Rex Power Magnetics Catalog
Rex Power Magnetics Catalog
DRY TYPE
TRANSFORMERS
DISTRIBUTION TRANSFORMERS
STANDARD & SPECIAL SPEC
K-FACTOR RATED
DRIVE ISOLATION
ELECTROSTATIC SHIELDED
AUTOTRANSFORMER
ENCAPSULATED
A Aluminum (where available) ESP Special Enclosure spec (eg: Special paint color, tamper
Rex Power Magnetics is the industry leader in delivery responsiveness, proof, enclosure with doors, etc)
supported by our vertically integrated in-house design, manufacturing, and
testing capabilities. We pride ourselves on our technology leadership supported ③ - Base kVA Rating K13 K-Factor rated (K4, K9, K13, K20, K30)
by our extensive R&D activities, engineering expertise, and manufacturing Standard 1 phase kVA levels: M Special markings, nameplate, tag, etc.
know-how. 1, 2, 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 150, 200, 250, 330
S1 Electrostatic Shielding (S1, S2, S3) (see pg 16)
Standard 3 phase kVA levels:
3, 6, 9, 15, 30, 45, 75, 112.5, 150, 225, 300, 450, 500, 750 T115 Temperature rise 115 ˚C
T80 Temperature rise 80 ˚C
④&⑤ - Primary & Secondary Winding Voltage(s)
W1 6 taps: 2 x 2.5% FCAN, 4 x 2.5% FCBN
For Single Phase: Use Group 1. Use group 2 for split
X Special feature (eg: Specified dimensions, inrush rating,
windings.
impedance, vector diagram, etc.)
For general information about Rex Power Magnetics, our complete product For Three Phase: Use Group 1 for delta windings; use group
3 for wye (star) windings. Y1 External neoprene anti-vibration pads supplied
offering, and our general terms of sale, please visit our website: www.
rexpowermagnetics.com For Autotransformer: Use Group 1 only. Y2 Special Lugs (deviation from standard)
Rex has print/PDF catalogs available for: For a voltage other than the ones indicated below, use X
• Power Transformers (under 1000 V).
⑦ - Efficiency Level
• Transformers for Hazardous Locations
Group 1 Group 2 Group 3 For more information about transformer efficiency and the
• Control Transformers
• Reactors A 120 H 480 K 120/240 M 208Y/120 minimum efficiency levels, see page 6.
• Mini Power Centers A1 115 H1 460 K1 115/230 N 416Y/240 No suffix For transformers which are excluded from
A2 110 H2 440 K2 110/220 N1 400Y/231 minimum efficiency legislation.
Table of Contents B 208 J 600 L 240/480 N2 415Y/240
Z3 Meets or exceeds current North American
Topic Page B1 200 J1 575 L1 230/460 P 480Y/277
minimum efficiency standards, known as
C 240 J2 550 L2 220/440 P1 460Y/266 NRCan 2019 (Canada) and DOE 2016 (USA).
Rex Part Numbering System 2
C1 230 J3 690 P2 440Y/254
Transformer Selection 3 ZX Custom efficiency level, to be specified.
C2 220 Q 600Y/347
General Product Information 4-8
D 277 Q1 575Y/332 There exist a number of legacy efficiency levels that have
Isolation Transformer - Single Phase 9 - 12
E 347 Q2 550Y/318 been phased out (Z, Z2, ZCSL3, ZNP). Inquire with Rex sales
Isolation Transformer - Three Phase 13 - 18 F 380 Q3 690Y/398 if clarification is required on these levels.
Autotransformers (Single & Three Phase) 19 - 24 G 416 R 380Y/220
Encapsulated Transformers (Single & Three Phase) 25 - 30 G1 400 S 240Y/139
Shielded Transformers 31 G2 415 S1 230Y/133
K Factor rated transformers 32 S2 220Y/127
Drive Isolation Transformers 33 - 38
Pg. 1 Pg. 2
Transformer Selection General Product Information
For each of the products in this catalog, there are details about their intended application and purpose; Rex’s standard
specification is shown, and available alternate specifications are described. To select the rating for the desired transformer, Lifting Eyes
a number of factors may be relevant: Provisions for future expansion, oversizing for purposes of efficiency or redundancy,
etc. Fundamentally, however, the kVA rating is derived from the required Voltage [V] and Current [A]. The formulas and
tables below may serve as a convenient reference.
Three Phase𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉
Applications
× 𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴 × 1.73
𝑘𝑘𝑘𝑘𝑘𝑘!∅ = Grounding Strap
• Determine primary (supply)
1000 voltage and secondary (load) Line current [A] at rated Three Phase voltage Mechanical type
voltage. Determine currents.
• Confirm 3 phase, 60 Hz operation
kVA 208 V 240 V 480 V 600 V terminal lugs (Al/Cu)
• Determine kVA rating by×
𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉 formula
𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴or lookup table, to meet 3 8.3 7.2 3.6 2.9
𝑘𝑘𝑘𝑘𝑘𝑘required
or exceed !∅ = current. 6 16.6 14.4 7.2 5.8
• Select a standard kVA rating1000equal to or greater than Neoprene
requirement. 9 25.0 21.7 10.7 8.7
Anti-vibration isolators
• Make a determination of transformer type (IE 15 41.7 36.1 18.1 14.5
Autotransformer, K-Factor Rated, Encapsulated, Isolation Low Voltage
transformer, etc). 30 83.4 72.3 36.1 28.9 Winding end-margin supports and winding
45 125 108 54.2 43.4 blocking for mechanical support of the coil
75 208 181 90.3 72.3
Formula for calculating Three Phase kVA Reinforced Cooling ducts
112.5 313 271 135 108
𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉 × 𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴 × 1.73 150 417 361 181 145
𝑘𝑘𝑘𝑘𝑘𝑘!∅ =
1000 225 625 542 271 217 High-temperature insulation
*Use line-line volts Optional Electrostatic Shield
300 834 723 361 289
High Voltage
Transformer Rating for Motor Horsepower (HP, Three Phase)
Heavy-duty formed steel core clamps with winding
Motor HP 2 3 5 7.5 10 15 20 25 clamping-bolts and metallic tie plates
Actual kVA Required 2.4 3.42 5.73 8.4 10.3 15 19.8 24.4
Closest Standard kVA 3.0 6.0 6.0 9.0 15 15 30 30
Pg. 3 Pg. 4
General Product Information General Product Information
The following attributes are generally applicable to the each of the products detailed in this catalog. Specific details, Lugs, Terminals, Connections Seismic Rating
exceptions, and variants are noted in each product’s corresponding section.
• Transformers ship with suitably sized mechanical Cu-Al • Rex transformers were shake table tested for Seismic
Core Design & Approvals lugs and hardware for cable connection, or suitably withstand capability in accordance with the combined
sized and cleaned terminal pads with the appropriate requirements of the International Building Code 2012
• Rex three-phase transformers utilize three-legged cores • CSA certified, File No. LR 34493 NEMA hole pattern. (IBC 2012), The California Building Code 2013 (CBC
and single-phase transformers utilize two-legged cores, • UL Listed, File No. E108255 • As an option, special lugs and non-standard terminal 2013), and the National Building Code of Canada
unless otherwise specified. Alternate constructions are • Transformers are designed with sophisticated locations may be specified and quoted. 2010 (NBC 2010). As required by these codes, Rex
available such as shell-type, four-leg, and five-leg. computerized modeling tools, based on years of • 3-phase isolation transformers up to 300 kVA (600 transformers demonstrated their ability to function after
• Only high-quality grain-oriented silicon steel is used. research and test data. Designers are capable of V or 480 V to 208Y/120 V), and 1-phase isolation the seismic tests, when suitably bolted & anchored to a
Core steel is precision cut and stacked for reduced noise exploiting the benefits of the latest in high performance transformers up to 100 kVA (600 V or 480 V to fixed structure.
and losses. Cores are clamped with heavy-duty steel materials that have become available, such as high- 240/120V), are supplied with lugs on primary and • Rex Power Magnetics cannot provide seismic
brackets and metallic tie plates. permeability laser-scribed grain-oriented silicone steel secondary terminals per column 1 of the table below. engineering consulting services. Rex’s seismic approval,
• A variety of core construction methods are available, and high-temperature conductor insulation. • Isolation transformers where Primary or Secondary combined with information about transformer mass and
such as “Step-lap miter-core,” “Distributed-gap core,” • Rex Standard Isolation transformers are manufactured voltages are other than those indicated above, or the center of gravity can simplify the work of the seismic
and “Interleaved butt-stacked core.” with insulating materials that comply with CSA Winding rating exeeds 300 kVA (3Ø), or 100 kVA (1Ø), primary engineer, reducing overall project costs.
Coils Insulation System Class 220 °C as follows: Maximum and secondary lugs are provided per column 2 of the • Rex has available a variety of vibration absorbing
acceptable temperature rise based on average ambient table below. materials, and can supply seismic spring/snubber
• All Rex windings (coils) are of high quality magnet wire of 30 °C during any 24 hr period and a maximum • Drive Isolation Transformer, Encapsulated Transformers, assemblies, where specified by outside engineer.
(copper or aluminum are available). ambient of 40 °C at any time. Altitude not to exceed and Autotransformers are supplied with primary and
• Class 220 °C insulation is used throughout the coil 1000 m (3000 ft) above sea level. Rex can accommodate secondary lugs per column 2 of the table below.
Transformer Efficiency
winding process. Class 220 is the highest insulation specs for special ambient and altitude. • Transformers must meet regulations for minimum
level recognized by the transformer industry. • Unless otherwise specified, Rex follows applicable CSA/ Rex Lug Name efficiency levels. The rules are applicable for kVA levels 15
Current [Per phase] Range of Wire
• Coils are designed with reinforced cooling ducts. UL guidelines and internal engineering guidelines for kVA and up (1 and 3 phase). Some transformer types are
Range Size per Lug
• The complete core & coil assembly is impregnated in electrical performance criteria such as X/R ratio, Voltage Col. 1 Col. 2 excluded. For transformers where compliance is required,
polyester resin and baked. Regulation, Inrush Current, Impedance, Losses, Short Up to 90 A LA LA 2-14 AWG the transformer bears the “Green Line” trademark.
• Standard ±5% or ±2 x 2.5% primary voltage taps are Circuit Withstand Performance, and Electromagnetic
Green Line
91 - 135 A LB LB 2/0 -6 AWG
provided on all isolation type transformers. Alternate Field Intensity. 136 - 230 A LC LC 300 MCM - 6 AWG
tapping arrangements are available depending on Temperature Rise 231 - 340 A LD LD 600 MCM - 2 AWG
High Efficiency Transformers
product and size. • Canadian and US minimum efficiency levels are
• Taps for supply voltage compensation are pre-cleaned • Rex transformers are designed with due consideration 341 - 368 A 2xLC Pads 300 MCM - 6 AWG
to ensure that the hottest spot in the coil does not 369 - 544 A 2xLD Pads 600 MCM - 2 AWG
harmonized. They are commonly referred to as “NRCan
and rated for the full-capacity of the transformer. 2019” and “DOE 2016,” respectively.
exceed the temperature class of the insulation. 545 - 714 A 3xLD Pads 600 MCM - 2 AWG
Vector Diagram • Ordinary ambient conditions are defined to be ranging • In Canada, the NRCan 2019 referes to Natural Resources
715 - 952 A 4xLD Pads 600 MCM - 2 AWG
from -20 °C to +30 °C (daily average), with a max Canada “SOR/2018-201, Amendment 14.” Provincial rules
• For transformers where a Delta primary and a Wye 952 A + Pads Pads n/a are harmonized so as to make the rule enforceable for
secondary are specified, Rex’s standard vector temporary ambient of 40 °C. CSA and UL provide
configuration is Dyn1 (30° phase shift, lagging). guidelines for estimation of the hot spot relative to the Sound Level interprovincial trade. In Ontario, the rule is known as “ON
average. Reg. 404/12.” The applicable Test Standard is C802.2-
• Rex is able to provide Dyn11, Dd, Yy, and a number of When energized, transformers emit a hum, largely due
• Rex utilizes class 220 °C insulation throughout the coil 2012.
other vector configurations per specification. Please to the magnetization of the core. The tables below show
for ventilated transformers that are designed with 150 • In USA, the DOE 2016 refers to CFR 10 part 431.
include X in the part number. the maximum audible sound levels for each kVA range.
°C rise. Specifying 115 °C or 80 °C rise is available as an • In forming the Rex Part Number for your transformer, use
Rex transformers comply with these maximums; Modern
Testing option. high efficiency transformers operate with sound levels far
suffix Z3 where efficiency levels are applicable.
• Excluded transformer types:
• Rex Power Magnetics produces and tests all products in below theses levels. Further lower sound levels can be
• Transformers with a nominal • Non-ventilated transformers
full compliance with the requirements of its CSA and UL specified. Column 1 indicates the maximum for ventilated frequency other than 60 Hz (incl. encapsulated transformers)
approvals. transformers. Column 2 indicates the maximum for sealed • Autotransformers • testing transformers
• Reference test standards & documents include: transformers, as well as encapsulated transformers. • Drive (isolation) transformers • furnace transformers
• CSA C22.2 #47 that have two or more • welding transformers
Single Phase Three Phase
• UL 1561 output windings or a nominal • Special impedance transformers
• UL 5085-2/CSA C66.2 Rating Col 1 Col 2 Rating Col 1 Col 2 low-voltage line current of • Transformers that have a
• CSA C66.1 [kVA] [dB] [dB] [kVA] [dB] [dB] more than 1500 A; nominal low-voltage line current
• Grounding transformers of 4000 A or more;
• CSA C9 0-9 40 45 0-9 40 45
• Rectifier transformers • On-load regulating transformers
• IEEE C57.12.91 10 - 50 45 50 10 - 50 45 50
• The Rex test facility has been certified based on ISO/ Packaging & Warranty 51 - 100 50 55 51 - 150 50 55
• Sealed transformers • Resistance grounding
transformers
IEC 17025:2005 (CSA Category Program) • Transformer ships on a suitably sized skid, with nylon 101 - 150 50 57 151 - 300 55 57
• Witnessed testing is available (Toronto, Canada). • Additionally, The US DOE exempts the following types:
covering, straps, and anti-stacking markers. 151 - 333 55 59 301 - 500 60 59 • Drive (isolation) transformers
• Rex’s standard warranty terms are online. Typical • Uninterruptible power supply transformers
334 - 500 60 59 501 - 700 62 61
warranty duration is 1 year, or as specified. • Transformers with a tap range of 20 percent or more
501 - 1000 64 61 701 - 1000 64 63
Pg. 5 Pg. 6
General Product Information General Product Information
Enclosures Enclosure Types Reference Charts - Standard Enclosure Details
• Standard enclosures are constructed of formed sheet • Rex transformers are available with a variety of different The tables below provide details on Rex’s Standard Enclosures.
steel. After fabrication, all enclosure panels are finished enclosure types: • Each products page specifiies which enclosure is used; Rex can supply customized enclosures where required.
in ASA 61 gray powder coating, suitable for most • Type 1 (NEMA 1): Enclosures are constructed for indoor
industrial and commercial installations. Knock-Outs use to provide a degree of protection to personnel Standard Ventilated Enclosures (Type 1 and 3R)
(KOs) for conduit are provided where typically required. against access to hazardous parts and to provide a Type 3R Outdoor
Standard Indoor Enclosure (Type 1 or Type 3R Indoor)
Removable front cover allows access to terminals. degree of protection of the equipment inside the (with kit installed)
Ventilation openings are coordinated with coil cooling enclosure against ingress of solid foreign objects (falling Enclosure Width Depth Height Wall Mounting* Floor Mounting* Depth Enclosure
Mounting Type
ducts to permit natural air circulation. dirt). Rex enclosure name: E1-# Name [inch] [inch] [inch] d, A x B [inch] d, C x E [inch] [inch] Name
• Enclosures E1-2 through E3R-7 can be wall mounted • Type 2 (NEMA 2): Similar to type 1; additionally, E1-0 Floor Type 1 9.50 7.00 8.00 n/a 3/16”, 5” x 8” n/a n/a
in addition to floor mounting. Wall mount brackets are provides a degree of protection with respect to harmful E1-1 Floor Type 1 12.00 9.00 9.30 n/a 5/16’, 6” x 12.94 n/a n/a
shipped already attached and do not require removal effects on the equipment due to the ingress of water
E1-2 Floor/Wall Type 1 11.00 11.00 14.00 5/8”, 8” x 13.25” 5/8”, 13.25” x 8” 16.07 E3R-2-W
of floor mount brackets; simply turn the wall mount (dripping and light splashing). Rex enclosure name: E2-#
brackets outwards and use. • Type 3R Indoor (NEMA 3R): Sprinkler-proof, when E1-3 Floor/Wall Type 1 15.50 11.00 14.00 5/8”, 8” x 17.75” 5/8”, 17.75” x 8” 16.07 E3R-3-W
• Wall mountable transformers do not require additional the angle between sprinkler heads and the opening E3R-4 Floor/Wall Type 3R indoor 15.75 16.00 21.00 1/2”, 8” x 17.75” 1/2”, 17.99” x 7.5” 21.12 E3R-4-W
structural support or catch-pan underneath, for most does not exceed 45⁰ from vertical. Most Rex standard E3R-5 Floor/Wall Type 3R indoor 20.50 16.00 25.00 1/2”, 8” x 22.50” 1/2”, 22.74” x 7.5” 21.62 E3R-5-W
installations. Catch pan is available if required. enclosures are Type 3R Indoor as a standard, without
E3R-6 Floor/Wall Type 3R indoor 20.50 20.75 30.00 1/2”, 8” x 22.50” 1/2”, 22.74” x 10” 26.39 E3R-6-W
• Floor or platform mount enclosures are equipped with any need for additional kits or hardware. Rex enclosure
integral lifting lugs, and can be suspension mounted name: E3R-# E3R-7 Floor/Wall Type 3R indoor 24.50 21.75 36.00 1/2”, 11” x26.50” 1/2”, 26.11” x 11.5” 29.37 E3R-7-W
using the floor mounting points. • Type 3R Outdoor (NEMA 3R): While there is no E3R-8 Floor Type 3R indoor 30.75 33.40 44.00 n/a 5/8”, 23.19” x 25” 37.49 E3R-8-W
distinction in the definition of the technical requirements E3R-8S Floor Type 3R indoor 27.00 29.00 47.00 n/a 5/8”, 17.13” x 20” 29.00 E3R-8S-W
Available kits and components of Type 3R Indoor vs outdoor, Rex’s outdoor variant
E3R-9 Floor Type 3R indoor 40.00 38.00 52.00 n/a 5/8”, 27.50” x 29” 41.75 E3R-9-W
• Weather kit: Convert Type 1 or Type 3R indoor includes additional covers and protection against snow
and rain. This is recommended for outdoor units; for E3R-9S Floor Type 3R indoor 32.00 32.00 52.00 n/a 5/8”, 20.15” x 25” 32.00 E3R-9S-W
enclosures to Type 3R outdoor. To include this kit with
your transformer, add suffix E3R to part number. more severe exposure conditions (wind blown snow & E3R-10 Floor Type 3R indoor 46.00 50.00 66.00 n/a 5/8”, 36” x 30” 50.00 E3R-10-W
• Tray or catch pan: For use if transformer may be rain, rodents, etc) further protection should be specified. E3R-11 Floor Type 3R indoor 60.00 55.00 70.70 n/a 5/8”, 37” x 30” 55.00 E3R-11-W
mounted above or near combustible items. Rex enclosure name: E3R-#-W. To specify this type of
E3R-12 Floor Type 3R indoor 73.00 56.00 79.50 n/a 5/8”, 37” x 30” 56.00 E3R-12-W
• Wall Mount bracket: For wall mounting E3R-8. Note, enclosure, include suffix E3R in part number.
* See diagram at bottom of page 7 for illustrations of A, B, C, d, E
bolting hardware not included. • Type 4 (NEMA 4): Indoor or outdoor, Water tight,
• Metallic Skid Base (with or without cage). Intended for dust tight, sleet resistant. Provides ultimate level of Type 12 enclosures
applications where frequent forklift or crane handling is protection. Rex enclosure name: E4-#. To specify in part Enclosure Width Depth Height Floor Mounting*
number: E4. For Stainless Steel Type 304, use E4X. Type Mounting
expected (IE mobile power duty). Name [inch] [inch] [inch] d, C x E [inch}
316L is available.
E12-6 Floor 20.50 25.40 30.00 1/2”, 22.74” x 10”
• Type 12 (NEMA 12): Commonly referred to as “dust-
tight” and compared to IP 52. Rex can meet this E12-7 Floor 24.50 26.40 36.00 1/2”, 26.11” x 11.5”
requirement by supplying a Type 4 (which exceeds the E12-8 Floor 30.75 34.50 44.00 5/8”, 23.19” x 25”
requirement), or a ventilated (filtered) construction. Rex E12-9 Floor 40.00 37.70 52.00 5/8”, 27” x 29”
enclosure name: E12-#. To specify in part number: E12. E12-10 Floor 46.00 46.30 66.00 5/8”, 36” x 30”
E12-11 Floor 60.00 51.30 70.70 5/8”, 37” x 30”
E12-12 Floor 73.00 51.70 79.50 5/8”, 37” x 30” * See diagram at bottom of page 7 for illustrations of C, d, E
Type 4 enclosures
Enclosure Width Depth Height Floor Mounting*
Mounting
Type 3R Indoor enclosure (left) versus the same enclosure equipped Name [inch] [inch] [inch] d, C x E [inch}
with optional weather kit for Type 3R Outdoor (right) E4-4 Floor 15.50 16.50 18.00 5/8”, 11.25” x 18.375”
Special Features and Customization E4-5 Floor 21.50 16.75 20.50 5/8”, 15.25” x 19.50”
E4-6 Floor 21.50 22.00 27.00 5/8”, 15.25” x 24.00”
Rex can meet most requests for special features. Ex:
• Special paint color, process, or finishing E4-7 Floor 24.50 22.25 31.50 5/8”, 19.00” x 24.25”
• Special dimensions, special mounting E4-8 Floor 30.75 30.50 32.00 5/8”, 25.00” x 32.50”
• Access doors instead of panels, padlock-able E4-9 Floor 40.00 34.00 46.00 5/8”, 29.00” x 36.00”
• Tamper-proof hardware Wireframe illustration of enclosure, with dimension labels for E4-10 Floor 46.50 43.25 64.50 5/8”, 30.00” x 45.25”
• Anti-Condensation coating inside top cover wall mounting and floor mounting (see page 8)
E4-11 Floor 60.00 50.50 71.00 5/8”, 30.00” x 52.50”
• Special materials (Stainless 304, 316L, Aluminum)
E4-12 Floor 73.00 48.50 79.50 5/8”, 30.00” x 52.50” * See diagram at bottom of page 7 for illustrations of C, d, E
Pg. 7 Pg. 8
Isolation Transformer - Single Phase - Type S Isolation Transformer - Single Phase - Type S
Background Features & Specifications
Rex Single Phase Isolation Transformers are manufactured Specification Rex Standard Optionally Available
under CSA file number LR34493, and UL Listed under File
Capacity 1, 2, 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, Smaller kVA’s are classified as control transformers. Larger
number E108255.
150, 200, 250, 330 kVA’s are classified as power transformers.
These general purpose transformers are ideal for supplying Voltage class 1.2 kV (CSA), 600 V (UL) Higher voltage classes are classified as power transformers
auxiliary lighting circuits and other commercial/industrial Conductor C - Copper or A - Aluminum n/a
circuits from primary supply voltages under 1000V. In all
cases where the load is grounded, isolation transformers Cooling Self cooled (ANN) ANC (Non ventilated units)
should be used. Frequency 60 Hz 50/60 Hz (use 50) .
Catalog Number & Application Notes Insulation System Class 220 (220 ⁰C at hottest spot, 150 ⁰C n/a
average rise)
S - / /.../ / Photos: Single Phase Transformer - Enclosed or Core & Coil
Temperature Rise 150 ⁰C average rise 115 ⁰C (use T115), 80 ⁰C (use T80)
1 2 3 4 5 6 7 Connection diagrams K Factor Rating K1 - No K-Factor Available K4, K9, K13, K20 (see page 32)
Impregnation Polyester Resin Dipped and Baked • Epoxy dipped and Baked
① - ‘S’ Single Phase Isolation Transformer H1 H2
1Ph0-NT-DO-1
• Other custom specifications available
Standard for
② - Conductor Material 1, 2 & 3 kVA Efficiency level Meets North American Energy Efficiency Higher levels may be specified (use ZX)
X3 X2 Standards: U.S. DOE 2016, NRCan 2019
C Copper
X1 X4
No taps
Taps See Connection diagrams (p.9) +2 FCAN, -4 FCBN taps (use W1)
A Aluminum (available 15 kVA and up) Other primary or secondary tap configurations (use X)
H1 H2 H3 H4 1Ph0-ST1/1-DO-1
Standard for Connection diagram See Connection diagrams (p.9) Tertiary windings, alternate configurations (use X)
③ - Base kVA Rating
5 kVA Terminations Lugs or pads - see table (p.6) Specific Cu-Al lugs available. (Use Y2)
• Select from standard 1 phase kVA levels below, or any X3 X2
Taps: +/- 1 x 5%
X1 X4
Wiring Terminals are on front or front/back. Pad or lug location may be specified (use X)
other level 1 - 1000 kVA: 1, 2, 3, 5, 7.5, 10, 15, 25, 37.5,
50, 75, 100, 150, 200, 250, 330. H1 H2
1Ph0-ST1/1-DO-2
• Note: Use 7 for 7.5, and 37 for 37.5. Standard for Electrical Performance Per page 5. Special X/R ratio, Inrush current, Short Circuit Withstand
1 2 3 1 2 3
capability, EMF intensivity, etc. (use X)
7.5 kVA
④&⑤ - Primary & Secondary Winding Voltage(s) X4
X2 X3
X1
Taps: +/- 1 x 5% Impedance Per CSA C9 Special impedance may be specified (use X)
• See page 2; select letter codes corresponding to the Sound Level Per CSA C9 and NEMA ST-20 (see p.6) 3 dB below CSA level, or other (use X)
primary voltage from group 1. H1 H2
1Ph0-ST2/2-DO-2 Enclosure Type CSA Type 1 or 3R indoor, depending on kVA, • No enclosure, Core & Coil only (use C&C)
• Secondary connection is commonly split. Select secondary 1 2 3 4 5 1 2 3 4 5 Standard for see chart • CSA Type 3R Outdoor (use E3R)
from group 2. 10 to 150 kVA • Type 4, non-ventilated (use E4)
• For a special voltage, use X and specify voltage. X2 X3 Taps: +/- 2 x 2.5% • Type 12, ventilated (use E12)
• Standard connection diagram is shown to the right. For
X4 X1
• Special dimensions and construction (use X)
special connection or tapping, use X in ⑥ 1Ph0-CT2/2-DO-2 Enclosure Material Steel panels, Combination of 12, 14, & 16 ga Other gauge, Stainless Steel 304, Stainless Steel 316L,
Galvanneal, Aluminum.
Standard for
⑥ - Optional Special Features Enclosure Finish ASA 61 Gray Powder Coat Bare Stainless, special color/finish (use ESP)
200 kVA and up
• A variety of optional special features exist. Page 2 lists Taps: +/- 2 x 2.5% Approvals CSA Certified and UL Listed IEC (use CE), European or other spec, ABS, Lloyds Registry,
many of the most commonly specified options. Page 10 CSA File # LR34493 (5kV Max, 900kVA Max) Canadian Coast Guard, and more. Also see Hazardous
offers additional information. Efficiency Reference Table (Single Phase) UL File # E108255 (600V Max, 750kVA Max) Location Catalog
Thermostat Not supplied Available NC 185, NC 200, or other (use X)
⑦- Efficiency Level kVA Efficiency [%] Mounting Floor only, or floor/wall, depending on size. Special mounting available
• The table on the right shows the efficiency levels for Efficiency is reported at See tables (p. 12)
15 97.70
single phase dry type transformers (Canada & USA). • 35% load,
• Transformers rated <15 kVA are excluded. Other excluded 25 98.00 Nameplate Metallic Foil, English/French Aluminum, Stainless Steel (use M)
• purely sinusoidal,
types are listed on page 6. In such cases, leave ⑦ blank. 37.5 98.20
• power factor of 1, Seismic Canada Zone 6, USA Zone 4. See page 6 for Rex can facilitate site specific Seismic approvals. Mason
• In forming the Rex Part Number for your transformer, use 50 98.30 • Average winding
more detail. Super W pads, or other specified snubbers.
suffix Z3 where efficiency levels are applicable. temperature of 75 C. Testing See page 5 Optional tests available, such as temperature-rise test,
75 98.50
• If a special efficiency level is required, use ZX, and specify For non standard kVA, use sound level, EMF, etc. (Ordered separately)
efficiency with request. 100 98.60
linear interpolation. Shipping Bolted to skid, with nylon cover Shrink wrap, special skid, export crating
150 98.70
Optional Features Special ambient temperature, Special altitude, Anti-Condensation Strip Heaters, Thermal Sensing and
250 98.80
Indication (analog/digital), Surge protection, Breaker Integration, Power Monitoring, etc.
330 98.90
Pg. 9 Pg. 10
Isolation Transformer - Single Phase - Type S Isolation Transformer - Single Phase - Type S
Reference Charts - Electrical Performance - Type 1 and 3R enclosures Reference Charts - Dimensions - Type 1 and 3R enclosures
The tables below provide typical standard values for three phase transformers with standard specification. The tables below provide typical standard values for three phase transformers with standard specification.
• Sample catalog numbers are shown for 600 V to 120/240 V. For other voltage codes, please see page 2 • The values reported below will not vary with the selection of special voltages, shielding, and some other options
• The values reported below will not vary with the selection of special voltages, shielding, and some other options • Special specifications such as K-Factor Rating and Temperature Rise may affect dimensions and the values below;
• Special specifications such as K-Factor Rating and Temperature Rise may affect dimensions and the values below; Contact Rex Sales for application specific information.
Contact Rex Sales for for application specific information. For additional enclosure details (such as mounting), consult page 8.
Copper windings (Type SC) Copper windings (Type SC)
Average 600 V : 120/240 Standard Indoor Enclosure (Type 1 or Type 3R Indoor) Type 3R Outdoor
Efficiency Standard (with kit installed)
Sound
kVA (35% load, Impedance Primary Taps Connection Catalog # kVA
75 OC) Level Lugs Width Depth Height Weight Enclosure Depth Enclosure
Diagram Refer to page 2 for Mounting Type
[dB] (HV/LV)
voltage codes
[inch] [inch] [inch] [lbs] Name [inch] Name
5 n/a 5.5% - 7% 40 +/- 1 x 5% 1Ph0-ST1/1-DO-1 LA/LA SC5J-K 5 Floor/Wall 11.00 11.00 14.00 80 E1-2 Type 1 16.07 E3R-2-W
7.5 n/a 5.5% - 7% 40 +/- 1 x 5% 1Ph0-ST1/1-DO-2 LA/LA SC7J-K 7.5 Floor/Wall 15.75 16.00 21.00 128 E3R-4 Type 3R indoor 21.12 E3R-4-W
10 n/a 5% - 6.5% 40 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LA/LA SC10J-K 10 Floor/Wall 15.75 16.00 21.00 135 E3R-4 Type 3R indoor 21.12 E3R-4-W
15 97.70% 3.5% - 5.5% 45 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LA/LA SC15J-K/Z3 15 Floor/Wall 15.75 16.00 21.00 150 E3R-4 Type 3R indoor 21.12 E3R-4-W
25 98.00% 3.5% - 5.5% 45 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LA/LB SC25J-K/Z3 25 Floor/Wall 20.50 20.75 30.00 225 E3R-6 Type 3R indoor 26.39 E3R-6-W
37.5 98.20% 3.5% - 5% 45 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LA/LC SC37J-K/Z3 37.5 Floor/Wall 20.50 20.75 30.00 272 E3R-6 Type 3R indoor 26.39 E3R-6-W
50 98.30% 3.5% - 5% 50 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LA/LC SC50J-K/Z3 50 Floor/Wall 20.50 20.75 30.00 348 E3R-6 Type 3R indoor 26.39 E3R-6-W
75 98.50% 3.5% - 5% 50 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LB/LD SC75J-K/Z3 75 Floor/Wall 24.50 21.75 36.00 444 E3R-7 Type 3R indoor 29.37 E3R-7-W
100 98.60% 3.5% - 5% 50 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LC/2xLD SC100J-K/Z3 100 Floor 27.00 29.00 47.00 711 E3R-8S Type 3R indoor 29.00 E3R-8S-W
150 98.70% 3.5% - 5% 55 +/- 2 x 2.5% 1Ph0-ST2/2-DO-2 LD/PADS SC150J-K/Z3 150 Floor 27.00 29.00 47.00 851 E3R-8S Type 3R indoor 29.00 E3R-8S-W
200 98.75% 4% - 6% 55 +/- 2 x 2.5% 1Ph0-CT2/2-DO-2 LD/PADS SC200J-K/Z3 200 Floor 32.00 32.00 52.00 1170 E3R-9S Type 3R indoor 32.00 E3R-9S-W
250 98.80% 4% - 6% 55 +/- 2 x 2.5% 1Ph0-CT2/2-DO-2 PADS SC250J-K/Z3 250 Floor 32.00 32.00 52.00 1308 E3R-9S Type 3R indoor 32.00 E3R-9S-W
330 98.90% 4% - 6% 60 +/- 2 x 2.5% 1Ph0-CT2/2-DO-2 PADS SC330J-K/Z3 330 Floor 32.00 32.00 52.00 1720 E3R-9S Type 3R indoor 32.00 E3R-9S-W
Pg. 11 Pg. 12
Isolation Transformer - Three Phase - Type B Isolation Transformer - Three Phase - Type B
Background Features & Specifications
General Purpose Three Phase Isolation Transformers are Specification Rex Standard Optionally Available
intended for most commercial and industrial settings where
Capacity 3, 6, 9, 15, 30, 45, 75, 112.5, 150, 225, 300, Larger kVA’s are classified as power transformers.
robust and reliable power transformation is required.
450, 500, 750.
Hotels, schools, factories, and other such buildings will use
transformers to feed lighting, heating, and general power Voltage class 1.2 kV (CSA), 600 V (UL) Higher voltage classes are classified as power transformers
distribution panels, rated 600 V and below. Conductor C - Copper or A - Aluminum n/a
• Transformers are available in a variety of enclosed types
or as a Core & Coil. Cooling Self cooled (ANN) ANC (Non ventilated units)
• These transformers are intended for linear loads. Various Photos: Three Phase Transformer - Enclosed or Core & Coil Frequency 60 Hz 50/60 Hz (use 50).
options and features available on these transformers
can be specified to accommodate electrical system Connection diagrams Insulation System Class 220 (220 ⁰C at hottest spot, 150 ⁰C n/a
average rise)
requirements. For non-linear loads with a harmonic H2 X2
3PDyn1-NT
component in the power, consult the sections of this Temperature Rise 150 ⁰C average rise • 115 ⁰C (use T115), 80 ⁰C (use T80)
Standard for
catalog for K-Factor Rating (p. 28) and Drive Isolation X0
3 kVA K Factor Rating K1 - No K-Factor • Available K4, K9, K13, K20 (see page 32)
Transformers (p. 29) X1
No Taps Impregnation Polyester Resin Dipped and Baked • Epoxy dipped and Baked
H1 H3 X3
• Other custom specifications available
Catalog Number & Application Notes
3PDyn1-ST1/1 Efficiency level Meets North American Energy Efficiency Higher levels may be specified (use ZX)
/
H2
- / /.../
1
B
3
2
X2
Wiring Terminals are on front or front/back. Pad or lug location may be specified (use X)
5
use W1 Sound Level Per CSA C9 and NEMA ST-20 (see p.6) 3 dB below CSA level, or other (use X)
3
H1 2
1
X0
•
1
•
4
5 6 X0
Galvanneal, Aluminum.
• For a special voltage, use X and specify voltage. H2
3PDyn1-CT2/4
X2
Enclosure Finish ASA 61 Gray Powder Coat Bare Stainless, special color/finish (use ESP)
• Standard connection diagram is shown to the right. For
8 7
6
Approvals CSA Certified and UL Listed IEC (use CE), European or other spec, ABS, Lloyds Registry,
1
up; use W1
5 6
7 8 X0
X1 CSA File # LR34493 (5kV Max, 900kVA Max) Canadian Coast Guard, and more. Also see Hazardous
Taps: +2 x 2.5%, -4 x 2.5%
H1 H3
UL File # E108255 (600V Max, 750kVA Max) Location Catalog
⑥ - Optional Special Features
86 421 3 57 X3
Pg. 13 Pg. 14
Isolation Transformer - Three Phase - Type B Isolation Transformer - Three Phase - Type B
Reference Charts - Electrical Performance - Type 1 and 3R enclosures Reference Charts - Dimensions - Type 1 and 3R enclosures
The tables below provide typical standard values for three phase transformers with standard specification. The tables below provide typical standard values for three phase transformers with standard specification.
• Sample catalog numbers are shown for 600 V delta to 208Y/120 V. For other voltage codes, please see page 2 • The values reported below will not vary with the selection of special voltages, shielding, and some other options
• The values reported below will not vary with the selection of special voltages, shielding, and some other options • Special specifications such as K-Factor Rating and Temperature Rise may affect dimensions and the values below;
• Special specifications such as K-Factor ratings and Temperature Rise may affect dimensions and the values below; Contact Rex Sales for application specific information.
Contact Rex Sales for application specific information. For additional enclosure details (such as mounting), consult page 8.
Pg. 15 Pg. 16
Isolation Transformer - Three Phase - Type B Isolation Transformer - Three Phase - Type B
Reference Charts - Electrical Performance - Type 12 and Type 4 enclosures Reference Charts - Dimensions - Type 12 and Type 4 enclosures
The tables below provide typical standard values for three phase transformers with standard specification. The tables below provide typical standard values for three phase transformers with standard specification.
• Sample catalog numbers are shown for 600 V delta to 208Y/120 V. For other voltage codes, please see page 2 • The values reported below will not vary with the selection of special voltages, shielding, and some other options
• The values reported below will not vary with the selection of special voltages, shielding, and some other options • Special specifications such as K-Factor Rating and Temperature Rise may affect dimensions and the values below;
• Special specifications such as K-Factor Rating and Temperature Rise may affect dimensions and the values below; Contact Rex Sales for application specific information.
Contact Rex Sales for for application specific information. For additional enclosure details (such as mounting), consult page 8.
Copper windings, Type 12 ventilated (Type BC.../E12) Copper windings, Type 12 ventilated (Type BC.../E12)
Average 600 V : 208Y/120 Standard Enclosure (Type 12)
Efficiency Standard
Sound
kVA (35% load, Impedance Primary Taps Connection Catalog # kVA
75 OC) Level Lugs Width Depth Height Weight Enclosure
Diagram Refer to page 2 for Mounting
[dB] (HV/LV)
voltage codes
[inch] [inch] [inch] [lbs] Name
15 97.89 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA BC15J-M/E12/Z3 15 Floor 20.50 25.40 30.00 271 E12-6
30 98.23 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA BC30J-M/E12/Z3 30 Floor 20.50 25.40 30.00 340 E12-6
45 98.40 3.5% - 5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LB BC45J-M/E12/Z3 45 Floor 20.50 25.40 30.00 437 E12-6
75 98.60 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LC BC75J-M/E12/Z3 75 Floor 24.50 26.40 36.00 625 E12-7
112.5 98.74 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LD BC112J-M/E12/Z3 112.5 Floor 30.75 34.50 44.00 960 E12-8
150 98.83 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/2xLD BC150J-M/E12/Z3 150 Floor 30.75 34.50 44.00 1115 E12-8
225 98.94 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/3xLD BC225J-M/E12/Z3 225 Floor 40.00 37.64 52.00 1700 E12-9
300 99.02 4% - 6% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/4xLD BC300J-M/E12/Z3 300 Floor 40.00 37.64 52.00 2095 E12-9
450 99.11 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS BC450J-M/E12/Z3 450 Floor 46.00 46.25 66.00 3460 E12-10
500 99.23 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS BC500J-M/E12/Z3 500 Floor 46.00 46.25 66.00 3640 E12-10
750 99.28 4% - 6% 64 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS BC750J-M/E12/Z3 750 Floor 60.00 55.00 70.67 4995 E12-11
Copper windings, Type 4 Totally Enclosed, Non Ventilated (Type BC.../E4) Copper windings, Type 4 Totally Enclosed, Non Ventilated (Type BC.../E4)
Average 600 V : 208Y/120 Standard Enclosure (Type 4)
Efficiency Standard
Sound
kVA (35% load, Impedance Primary Taps Connection Catalog # kVA
75 OC) Level Lugs Width Depth Height Weight Enclosure
Diagram Refer to page 2 for Mounting
[dB] (HV/LV)
voltage codes
[inch] [inch] [inch] [lbs] Name
15 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA BC15J-M/E4 15 Floor 21.50 22.00 27.00 310 E4-6
30 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA BC30J-M/E4 30 Floor 21.50 22.00 27.00 376 E4-6
45 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LB BC45J-M/E4 45 Floor 24.50 22.25 31.50 525 E4-7
75 n/a 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LA/LC BC75J-M/E4 75 Floor 30.75 30.40 32.00 850 E4-8
112.5 n/a 4% - 6% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LB/LD BC112J-M/E4 112.5 Floor 30.75 30.50 32.00 995 E4-8
150 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/2xLD BC150J-M/E4 150 Floor 40.00 34.00 46.00 1700 E4-9
225 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/3xLD BC225J-M/E4 225 Floor 46.50 43.25 64.50 2300 E4-10
300 n/a 4% - 6% 64 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/4xLD BC300J-M/E4 300 Floor 46.50 43.25 64.50 2700 E4-10
450 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS BC450J-M/E4 450 Floor 60.00 50.50 71.00 4160 E4-11
500 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS BC500J-M/E4 500 Floor 60.00 50.50 71.00 4400 E4-11
750 n/a 4% - 6% 64 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS BC750J-M/E4 750 Floor 73.00 48.50 80.00 6400 E4-12
Pg. 18
Pg. 17
Autotransformer - Single & Three Phase - Type M & R Autotransformer - Single & Three Phase - Type M & R
Background Features & Specifications
Autotransformers are an economical and compact means Specification Rex Standard Optionally Available
of connecting electrical equipment to a power supply of a Capacity Single Phase: 3, 5, 7.5, 10, 15, 25, 37.5, 50, Larger kVA’s are available and may be classified as power
different voltage. Part of the winding is common to both 75, 100, 150, 225 transformers
the primary and secondary circuits. This means there is no Three Phase: 3, 6, 9, 15, 30, 45, 75, 112.5,
isolation between the two, which may not be acceptable 150, 225, 300
on some power systems where isolation is required, or if Voltage class 1.2 kV (CSA), 600 V (UL) Higher voltage classes are classified as power transformers
there is no grounded neutral on the secondary side of the Conductor C - Copper or A - Aluminum n/a
upstream transformer. Typical applications include motor Cooling Self cooled (ANN) ANC (Non ventilated units)
loads of industrial machinery, electric heating, and air Photo: Three Phase Autotransformers Frequency 60 Hz 50/60 Hz (use 50) .
conditioners. Specialty autotransformers are also available, Left: 240 Y to 208 Y in chalk white enclosure Insulation System Class 220 (220 ⁰C at hottest spot, 150 ⁰C n/a
such as: Right: 600 Y to 480 Y in standard enclosure average rise)
• Autotransformer for motor-starters
• Autotransformer for battery-chargers Application Notes Temperature Rise 150 ⁰C average rise 115 ⁰C (use T115), 80 ⁰C (use T80)
• Zig-Zag Grounding autotransformers K Factor Rating K1 - No K-Factor Available K4, K9, K13, K20 (see page 32)
• As can be seen in the connection diagram below, the
Contact our inside sales department for more information Impregnation Polyester Resin Dipped and Baked Epoxy dipped and Baked
typical configuration is without taps. Taps are optionally
Other custom specifications available
Catalog Number & Application Notes available (use suffix X).
Efficiency level No applicable efficiency compliance required Higher levels may be specified (use ZX)
• See page 21 & 22 for the enclosure and weight for some
- / /.../ / of the most commonly specified voltage pairs. Other Taps None. See Connection diagrams (p.19) +1 FCAN, -1 FCBN taps (use W1)
Other primary or secondary tap configurations (use X)
primary and secondary voltages are available.
1 2 3 4 5 6 7 • The details of page 21 & 22 are for the more commonly Connection diagram See Connection diagrams (p.19) Tertiary windings, alternate configurations (use X)
specified copper wound autotransformers. Aluminum Terminations Lugs or pads - see table (p.6) Specific Cu-Al lugs available (use Y2)
① - Autotransformer Type wound autotransformers are available for some ratings, Accesible Neutral terminal (use N)
M Single Phase Autotransformer and they can represent an economical alternative. Wiring Terminals are on front or front/back. Pad or lug location may be specified (use X)
R Three Phase Autotransformer • Autotransformers may also be specified as encapsulated Electrical Performance Per page 5. Special X/R ratio, Inrush current, Short Circuit Withstand
types using suffix EP. capability, EMF intensivity, etc. (use X)
② - Conductor Material • May be used in step-up or step-down configuration. Impedance Autotransformers typically have a lower Special impedance may be specified (use X)
• Low voltage Regulation; Less than 3%. impedance value than isolation transformers
C Copper (approximately 1 - 4%)
• Built with the same demanding specification as our
A Aluminum (available in some cases - See p.22) isolation transformers. Sound Level Per CSA C9 and NEMA ST-20 (see p.6) 3 dB below CSA level, or other (use X)
• Rugged bracing, spacious and practically arranged wiring Enclosure Type CSA Type 1 or 3R indoor, depending on kVA, • No enclosure, Core & Coil only (use C&C)
③ - Base kVA Rating see charts (p. 21, 22) • CSA Type 3R Outdoor (use E3R)
compartment, versatile and tough enclosure.
• For Singe Phase: Select from standard kVA levels below, • Class 220 insulation is used. • Type 4, non-ventilated (use E4)
or any other level 3 - 1000+ kVA: 3, 5, 7.5, 10, 15, 25, • Type 12, ventilated (use E12)
• Autotransformers can be supplied in Type 12 and Type 4
37.5, 50, 75, 100, 150, 225 (Note: Use 7 for 7.5, and 37 • Special dimensions and construction (use X)
boxes as well (use suffix E12 or E4, resepectively).
for 37.5). Enclosure Material Steel panels, Combination of 12, 14, & 16 ga Other gauges, Stainless Steel 304, Stainless Steel 316L,
• For three phase autotransformers, there is no connection
• For Three Phase: Select from standard kVA levels below, Galvanneal, Aluminum.
point to the neutral, unless specifically requested as an
or any other level 1.5 - 1000+ kVA: 3, 6, 9, 15, 30, 45, Enclosure Finish ASA 61 Gray Powder Coat Bare Stainless, special color/finish (use ESP)
optional feature (use suffix N).
75, 112.5, 150, 225, 300 (Note: Use 112 for 112.5) Approvals CSA Certified and UL Listed IEC (use CE), European or other spec, ABS, Lloyds Registry,
Connection diagrams CSA File # LR34493 Canadian Coast Guard, and more. Also see Hazardous
④&⑤ - Primary & Secondary Winding Voltage(s) UL File # E108255 Location Catalog
1PhA-NT-1 Thermostat Not supplied Available N.C.-185, N.C.-200, or other (use X)
• See page 2; select letter codes corresponding to the
primary and secondary voltage from group 1. Standard for Mounting Floor only, or floor/wall, depending on size. Special mounting available
Single Phase See tables (p. 21, 22)
• For a special voltage, use X and specify voltage. H0 / X0 X1 H1
• Standard connection diagram is shown to the right. For No Taps Nameplate Metallic Foil, English/French Aluminum, Stainless Steel (use M)
special connection or tapping, use X in ⑥ Seismic Canada Zone 6, USA Zone 4. See page 6 for Rex can facilitate site specific Seismic approvals. Mason
H1
3PhA-NT-1 more detail. Super W pads, or other specified snubbers.
X1
Standard for Testing See page 5 Optional tests available, such as temperature-rise test,
⑥ - Optional Special Features X2 Three Phase sound level, EMF, etc. (Ordered separately)
• A variety of optional special features exist. These are
H2
X3 No Taps Shipping Bolted to skid, strapped, with nylon cover Shrink wrap, special skid, export crating
noted in the specification (p.20). Some of the most H3
Optional Features Special ambient temperature, Special altitude, Anti-Condensation Strip Heaters, Thermal Sensing and
commonly specified ones are noted on p.2. Indication (analog/digital), Surge protection, Breaker Integration, Power Monitoring, etc.
H1
3PhA-ST-1/1
• Autotransformers are exempt from North American H4
Optional for
H7
Efficiency regulation. X1
X2
X3
H8
H5
H2 Three Phase
H6
H9
Taps: +/- 1 x 5%
H3
Pg. 19 Pg. 20
Autotransformer - Single Phase, Copper - Type MC Autotransformer - Three Phase, Copper - Type RC
Reference Charts - Enclosure & Weight - Single Phase Autotransformer Reference Charts - Enclosure & Weight - Three Phase Autotransformer - Copper
The tables below provides the weight and enclosure number for single phase autotransformers with standard specification. The tables below provides the weight and enclosure number for three phase autotransformers with standard specification.
Contact Rex Sales for for application specific information. Contact Rex Sales for for application specific information.
600 V : 480 V 600 V : 416 V 600 V : 380 V 600 V : 480 V 600 V : 416 V 600 V : 380 V
kVA Weight Enclosure Weight Enclosure Weight Enclosure kVA Weight Enclosure Weight Enclosure Weight Enclosure
Catalog # Catalog # Catalog # Catalog # Catalog # Catalog #
[lbs] Name [lbs] Name [lbs] Name [lbs] Name [lbs] Name [lbs] Name
3 MC3J-H 31 E1-0 MC3J-G 40 E1-0 MC3J-F 40 E1-0 3 RC3J-H 21 E1-0 RC3J-G 32 E1-0 RC3J-F 38 E1-0
5 MC5J-H 33 E1-0 MC5J-G 47 E1-1 MC5J-F 45 E1-1 6 RC6J-H 34 E1-1 RC6J-G 70 E1-1 RC6J-F 75 E1-1
7.5 MC7J-H 35 E1-1 MC7J-G 50 E1-1 MC7J-F 50 E1-1 9 RC9J-H 45 E1-1 RC9J-G 85 E1-1 RC9J-F 110 E1-3
10 MC10J-H 40 E1-1 MC10J-G 65 E1-1 MC10J-F 70 E1-2 15 RC15J-H 65 E1-1 RC15J-G 120 E1-3 RC15J-F 140 E1-3
15 MC15J-H 65 E1-1 MC15J-G 80 E1-2 MC15J-F 85 E1-2 30* RC30J-H 115 E1-3 RC30J-G 135 E1-3 RC30J-F 187 E3R-5
25 MC25J-H 70 E1-2 MC25J-G 140 E3R-4 MC25J-F 140 E3R-4 45* RC45J-H 135 E1-3 RC45J-G 180 E3R-5 RC45J-F 206 E3R-5
37.5 MC37J-H 117 E3R-4 MC37J-G 145 E3R-4 MC37J-F 165 E3R-4 75* RC75J-H 225 E3R-5 RC75J-G 285 E3R-5 RC75J-F 293 E3R-5
50 MC50J-H 143 E3R-4 MC50J-G 200 E3R-6 MC50J-F 205 E3R-6 112.5* RC112J-H 250 E3R-5 RC112J-G 314 E3R-5 RC112J-F 425 E3R-6
75 MC75J-H 156 E3R-4 MC75J-G 225 E3R-6 MC75J-F 265 E3R-6 150* RC150J-H 271 E3R-6 RC150J-G 497 E3R-7 RC150J-F 530 E3R-7
100 MC100J-H 222 E3R-6 MC100J-G 282 E3R-6 MC100J-F 320 E3R-6 225* RC225J-H 381 E3R-6 RC225J-G 510 E3R-7 RC225J-F 687 E3R-7
150 MC150J-H 291 E3R-6 MC150J-G 360 E3R-6 MC150J-F 410 E3R-6 300* RC300J-H 479 E3R-7 RC300J-G 935 E3R-8 RC300J-F 833 E3R-8
225 MC225J-H 379 E3R-6 MC225J-G 580 E3R-7 MC225J-F 680 E3R-8S
600 V : 240 V 480 V : 240 V 240 V : 208 V 600 V : 240 V 600 V : 208 V 480 V : 240 V
kVA Weight Enclosure Weight Enclosure Weight Enclosure kVA Weight Enclosure Weight Enclosure Weight Enclosure
Catalog # Catalog # Catalog # Catalog # Catalog # Catalog #
[lbs] Name [lbs] Name [lbs] Name [lbs] Name [lbs] Name [lbs] Name
3 MC3J-C 45 E1-0 MC3H-C 50 E1-0 MC3C-B 30 E1-0 3 RC3J-C 50 E1-1 RC3J-B 55 E1-1 RC3H-C 55 E1-1
5 MC5J-C 65 E1-1 MC5H-C 60 E1-1 MC5C-B 36 E1-0 6 RC6J-C 75 E1-1 RC6J-B 70 E1-1 RC6H-C 75 E1-1
7.5 MC7J-C 81 E1-2 MC7H-C 75 E1-2 MC7C-B 45 E1-0 9 RC9J-C 120 E1-3 RC9J-B 110 E1-3 RC9H-C 95 E1-3
10 MC10J-C 92 E3R-4 MC10H-C 85 E1-2 MC10C-B 50 E1-0 15* RC15J-C 155 E1-3 RC15J-B 135 E1-3 RC15H-C 110 E1-3
15 MC15J-C 130 E3R-4 MC15H-C 105 E3R-4 MC15C-B 60 E1-0 30* RC30J-C 225 E3R-5 RC30J-B 225 E3R-5 RC30H-C 200 E3R-5
25 MC25J-C 165 E3R-4 MC25H-C 182 E3R-4 MC25C-B 70 E1-1 45* RC45J-C 287 E3R-5 RC45J-B 271 E3R-5 RC45H-C 250 E3R-5
37.5 MC37J-C 220 E3R-6 MC37H-C 212 E3R-4 MC37C-B 63 E3R-4 75* RC75J-C 345 E3R-6 RC75J-B 390 E3R-6 RC75H-C 360 E3R-6
50 MC50J-C 250 E3R-6 MC50H-C 240 E3R-6 MC50C-B 112 E3R-6 112.5* RC112J-C 480 E3R-7 RC112J-B 610 E3R-7 RC112H-C 500 E3R-6
75 MC75J-C 370 E3R-7 MC75H-C 326 E3R-6 MC75C-B 132 E3R-6 150* RC150J-C 620 E3R-7 RC150J-B 791 E3R-8 RC150H-C 641 E3R-7
100 MC100J-C 440 E3R-7 MC100H-C 360 E3R-6 MC100C-B 181 E3R-6 225* RC225J-C 995 E3R-8 RC225J-B 1008 E3R-8 RC225H-C 947 E3R-8
150 MC150J-C 665 E3R-8S MC150H-C 585 E3R-7 MC150C-B 218 E3R-6 300* RC300J-C 1300 E3R-8 RC300J-B 1426 E3R-8 RC300H-C 1076 E3R-8
225 MC225J-C 1060 E3R-8S MC225H-C 932 E3R-8S MC225C-B 350 E3R-7
240 V : 120 V 480 V :208 V 240 V :208 V * Catalog numbers shown in bold
kVA kVA italics are available with aluminum
Weight Enclosure Weight Enclosure Weight Enclosure
Catalog # Catalog # Catalog # windings. See Pg. 23.
[lbs] Name [lbs] Name [lbs] Name
3 MC3C-A 40 E1-0 3 RC3H-B 60 E1-1 RC3C-B 31 E1-0
5 MC5C-A 45 E1-1 6 RC6H-B 80 E1-1 RC6C-B 45 E1-0
7.5 MC7C-A 70 E1-2 9 RC9H-B 100 E1-3 RC9C-B 50 E1-1
10 MC10C-A 80 E1-2 15* RC15H-B 110 E1-3 RC15C-B 60 E1-1
15 MC15C-A 122 E3R-4 30* RC30H-B 235 E3R-5 RC30C-B 85 E1-1
25 MC25C-A 152 E3R-4 45* RC45H-B 290 E3R-5 RC45C-B 90 E3R-3
37.5 MC37C-A 184 E3R-4 75* RC75H-B 350 E3R-6 RC75C-B 171 E3R-5
50 MC50C-A 240 E3R-6 112.5* RC112H-B 550 E3R-7 RC112C-B 228 E3R-5
75 MC75C-A 330 E3R-6 150* RC150H-B 700 E3R-7 RC150C-B 277 E3R-6
100 MC100C-A 400 E3R-6 225* RC225H-B 887 E3R-8 RC225C-B 338 E3R-6
150 MC150C-A 532 E3R-7 300* RC300H-B 1217 E3R-8 RC300C-B 358 E3R-6
225 MC225C-A 874 E3R-8S
Pg. 21 Pg. 22
Autotransformer - Three Phase, Aluminum - Type RA Autotransformer, Encapsulated - Three Phase RA.../EP and RC.../EP
Reference Charts - Enclosure & Weight - Three Phase Autotransformer - Aluminum Reference Charts - Enclosure & Weight - Three Phase Encapsulated Autotransformer
The tables below provides the weight and enclosure number for three phase autotransformers with standard specification. The tables below provides the weight and enclosure number for three phase encapsulated autotransformers with standard
Contact Rex Sales for for application specific information. specification. Contact Rex Sales for for application specific information.
600 V : 480 V 600 V : 416 V 600 V : 380 V Copper windings, Type 3R Outdoor (Type RC.../EP)
kVA Weight Enclosure Weight Enclosure Weight Enclosure 600 V : 480 V
Catalog # Catalog # Catalog #
[lbs] Name [lbs] Name [lbs] Name kVA Lugs Weight
Catalog # Enclosure Name
15 n/a n/a n/a RA15J-G 100 E1-3 RA15J-F 105 E1-3 (HV/LV) [lbs]
30 RA30J-H 105 E1-3 RA30J-G 170 E3R-5 RA30J-F 180 E3R-5 3 RC3J-H/EP LA/LA 97 E3R-3PEP-1
45 RA45J-H 150 E3R-4 RA45J-G 210 E3R-6 RA45J-F 220 E3R-6 6 RC6J-H/EP LA/LA 100 E3R-3PEP-1
75 RA75J-H 190 E3R-5 RA75J-G 250 E3R-6 RA75J-F 270 E3R-6 9 RC9J-H/EP LA/LA 156 E3R-3PEP-1
112.5 RA112J-H 255 E3R-6 RA112J-G 320 E3R-6 RA112J-F 345 E3R-6 15 RC15J-H/EP LA/LA 189 E3R-3PEP-2
150 RA150J-H 310 E3R-6 RA150J-G 370 E3R-6 RA150J-F 490 E3R-7 30 RC30J-H/EP LA/LA 240 E3R-3PEP-2
225 RA225J-H 360 E3R-6 RA225J-G 520 E3R-7 RA225J-F 690 E3R-8 45 RC45J-H/EP LA/LA 394 E3R-3PEP-3
300 RA300J-H 500 E3R-7 RA300J-G 680 E3R-8 RA300J-F 825 E3R-8 75 RC75J-H/EP LA/LB 559 E3R-3PEP-4
112.5 RC112J-H/EP LB/LC 630 E3R-3PEP-5
150 RC150J-H/EP LC/LC 742 E3R-3PEP-5
600 V : 240 V 600 V : 208 V 480 V : 240 V 225 RC225J-H/EP LC/LD 867 E3R-3PEP-6
kVA Weight Enclosure Weight Enclosure Weight Enclosure 300 RC300J-H/EP LD/Pads 1205 E3R-3PEP-7
Catalog # Catalog # Catalog #
[lbs] Name [lbs] Name [lbs] Name
15 RA15J-C 120 E1-3 RA15J-B 170 E3R-5 RA15H-C 110 E1-3
30 RA30J-C 190 E3R-5 RA30J-B 250 E3R-6 RA30H-C 180 E3R-5 Aluminum windings, Type 3R Outdoor (Type RA.../EP)
45 RA45J-C 260 E3R-6 RA45J-B 270 E3R-6 RA45H-C 240 E3R-6
75 RA75J-C 365 E3R-6 RA75J-B 345 E3R-6 RA75H-C 305 E3R-6
600 V : 480 V
112.5 RA112J-C 500 E3R-7 RA112J-B 520 E3R-7 RA112H-C 440 E3R-7 kVA Lugs Weight
Catalog # Enclosure Name
150 RA150J-C 690 E3R-8 RA150J-B 710 E3R-8 RA150H-C 515 E3R-7 (HV/LV) [lbs]
225 RA225J-C 840 E3R-8 RA225J-B 920 E3R-8 RA225H-C 790 E3R-8 15 RA15J-H/EP LA/LA 194 E3R-3PEP-2
300 RA300J-C 1265 E3R-9 RA300J-B 1275 E3R-9 RA300H-C 995 E3R-8 30 RA30J-H/EP LA/LA 256 E3R-3PEP-2
45 RA45J-H/EP LA/LA 375 E3R-3PEP-3
75 RA75J-H/EP LA/LB 492 E3R-3PEP-4
480 V :208 V 240 V :208 V 112.5 RA112J-H/EP LB/LC 657 E3R-3PEP-5
150 RA150J-H/EP LC/LC 737 E3R-3PEP-5
kVA Weight Enclosure Weight Enclosure
Catalog # Catalog # 225 RA225J-H/EP LC/LD 829 E3R-3PEP-6
[lbs] Name [lbs] Name
300 RA300J-H/EP LD/Pads 1152 E3R-3PEP-7
15 RA15H-B 160 E3R-5 RA15C-B 60 E1-2
30 RA30H-B 195 E3R-5 RA30C-B 80 E1-3
45 RA45H-B 240 E3R-6 RA45C-B 95 E1-3
75 RA75H-B 260 E3R-6 RA75C-B 155 E3R-5
Reference Chart - Enclosure details for Encapsulated Transformers
112.5 RA112H-B 480 E3R-7 RA112C-B 195 E3R-6 Type 3R Outdoor Type 4
150 RA150H-B 700 E3R-8 RA150C-B 220 E3R-6
225 RA225H-B 850 E3R-8 RA225C-B 260 E3R-6 Enclosure Enclosure
Mounting Width Depth Height Wall Mounting* Floor Mounting* Depth
300 RA300H-B 1210 E3R-9 RA300C-B 320 E3R-6 Name [inch] [inch] [inch] d, A x B [inch] d, C x E [inch] Name [inch]
E3R-3PEP-1 Floor/Wall 11.00 10.00 15.25 1/2", 12.50" x 8" 7/16", 12.5" x 7" E4-3PEP-1 12.00
E3R-3PEP-2 Floor/Wall 15.00 11.00 15.25 1/2", 16.50" x 8" 1/2", 16.5" x 8" E4-3PEP-2 13.00
E3R-3PEP-3 Floor/Wall 18.00 12.50 17.00 1/2", 19.50" x 8" 1/2", 19.5" x 9.5" E4-3PEP-3 14.50
E3R-3PEP-4 Floor/Wall 21.00 14.00 17.50 5/8", 22.50" x 10" 1/2", 22.5" x 10" E4-3PEP-4 16.00
E3R-3PEP-5 Floor/Wall 21.00 18.00 20.00 5/8", 22.50" x 10" 1/2", 22.5" x 14.5" E4-3PEP-5 20.00
E3R-3PEP-6 Floor 26.00 18.00 25.00 n/a 1/2", 28.5" x 15" E4-3PEP-6 20.00
E3R-3PEP-7 Floor 32.00 18.00 30.00 n/a 1/2", 34.5" x 15" E4-3PEP-7 20.00
Pg. 23 Pg. 24
Encapsulated Transformer - Single & Three Phase - Option EP Encapsulated Transformer - Single & Three Phase - Option EP
Background Features & Specifications
Standard dry type ventilated transformers are cooled by Specification Rex Standard Optionally Available
circulating the surrounding air through the windings. For Capacity Single Phase: 0.25, 0.5, 0.75, 1, 1.5, 2, 3, 5, For larger kVA, consider Totally Enclosed Non-Ventilated
trouble-free operation and long life expectancy, the ambient 7.5, 10, 15, 25, 37.5, 50, 75, 100 transformers, or Cast Coil Transformers.
air must be reasonably free of dust, moisture, corrosive Three Phase: 1, 2, 3, 6, 9, 15, 30, 45, 75,
gasses, or loose debris that may clog the inlets and outlets. 112.5. 150
For environments where this requirement cannot be met, Voltage class 1.2 kV (CSA), 600 V (UL) Up to 5 kV available (CSA only)
polyester resin encapsulated transformers are ideal. Typical Conductor C - Copper or A - Aluminum n/a
Applications include: abnormally corrosive, damp, or dusty Cooling Self cooled (ANC) n/a
indoor or outdoor installations (industrial, commercial,
Frequency 60 Hz 50/60 Hz (use 50) .
residential). Examples include mining duty, pump house,
Insulation System Class 200 (200 ⁰C at hottest spot, 130 ⁰C n/a
pulp and paper, petrochemical, and steel industries, as well
Construction Type 1 Construction Type 2 average rise)
as mobile power assemblies.
Singe Phase units Three Phase units Temperature Rise 130 ⁰C average rise 115 ⁰C (use T115), 80 ⁰C (use T80)
Catalog Number & Application Notes Wiring Compartment is
located at underside
Wiring Compartment is located at front K Factor Rating K1 - No K-Factor Available K4, K9, K13, K20 (see page 32)
Impregnation Encapsulated in silica sand and polyester n/a
- / /.../EP/.../ Construction resin
1 2 3 4 5 6
Efficiency level No applicable efficiency compliance required Efficiency levels may be specified (use ZX)
• A mixture of silica sand and polyester resin forms a solid
Taps See Connection diagrams (Single Phase: p.9, +2 FCAN, -4 FCBN taps (use W1)
block, encasing and protecting the core & coil, while
① - Encapsulated Transformer Type significantly reducing audible noise.
Three Phase: p.13) Other primary or secondary tap configurations (use X)
S Single Phase Connection diagram See Connection diagrams (Single Phase: p.9, Tertiary windings, alternate configurations (use X)
• The polyester resin has a temperature class of 200. Class
Three Phase: p.13)
B Three Phase 220 insulation is used for coil insulation, however the
Terminations Lugs or pads - see table (p.6) Specific Cu-Al lugs available. (Use Y2)
temperature class must be considered to be Class 200
② - Conductor Material due to the presence of the polyester resin. Thus, the Wiring Wiring compartment located at underside or Pad or lug location may be specified. Wiring compartment
front. See construction diagrams, p. 25 location may be specified. (use X)
C Copper transformer is designed for 130 ⁰C temperature rise. 115
⁰C rise, 80 ⁰C rise, or other temperature rise levels may be Electrical Performance Per page 5. Note: Encapsulated transformers Special X/R ratio, Minimum Inrush current, Short Circuit
A Aluminum (available 15 kVA and up) typically have a higher inrush current (startup Withstand capability, EMF intensivity, etc. (use X)
specified.
current) versus ventilated transformers
③ - Base kVA Rating • The core is solidly grounded (brought out to ground lug)
Impedance Encapsulated transformers normally have Special impedance may be specified (use X)
• Enclosure is constructed of heavy gauge steel with
• For Singe Phase: Select from standard kVA levels below, a lower impedance value than ventilated
powder coated finish, suitable for type 3R or type 4 transformers (approximately 1 - 2%)
or any other level 0.25 - 125 kVA: 0.25, 0.5, 0.75, 1, 1.5,
applications, indoor or outdoor. Optional stainless steel
2, 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100 (Note: Use 7 Sound Level Per CSA C9 and NEMA ST-20 (see p.6) 3 dB below CSA level, or other (use X)
enclosures are recommended where the enclosure is
for 7.5, and 37 for 37.5.) Enclosure Type CSA Type 3R outdoor Type 4, non-ventilated (use E4)
exposed to severe corrosive environments.
• For Three Phase: Select from standard kVA levels below, Enclosure Material Steel panels, Combination of 12, 14, & 16 ga Other gauges, Stainless Steel 304, Stainless Steel 316L,
• Transformer core & coil is designed and wound with
or any other level 1 - 150 kVA: 1, 2, 3, 6, 9, 15, 30, 45, Galvanneal
unique attributes to optimize thermal performance.
75, 112.5. (Note: Use 112 for 112.5) Enclosure Finish ASA 61 Gray Powder Coat Bare Stainless, special color/finish (use ESP)
• Wiring compartment is spacious, cool, and easily
④&⑤ - Primary & Secondary Winding Voltage(s) accessible. Bottom access is provided on smaller units (see Approvals CSA Certified and UL Listed IEC (use CE), European or other spec, ABS, Lloyds Registry,
type 1), and front access for larger units (see type 2). CSA File # LR34493 Canadian Coast Guard, and more. Also see Hazardous
• Single phase: See page 2. Select letter code corresponding UL File # E108255 Location Catalog
to the primary voltage from group 1. Secondary • These epoxy transformers are considered suitable
for “ordinary locations”; Transformers for “Hazardous Thermostat Not supplied Available N.C.-185, N.C.-200, or other (use X)
connection is commonly split; Select from group 2.
Locations” as defined by IEC or CSA are available as Mounting Floor only, or floor/wall, depending on size. Special mounting available
• Three phase: See page 2. Select letter codes See tables (p. 27, 28)
corresponding to the primary and secondary voltages well: Please see our catalog “Transformers for Hazardous
Locations” Nameplate Metallic Foil, English/French Aluminum, Stainless Steel (use M)
from group 1 (delta connected) and/or group 3 (wye or
• Encapsulated transformers can be mated to primary & Seismic No approval (not tested as with ventilated Rex can facilitate site specific Seismic approvals. Mason
star connected).
secondary protection, in a factory-wired and CSA/UL transformers), however due to their fully Super W pads, or other specified snubbers.
• For a special voltage, use X and specify voltage. encapsulated construction, they are well
• Standard connection diagrams are the same as with non approved assembly: “Mini Power Center” - A dedicated
suited for environments where vibration may
encapsulated transformers. For special connection or brochure can be found at www.rexpowermagnetics.com
be present.
tapping, use X in ⑥. • Encapsulated transformers are exempt from DOE and
Testing See page 5 Optional tests available, such as temperature-rise test,
NRCan requirements for efficiency level, however,
⑥ - Optional Special Features encapsulated transformers are very efficient and most
sound level, EMF, etc. (Ordered separately)
Shipping Bolted to skid, with nylon cover Shrink wrap, special skid, export crating
• EP must be listed in the part number designs meet and exceed the requirements.
• A variety of optional special features exist. These are Optional Features Special ambient temperature, Special altitude, Anti-Condensation Strip Heaters, Thermal Sensing and
Indication (analog/digital), Surge protection, Breaker Integration, Power Monitoring, etc.
noted in the specification (p.24). Some of the most
commonly specified ones are noted on p.2.
• There is no need for a suffix to denote efficiency level -
Encapsulated transformers are exempt.
Pg. 25 Pg. 26
Encapsulated Transformer - Single Phase - Option EP Encapsulated Transformer - Single Phase - Option EP
Reference Charts - Electrical Performance - Type 3R and Type 4 enclosures Reference Charts - Dimensions - Type 3R and Type 4 enclosures
The tables below provide typical standard values for encapsulated transformers with standard specification. The tables below provide typical standard values for three phase transformers with standard specification.
• Sample catalog numbers are shown for 600 V to 120/240 V. For other voltage codes, please see page 2. • The values reported below will not vary with the selection of special voltages, shielding, and some other options
• The values reported below will not vary with the selection of special voltages, shielding, and some other options. • Special specifications such as K-Factor Rating and Temperature Rise may affect dimensions and the values below;
• Special specifications such as higher K-Factor ratings and Temperature Rise may affect dimensions and the values Contact Rex Sales for application specific information.
below; Contact Rex Sales for for application specific information.
Copper windings (Type SC.../EP) - No efficiency spec - Electrical Performance Copper windings (Type SC.../EP) - No efficiency spec - Dimensions
600 V : 120/240 Type 3R Outdoor Type 4
Const. Standard
Weight Enclosure
kVA Type Primary Taps Connection Catalog # kVA
[lbs] Name Lugs Width Depth Height Wall Mounting* Floor Mounting* Enclosure Name
(see p.25) Diagram Refer to page 2 for Mounting
(HV/LV) [inch] [inch] [inch] d, A x B [inch] d, C x E [inch] (Dimensions avail. online)
voltage codes
0.25 Type 1 none 1Ph0-NT-D0-1 17 E3R-1PEP-1 Leads SC0.25J-K/EP 0.25 Wall 5.25 4.50 8.75 7/16”, 10.0” x 2” n/a E4-1PEP-1
0.5 Type 1 none 1Ph0-NT-D0-1 20 E3R-1PEP-1 Leads SC0.5J-K/EP 0.5 Wall 5.25 4.50 8.75 7/16”, 10.0” x 2” n/a E4-1PEP-1
0.75 Type 1 none 1Ph0-NT-D0-1 23 E3R-1PEP-2 Leads SC0.75J-K/EP 0.75 Wall 6.00 5.25 9.75 7/16”, 11.0” x 2” n/a E4-1PEP-2
1 Type 1 none 1Ph0-NT-D0-1 27 E3R-1PEP-2 Leads SC1J-K/EP 1 Wall 6.00 5.25 9.75 7/16”, 11.0” x 2” n/a E4-1PEP-2
1.5 Type 1 none 1Ph0-NT-D0-1 40 E3R-1PEP-3 Leads SC1.5J-K/EP 1.5 Wall 7.50 6.50 11.25 7/16”, 12.5” x 2” n/a E4-1PEP-3
2 Type 1 +/- 1 x 5% 1Ph0-NT-D0-1 45 E3R-1PEP-3 Leads SC2J-K/EP 2 Wall 7.50 6.50 11.25 7/16”, 12.5” x 2” n/a E4-1PEP-3
3 Type 1 +/- 1 x 5% 1Ph0-NT-D0-1 55 E3R-1PEP-3 Leads SC3J-K/EP 3 Wall 7.50 6.50 11.25 7/16”, 12.5” x 2” n/a E4-1PEP-3
5 Type 2 +/- 1 x 5% 1Ph0-ST1/1-D0-1 155 E3R-1PEP-4 LA/LA SC5J-K/EP 5 Floor/Wall 12.50 12.50 15.00 1/2", 14.0" x 8” 1/2", 9.5" x 14.0” E4-1PEP-4
7.5 Type 2 +/- 1 x 5% 1Ph0-ST1/1-D0-1 210 E3R-1PEP-4 LA/LA SC7.5J-K/EP 7.5 Floor/Wall 12.50 12.50 15.00 1/2", 14.0" x 8” 1/2", 9.5" x 14.0” E4-1PEP-4
10 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 230 E3R-1PEP-5 LA/LA SC10J-K/EP 10 Floor/Wall 15.00 15.00 18.00 1/2", 10.0" x 16.5" 1/2", 16.5" x 10.0" E4-1PEP-5
15 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 296 E3R-1PEP-5 LA/LA SC15J-K/EP 15 Floor/Wall 15.00 15.00 18.00 1/2", 10.0" x 16.5" 1/2", 16.5" x 10.0" E4-1PEP-5
25 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 310 E3R-1PEP-6 LA/LB SC25J-K/EP 25 Floor/Wall 18.00 14.00 25.00 1/2", 14.0" x 19.5" 1/2", 19.5" x 11.0" E4-1PEP-6
37.5 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 625 E3R-1PEP-6 LA/LC SC37.5J-K/EP 37.5 Floor/Wall 18.00 14.00 25.00 1/2", 14.0" x 19.5" 1/2", 19.5" x 11.0" E4-1PEP-6
50 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 750 E3R-1PEP-7 LA/LC SC50J-K/EP 50 Floor 19.00 16.00 28.00 n/a 1/2”, 20.5" x 13.0" E4-1PEP-7
75 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 960 E3R-1PEP-8 LB/LD SC75J-K/EP 75 Floor 25.00 20.00 33.00 n/a 1/2", 26.5" x 17.0" E4-1PEP-8
100 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 1460 E3R-1PEP-8 LC/PADS SC100J-K/EP 100 Floor 25.00 20.00 33.00 n/a 1/2", 26.5" x 17.0" E4-1PEP-8
Aluminum windings (Type SA.../EP) - No efficiency spec - Electrical Performance Aluminum windings (Type SA.../EP) - No efficiency spec - Dimensions
600 V : 120/240 Type 3R Outdoor Type 4
Const. Standard
Weight Enclosure
kVA Type Primary Taps Connection Catalog # kVA
[lbs] Name Lugs Width Depth Height Wall Mounting* Floor Mounting* Enclosure Name
(see p.25) Diagram Refer to page 2 for Mounting
(HV/LV) [inch] [inch] [inch] d, A x B [inch] d, C x E [inch] (Dimensions avail. online)
voltage codes
15 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 296 E3R-1PEP-5 LA/LA SA15J-K/EP 15 Floor/Wall 15.00 15.00 18.00 1/2", 10.0" x 16.5" 1/2", 16.5" x 10.0" E4-1PEP-5
25 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 310 E3R-1PEP-6 LA/LB SA25J-K/EP 25 Floor/Wall 18.00 14.00 25.00 1/2", 14.0" x 19.5" 1/2", 19.5" x 11.0" E4-1PEP-6
37.5 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 625 E3R-1PEP-6 LA/LC SA37.5J-K/EP 37.5 Floor/Wall 18.00 14.00 25.00 1/2", 14.0" x 19.5" 1/2", 19.5" x 11.0" E4-1PEP-6
50 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 750 E3R-1PEP-7 LA/LC SA50J-K/EP 50 Floor 19.00 16.00 28.00 n/a 1/2”, 20.5" x 13.0" E4-1PEP-7
75 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 960 E3R-1PEP-8 LB/LD SA75J-K/EP 75 Floor 25.00 20.00 33.00 n/a 1/2", 26.5" x 17.0" E4-1PEP-8
100 Type 2 +/- 2 x 2.5% 1Ph0-ST2/2-D0-2 1460 E3R-1PEP-8 LC/PADS SA100J-K/EP 100 Floor 25.00 20.00 33.00 n/a 1/2", 26.5" x 17.0" E4-1PEP-8
* See diagrams at right for
illustration of wall and floor
mounting points.
Copper windings (Type BC.../EP) - No efficiency spec - Electrical Performance Copper windings (Type BC.../EP) - No efficiency spec - Dimensions
600 V : 208Y/120 Type 3R Outdoor Type 4
Const. Standard
Weight Enclosure
kVA Type Primary Taps Connection Catalog # kVA
[lbs] Name Lugs Width Depth Height Wall Mounting* Floor Mounting* Enclosure Depth
(see p.25) Diagram Refer to page 2 for Mounting
(HV/LV)
voltage codes
[inch] [inch] [inch] d, A x B [inch] d, C x E [inch] Name [inch]
1.5 Type 2 none 3PDyn1-ST1/1 145 E3R-3PEP-1 LA/LA BC1.5J-M/EP 1.5 Floor/Wall 11.00 10.00 15.25 1/2", 12.50" x 8" 7/16", 12.5" x 7" E4-3PEP-1 12.00
2 Type 2 none 3PDyn1-ST1/1 150 E3R-3PEP-1 LA/LA BC2J-M/EP 2 Floor/Wall 11.00 10.00 15.25 1/2", 12.50" x 8" 7/16", 12.5" x 7" E4-3PEP-1 12.00
3 Type 2 +/- 1 x 5% 3PDyn1-ST1/1 175 E3R-3PEP-2 LA/LA BC3J-M/EP 3 Floor/Wall 15.00 11.00 15.25 1/2", 16.50" x 8" 1/2", 16.5" x 8" E4-3PEP-2 13.00
6 Type 2 +/- 1 x 5% 3PDyn1-ST1/1 185 E3R-3PEP-2 LA/LA BC6J-M/EP 6 Floor/Wall 15.00 11.00 15.25 1/2", 16.50" x 8" 1/2", 16.5" x 8" E4-3PEP-2 13.00
9 Type 2 +/- 1 x 5% 3PDyn1-ST1/1 240 E3R-3PEP-3 LA/LA BC9J-M/EP 9 Floor/Wall 18.00 12.50 17.00 1/2", 19.50" x 8" 5/8", 19.5" x 9.5" E4-3PEP-3 14.50
15 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 350 E3R-3PEP-4 LA/LA BC15J-M/EP 15 Floor/Wall 21.00 14.00 17.50 5/8", 22.50" x 10.0" 1/2", 22.5" x 10.0" E4-3PEP-4 16.00
30 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 520 E3R-3PEP-5 LA/LA BC30J-M/EP 30 Floor/Wall 21.00 18.00 20.00 5/8", 22.50" x 10.0" 1/2", 22.5" x 14.5" E4-3PEP-5 20.00
45 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 775 E3R-3PEP-6 LA/LB BC45J-M/EP 45 Floor 26.00 18.00 25.00 n/a 1/2", 28.5" x 15.0" E4-3PEP-6 20.00
75 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 1298 E3R-3PEP-7 LA/LC BC75J-M/EP 75 Floor 32.00 18.00 30.00 n/a 1/2", 34.5" x 15.0" E4-3PEP-7 20.00
112.5 Type 2 +/- 2 x 2.5% 3PDyn1-CT2/2 1365 E3R-3PEP-8 LB/LD BC112J-M/EP 112.5 Floor 36.00 25.00 32.00 n/a 1/2", 38.5" x 20.0" E4-3PEP-8 27.00
150 Type 2 +/- 2 x 2.5% 3PDyn1-CT2/2 2020 E3R-3PEP-9 LC/PADS BC150J-M/EP 150 Floor 36.00 25.00 36.00 n/a 1/2", 38.5" x 20.0" E4-3PEP-9 27.00
Aluminum windings (Type BA.../EP) - No efficiency spec - Electrical Performance Aluminum windings (Type BA.../EP) - No efficiency spec - Dimensions
600 V : 208Y/120 Type 3R Outdoor Type 4
Const. Standard
Weight Enclosure
kVA Type Primary Taps Connection Catalog # kVA
[lbs] Name Lugs Width Depth Height Wall Mounting* Floor Mounting* Enclosure Depth
(see p.25) Diagram Refer to page 2 for Mounting
(HV/LV)
voltage codes
[inch] [inch] [inch] d, A x B [inch] d, C x E [inch] Name [inch]
15 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 350 E3R-3PEP-4 LA/LA BA15J-M/EP 15 Floor/Wall 21.00 14.00 17.50 5/8", 22.50” x 10.0" 1/2", 22.5" x 10.0" E4-3PEP-4 16.00
30 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 520 E3R-3PEP-5 LA/LA BA30J-M/EP 30 Floor/Wall 21.00 18.00 20.00 5/8", 22.50" x 10.0" 1/2", 22.5" x 14.5" E4-3PEP-5 20.00
45 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 775 E3R-3PEP-6 LA/LB BA45J-M/EP 45 Floor 26.00 18.00 25.00 n/a 1/2", 28.5" x 15.0" E4-3PEP-6 20.00
75 Type 2 +/- 2 x 2.5% 3PDyn1-ST2/2 1298 E3R-3PEP-7 LA/LC BA75J-M/EP 75 Floor 32.00 18.00 30.00 n/a 1/2", 34.5" x 14.5" E4-3PEP-7 20.00
112.5 Type 2 +/- 2 x 2.5% 3PDyn1-CT2/2 1365 E3R-3PEP-8 LB/LD BA112J-M/EP 112.5 Floor 36.00 25.00 32.00 n/a 1/2", 38.5" x 20.0" E4-3PEP-8 27.00
150 Type 2 +/- 2 x 2.5% 3PDyn1-CT2/2 2100 E3R-3PEP-9 LC/PADS BA150J-M/EP 150 Floor 36.00 25.00 36.00 n/a 1/2", 38.5" x 20.0" E4-3PEP-9 27.00
* See diagrams at right for
illustration of wall and floor
mounting points.
Pg. 29 Pg. 30
Electrostatic Shielding - Option S1, S2, S3 K-Factor Rated Transformer - Option K4, K9, K13, etc.
Background Background
Electrostatic (Faraday) Shielding is an optional feature for Today’s modern electronic devices, such as computers,
transformers which provides a degree of protection for copiers, printers, and display terminals utilize switching-
sensitive electrical and electronic equipment from high mode power supplies, which are non-linear in the loading
frequency voltages (electrical noise) or transients. This placed on the transformer. Systems designed without due
feature is available on most isolation type transformers, consideration tend to exhibit significant power system
including encapsulated & K-factor rated transformers. It problems, such as:
is a relatively low cost means of protection from this type • Circuit breakers and fuses tripping far below their current
of power quality problem. Typical applications include ratings
computer and electronic loads, instrumentation, medical • Neutrals in transformers and panel boards are much
equipment, and industrial equipment (PLC, Process Control). hotter than their ratings.
Electrical noise is comprised of two types: • Distribution transformers overheat, even when operating
Normal mode: Noise which appears between the hot and Photo: Electrostatic shield connection to the ground lug well within their specified nameplate ratings.
neutral current carrying conductors. These problems are often the result of harmonics. The solid-
Common mode: Noise which appears between both the hot Application Notes state switching elements (SCRs, transistors, and capacitors) Photo: Double-Rated Neutral
and neutral conductor, relative to the ground. • Four types of electrostatic shielding are available, offering continually switch on and off to extract a Direct Current
Common mode noise is more prevalent and should be the (DC) from the sinusoid. This reflects a higher frequency
key criterion for any noise suppression device.
incrementally greater degrees of common-mode noise
waveform on the supply line, which is a multiple of the Features & Specifications
attenuation.
• The ratio of the common mode noise attenuation is fundamental frequency. These reflected signals become The K-Factor rating of a transformer is an index of the
Features & Specifications expressed in decibels (dB) or as a ratio. added to the original (fundamental) frequency. The result is transformer’s ability to supply harmonic content in its load
• The shielded transformer suppresses common mode • Use suffix “S1” or “S2” or “S3” or “X” in part number, as a distorted voltage and current signal, with taller peaks and current while operating within its temperature limits. For
noise thanks to the presence of a broad (full height) foil per Rex Catalog Number system irregular shapes. The diagram below illustrates the typical dry type transformers, a “K-Factor” calculation is made to
conductor that is wound in between the primary and • The table below provides the typical attenuation with distorted wave shape that is produced with the addition of determine the amount of harmonic content present in a
secondary windings. 3rd order and 5th order harmonics power system. K-Rated transformers are sized to handle
each type of shield.
• The conductor material is typically selected to be the 100% of the fundamental 60 Hz load, plus the non-linear
same as the winding material; copper or aluminum. loading level denoted by the K factor. The neutral of the
• The grounded shield provides a low-resistance path to transformer is sized at 200% of the current rating of the
ground by the effect of capacitive coupling. This prevents Power with high frequency common phase connections.
high frequency signals present in the source voltage
from reaching the secondary of the transformer, and
mode noise is connected to the primary
side of the transformer.
Application Notes
subsequently, the connected load. • A K-Factor may be specified on an isolation transformer,
• The electrostatic shield will not perform any function or encapsulated transformer
with regards to harmonic current or voltage distortion of SHIELDED TRANSFORMER • Commonly specified K factors are K4, K9, K13, and K20.
waveforms. • Use suffix “K4” or “K9” or “K13” or “K13” in part number,
ld
Sh
ci g
pa in
ta
Ca ind
ry
da
ad
ar
Example:
on
im
Lo
c
Fundamental frequency = 60 Hz
Se
Pg. 33 Pg. 34
Drive Isolation Transformer (DIT) - Type D - For U.S.A. Drive Isolation Transformer (DIT) - Type D - For U.S.A.
Reference Charts - Electrical Performance - Type 3R enclosures Reference Charts - Dimensions - Type 3R enclosures
The tables below provide typical standard values for drive isolation transformers with standard specification. The tables below provide typical standard values for drive isolation transformers with standard specification.
• Sample catalog numbers are shown for 460 V delta to 460Y/266 V. For other voltage codes, please see page 2. • The values reported below will not vary with the selection of special voltages, shielding, and some other options
• The values reported below will not vary with the selection of special voltages, shielding, and some other options. • Special specifications such as higher K-Factor ratings and Temperature Rise may affect dimensions and the values
• Special specifications such as higher K-Factor ratings and Temperature Rise may affect dimensions and the values below; Contact Rex Sales for application specific information.
below; Contact Rex Sales for for application specific information. For additional enclosure details (such as mounting), consult page 8.
Copper windings (Type DC) - No efficiency spec (for USA installation only) Copper windings (Type DC) - No efficiency spec (for USA installation only)
Efficiency Average Standard 460 V : 460Y/266 V Standard Indoor Enclosure (Type 1 or Type 3R Indoor) Type 3R Outdoor
Drive
kVA (35% load, Impedance Sound Primary Taps Connection Lugs kVA Width Depth Height Weight Enclosure Depth Enclosure
HP 75 OC) Level [dB] Sample Catalog # Mounting Type
Diagram (HV/LV) Refer to page 2 for voltage codes [inch] [inch] [inch] [lbs] Name [inch] Name
5 9 n/a 5% - 6.5% 40 +/- 1 x 5% 3PDyn1-ST1/1 Terminal Block DC9H1-P1 9 Floor/Wall 15.75 16.00 21.00 150 E3R-4 Type 3R indoor 21.12 E3R-4-W
8 11 n/a 5% - 6.5% 45 +/- 1 x 5% 3PDyn1-ST1/1 LA/LA DC11H1-P1 11 Floor/Wall 20.50 16.00 25.00 175 E3R-5 Type 3R indoor 21.62 E3R-5-W
10 14 n/a 5% - 6.5% 45 +/- 1 x 5% 3PDyn1-ST1/1 LA/LA DC14H1-P1 14 Floor/Wall 20.50 16.00 25.00 205 E3R-5 Type 3R indoor 21.62 E3R-5-W
15 20 n/a 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC20H1-P1 20 Floor/Wall 20.50 16.00 25.00 240 E3R-5 Type 3R indoor 21.62 E3R-5-W
20 27 n/a 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC27H1-P1 27 Floor/Wall 20.50 20.75 30.00 270 E3R-6 Type 3R indoor 26.39 E3R-6-W
25 34 n/a 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC34H1-P1 34 Floor/Wall 20.50 20.75 30.00 310 E3R-6 Type 3R indoor 26.39 E3R-6-W
30 40 n/a 3.5% - 5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC40H1-P1 40 Floor/Wall 20.50 20.75 30.00 350 E3R-6 Type 3R indoor 26.39 E3R-6-W
40 51 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC51H1-P1 51 Floor/Wall 20.50 20.75 30.00 460 E3R-6 Type 3R indoor 26.39 E3R-6-W
50 63 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC63H1-P1 63 Floor/Wall 24.50 21.75 36.00 515 E3R-7 Type 3R indoor 29.37 E3R-7-W
60 75 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LB DC75H1-P1 75 Floor/Wall 24.50 21.75 36.00 605 E3R-7 Type 3R indoor 29.37 E3R-7-W
75 93 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LB DC93H1-P1 93 Floor 30.75 33.40 44.00 790 E3R-8 Type 3R indoor 37.49 E3R-8-W
100 118 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/LC DC118H1-P1 118 Floor 30.75 33.40 44.00 865 E3R-8 Type 3R indoor 37.49 E3R-8-W
125 145 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/LC DC145H1-P1 145 Floor 30.75 33.40 44.00 980 E3R-8 Type 3R indoor 37.49 E3R-8-W
150 175 n/a 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/LC DC175H1-P1 175 Floor 40.00 38.00 52.00 1310 E3R-9 Type 3R indoor 41.75 E3R-9-W
200 220 n/a 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/LD DC220H1-P1 220 Floor 40.00 38.00 52.00 1420 E3R-9 Type 3R indoor 41.75 E3R-9-W
250 275 n/a 4% - 6% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DC275H1-P1 275 Floor 40.00 38.00 52.00 1745 E3R-9 Type 3R indoor 41.75 E3R-9-W
300 330 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DC330H1-P1 330 Floor 40.00 38.00 52.00 1895 E3R-9 Type 3R indoor 41.75 E3R-9-W
400 440 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DC440H1-P1 440 Floor 46.00 50.00 66.00 2495 E3R-10 Type 3R indoor 50.00 E3R-10-W
500 550 n/a 4% - 6% 62 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DC550H1-P1 550 Floor 46.00 50.00 66.00 2665 E3R-10 Type 3R indoor 50.00 E3R-10-W
Aluminum windings (Type DA) - No efficiency spec (for USA installation only) Aluminum windings (Type DA) - No efficiency spec (for USA installation only)
Efficiency Average Standard 460 V : 460Y/266 V Standard Indoor Enclosure (Type 1 or Type 3R Indoor) Type 3R Outdoor
Drive
kVA (35% load, Impedance Sound Primary Taps Connection Lugs kVA Width Depth Height Weight Enclosure Depth Enclosure
HP 75 OC) Level [dB] Sample Catalog # Mounting Type
Diagram (HV/LV) Refer to page 2 for voltage codes [inch] [inch] [inch] [lbs] Name [inch] Name
15 20 n/a 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA20H1-P1 20 Floor/Wall 20.50 16.00 25.00 250 E3R-5 Type 3R indoor 21.62 E3R-5-W
20 27 n/a 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA27H1-P1 27 Floor/Wall 20.50 20.75 30.00 250 E3R-6 Type 3R indoor 26.39 E3R-6-W
25 34 n/a 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA34H1-P1 34 Floor/Wall 20.50 20.75 30.00 280 E3R-6 Type 3R indoor 26.39 E3R-6-W
30 40 n/a 3.5% - 5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA40H1-P1 40 Floor/Wall 20.50 20.75 30.00 305 E3R-6 Type 3R indoor 26.39 E3R-6-W
40 51 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA51H1-P1 51 Floor/Wall 20.50 20.75 30.00 400 E3R-6 Type 3R indoor 26.39 E3R-6-W
50 63 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA63H1-P1 63 Floor/Wall 24.50 21.75 36.00 470 E3R-7 Type 3R indoor 29.37 E3R-7-W
60 75 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LB DA75H1-P1 75 Floor/Wall 24.50 21.75 36.00 510 E3R-7 Type 3R indoor 29.37 E3R-7-W
75 93 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LB DA93H1-P1 93 Floor 30.75 33.40 44.00 770 E3R-8 Type 3R indoor 37.49 E3R-8-W
100 118 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/LC DA118H1-P1 118 Floor 30.75 33.40 44.00 825 E3R-8 Type 3R indoor 37.49 E3R-8-W
125 145 n/a 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/LC DA145H1-P1 145 Floor 30.75 33.40 44.00 915 E3R-8 Type 3R indoor 37.49 E3R-8-W
150 175 n/a 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/LC DA175H1-P1 175 Floor 40.00 38.00 52.00 1230 E3R-9 Type 3R indoor 41.75 E3R-9-W
200 220 n/a 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/LD DA220H1-P1 220 Floor 40.00 38.00 52.00 1335 E3R-9 Type 3R indoor 41.75 E3R-9-W
250 275 n/a 4% - 6% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DA275H1-P1 275 Floor 40.00 38.00 52.00 1475 E3R-9 Type 3R indoor 41.75 E3R-9-W
300 330 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DA330H1-P1 330 Floor 40.00 38.00 52.00 1540 E3R-9 Type 3R indoor 41.75 E3R-9-W
400 440 n/a 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DA440H1-P1 440 Floor 46.00 50.00 66.00 2405 E3R-10 Type 3R indoor 50.00 E3R-10-W
500 550 n/a 4% - 6% 62 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DA550H1-P1 550 Floor 46.00 50.00 66.00 2670 E3R-10 Type 3R indoor 50.00 E3R-10-W
Pg. 35 Pg. 36
Drive Isolation Transformer (DIT) - Type D - Canada Drive Isolation Transformer (DIT) - Type D - For Canada
Reference Charts - Electrical Performance - Type 3R enclosures Reference Charts - Dimensions - Type 3R enclosures
The tables below provide typical standard values for drive isolation transformers with standard specification. The tables below provide typical standard values for drive isolation transformers with standard specification.
• Sample catalog numbers are shown for 575 V delta to 460Y/266 V. For other voltage codes, please see page 2. • The values reported below will not vary with the selection of special voltages, shielding, and some other options
• The values reported below will not vary with the selection of special voltages, shielding, and some other options. • Special specifications such as higher K-Factor ratings and Temperature Rise may affect dimensions and the values
• Special specifications such as higher K-Factor ratings and Temperature Rise may affect dimensions and the values below; Contact Rex Sales for application specific information.
below; Contact Rex Sales for for application specific information. For additional enclosure details (such as mounting), consult page 8.
Copper windings (Type DC) - NRCan 2019 (Canada) compliant Copper windings (Type DC) - NRCan 2019 (Canada) compliant
Efficiency Average Standard 575 V : 460Y/266 V Standard Indoor Enclosure (Type 1 or Type 3R Indoor) Type 3R Outdoor
Drive
kVA (35% load, Impedance Sound Primary Taps Connection Lugs kVA Width Depth Height Weight Enclosure Depth Enclosure
HP 75 OC) Level [dB] Sample Catalog # Mounting Type
Diagram (HV/LV) Refer to page 2 for voltage codes [inch] [inch] [inch] [lbs] Name [inch] Name
5 9 n/a 5% - 6.5% 40 +/- 1 x 5% 3PDyn1-ST1/1 Terminal Block DC9J1-P1 9 Floor/Wall 15.75 16.00 21.00 150 E3R-4 Type 3R indoor 21.12 E3R-4-W
8 11 n/a 5% - 6.5% 45 +/- 1 x 5% 3PDyn1-ST1/1 LA/LA DC11J1-P1 11 Floor/Wall 20.50 16.00 25.00 175 E3R-5 Type 3R indoor 21.62 E3R-5-W
10 14 n/a 5% - 6.5% 45 +/- 1 x 5% 3PDyn1-ST1/1 LA/LA DC14J1-P1 14 Floor/Wall 20.50 16.00 25.00 205 E3R-5 Type 3R indoor 21.62 E3R-5-W
15 20 98.00% 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC20J1-P1/Z3 20 Floor/Wall 20.50 16.00 25.00 290 E3R-5 Type 3R indoor 21.62 E3R-5-W
20 27 98.16% 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC27J1-P1/Z3 27 Floor/Wall 20.50 20.75 30.00 320 E3R-6 Type 3R indoor 26.39 E3R-6-W
25 34 98.28% 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC34J1-P1/Z3 34 Floor/Wall 20.50 20.75 30.00 355 E3R-6 Type 3R indoor 26.39 E3R-6-W
30 40 98.34% 3.5% - 5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC40J1-P1/Z3 40 Floor/Wall 20.50 20.75 30.00 370 E3R-6 Type 3R indoor 26.39 E3R-6-W
40 51 98.44% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC51J1-P1/Z3 51 Floor/Wall 20.50 20.75 30.00 450 E3R-6 Type 3R indoor 26.39 E3R-6-W
50 63 98.52% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DC63J1-P1/Z3 63 Floor/Wall 24.50 21.75 36.00 635 E3R-7 Type 3R indoor 29.37 E3R-7-W
60 75 98.60% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LB DC75J1-P1/Z3 75 Floor/Wall 24.50 21.75 36.00 585 E3R-7 Type 3R indoor 29.37 E3R-7-W
75 93 98.67% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LB DC93J1-P1/Z3 93 Floor 30.75 33.40 44.00 880 E3R-8 Type 3R indoor 37.49 E3R-8-W
100 118 98.75% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LC DC118J1-P1/Z3 118 Floor 30.75 33.40 44.00 930 E3R-8 Type 3R indoor 37.49 E3R-8-W
125 145 98.82% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/LC DC145J1-P1/Z3 145 Floor 30.75 33.40 44.00 1080 E3R-8 Type 3R indoor 37.49 E3R-8-W
150 175 98.87% 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/LC DC175J1-P1/Z3 175 Floor 40.00 38.00 52.00 1350 E3R-9 Type 3R indoor 41.75 E3R-9-W
200 220 98.93% 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/LD DC220J1-P1/Z3 220 Floor 40.00 38.00 52.00 1630 E3R-9 Type 3R indoor 41.75 E3R-9-W
250 275 98.99% 4% - 6% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/PADS DC275J1-P1/Z3 275 Floor 40.00 38.00 52.00 1985 E3R-9 Type 3R indoor 41.75 E3R-9-W
300 330 99.04% 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/PADS DC330J1-P1/Z3 330 Floor 40.00 38.00 52.00 2340 E3R-9 Type 3R indoor 41.75 E3R-9-W
400 440 99.10% 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DC440J1-P1/Z3 440 Floor 46.00 50.00 66.00 2925 E3R-10 Type 3R indoor 50.00 E3R-10-W
500 550 99.16% 4% - 6% 62 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DC550J1-P1/Z3 550 Floor 46.00 50.00 66.00 3595 E3R-10 Type 3R indoor 50.00 E3R-10-W
Aluminum windings (Type DA) - NRCan 2019 (Canada) compliant Aluminum windings (Type DA) - NRCan 2019 (Canada) compliant
Efficiency Average Standard 575 V : 460Y/266 V Standard Indoor Enclosure (Type 1 or Type 3R Indoor) Type 3R Outdoor
Drive
kVA (35% load, Impedance Sound Primary Taps Connection Lugs kVA Width Depth Height Weight Enclosure Depth Enclosure
HP 75 OC) Level [dB] Sample Catalog # Mounting Type
Diagram (HV/LV) Refer to page 2 for voltage codes [inch] [inch] [inch] [lbs] Name [inch] Name
15 20 98.00% 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA20J1-P1/Z3 20 Floor/Wall 20.50 16.00 25.00 260 E3R-5 Type 3R indoor 21.62 E3R-5-W
20 27 98.16% 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA27J1-P1/Z3 27 Floor/Wall 20.50 20.75 30.00 305 E3R-6 Type 3R indoor 26.39 E3R-6-W
25 34 98.28% 3.5% - 5.5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA34J1-P1/Z3 34 Floor/Wall 20.50 20.75 30.00 350 E3R-6 Type 3R indoor 26.39 E3R-6-W
30 40 98.34% 3.5% - 5% 45 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA40J1-P1/Z3 40 Floor/Wall 20.50 20.75 30.00 370 E3R-6 Type 3R indoor 26.39 E3R-6-W
40 51 98.44% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA51J1-P1/Z3 51 Floor/Wall 20.50 20.75 30.00 435 E3R-6 Type 3R indoor 26.39 E3R-6-W
50 63 98.52% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LA DA63J1-P1/Z3 63 Floor/Wall 24.50 21.75 36.00 565 E3R-7 Type 3R indoor 29.37 E3R-7-W
60 75 98.60% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LA/LB DA75J1-P1/Z3 75 Floor/Wall 24.50 21.75 36.00 620 E3R-7 Type 3R indoor 29.37 E3R-7-W
75 93 98.67% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LB DA93J1-P1/Z3 93 Floor 30.75 33.40 44.00 825 E3R-8 Type 3R indoor 37.49 E3R-8-W
100 118 98.75% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LB/LC DA118J1-P1/Z3 118 Floor 30.75 33.40 44.00 965 E3R-8 Type 3R indoor 37.49 E3R-8-W
125 145 98.82% 3.5% - 5% 50 +/- 2 x 2.5% 3PDyn1-ST2/2 LC/LC DA145J1-P1/Z3 145 Floor 30.75 33.40 44.00 1090 E3R-8 Type 3R indoor 37.49 E3R-8-W
150 175 98.87% 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/LC DA175J1-P1/Z3 175 Floor 40.00 38.00 52.00 1650 E3R-9 Type 3R indoor 41.75 E3R-9-W
200 220 98.93% 3.5% - 5% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LC/LD DA220J1-P1/Z3 220 Floor 40.00 38.00 52.00 1960 E3R-9 Type 3R indoor 41.75 E3R-9-W
250 275 98.99% 4% - 6% 55 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/PADS DA275J1-P1/Z3 275 Floor 40.00 38.00 52.00 2070 E3R-9 Type 3R indoor 41.75 E3R-9-W
300 330 99.04% 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 LD/PADS DA330J1-P1/Z3 330 Floor 40.00 38.00 52.00 2600 E3R-9 Type 3R indoor 41.75 E3R-9-W
400 440 99.10% 4% - 6% 60 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DA440J1-P1/Z3 440 Floor 46.00 50.00 66.00 3100 E3R-10 Type 3R indoor 50.00 E3R-10-W
500 550 99.16% 4% - 6% 62 +/- 2 x 2.5% 3PDyn1-CT2/2 PADS DA550J1-P1/Z3 550 Floor 46.00 50.00 66.00 3840 E3R-10 Type 3R indoor 50.00 E3R-10-W
Pg. 37 Pg. 38
Our full range of dry type products
General Purpose Transformers Input & Output Reactors
Distribution/Isolation, CE Marked Motor Guarding Transient Filters
Autotransformers DC Chokes, Saturable-Core Reactors
K Factor-Rated, Drive Isolation Inter-Bridge Reactors
Electrostatically Shielded / Ultra Isolating Air Core Reactors
Motor Starting Auto Transformers NEMA -1, -2, 3R, 4, 4X, 12
Specialty Transformers Stainless Steel 304 & 316
Non-standard voltages & vector diagram Specialty Industrial Enclosures
Encapsulated / Potted transformers Transformer Cores
Marine Duty (with applicable certificates) Snubbers (RC) with/without monitoring
Power transformers (up to 15 MVA, 200 kV BIL) Low & High Voltage Standoffs, Insulators
VPI/VPE/Cast Coil, Snubbers Surge (lightning) Arresters
Transformers for Hazardous Locations Testing, Refurbishment, & Repair
Mini Power Centers Replacement of windings, core, etc.
www.rexpowermagnetics.com
Toll Free USA/Canada: 1 (800) 387-2840
Tel: (905) 695-8844, Fax: (905) 695-8855
[email protected]
65 Basaltic Rd.,
Concord, Ontario,
Canada, L4K 1G4
Find us on:
YouTube
Facebook
LinkedIn
##"!&"%( "'%,,#"*%%!&"% %&/////////////////////////// 6
+"*%!&.
+"*%!&1!#',/////////////////////////////////////////////////////////// 6
$%$5;:6$
;445 '!%+"*%%!&"% %&!&///////////////////////////////////////////////////////////// 7
#$%#! !('(%%
#$%
! $$ #$.............................................................................................. 7
(&'" %,',#%!&"% %&/
)$%)!,'!"",. *! $%#& $ &#$ ##............................................... 8
!!")"!.!(&'" %
&%).$%## # ""!&'%("!/////////////////////////////////////////////////////////////////////////////////////////////////// 9
$&$%!# %# (%.
%%#%#% &&#$$&#!# 01.................................................................... 9
#+&%&#+
$& ................................................................................................................ 9
&$% #$#'%* %
&$% #% # % +
%# + "%"!&'%("!////////////////////////////////////////////////////////////////////////////////////////////////// :
+(# &$$
%# & &%% (##$ ## $$$..................................................................................... :
%
%%$+% !*
#$%"%!"%,',# #
%% $.......................................................................................... :
#"*% !#%"('&%
#%$%# & &% #% &'"%,,#%!&"% %&//////////////////////////////////////////////////////////////////////////// ;
#%# *.
*! $%#& $% #$ ##.................................................... <
)!# &%&$
&$% $$!%* $ $%#& %&#$ $% $#$ ##$............................... =
%#$ ##$+ (##$ ##$
&!% 5879+ !#$ (%
%##$ ##*!$........................................................... =
$%#& %#$ ##$+
!%,!,""*%%!&"% %&/////////////////////////////////////////////////////////////// >
#% #$+&% %#$ ##$+ %#
% %#$ ##$+
"*///%!&"% %&///////////////////////////////////////////////////////////////////////// 65
&$% $&#$+&$% &%
%#$% #$+ %# !$(##"!&!(&'" &!&000000000000000000000////// 65
! (#!# &%$
$#'$.
&!! #%* $# &!////////////////////////////////////////////////////////////////////////////////////////////////////////////////// 66
&(&'!!)&' !'!
%&%!)"# !'. +'!%!"&(%&//////////////////////////////////////////////////////////////////////////////////////// 67
(&% %"&!%+
%!# $$$) (#
!&"!&!'&2%&"*%%!&"% %&/////////////////////////////////// 68
$ &*)!$
$%$!# &%
$#' #.
+"*%!&&#%"('")!%"!-&"!"
!# &#$'$-#$%* &#
&(#%"%)%,%&#"!&)!&&
$&!! #%* &#!$$ #
&$% #$#' &#'#*
%#%/ &$$+
&%&#+%$
!$,$ * &#
!"",%&#$&!! #%
* &#&$%#*2 #%+
#)!#$+%
!%+&%&#
(/ (.
& '"'% " ! ! '! !"%$"! " !!!
!" #!'!"!"% $"! #!" )!"#) #"'!+
' '!#" " #" !+
&
% ! $!#"' '"'% " ! !#
".1 "02/--+" ! *
0
&
% !!" "'"!)#"# )"!"!" !"'
'"'" ! !) " #"!)% " ! ! "#".1 /--+
& #"! !" !")#% " ! !+
!$+
&
% !"!"!"" ""'" #"!%
" ! !# !) !) "!)!! !)!%!#"# #!"!# !+
.
$% #$ ##$+&%#*%*!%#$ ## #&$#$'# %$/
#'$ #$ ##$+!*$% %%#"&#%$ '#$!
#'$ ### $/';0!&$,780!&$,7<0!&$,8:0!&$/
%# $%*#$ ##$+$% !# %%$*$%$# 0#"&*%#$%$%%
&#&% $(% $%#& $/
#*%#$ ##$.#%#/+$% !# #(% (#%$%# &% #
% % $$$(#$&%#%#)!%*, (# !# $%$,$% '# !$/
) (#$#$ ##$#&%% %)<68
0723$%#$/
-
#
. -% #%/+ (#%#$ ##$ #&$(## &##%$#!#$%/'
#$, #)!
:,
=,
79,
86,
96,%/
(,,,$$ #$ ##$+$% ('#* (%# $$ &%$ %
$&#/
( &-
'#$ ##$+$% % (#% #&&/
!#"&*$$+ !#%%#"&$ %#%;6 +/
! )*!!$+) (#$%#$ ##$($#'&&!#$$&#
!#%(%! *$%##$/ #!! $(%#$ !# $ #(## #
%%$#!#$%! )*#$ % %! *$%#!#% $/
+
1 # '$ $ #&%&#$ #!$ !%*$%(% #(% &% %# ! (#
1 &$ # (%!##*$ #*$(%#
1 %*! #%%# %#$% % #(%!#%&#$
1
&%## &#$$% #$ % #$
1 %#!%#$% ' $ (%%#$ ##$
%#+
1 # &&%#*$
1 0'# &$% #&%#$$$ '#
% %$&## &$%#&%&#
1 # '$ #$$ & #$$$&#$#$%#%$
1 ##$% #$.$%#& ,%#%, #$% $$
1 # '$ $ ## ,$,
1 # '$ $ #&$&%%#*
1 &$
1
*%# $*$%$
1 &*$&%&$
1 ! $&#$,
7,
92(% #(% &%%#$3,
:,
78-$!!% #%#
8
Coil Support
Blocks
Disk Wound
High Voltage
Winding
&% " ! !#(" !%#!" #*"'!!"
'"!)%% $"#! " #"!" ")#!!" #)
" %"!" " !!*%! !#""%"!"!# $"!!#!
$* '%! #"# #"'&% ###" *
%$"%!'!" -.%# !" #""" '" #&
! " #" !*
!!" #!!"! !!$'%#"# !"
% """" *' ! " '
!#"'!!"!##"!*
!"!#!"" ""$"'"" ! *%
" "# "" ! "!""!#*!% " "# !
"
"#")""" "# )"
&% " ! ! #"# %"!"!!110/!#*'" "#
!!""" !"!"#"' #!)#& !)! '!" "
,!!)&!$)!!"!'!" +!!#"!!*
2
!$ #"
&)
)
,
(
) %
$&"$&
$ (
!
(
$
$
(!
$
(&
#$
(
(
%$
(
&
%(
$
"
$
" (
%
$
"(
!
" &
"$
!
$(
"
$
#
#
" #
$(
$
!
#
!($
!" #
&"
!
$(
,
#
!
!
#
&'
$
#
!$
#
!
% %
#
"
#
#
$
#
#
!$
#
#
!
#
#
$
#
$+*(#
,
Upper Core
Clamp
Coil Support
Blocks
Upper Core
Yoke
Cast Epoxy
High Voltage
Winding
Cooling Ducts
Lower Core
Clamp
Coil Support
Blocks
* $$"$$
%
$!&$ #'
*
!
' ! $)#2518
!!'
!$
'
!'
* #$ ")!$"!$"#
'#!
)'
* )$ +#,
#$-
! 251.$'
* "
$"! '
##$ ! ' !
$ !)
'
)
&
&)
$2431
!
!'
* $$$
'#
! ""# #
"' $
$!
"
$
"$#'
!##+,
The following charts illustrate the currently legislated 99(12
98(83
minimum efficiency levels. Please note that there is a 98(99
98(67
separate chart for each range of Transformer BIL levels. 98(81
Values in blue or red represent the current standard for 98(57
98(69
Canadian Transformers, which are known as C802.2 levels, 98(42
98(51
or DOE2010 levels. The values in green represent the
98(30
recently increased minimum efficiency levels for 98(36
98(12
transformers for the USA market, known as “DOE 2016.” It is 98(13
expected that Canadian minimum levels will harmonize 97(86
97(86
with the American levels in 2018. 97(63
97(63
97(18
2010%"
2016& 97(18
$ #2545
99(42
&+<,)-75'50<!#
*
99(38
99(34
99(31
99(47
2010%"
2016&
99(27
99(43
$ #96=
99(22 99(33
99(37
99(14
99(28 99(28
99(07
!##+,
99(21 99(24
98(96
99(09 99(20
99(33
98(82
98(93 99(15
98(73 99(28
!##+,
98(82
99(09
98(60
98(65
99(21
98(99
98(49 99(11
98(52
98(33 98(91
99(02
98(33
98(10 98(80
98(10 98(89
97(90 98(63
97(90
98(69
97(50
97(50 98(53
98(57
&+<,)-75'50<!#
*
&+<,)-75'50<!#
*
"*%%$(!,'%" !&%" '%&'%("!&,&' &%)%'(," !#%&!'0
"&%'"&"(%'%'!'!&',.''%!&"% %.%%(!."%&*'%0
" #%)!' !'%%! *' &!&) '%"! $(# !' ! '" &&, #"&& ' "!%!&. "%
!2#"('%&3!"'!% "'%&"(!0"*)%.'&&!"'*,&#"&&"%
#%! ,"!"&'&"% '(&(�
!&'"!"'%$(# !'&!*'"*'%" ! &&"!&0
+
"*%
!& & )"# " #' ! " "* &&"! #"*% ! &'%("! '%!&"% %&
'')'+'%!&'%,(+!(',=<@"%%'!'&'!%'%!&"% % &&"!0
!&'%!&"% %&;995;999#%"('%" !&!'"%%":995<99 (&&
!' ')!',"'(!'0+1&&#,&!&'%!&"% %&!"*%'& &&"!&
,'"%":9"%%#!!"!'&#"!0
&"*&"%''%!&"% %&'""''#%,!,""!!(!*'"('!,%&'%"!&
('"!'%(&) !&0
&&"(%(&'" '%!&"% %"%!&.+
"*%
!&&&"&'%('(%!#%#%'"*"%*'
"(%(&'" %&"!)%,(!$(!&#-#%"'&0(%!!%!#%' !'1&"(&"!"!!(
%&%!#%"(')"# !' !&*)'%&"(%&'""%(!$(!#%&"("!&'"
*)%',"!&.!!(&'%&%!!%" %"&#'" '&'$(# !'0
""*!&&'" !)&('"%&#-(&'" %%$(% !'&!%!',%&/
4%4"('#('4(%%!''&'&'"%'&!%('%%&
4#',('%4%"(!!4'%!&"% %
4), #!%!"%"%&"%!()!8 !(',
4%!&"% % ''"!('" %)4"!'%")(( 4'#!%
4
!&('"%!'%"!*'
!)"'%("!&,&'
4'%"*4#%" !!'%!&"% %&
4
(#%'!%"!4"%%'"%
4(%%!' !%"%%'"%&
4!(%&6(&%('7"%#%"'"!%"
&*'!&(%&
4%!&"% %&*'&#&& #%")&"!&
:9
"
$ #"
!
2
01(./(-.(
"(
*
$
" $(
* $
$"
$
"(
*
#
$
!
$
!
$
(
$
$
"
"
(
* % " $
!
$
( &&
/
)
"
$"(
* $
"
"
$
(
* $
!
"(
*
$
""
"
"
(
*
$
$ ))
$))
$
(
"
+ ",'
* !& '$
$
!
"
$ "
!
(
* $
!
$
"
(
*
&'$ !
STANDARD IMPEDANCE RANGE
(
$
%
VOLTAGE CLASS UP TO 2000 KVA OVER 2000 KVA
%
!
+
(, 5.0 KV 4.0-6.0 % 6.0-7.0 %
8.7 KV 4.5-6.5 % 6.0-8.0 %
* !$
! 15.0 KV
25.0 KV
5.5-7.0 % 6.5-8.0 %
6.5-7.5 % 7.0-8.5 %
+
,$
( 35.0 KV 6.5-7.5 % 7.0-8.5 %
..
!
$
"
% !
&
"
"
"
%
"(& ('
&
%
"#
%
")& )'
&
&
%
"+& +'
&
$
$ $$ %&
$
"
!"%
)
"%"%
"+& +'
&
*$
%
$$%"%
"()& ()'
$$$%
&
%
$$
%
&%
)
'(
The dimensions shown here serve only as a general guideline. These values will vary with efficiency and other criteria.
KVA WIDTH DEPTH HEIGHT WEIGHT WIDTH DEPTH HEIGHT WEIGHT TOT.WT.
DIMENSIONS IN INCHES LBS DIMENSIONS IN INCHES LBS LBS
!" "
"
(*
+#&#+" # ##)&$&#)(( #'"&#)&'&#!#)&+'(0
"""'#"'
! & &
*" 6-2'362'5511#6-2'362'5522
*$!
(.)5--)054)/51-
* )&,#"'
* $ + 32
%%%
1 .1
' ) # ! ! !
)$ ! !*".0 (/0---+ '(&)#"2
'# #"/
&&"'#&!&'
'(# /"
#"'(&)#" )(#(&"'#&!&'
)'(#"-$#!$ (+($&!&-'#""(' &*
'# #"
&#"#+&/&/&")(-/$ ) #"/
#(#&(&"
&*(#"'(&)#" )
" !
)"%%" ! !
"$)(")($)((#&'
3(/ (&#'( -
#(#&)&"&"'"( (&'
(&
'# "
) $ #'/()& 3#&(#&'
&!#"
"
"(&3&(#&'
(&#!" # (
&#"#&#&&#&(#&'
$#,-#/ .&#)'##" )!# !
&")(--$'4+($$ &('5
37/38/39/3:/3:,/378
"#+&"(&' (" ''( "$ "(
"-" (& "- )'(#!+(&"$ (-
")'(& " #')&'
""$+("")(## () ""(' )$" "!
.&#)'3##"&"'#&!&'4 ''7/*85 #+" *# (("#'"
"') (#&'
)" , ! !*0-"10--+ )&4 (""5&&'(&'
" #'/$"(- /#&# ) ! !&
# !"&
#)"( "(' $ !"(#+""'/#&/"') #"/(1
)&7:;/666'%11'"/!")()&"/")'(#!&'&* (-"#"#&/"#&(##&#"(#/"(&#
06727<
INPUT REACTORS
OUTPUT REACTORS
MOTOR GUARDING TRANSIENT FILTERS
AC LINE REACTORS AND MOTOR GUARDING TRANSIENT FILTERS
REX POWER MAGNETICS LINE REACTORS ARE TODAY’S SOLUTION TO
SCR DRIVE / INVERTER APPLICATION PROBLEMS
Inductors placed at the input and output
of electrical equipment can provide
Rex Power Magnecs,
established in 1972 is an ISO 9001
protecon and improve performance.
registered leading manufacturer Line Reactors absorb many power line
of CSA cered and UL listed disturbances which could damage or
custom dry type Transformers.
Rex is driven by technology, shut down your inverters, variable speed
innovaon, and customer controllers, or other voltage-sensive
service, and has a track record of
equipment.
sustained protable growth.
With a central and integrated
engineering, manufacturing, and • Rex Line Reactor designs conform to
customer service facility located
just north of Toronto, Ontario, UL, CSA, and IEC internaonal standards.
Canada, and warehouses • Three phase AC line reactors when used
throughout Canada and the
United States, the company as input or output lters on inverter
oers a broad range of dry type electronic speed drive applicaons
power magnec products to provide several signicant benets
markets throughout North
America and internaonally. which are explained in this catalogue.
The Rex product line includes • Rex Motor Guarding Transient Filters incorporate reactors and resistors. When these
custom designed specialty devices are placed on the output of adjustable frequency drives they protect the motor
transformers, Power Transformers
windings from the damaging voltage spikes associated with the fast switching eects of
up to 15 MVA and 35,000 Volts,
distribuon transformers, IGBT’s and long lines and cables.
reactors, autotransformers, control
and machine tool transformers,
custom enclosures, custom cut
FEATURES BENEFITS
electrical steel cores, and other • Easy to install • Reduce electrical line noise
power magnec products and
• High saturaon levels • Protect and extend the life of S.C.R.’s and
services. Supported by considerable
and sustained investment in • Smaller and less expensive than isolaon transistors
research and development, transformers • Filter power line disturbances
new and automated equipment, • Reduce harmful surge current • Limit short circuit currents
and ecient processes Rex Power • Available in open or NEMA 1 enclosed • Important in achieving compliance to IEEE
Magnecs connually expands construcon 519
and enhances its product and
service oering. • Conforms to CSA, UL, and IEC standards • Reduce harmonic distoron
• Available in a wide range of standard • Reduce nuisance tripping
We pride ourselves: rstly in our
superior delivery responsiveness
rangs • Reduce Telephone Inuence Factor (TIF)
supported by our passion for • IS0 9001 registered quality system • DIN rail mounng available in some rangs
customer service and our vercally • CE marking available
integrated in-house design,
manufacture, and tesng
capabilies; and secondly in our INDEX
Technology leadership supported
by our industry leading R&D eort,
LINE REACTORS: Page
Construcon 2
engineering experse, technical
Applicaons and benets as input reactors 3
competence, and manufacturing Applicaons and benets as output reactors 4
know-how. Selecon charts 5&6
Dimensions and weights 7&8
MOTOR GUARDING TRANSIENT FILTERS:
Applicaons and benets 9
1 — Rex Power Magnecs Selecon Chart and Dimensions 10
CONSTRUCTION
GENERAL ENCLOSURES
Tradionally the construcon of Line Reactors has presented Reactor enclosures are manufactured from 14 gage
a challenge for manufacturers because, by the nature formed steel panels which are washed, rinsed, corrosion
of their applicaon, reactors are regularly subjected to coated and painted with ASA 61 grey powder paint
overload condions and severe power disturbances. suitable for most industrial and commercial applicaons.
When ordering an enclosure alone for use with an
To control their impedance, Line Reactors are manufactured open-type (core & coil) unit, a special bracket is required
with gaps in their magnec ux path. Maintaining the for mounng. Contact our oce for details.
mechanical integrity and the consistency of these gaps
requires parcular care during engineering, design, and
construcon. STANDARD TECHNICAL SPECIFICATIONS
Rex Power Magnecs through years of experience in • Max ambient temperature 40 ° C.
reactor applicaons has developed a unique combinaon • Insulaon class 155 ° C—Temperature rise up to 100° C.
of design techniques, ulizing materials and assembly • Insulaon class 185 ° C—Temperature rise up to 115° C.
pracces that result in a product with reduced losses • Insulaon class 220 ° C—150 °C rise maximum.
and low audible sound levels, providing years of reliable • CSA cered / UL listed
service under adverse condions.
• Current overload capability: 150% for 1 min.
• Saturaon rang: not less than 250% of rated current
(50% rated inductance min. at 350% rated current).
CORE
Manufactured from low loss, grain oriented silicon steel
shunts, and assembled to reduce audible sound and
INDUCTANCE
Ldc=0%
sta for detailed applicaon assistance.
Ldc=1% SPECIFYING LINE REACTORS
Ldc=5%
It is common to specify the value of the impedance on the
Ldc=10% basis of a percentage (i.e. 5%) of the base impedance (at
the rated line frequency i.e. 60Hz.) of the load.
Standard reactors are oered in sizes of 3% and 5% in
Percent Line Inductance
specic current and voltage rangs. Depending on the
requirements, custom reactors of other sizes and rangs
Figure 3. Current Distoron Factor versus Line and DC Link In- can be supplied by consulng the factory.
ductance The impedance rang is determined by the rao of the
Figure 3 demonstrates the eect of various amounts of voltage drop across the reactor to the supply voltage
line and DC inductance on line harmonics. The quality of when operated at rated current.
the line current is measured on the basis of line current Line reactor applicaons typically require an impedance
distoron factor (IDF) vs. percent of inserted line of 2% or 3%. In some more severe applicaons (higher
inductance and dierent DC inductances. transients or where improved line current quality is
required, etc.) an impedance of 4% to 5% could be specied.
3 — Applicaons
APPLICATIONS & BENEFITS OF LINE REACTORS AS OUTPUT REACTORS
Output
Inductors
Cable
DRIVE MOTOR Figure 5a. depicts the voltage output of a PWM drive, measured
directly at the drive terminals. Note the characterisc paern
of individual narrow pulses of xed height and variable width.
Note the steep leading and trailing edges represenng high
frequency content.
Figure 4. Typical Output Reactor Conguraon
inverter output.
Combining Line Reactors with resistors results in the
formaon of highly eecve motor guarding lters which
further reduce dv/dt and the voltage peaks (to less than
125%) appearing at the motor, see Fig. 5d. The voltage
stresses are reduced to levels well within the design limits
of motor insulaon thereby restoring full insulaon life
expectancy. The incremental cost of adding the lter
components to the reactors in minimal. See page 9 for Figure 5d. demonstrates the eecveness of REX Motor
informaon on Rex Motor Guarding Output Filters Guarding Output Filters in reducing spikes and overshoots.
4 — Applicaons
SELECTION GUIDE FOR LINE REACTORS
1. Determine the HP (horse power) rang or the current rang of the drive or motor.
2. Select the supply voltage. (208, 240, 480, or 600 Volts)
3. Determine the % impedance required for the applicaon.
4. From the table below, select the Part No. of the reactor corresponding to the current/HP, Voltage and
the % impedance.
5. For each Part No. selected, the inductance, dimensions, and the weight is given in the following two pages.
TYPICAL CONFIGURATIONS:
VARIABLE
SPEED
DRIVE
5 — Selecon Charts
SELECTION GUIDE FOR LINE REACTORS
Rang Voltage= 480 Volts Voltage= 600 Volt
HP Maximum Impedance Maximum Impedance
Current Current
3% 5% 3% 5%
(Amps) (Amps)
1 2 3PR-0002C3H 3PR-0002C5H 2 3PR-0002C3H 3PR-0002C5H
1.5 4 3PR-0004C3H 3PR-0004C5H 2 3PR-0002C5L 3PR-0002C3H
2 4 3PR-0004C3H 3PR-0004C5H 4 3PR-0004C3H 3PR-0004C5H
Note: All Rex enclosures larger than #3 are standard NEMA 3R sprinkler proof. Boxes #7 and smaller can be oor or wall mounted.
Consult the website or our engineering department for the most up-to-date informaon on enclosures.
6 — Selecon Charts
REACTOR DIMENSIONS
Add the sux /E at the end of the part number to denote enclosed style.
OPEN STYLE ENCLOSED STYLE
Inductance Dimensions (Inches) Weight Approx.
Catalogue No. Max. Amps (mH) A/B/C/D/E (Lbs) Enclosure Weight (Lbs)
3PR-0002C5L 2 9.19 4.25/2.375/4.375/2.875/2.25 4.0 #0 13.0
3PR-0002C3H 2 13.78 4.25/2.75/4.375/2.875/2.50 4.5 #0 13.5
3PR-0002C5H 2 22.97 4.25/3.00/4.375/2.875/2.625 5.3 #0 14.3
3PR-0004C3L 4 2.78 4.25/2.25/4.375/2.875/2.125 5.8 #0 14.8
3PR-0004C5L 4 4.59 4.25/2.625/4.375/2.875/2.375 6.5 #0 15.5
3PR-0004C3H 4 6.89 4.25/3.00/4.375/2.875/2.50 7.0 #0 16.0
3PR-0004C5H 4 11.49 4.25/3.125/4.375/2.875/2.75 8.0 #0 17.0
3PR-0008C3L 8 1.38 6.00/3.375/4.875/2.00/2.375 6.8 #0 15.0
3PR-0008C5L 8 2.30 6.00/3.50/4.875/2.00/2.50 7.3 #0 16.3
3PR-0008C3H 8 3.45 6.00/4.00/4.875/2.00/2.75 9.0 #0 18.0
3PR-0008C5H 8 5.73 6.00/4.375/4.875/2.00/3.375 10.8 #0 19.8
3PR-0011C3L 11 1.00 6.00/3.375/4.875/2.00/2.625 7.3 #0 16.3
3PR-0011C5L 11 1.67 6.00/3.50/4.875/2.00/2.75 8.7 #0 17.7
3PR-0011C3H 11 2.50 6.00/3.75/4.875/2.00/2.875 10.1 #0 19.1
3PR-0011C5H 11 4.18 6.00/4.125/4.875/2.00/3.125 12.0 #0 21.0
3PR-0017C3L 17 0.65 6.00/3.875/4.875/2.00/3.00 10.0 #0 19.0
3PR-0017C5L 17 1.08 6.00/4.25/4.875/2.00/3.125 12.0 #0 21.0
3PR-0017C3H 17 1.62 6.00/4.375/4.875/2.00/3.25 13.8 #0 22.8
3PR-0017C5H 17 2.70 6.00/4.50/4.875/2.00/3.50 15.0 #0 24.0
3PR-0027C3L 27 0.41 7.00/4.00/6.00/3.25/2.75 14.6 #0 23.6
3PR-0027C5L 27 0.68 7.00/4.50/6.00/3.25/3.25 15.8 #0 24.8
3PR-0027C3H 27 1.02 7.00/4.75/6.00/3.25/3.375 18.6 #0 27.6
3PR-0027C5H 27 1.70 7.00/5.00/6.00/3.25/3.75 21.4 #0 30.4
3PR-0034C3L 34 0.32 7.00/4.625/6.00/3.25/3.00 16.4 #0 25.4
3PR-0034C5L 34 0.54 7.00/5.00/6.00/3.25/3.375 19.6 #0 28.6
3PR-0034C3H 34 0.81 7.00/5.25/6.00/3.25/3.625 22.6 #0 31.6
3PR-0034C5H 34 1.35 7.00/5.50/6.00/3.25/3.875 25.0 #0 34.0
3PR-0045C3L 45 0.25 9.00/4.25/7.00/3.00/2.625 25.0 #1 35.0
3PR-0045C5L 45 0.41 9.00/5.00/7.00/3.00/3.375 29.9 #1 40.9
3PR-0045C3H 45 0.61 9.00/5.25/7.00/3.00/3.625 34.5 #1 45.5
3PR-0045C5H 45 1.02 9.00/6.00/7.00/3.00/4.375 41.2 #1 52.2
3PR-0060C3L 60 0.18 9.00/4.75/7.00/3.00/3.125 25.5 #1 36.5
3PR-0060C5L 60 0.31 9.00/5.25/7.00/3.00/3.625 30.0 #1 41.0
3PR-0060C3H 60 0.46 9.00/6.00/7.00/3.00/4.375 40.0 #1 51.0
3PR-0060C5H 60 0.77 9.00/6.125/7.00/3.00/4.50 48.0 #1 59.0
3PR-0080C3L 80 0.14 9.00/6.00/7.00/3.00/3.125 28.3 #2 42.3
3PR-0080C5L 80 0.23 9.00/6.50/7.00/3.00/3.625 35.0 #2 49.0
3PR-0080C3H 80 0.35 9.00/7.00/7.00/3.00/4.50 40.0 #2 54.0
3PR-0080C5H 80 0.57 9.00/7.50/7.00/3.00/4.75 51.0 #2 65.0
DRIVE MOTOR
C
OUTPUT VOLTAGE
INPUT VOLTAGE
9 — Applicaons
Figure 11.Dimensioned view of a Rex Motor Guarding Filter
MOTOR GUARDING TRANSIENT FILTERS
Filter Reactors
Current Part No. Dimensions Enlosure #
Rang [A] Open Core&Coil See Pg 6 Weight (Lbs)
A/B/C/D/E Open Enclosed
2 2C5LF 8.25/6.50/7.00/7.25/2.00 0 5 14
4 4C5LF 8.25/6.50/7.00/7.25/2.00 0 6 15
8 8C5LF 8.25/6.50/7.00/7.25/2.00 0 9 19
11 11C5LF 8.25/6.50/7.00/7.25/2.00 0 10 20
17 17C5LF 8.25/6.50/7.00/7.25/2.00 1 11 23
27 27C5LF 8.25/7.20/7.00/7.25/2.00 1 19 32
34 34C5LF 8.25/7.20/7.00/7.25/2.00 1 25 37
45 45C5LF 11.00/9.00/8.10/10.00/4.00 3 29 48
60 60C5LF 11.00/9.00/8.10/10.00/4.00 3 30 50
80 80C5LF 11.00/12.00/6.80/10.00/4.00 4 42 68
100 100C5LF 11.00/12.00/6.80/10.00/4.00 4 47 78
130 130C5LF 11.00/12.00/6.80/10.00/4.00 4 48 79
160 160C5LF 11.00/13.00/8.20/10.00/4.00 4 49 88
200 200C5LF 11.00/13.00/8.20/10.00/4.00 4 68 99
255 255C5LF 11.00/13.00/8.20/10.00/4.00 4 84 115
320 320C5LF 11.00/13.00/8.20/10.00/4.00 6 90 150
410 410C5LF 14.00/14.50/14.00/13.00/6.00 6 95 158
500 500C5LF 20.00/16.00/18.00/19.00/8.00 6 140 200
600 600C5LF 20.00/17.50/18.00/19.00/8.00 6 148 210
• Rex lters are current rated, therefore easy to specify. Simply use the total motor load current to select
the appropriate lter rang.
• Filters are available enclosed or open style. Add the sux /E at the end of the part number to denote
enclosed style.
10 — Selecon Charts
View or download all of our product catalogs and brochures from our website:
www.rexpowermagnecs.com
Contains up to date informaon on: Contact and Sales info:
• Drawings and engineering specicaons Tel 905.695.8844 or Fax 905.695.8855
• Selecon and eciency calculaon tools TOLL FREE USA/CANADA 1-800-387-2840
• Ordering informaon E-mail: sales@rexpowermagnecs.com
• Warranty and terms & condions 65 Basalc Road, Concord, ON, L4K 1G4
Our 145,000 sq. . design, manufacturing, and customer service facility in Concord, north of Toronto, Ontario
C S 500 A - C /
FUSING OPTIONS
Rex Power Magnetics is the
industry leader in delivery Rex Power Magnetics industrial control transformers are available with 13/32” X 1 1/2”
responsiveness, supported by our or 1/4” X 1 1/4” secondary fusing options. These may be factory installed or available in
vertically integrated in-house kit form for field installation.
design, manufacture, and testing Various primary fusing options are available for rejection or non-rejection type fuses up
capabilities. We pride ourselves to 600 V. Detailed information is available on page 6. Consult website for the most cur-
on our technology leadership rent information.
supported by our extensive R&D
activities, engineering expertise,
and manufacturing know-how.
CONTROL TRANSFORMER SELECTION
SINGLE PHASE TRANSFORMER NOTE: Complex vector analysis of each component with-
Industrial control transformers are used to convert the in a control circuit may be required to determine the accu-
available supply voltage to the voltage that is required to rate inrush load power factor. Rex has determined a 30%
supply industrial control circuits and motor control loads. power factor to be the typical control transformer re-
These loads consist of a combination of electromagnetic quirement for a representative mix of devices.
devices such as solenoid operated valves, switches, bells,
alarms, and other components such as indicator lights,
4. Select the control transformer VA requirement: For
timers, electronic equipment, and logic boards.
proper transformer VA selection, adjustments must
Some components of a circuit, especially electromagnetic be made for supply voltage variations. Should the
devices require a very high level of power at start-up. This supply voltage be relatively stable and fluctuates no
start-up power requirement is called inrush VA. After their more than +/- 5%, refer to the 90% secondary voltage
initial start-up these components settle down to a lower column of the regulation data table. If the supply volt-
power requirement for normal continuous operation. This age fluctuates as much as +/- 10% refer to the 95%
lower operating power requirement is called Sealed or column. Go down the column until the Total Inrush
Steady State VA. VA closest to but not less than that calculated in step
Some devices can draw up to 10 times the normal oper- 3. Read to the far left column to select the continuous
ating or sealed current for periods of up to 50 milliseconds nominal VA rating of the control transformer re-
upon start up. quired.
Most devices have a minimum voltage requirement for 5. Determine the input and output voltage require-
normal operation at both start-up and steady state condi- ments: The input voltage and frequency is the avail-
tions. able supply voltage. The output voltage required is
Control transformers must be designed, constructed, and the control circuit voltage to be supplied by the trans-
selected to ensure that they provide the output voltage former.
stability needed for trouble free operation of all circuit 6. Determine the transformer catalog number: Refer to
components. the catalog numbering system to select the proper
Rex control transformers incorporate several features to catalog number for the transformer with the input
optimize output voltage stability and regulation when and output voltage and the continuous VA required
supplying industrial control circuits with high inrush cur- for the application
rent requirements. Regulation Data Table
To ensure that the selected control transformer is sized
Continuous VA Inrush VA at 30% Power Factor
adequately and suitable for the application, the following
Transformer 90% Secondary 95% Secondary
6 step selection guidance should be followed.
Name Plate
Rating Voltage Voltage
25 145 105
SELECTION GUIDE 50 240 190
75 450 320
1. Calculate the Total Inrush VA Required: From the 100 700 470
data supplied by the manufacturers of the individual
150 1020 750
devices of the control circuit, add the inrush VA re-
quirements of each device to be energized simultane- 200 1700 1200
ously. 250 2150 1450
2. Calculate the total sealed VA required: From the data 350 3800 2750
supplied by the manufacturers of the individual devic- 500 5500 3750
es of the control circuit, add the sealed VA require- 750 9800 6650
ments of all the components within the circuit.
1000 15400 10300
3. Calculate the Total Circuit Inrush VA: The Total Cir-
cuit Inrush VA requirement is equal to Total Inrush VA 1500 20000 12450
+ Total Sealed VA. 2000 22000 17000
3000 42000 29000
2
Standard Featurs of Common and Enclosed Types
APPLICATION CONSTRUCTION
Rex Power Magnetics Control Transformers are specifical- Rex cores feature high-permeability silicon steel lamina-
ly designed for electrical control applications where sec- tions which are welded into a one piece construction as-
ondary voltage stability is maintained within practical lim- suring low noise and optimum efficiency. All coils are com-
its, accommodating momentary inrush current. puter designed and wound on accurate coil winding ma-
chines utilizing copper magnet wire and premium grade
These transformers can be used to adjust load require- insulating material.
ments to match supply voltage in control panels. They are All Rex control transformers are fully tested by qualified
suitable for operating machine lights, small motors, sole- personnel, and are CSA certified file No. LR34493, UL
noids, indicator lights, etc., and to provide circuit isolation. listed file No, E110286
FEATURES
Ratings from 25 VA to 7500 VA available
Voltage class approval:
CSA: 750 V max Transformer pictured above illustrates our standard
construction.
UL: 600 V max
Vertical or Horizontal mounting
Sound level below 40 dB
OPTIONS
Markings, additive polarity Special designs are available upon request
Insulation systems: Frequencies other than 60 Hz
25 - 500 VA class 130 °C, 80 °C temp Rise Max Multiple primary and secondary voltages
501 - 7500 VA class 180 °C , 115 °C temp Rise Max Electrostatic Shielding
Lead wire or screw type terminations
See page 5 for potted-coil design for harsh environ-
NOTE: For connections refer to typical schematic dia- ments
grams on inside front cover. Terminal blocks
Fig. 1 - single primary - dual secondary Fuse kits
Fig. 2 - dual primary - dual secondary Designed to comply with CE
Fig. 3 - single primary - single secondary
CE markings are available, consult head office
Fig. 4 - dual primary - single secondary
3
Single Phase Open Style - Type CS
FEATURES
Standard screw type terminals
Clearly marked terminals for easy wiring
Conservative design for cool, long-lasting operation
Vacuum impregnated and baked for quiet operation
Smooth and uniform varnish finish
Easy to read nameplate
Suitable for mounting in ventilated enclosures
4
Single Phase Enclosed Style (CE) and Encapsulated Winding Style (CP)
Overall dimensions
5
FUSING OPTIONS
Selected options are shown, see website for most complete and up-to-date listing. Part numbers shown can be added to catalog numbers. Fuses not included.
P/N: C4
P/N: F4 or P/N: F12
F5 (3 pole)
P/N: C5
FUSE KIT
(1, 2, or 3 pole) 4
F6 (kit)
Warranty
Rex Power Magnetics warrants to its customers that the products delivered conform
to the specifications and are free from defects in material and workmanship for a
period of one year. For additional detail, consult factory or visit website.
Defects Sustained Research and Development for
technology leadership and improvement
If any defect in material or workmanship develops within one year from the date of
shipment, Rex will replace or repair the defective part (at its discretion), F.O.B. facto-
ry, if (a) Rex has been notified in writing immediately upon the defect coming to light,
(b) it has been shipped prepaid to Rex without delay, and (c) the product has not been
misused, abused, altered, neglected, improperly installed, or damaged.
Cancellation
No order accepted by Rex may be altered or modified by the purchaser unless agreed
to in writing signed by an authorized official of Rex and no such order may be can- Extensive testing and repair capabilities, and
celled or terminated except upon payment of Rex’s loss and expense arising from
such cancellation. flexible, responsive engineering team
6
View or download all of our product catalogs and brochures from our website:
www.rexpowermagnetics.com
Contains up to date information on: Contact and Sales info:
Drawings and engineering specifications Tel 905.695.8844 or Fax 905.695.8855
Selection and efficiency calculation tools TOLL FREE USA/CANADA 1-800-387-2840
Ordering information E-mail: [email protected]
Warranty and terms & conditions 65 Basaltic Rd., Concord, ON, L4K 1G4
Our 145 000 sq. ft. design, manufacturing, and customer service facility in Toronto, Ontario
MINI
POWER
CENTER
Simple
Elegant
Smart
Encapsulated transformer complete with
primary circuit breaker protection and
secondary main breaker distribution loadcenter
Save Time: Pre-wired, ready for hook up
Save Space: Compact wall mountable configuration
Save Money: Installing one component versus three Publication Date: 9/2020
Rex Power Magnetics Mini Power Center - Introduction
Practical, time saving, and customizable!
Rex Power Magnetics’ Mini Power Centers combine three
individual components into a single pre-wired assembly:
a primary main breaker, an encapsulated isolation
transformer, and a main breaker load center. With all of
the components installed and factory wired in a single
rugged enclosure, field installation time is reduced and
simplified extensively. Mini Power Centers are used on
single-phase and three-phase low voltage distribution
systems and loads requiring 208Y/120V three-phase
or 120/240V single-phase. While the Load Center is
normally shipped without the secondary branch breakers,
Rex can supply and install them if a panel schedule is
provided.
Shown on brackets for display only. Floor mounting is optionally available.
Applications
◆ Industrial Loads (factory, laboratory, etc)
Typical appearance for smaller sizes
◆ Commercial (EV charging, parking lots, etc.)
◆ Temporary Power (rental application, generator power)
◆ Tunnel Power (emergency power, tunnel lighting, mining)
◆ General Purpose (lighting, distribution, etc.)
Sec. Breaker
Dimensions (Type 3R)
Pri. Breaker
[Max quantity]
Diagram*
Type Catalog # kVA
1-pole
2-pole
3-pole
W D H wt Enclosure
[inch] [inch] [inch] Name
[lbs]
Dimensions [inches]
Enclosure A B C D E F G H
Name
E3R-1PMPC-1 17.25 12.50 39.50 13.56 25.94 8.00 11.50 19.38
E3R-1PMPC-2 17.25 14.50 50.50 16.56 33.94 8.00 18.50 19.38
E3R-1PMPC-3 18.00 14.50 59.50 23.56 35.94 8.00 26.50 20.13
E3R-1PMPC-4 24.00 16.00 60.50 23.56 36.94 8.00 27.00 26.13
E3R-3PMPC-1 18.00 12.50 43.50 15.56 27.94 8.00 14.50 20.13
E3R-3PMPC-2 23.25 14.00 52.50 16.06 36.44 8.00 19.25 25.38
E3R-3PMPC-3 23.25 18.00 55.00 18.56 36.44 8.00 21.75 25.38
E3R-3PMPC-4 25.50 18.00 65.50 23.56 41.94 8.00 29.50 27.63
Get detail cut sheets (drawings) for each of our standard sizes:
www.rexpowermagnetics.com
Tables & Diagrams
Copper Bus & Bolt-On Breaker Load Center MPC (CSA only)
Breakers
Sec. Breaker
Dimensions (Type 3R)
Pri. Breaker
[Max quantity]
Diagram*
Type Catalog # kVA
1-pole
2-pole
3-pole
W D H wt Enclosure
[inch] [inch] [inch] Name
[lbs]
Three
MP3C9J-M/BO/CLC 9 3 20A1 30A6 18 8 6 23.25 12.5 45.5 395 E3R-3PMPC-1B
Phase MP3C15J-M/BO/CLC 15 4 30A1 50A6 30 14 10 23.25 14.0 52.5 520 E3R-3PMPC-2B
600 V
MP3C22J-M/BO/CLC 22.5 4 50A1 70A6 30 14 10 23.25 18.0 55.0 710 E3R-3PMPC-3B
to
208Y/ MP3C30J-M/BO/CLC 30 4 70A1 100A6 30 14 10 23.25 18.0 55.0 780 E3R-3PMPC-3B
120 V MP3C45J-M/BO/CLC 45 4 90A 1
150A 7
30 14 10 25.50 18.0 65.0 1000 E3R-3PMPC-4B
Three
MP3C9H-M/BO/CLC 9 3 25A2 30A6 18 8 6 23.25 12.5 45.5 395 E3R-3PMPC-1B
Phase MP3C15H-M/BO/CLC 15 4 40A 2
50A 6
30 14 10 23.25 14.0 52.5 520 E3R-3PMPC-2B
480V
MP3C22H-M/BO/CLC 22.5 4 60A 2
70A 6
30 14 10 23.25 18.0 55.0 710 E3R-3PMPC-3B
to
208Y/ MP3C30H-M/BO/CLC 30 4 80A2 100A6 30 14 10 23.25 18.0 55.0 780 E3R-3PMPC-3B
120 V MP3C45H-M/BO/CLC 45 4 125A 1
150A 7
30 14 10 25.50 18.0 65.0 1000 E3R-3PMPC-4B
*See back page for Electrical Connection Diagrams
1. Eaton Type FDB Breaker
2. Eaton Type EHD Breaker
6. Eaton Type BAB Breaker
7. Eaton Type ED Breaker
Dimensions [inches]
Enclosure A B C D E F G H
Name
E3R-1PMPC-1B 23.25 12.50 43.50 13.56 25.94 8.00 11.50 25.38
E3R-1PMPC-2B 23.25 14.50 53.00 16.56 36.44 8.00 18.50 25.38
E3R-1PMPC-3B 23.25 14.50 60.00 23.56 36.44 8.00 26.50 25.38
E3R-1PMPC-4B 23.25 16.00 65.00 23.56 41.44 8.00 27.00 25.38
E3R-3PMPC-1B 23.25 12.50 45.50 15.56 29.94 8.00 14.50 25.38
E3R-3PMPC-2B 23.25 14.00 52.50 16.06 36.44 8.00 19.25 25.38
E3R-3PMPC-3B 23.25 18.00 55.00 18.56 36.44 8.00 21.75 25.38
E3R-3PMPC-4B 25.50 18.00 65.00 23.56 41.44 8.00 29.50 27.63
Get detail cut sheets (drawings) for each of our standard sizes:
www.rexpowermagnetics.com
Electrical Connection Diagrams
Diagram 1 Diagram 2
TRANSFORMER ENCLOSURE TRANSFORMER ENCLOSURE
H1 H2 H1 H2
1 2 3 3 2 1 1 2 3 4 5 5 4 3 2 1
X1 X3 X2 X4 X1 X3 X2 X4
Diagram 3 Diagram 4
TRANSFORMER ENCLOSURE TRANSFORMER ENCLOSURE
H1 H2 H3 H1 H2 H3
3 2 1 3 2 1 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1
X0 X1 X2 X3 X0 X1 X2 X3
L3 L3
Loadcenter Branch
Loadcenter Branch
Circuit Breakers
Circuit Breakers
(not supplied)
(not supplied)
• Diagrams above are for illustrative purposes only and are not inteded to serve as a
reference electrical schematic for wiring.
Rex Power Magnetics operates its own fully independent, complete sheet metal fabrication and paint facility
to produce its own transformer enclosures, core clamps, brackets, and accessories, as well as manufactured
custom enclosures. The Rex engineering and design team consists of highly competent and qualified individu-
als with many years of transformer design experience.
REX TRANSFORMERS CONSTRUCTED FOR HAZARDOUS LOCATIONS
Rex offers three transformer options that are suitable for hazardous locations.
FEATURES Type HLA Type HLB Type HLC
Certification CSA and UL approval for CSA and UL approval for CSA and UL approval for
Class I, Division 2 Class I, Division 2 Class I, Division 2
Application Windings are encapsulated in As with HLA, the windings Conventional construction:
epoxy, preventing airborne are encapsulated. Addition- non-encapsulated, vented
contaminants from reaching ally, the connection be- design. Designed to con-
the coils, and thus pre- tween the leads and the form to specified tempera-
venting damage to electrical coils are encapsulated. Wir- ture code.
insulation. ing to the rest of the system
is done at the leads
Construction
Notes:
See following page for referenced figures
HLB variants of the above transformers will have the same outside appearance as HLA transformers,
with the addition of permanent cable glands.
Dimensions provided are for the standard HLA product, with Type 3R outdoor enclosure.
A specification drawing for your requested configuration may be available online, or by requesting it
from our engineering department.
IP 65 & IP 66 CONSTRUCTION
For applications where enclosure type is specified using
the IP system rather than the CSA / NEMA enclosure type
code, Rex is able to provide transformers with enclosures
marked in accordance to the IP system.
FIG. 8 FIG. 9
FIG. 1
FIG. 2 FIG. 10
FIG. 3
FIG. 11
FIG. 4
FIG. 5
FIG. 12
FIG. 6
FIG. 7
1 - Electrical configurations shown are the standard con- 2 - Outline dimensions and features shown are the standard
figurations. Alternate configurations can be specified specification. Alternate dimensions and features can be speci-
with your order. Standard configurations are subject to fied with your order. Standard specifications are subject to
change without notice. change without notice.
View or download all of our product catalogs and brochures from our website:
www.rexpowermagnetics.com
Contains up to date information on: Contact and Sales info:
Drawings and engineering specifications Tel 905.695.8844 or Fax 905.695.8855
Selection and efficiency calculation tools TOLL FREE USA/CANADA 1-800-387-2840
Ordering information E-mail: [email protected]
Warranty and terms & conditions 65 Basaltic Rd., Concord, ON, L4K 1G4
Our 145,000 sq. ft. design, manufacturing, and customer service facility in Concord, north of Toronto, Ontario
ENVIRONMENTALLY FRIENDLY:
Cast Coil transformers contain only chemically
non hazardous materials
SAFETY:
Cast Coil transformers are self extinguishing,
virtually eliminating the possibility for fire or
explosion. Installations do not require special
fire protection systems.
MAINTENANCE:
Cast Coil type transformers are virtually
maintenance free due to the smooth
crevice-free construction of the coils.
With proper precautions cast coil units
can be installed at ambient tempera-
tures as low as –25 °C and can be ener-
gized from a cold start.