a 10/100 Base-T network connection with status and link LEDs indicate network traffic.
Network Port
11 On/Off On/Off switch for unit power.
12 Inlet Fuse Provides for input power protection. See maintenance parts for fuse rating.
13 AC Line Inlet Provides for the input power connection. See specification on page 54 for voltage information.

6
inventory
Inspect the contents of the package to ensure that the parts included match those shown below. Report

missing or damaged contents to RT Systems or your TM3 reseller. However, if damage was due to shipping,

immediately report the damage to the shipping agent.


item description

The shipping and packaging materials are recyclable. Please save them for later use or dispose of them
appropriately.

TM3 monitoring unit


The main component in the shipment.

utility cd
The utility CD contains the Installation and Users Manual, Certification data, TM3 Base Station Programming Software, ip Set Software,
snmp MIB file, oid’s, sd card default configuration files and Freeware SNMP browser link.

SD card
The SD Card is installed on the TM3 Monitoring Unit and contains default configuration data.

10 position terminal block


Included are six terminal blocks for interfacing to the terminals at the back of the TM3 Monitoring Unit.

GSM antenna
A GSM antenna is supplied. The antenna has a magnetic base for easy fitment.

power cord:
A mains lead with BS 546 plug is supplied.

cross-over ethernet cable


The supplied cross-over Ethernet cable is used for interface directly to a laptop.

installation pack
The supplied installation pack consists of 10 cable ties, 4 screws for mounting TM3 unit on 19” rack and 6 cable tie mounts.

7
additional parts
Additional parts are not supplied with the TM3 Unit. These parts are installation specific and are supplied

by the installer.

NTC temperature sensors


Analogue sensor.

humidity/temperature sensor (dry contact)


Alerts are activated by means of a contact closing/opening when threshold is reached.

flood sensor
The water detector will detect potential flood risks in the server room caused by condensation water form air cons or burst

water pipes.

4-20mA current transducer


Monitor the amperage of ups and generator distribution boards.

4-20mA humidity sensor


Monitor humidity in server rooms. High humidity – condensation. Low humidity – static.

smoke detector sensor


An important addition to security and safety. These smoke detectors are easy to install and configure. The smoke detector must be

mounted on the ceiling for maximum smoke detection.

door contact sensor


Monitor and be alerted when there is access to server rooms, server cabinets.

8
installation
install the TM3 Unit
The TM3 Monitoring Unit is enclosed in a standard 1U 19” enclosure. Install the unit in the front of the rack, which requires one U of

rack space. When installing the TM3 Monitoring Unit, take into consideration the following:

symbol description

C Caution: Only connect approved devices to ports on the unit as directed in this manual. Plugging in other
devices may result in equipment damage.

N
Note: Install the appliance in an environment compatible with the maximum ambient temperature specified
in “Specifications” on page 54. Units installed in a closed or multi-unit rack assembly can experience a
greater operating ambient temperature than the ambient room temperature.

N Note: Install the unit in a way that allows sufficient airflow for safe operation.

N Note: When you install the unit in the rack, be sure that you do not create a hazardous condition due to
uneven mechanical loading. For example, do not use the unit as a shelf.

N Note: When you install the GSM antenna, be sure that you have good GSM reception. Install the antenna
preferably outside the rack assembly for improved reception.

9
power cord, network cable and GSM antenna connections
symbol description

C
Caution: Before you energise the appliance, review the electrical specifications to avoid overloading

the circuit.

C
Caution: Make sure you properly ground the appliance by plugging the power cord directly into a wall outlet

or by verifying the ground path if using a power strip.

N Note: The power cord provided is to be used only with the TM3 Monitoring Unit.

N Note: Only use the GSM antenna provided with the unit.

1. Connect the supplied power cord to the AC Line Inlet of the unit.

2. Secure the power cord to the power cord retainer bracket using the tie wraps.

3. Connect the supplied network cable to the 10/100 Base-T Network Port on the unit.

4. Plug the power cord into a power source.

5. Connect the GSM antenna to the unit.

10
sensor connection
temperature sensors
Connect the NTC temperature sensor at the back of the unit marked “Temperature Sensors” to any one of the available four inputs. Dry

Contact Temperature sensors can be connected to any one of the 15 inputs marked “Dry Contact Inputs”. To extend the temperature

sensor use standard CAT-5 cable to a maximum distance of 100 metres. Tie the cable to the cable support at the back of the unit using

the tie wraps provided.

flood sensors
Use the supplied flood sensors on the TM3 Monitoring Unit. Connect the flood sensor at the back of the unit marked “Flood Sensors”

to any one of the available two inputs. The flood sensors can be extended using standard CAT-5 cable to a maximum distance of 100

metres. Tie the cable to the cable support at the back of the unit using the tie wraps provided. Flood sensors to be installed with the

10kΩ end of line resistor terminated on the last flood sensor.

connect to
10Ω
TM3 unit

dry contacts
Third party dry contacts can be used (Normally Open or Normally Closed contact). Connect the dry contacts at the back of the unit

marked “Dry Contacts” to any one of 15 available inputs. Extend the dry contact using standard CAT-5 cable to a maximum distance of

100 metres. Tie the cable to the cable support at the back of the unit using the tie wraps provided. The dry contacts can be configured

active open (HIGH) or active closed (LOW). Follow third party installation instructions provided with the dry contacts.

11
4-20mA sensors
Use third party 4-20mA sensors as per specification on page 8. Connect the 4-20mA sensors at the back of the unit marked “4-20mA

Sensors” to any one of three available inputs. Extend the 4-20mA sensors using standard CAT-5 cable to a maximum distance as

specified by the sensor manufacturer. Tie the cable to the cable support at the back of the unit using the tie wraps provided. The TM3

Monitoring Unit implements a 100Ω sense resistor to which the 4-20mA sensor connects. At the back of the unit two 12V (200mA) power

supply and one 18V (50mA) power supply outputs are available for sensor power supply. Ensure that the 4-20mA sensor does not

overload the power supply. Two wire and three wire sensor connections are shown below. 4-20ma sensors that are available: Humidity,

Temperature, Amperage.

two wire sensor connection three wire sensor connection


4-20mA sensors TM3 unit 4-20mA sensors TM3 unit

+ V= power in + V= power in
+ S= signal output - V= power in GND
+ S= signal output

relay connection
Connect the cable that is connected to external device to the back of the unit to either one of the two relays. Common/Normally Open

or Common/Normally Closed contacts can be used. Relays can be Energised/De-energised by either going into the Dry Contacts Alarms

Configuration Page and selecting 0 = De-energise or 1 = Energise or by sending an SMS command to the TM3 Unit.

12
initial configuration
before the unit is used operationally the following minimum configuration is required
symbol description
n Set the unit’s time and date

N
n Connect TM3 to Laptop

n Configure the GSM settings

n Configure the Ethernet/network

Power up the unit and wait ± 1 minute before starting with initial configuration. An “I” in the right hand corner of the LCD indicates the

unit is busy initialising. “I” will only disappear when the GSM configuration is complete. The default display is displayed on the LCD. The

data available on the default display is the Time, Day and Temperature value of Temperature Sensor 1.

set the time and date


To set the unit’s time and date press the “Left/Clock Key” on the front panel of the unit. The data available for configuration is the Time,

Day of week and Date. Use the Right and Left keys to move the cursor to the data field which has to be adjusted. By pressing the Up or

Down key the data field will be incremented or decremented. After all data fields have been adjusted to the correct values, press the

Enter key to store the data.

13
After the Enter key has been pressed the following display will appear for a couple of seconds.

connecting laptop to TM3


n Connect crossover cable from TM3 to Laptop

n Set the local area connection on Laptop

– Internet protocol (TCP/IP) Properties

– General

– Use the following IP address: 192.168.0.49

Access the web interface by opening Internet Explorer (IE) and enter http://192.168.0.50 in the address bar, the login page of the

unit will be displayed on IE. Enter the default administrator user name “admin” and password “admin”, note that all letters are

lower case, the user name and password are case sensitive. The Home Page will appear when logged in.

14
GSM configuration
The GSM needs to be configured before the unit will be able to send SMSs. This is done on the web interface by performing the following

steps:

symbol description

N The GSM configuration should be done before the Sim Card is installed in the unit.

From the Home Page of the TM3 Monitoring Unit select Configuration, now select GSM from the options and the following GSM setup

page will be displayed:

15
The following data can be configured:
n Cellular Number Enter the cellular number of the Sim card installed in the unit. International
number format is required. The correct number is required for the unit’s Self Test
function to operate correctly.
n GSM Service Centre Number (SMSC) Enter the service provider Service Centre Number in this field. Obtain number
from the cellular service provider.
n PIN Code Enter the Sim card PIN code. If Sim does not have a PIN then refer to the
section below ‘Steps to add Pin to Sim card.’
n PUK Code Enter the Sim card PUK code.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert
back to the previous settings. The data will not be stored in this case.

Insert the Sim card in the unit. Refer to the maintenance section of this manual for the location of the Sim card holder. Wait a few seconds
and the GSM status indicator will start flashing once every 3 seconds and the “I” on the display will disappear.

symbol description

N If the “I” does not disappear then unit must be switched off and then on to complete initialisation.

Steps to add PIN to Sim card (Steps 2 to 4 may vary on certain Cellphones):
1. Insert Sim into a cellphone
2. Go to ‘Security’ settings.
3. Select ‘Phone and Sim card’
4. Select ‘Pin code request’
5. Change to ‘On’
6. You will be prompted for a PIN number.
7. Enter a unique Pin, Pin will be rejected 3 times.
8. You will be prompted for the PUK number.
9. Enter the PUK number.
10. Enter Unique Pin.
11. Pin will be accepted, then follow the ‘GSM Configuration’ steps.

16
ethernet/internet configuration (first time)
The unit is shipped with the following default network settings:

n IP Address 192.168.0.50

n Gateway Address 192.168.0.2

n Sub-Net Mask 255.255.255.0

n DNS IP Address 192.168.0.4

The Ethernet data can be changed and configured on the web interface. Select Configuration on the Home Page icon bar, now select

Ethernet/Internet and the Ethernet/Internet Configuration page appears.

17
The following data can be configured:

n E-mail address 1 E-mail address 1 to where alarm messages can be sent. A tick box is available,

when ticked this address will be used.

n E-mail address 2 E-mail address 2 to where alarm messages can be sent. A tick box is available,

when ticked this address will be used.

n Transmit alarms to e-mail addresses Enable the checkbox to send alarm message to the e-mail addresses provided

above.

n IP Address of TM3 Configure a static IP Address for the TM3 Monitoring Unit.

n Subnet Mask Configure the network subnet mask.

n IP Address of gateway Configure the network gateway IP Address.

n DNS Server IP Address Configure the network DNS server IP Address.

n MAC Address of TM3 A read-only field which displays the Mac Address of the unit

n From e-mail address Configure the unit’s e-mail address.

n Outgoing mail server Configure the outgoing mail server address.

n Outgoing Mail Server (SMTP) Authentication Click on checkbox if SMTP server requires authentication.

n SMTP User name SMTP User name.

n SMTP Password SMTP Password.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

The IP Set utility on the CD can be used to set the TM3’s IP Address. Enter the unit’s Mac Address and the required TM3 IP Address.

symbol description
While the majority of SNMP servers do not require authentication, in a case where it is required please

N
provide the information as described in the outgoing mail server (SMTP) authentication section. If you are
using the Microsoft Exhange E-mail Service, a mail box needs to be created and the log in credentials
entered onto the system.

18
configuration
This section describes generic configuration procedures which are required to configure a unit for a specific operational installation.

Configuring a unit entails the following basic steps by selecting the appropriate TABS on the web interface TAB bar:

Set up your contacts in the Contacts Configuration Page. Here you specify all the numbers and
Step 1:
names to which SMSs have to be sent.
Contacts

Set up the alarm profiles in the Alarm Profile Configuration Page. This specifies which alarms have
Step 2:
to be sent to which contacts.
Alarm Profiles

Set up the dry contact alarms in the Dry Contact Alarm Configuration Page. Alarm descriptions,
Step 3:
active levels and Enable/Disable settings are done on this page.
Dry Contact Alarms

Set up the analogue alarms in the Analogue Alarms Configuration Page. Analogue alarms include
Step 4: the temperature, flood, 4-20mA sensors and TM power supply. Transmission selection, Alarm
Analogue Alarms descriptions, and Enable/Disable settings are done on this page.

Miscellaneous configuration is performed in the Configuration Page and include the following:
n 4-20mA Sensors where threshold levels are configured
n GSM (refer to Initial Configuration GSM Configuration on page 15)
n Ethernet/Internet (refer to Initial Configuration Ethernet/Internet Configuration on page 17)
n Self Test where a weekly self test is scheduled
n Temperature Sensors, where the temperature sensor sampling period, hysteresis levels and
threshold levels are configured
Step 5:
n Disabled Alarms, where a daily disabled alarms report is scheduled
Configuration Page n Uncleared Alarms, where a daily uncleared alarms report is scheduled
n General, the Site identification name is specified as well as the dry contact alarm delay time.
The software version of the unit is displayed in this page
n Camera. A network enabled camera can be viewed on the web – interface. In this page the
camera IP Address is configured. Change the administrator and user passwords in this page
n SNMP configuration is done on this page where access parameters are entered

Change the administrator and user passwords and configure the auto logout on this page.
Step 6:
Security

19
contact configuration page

From the Home Page of the TM3 Monitoring Unit select Contact Configuration Page. The following page will be displayed:

The following data can be configured:

n Cellular Phone Number Enter the cellular number of the contacts to which SMSs are required to be

sent. International number format is required.

n Detailed name description Enter the name of the contact. This can be a person or machine.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

20
alarm profile configuration page

From the Home Page of the TM3 Monitoring Unit select the Alarm Profile Configuration Page. The alarm profiles are configurable on
three separate pages ie, Alarm Profile Matrix 1, Alarm Profile Matrix 2 and Alarm Profile Matrix 3. Each has to be configured in order to
complete the profiles for all the alarms. The following page will be displayed for matrix 2:

The following selections can be done:


n Alarm tick boxes A particular alarm can be directed to send an SMS to a specific contact when
ticked in the corresponding Alarm Input vs Contact tick box.
n Select/Deselect All To select or deselect All Alarms. Note that this selection is only applicable to the
alarms displayed on this page.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

21
dry contact alarm configuration page

From the Home Page of the TM3 Monitoring Unit select the Dry Contact Configuration Page. The following page will be displayed:

22
The following data can be configured:

n Name Tag This is the alarm name which uniquely identifies the alarm.

n HI Description Tag This is the alarm fault condition if Active HI is selected. If Active LOW is selected

the normal condition description of the alarm is entered.

n HI SMS Tick Box Tick this box if an SMS is required when this alarm condition is activated.

n LO Description Tag This is the alarm fault condition if Active LOW is selected. If Active HI is selected

the normal condition description of the alarm is entered.

n LO SMS Tick Box Tick this box if an SMS is required when this alarm condition is activated.

n Alarm Message for LCD Enter the alarm condition description for the LCD.

n Active HI/LOW Select the Active HI alarm condition for Dry Contacts which are normally closed,

activating the alarm when open. Select Active LOW alarm condition for Dry

Contacts which are normally open, activating the alarm when closed.

n Enable/Disable Three selection options are available:

1 = Enable Notification of alarm will be made on the LCD and SMS

if selected.

0 = Disable Notification of alarm is disabled. The daily Disabled Alarms

report will include all disabled alarms.

P = Permanently Disabled Notification of alarm is disabled and is not

included in the Disabled Alarms report.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

23
analogue alarms configuration page

transmission selection
From the Home Page of the TM3 Monitoring Unit select Analogue Alarms Configuration Page and Transmission Selection. The following

page will be displayed:

The following data can be configured:

n SMS tick box Select which alarms will be sent by SMS.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

24
analogue names
From the Home Page of the TM3 Monitoring Unit select Analogue Alarms Configuration Page and Analogue Names. The following page
will be displayed:

The following data can be configured:


n Name Tag This is the alarm name which uniquely identifies the alarm.
n LCD Identifier Enter the alarm condition description for the LCD.
n Enable/Disable Three selection options are available:
1 = Enable Notification of alarm will be made on the LCD and SMS
if selected.
0 = Disable Notification of alarm is disabled. The daily Disabled Alarms
report will include all disabled alarms.
P = Permanently Disabled Notification of alarm is disabled and is not
included in the Disabled Alarms report.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert
back to the previous settings. The data will not be stored in this case.

25
configuration page

The following configuration options are available on the Configuration Page:

n 4-20mA Sensor 1

n 4-20mA Sensor 2

n 4-20mA Sensor 3

n GSM

n Ethernet/Internet

n Self Test

n Temperature Sensors

n Disabled Alarms

n Uncleared Alarms

n General

n Camera

n SNMP

26
4-20mA sensor configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page. Select one of the three 4-20mA Sensor options for

configuration. The following page will be displayed. (The configuration procedure for all three sensors is identical.)

27
The following data can be configured:

n 4mA signal (zero level value) Enter the zero level of the connected sensor, corresponding to its 4mA level, in

this field.

n 20mA signal (full scale level value) Enter the full scale level of the connected sensor, corresponding to its

20mA level, in this field.

n Units of measure Enter the connected sensor units of measure, ie %RH for a humidity sensor.

n Alarm activation level The level at which an alarm needs to be activated is entered in this field.

n Hysteresis Enter the hysteresis level, below or above (depending on the activation direction)

the activation level at which the alarm will be de-activated. (Ref. note 1, pg 31)

n Alarm activation direction Select the alarm activation direction, ie increasing values or decreasing values.

n Sampling period Select the sampling period at which the sensor is sampled for display on the

Graph View. A maximum of 1 440 sample points are stored.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

28
self test configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select Self Test. The following page

will be displayed:

The following data can be configured:


n Day of scheduled weekly Self Test Select the day of the week when the scheduled self test will be performed.

n Time for scheduled weekly Self Test Enter the time of day when the scheduled self test will be performed.

n Send Self Test Result to e-mail addresses Tick this box if the self test result is required to be e-mailed to the addresses

configured in the Ethernet/Internet Configuration Page.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

29
temperature sensor configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select Temperature Sensors. The

following page will be displayed:

The following data can be configured:

n Non-critical Temperature sensor hysteresis (T1) Enter the hysteresis1 level below the Non-critical Threshold level, at which the

alarm will be de-activated.

n Critical Temperature sensor hysteresis (T2) Enter the hysteresis1 level below the Critical Threshold level, at which the alarm

will be de-activated.

n Sampling Period Select the sampling period at which the sensor is sampled for display on the

Graph View. A maximum of 1440 sample points are stored.

n Non-critical Threshold Enter the Non-critical Threshold level for the temperature sensor at which the

alarm will be activated.

n Critical Threshold Enter the Critical Threshold level for the temperature sensor at which the alarm

will be activated.

30
Note 1: Hysteresis represents the difference between the alarm activation set point (threshold) and the alarm cleared value. For example,

temperature sensor 1, non-critical alarm will be triggered at 26° C when the temperature increases, the alarm will be de-activated below

24° C due to the configured 1° C hysteresis. The following figure explains hysteresis further.
23°C 25°C 26°C

Alarm Triggered

Temperature decrease

Temperature increase
Alarm de-activated
 

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

31
disabled alarms configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select Disabled Alarms. The

following page will be displayed:

The following data can be configured:

n Time for broadcasting daily Disabled alarms report Enter the time of day when the daily Disabled alarms report will be compiled

and sent.

n Send Disabled alarms report to e-mail addresses Tick this box if the Disabled alarms report is required to be e-mailed to the

addresses configured in the Ethernet/Internet Configuration Page.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

32
uncleared alarms configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select Uncleared Alarms. The

following page will be displayed.

The following data can be configured:


n Time for broadcasting daily Enter the time of day when the daily Uncleared alarms report will be

Uncleared alarms report compiled and sent.

n Send Uncleared alarms report to Tick this box if the Uncleared alarms report is required to be e-mailed to

e-mail addresses the addresses configured in the Ethernet/Internet Configuration Page.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

33
general configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select General. The following page

will be displayed:

The following data can be configured:

n SITE ID of TM3 Enter a unique identification for the unit.

n Predefined Time Delay for discrete alarm inputs Select the discrete alarms time delay. This is the elapsed time from activation

of the alarm until the alarm is reported. Selection between 1 and 10 seconds

are available.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

34
camera configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select Camera. The following page

will be displayed:

The following data can be configured:

n IP address of Camera Enter the IP Address of the camera to be accessed.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

CCTV options that the TM3 can interface with:


n IP Camera – Stand-alone IP Camera can be viewed on the TM3 which would just allow viewing

n Digital Video Recorder (DVR) – Can display and record images from up to four cameras. Cameras and recordings can be viewed,

managed and configured via the DVR interface. The DVR can be set to record images upon motion detection, record images

according to a preset schedule or record images continuously. Communication with a site is available through the use of the audio-

in and audio-out functionality. A further four sensor inputs are available on the DVR which can trigger recordings, send email

notifications, sound alarms, and activate the available relay-output. To configure this device and the cameras please refer to the

CCTV manuals.

35
SNMP configuration page
From the Home Page of the TM3 Monitoring Unit select Configuration Page and from the option list select SNMP. The following page

will be displayed:

The following data can be configured:


n SNMP Manager IP address 1 IP Address to where SNMP traps are sent.

n SNMP Manager IP address 2 IP Address to where SNMP traps are sent.

n SNMP Manager IP address 3 IP Address to where SNMP traps are sent.

n SNMP Version 3 support Select between SNMP version 1 and SNMP version 3.

n SNMP v3 User Enter the Read Community for version 1 or the User name for version 3,

depending on the selection of point 4.

n SNMP v3 Password Enter the Write Community for version 1 or the Password for version 3,

depending on the selection of point 4.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert

back to the previous settings. The data will not be stored in this case.

36
security configuration page

From the Home Page of the TM3 Monitoring Unit select Security. The following page will be displayed:

The following data can be configured:


n Administrator password Change the administrator password. The administrator has read and write access of the
data, ie. can view and configure data. The default administrator password is “admin”.
n User password Change the user password. The user only has read access of the data ie can only
view data. The default user password is “user”.

n Log out automatically If ticked then unit will log out automatically.

n Auto log out timeout (min) Set the time (1-99 min) of when the unit must log out automatically.

Select Save to store data on the unit after all fields have been configured. Select Cancel and follow the prompted instructions to revert
back to the previous settings. The data will not be stored in this case.

symbol description

N Only one log-in connection is allowed on the TM3 Monitoring Unit. After accessing the web interface log out,
see next paragraph.

37
log out page

From the Home Page of the TM3 Monitoring Unit select Log Out. The following page will be displayed:

The operator will be prompted to confirm log out when Log Out is selected.

38
front panel functions
On the front panel of the TM3 Monitoring Unit there are a couple of functions available to either configure the unit or select a particular

function. The functions available are the following:

n TEMP Configure the temperature sensor thresholds and calibration data.

n SELF TEST Performs a self test of the unit.

n Disable/Enable All Alarms Disables or enables all alarms.

n Clock Set the time and date of the unit.

n Enter Displays raw input data for installation/fault finding purposes.

temp
To set a sensor’s temperature thresholds press the “Temp” key on the front panel of the unit.

Select the sensor to be configured by pressing “Temp” until the correct sensor number is displayed. Then press “Enter” to display the

current sensor threshold values.

The data available for configuration is “Non-Critical” and “Critical”. Use the Right and Left keys to move the cursor to the data field which

has to be adjusted. By pressing the Up or Down key the data field will be incremented or decremented. After all data fields have been

adjusted to the required values, press the Enter key to store the data.

A “Thresholds Stored” message will appear briefly while the data is being stored.

39
self test
By selecting the Self Test key, the unit performs a sequence of tests to determine its own health status. While the test is in progress, the

following screen will be displayed:

Once the self test has been completed, a message will be displayed indicating whether the test has been successful or not. In the event

of the test being successful, a “Self Test Pass” message appears on the LCD, else a “Self Test Fail” message will be displayed along

with a relevant message indicating the area of failure which can be one of the following:
n GSM Card Fault

n Ethernet Fault. Ethernet functionality will only be tested if the “Transmit alarms to e-mail” is ticked in the Ethernet/Internet

Configuration  page

n Power Supply Fault

40
disable/enable all alarms
By selecting the Disable/Enable All Alarms key, all alarms will be disabled. Indication of this condition is displayed on the LCD as well as

on the right top corner of the Home Page. To enable all alarms the Disable/Enable All Alarms key must be pushed again. Alarms will

enable after one hour if the Disable/Enable All Alarms key is not selected within the hour.

clock
Refer to the initial configuration section for the time and date configuration on page 13.

enter
Press Enter to select the telemetry menu where raw input data can be viewed. The following screen will appear:

Press Enter again to view ADC telemetry data. The following data can be viewed:
n Input voltage level

n Temperature sensors 1 to 4

n Flood sensors 1 and 2

n 4-20mA sensors 1 to 3

n GSM signal strength

To return to the main menu, press the Left/Clock/Cancel key.

41
GSM sms data access
The TM3 Monitoring Unit can be configured and interrogated using SMS messages. The SMS commands are listed below. Included on

the utility CD is a software utility MonitorProg.exe which can be used for configuration of the unit. Refer to the help function of the

software for operator instructions.

Message Structure Symbol Descriptions:

= Space
Y = Relay 1 or 2
YY = Alarm Number
XX = Minutes

no. sms message text description command valid message structure


string value
general
1 What is your Site ID? abc123 abc123
2 What is your signal strength? dabc12 dabc12
3 What is your time, day and date? 9aaaaa 9aaaaa
4 What is the software version of the Operating System? nBg006 nBg006
contacts
what is name and number of contact
5 What is the name and number of Contact 1? Anjm46 Anjm46
6 What is the name and number of Contact 2? Lmki12 Lmki12
7 What is the name and number of Contact 3? Alop12 Alop12
8 What is the name and number of Contact 4? 192ui7 192ui7
9 What is the name and number of Contact 5? zzxxcc zzxxcc
10 What is the name and number of Base station 1? 1op901 1op901
11 What is the name and number of Base station 2? anqoka anqoka
12 What is the name and number of Self Test Computer? cvbnam cvbnam
13 What is the name and number of Un-cleared/Disabled Alarms? qpoilm qpoilm
14 What is Name and No. of Global Alarm Contact? tsv319 tsv319
alarm status
15 Disable all alarms hgFeda hgFeda

42
no. sms message text description command valid message structure
string value
16 Disable all alarms for XX minutes nBg022 nBg022 XX
17 Re-enable all alarms Kkp5ef Kkp5ef
18 Disable alarm number YY jhgFed jhgFed YY
19 Permanently disable alarm number YY Vaq7b1 Vaq7b1 YY
20 Re-enable alarm number YY Lkp6ef Lkp6ef YY
21 What is the status of alarm number YY? (Active or Not) 9aaaac 9aaaac YY
relays
22 Make Output Y HI (Y = 1 or 2) 9aaaad 9aaaad Y
23 Make Output Y LO (Y = 1 or 2) 9aaaae 9aaaae Y
24 What is the Name Tag of Output Y? (Y = 1 or 2) nBg011 nBg011 Y
dry contact alarms
name tag
25 What is the Name Tag of alarm number YY? Jkp2ef Jkp2ef YY
hi description tag
26 What is the HI Description of alarm number YY? Gkp9ef Gkp9ef YY
lo description tag
27 What is the LO Description of alarm number YY? Hkp0ef Hkp0ef YY
configuration
self test
28 Perform a self test gFedab gFedab
29 What is your scheduled Self Test day and time? nBg007 nBg007
un-cleared alarm transmission
30 What is the scheduled time for un-cleared alarm transmissions? nBg014 nBg014
disabled alarm transmission
31 What is the scheduled time for disabled alarm transmissions? nBg012 nBg012
temperature sensors
temperature 1
32 What is the value of temperature 1? 9aaaab 9aaaab
33 What is the non-critical temperature threshold for sensor 1? nBg018 nBg018

43
no. sms message text description command valid message structure
string value
34 What is the critical temperature threshold for sensor 1? nBg019 nBg019
temperature 2
35 What is the value of temperature 2? 6kjG25 6kjG25
36 What is the non-critical temperature threshold for sensor 2? 6kjG28 6kjG28
37. What is the critical temperature threshold for sensor 2? 6kjG29 6kjG29
temperature 3
38 What is the value of temperature 3? 6kjG26 6kjG26
39 What is the non-critical temperature threshold for sensor 3? 6kjG32 6kjG32
40 What is the critical temperature threshold for sensor 3? 6kjG33 6kjG33
temperature 4
41 What is the value of temperature 4? 6kjG27 6kjG27
42 What is the non-critical temperature threshold for sensor 4? Vaq1b2 Vaq1b2
43 What is the critical temperature threshold for sensor 4? Vaq1b3 Vaq1b3

44
view data
The TM3 Monitoring Unit displays and collects numerous types of data which can be viewed on the web interface. Data can also be

accessed by SNMP and GSM SMS. On the web interface the following data can be viewed:

On the Home Page some configuration data is displayed. Alarm status and analogue values
Home Page
are displayed.

Alarm Log A record of the last 240 alarms can be viewed.

A graph of the temperature and 4-20mA sensors can be viewed. The graph contains
Graph View
1 440 data samples.

Camera View Connected camera images can be viewed on this page.

45
home page

The Home Page of the TM3 Monitoring Units displays the following information:
n Site IP address
n GSM number of the unit
n Site ID
n All alarms enable/disable status
n Individual alarms enabled/disabled status
n Temperature values of all four temperature sensors
n 4-20mA values with units
n Status of all alarms, red filled indicates alarm condition

n Relay condition, green filled indicates energised

46
alarm log

The time, date and alarm description is displayed on the alarm log. Up to 240 log entries are stored.

47
graph view

The analogue sensors sampled data are viewable on the web interface. The sensor name, start date and time as well as the sampling

period are displayed on the graph. Select the required sensor graph from the drop down list and select Update. By selecting

Download, Graph data can be viewed or saved on a PC in Microsoft Office Excel Worksheet Format.

48
camera view

Typical camera image of a computer room displayed on the web interface.

49
SNMP
The TM3 Monitoring Units implements SNMPv1 and SNMPv3 selectable on the SNMP Configuration Page.
SNMPv3 has the advantage of authentication above SNMPv1.

The following SNMP functionality is available on the TM3 Monitoring Unit.

Refer to the TM3 MIB.txt file supplied on the utility disc. The TM3 unit has been tested on the following freeware MIB browsers:

1. iReasoning

2. Whats up Gold

3. Service Check

sensor reading:
Read or Get of all four temperature sensor values and 4-20mA sensor values.

sensor alarm thresholds:


Read or Get1 and Set2 on all four temperature sensors for critical and non-critical thresholds as well as the 4-20mA thresholds.

alarm status:
Read or Get and Walk3 of all alarms 1 to 34 alarm status. This includes all temperature sensors, 4-20mA sensors, Flood Sensors, TM
Unit, DC voltage, Mains Power, Discrete Input Alarms and Relay Status.

traps:
Traps4 are sent for all alarms 1 to 34 as described above.

Note 1: Get is an SNMP function to retrieve data from the unit.


Note 2: Set is an SNMP function to modify data on the unit.
Note 3: Walk is an SNMP function to retrieve all the status data from the unit.
Note 4: Traps are SNMP messages of alarm triggers, transmitted by the unit to a network management system which monitors the

unit outputs.

50
maintenance
symbol description

N
NOTE: only qualified service and installation personnel are allowed to perform maintenance tasks on the TM3

Monitoring Unit.

W
WARNING: high voltage (110V/2240Vac) warning inside the TM3 enclosure.

The following items can be replaced as part of required maintenance.

C F

51
item description
A Power Inlet Fuse, 2A, 250V, 5x20 Glass Fuse
B Battery Fuse, 2A, 250V
C Power Supply
D 12V, 2.3AH Sealed Lead Acid Battery, PN PS2.3-12
E 3V Coin Cell Battery, CR2032
F SD Card
G GSM Sim Card

trouble shooting
problem cause/correction
Unit does not n Check that SD Card is installed and that default or specific configuration data is on the SD Card. Copy
complete initialization default configuration files from CD if not on SD Card.
n Check that the Sim Card is installed in the GSM Board.
n Check that the Sim Card PIN is configured correctly.
GSM Card Failure n Check that the GSM number is correct on the GSM Configuration Page. The unit sends an SMS to itself
during Self Test during self test and if the number is incorrect the SMS is not received.
The unit does not
n Check the fuse on the inlet AC adapter and replace if fused.
turn on
Unit switches off
n Check Battery Fuse and replace if fused.
during mains failure
n Check that backup battery is charged and healthy.
No SMS is sent when n Check that the GSM number is correct on the GSM Configuration Page. Number must be in
alarm is activated international  format.
n Check that the SMSC number is correct on the GSM Configuration Page. Number must be in international
format (check with your local cellular service provider for SMSC number)
n Check that the PIN number is correct on the GSM Configuration Page. Follow steps on page 16 if PIN
on SIM is not activated.
n Check that the PUK number is correct on the GSM Configuration Page.
n Check that SMS tick box is ticked in Dry Contacts Configuration Page.

52
n Check that SMS tick box is ticked in the appropriate Alarm Profile Matrix.
n Check that the associated contact number is entered and correct.
n Check that the GSM signal strength is at least more than 10.
n Check that your Sim card is paid up.

clean the TM3 monitoring unit


To clean the TM3 Monitoring Unit, gently wipe surfaces with a clean, dry cloth.

disposal
symbol description

WARNING: The TM3 unit contains replaceable lithium coin cell and lead acid batteries. Please take the

W batteries into consideration when disposing of the unit.

53
specifications
electrical
n Input voltage, nominal 110–240 VAC; 50/60 Hz
n Maximum total current draw 0,5 A

physical
n Dimensions (H x W x D) 44,45 x 480 x 282mm (Standard 1U 19” Rack)
n Weight 4,6 kg

environmental
n Elevation (above MSL)
Operating 0 to 3 000 m (0 to 10 000 ft)
Storage 0 to 15 000 m (0 to 50 000 ft)
n Temperature
Operating 0 to 45º C
Storage –15 to 65° C
n Humidity
Operating 0 to 95%, non-condensing
Storage 0 to 95%, non-condensing

output voltages
n Voltages 2 x 12Vdc and 1 x 18Vdc
n Current 2 x 200mA and 1 x 50mA

sensor inputs
Temperature sensors ±3°C
4-20mA sensors ±5%

power backup
n Battery backup time 4 to 6 hours, depending on current drawn on external power supplies

54
compliance (pending)

n Electrical Fast Transients (EFT) IEC 61000-4-4

n Electrostatic Discharge (ESD) IEC 61000-4-2

n Surges IEC 61000-4-5

n Radiated Susceptibility IEC 801-3

n Voltage Dips and Interruptions IEC 61000-4-11

n Conducted Susceptibility IEC 61000-4-6

n Emissions and Harmonics IEC 61000-3-3 and IEC 61000-3-2

n General Products Safety Directive 2001/95/EC

n RoHS Compliance 2002/95/EC

55
Notes
Notes
RT Systems Johannesburg RT Systems Cape Town
physical address postal address physical address
157 Barry Hertzog Ave Postnet Suite 93 34 Wandel Street
Emmarentia Ext 1 Private Bag X7 Gardens
2195 Parkview Cape Town
South Africa 2122 8001
tel cell
+27 11 646 5250 +27 83 547 9740
fax tel
+27 11 646 5704 +27 21 461 0558
e-mail fax
[email protected] +27 21 461 7457

www.rtsystems.co.za e-mail
[email protected]

You might also like