Fire Detection Principles
Fire Detection Principles
4 Fire Detection
4.1 Summary................................................................................................63
4.2 Basics.....................................................................................................65
4.2.1 Outbreak of a Fire ...................................................................................65
4.2.2 Development of a Fire.............................................................................66
4.2.3 Fire Phenomena......................................................................................67
4.2.4 Types of Fire ...........................................................................................69
4.2.5 Fire Detection System.............................................................................70
4.3 Fire Detectors ........................................................................................72
4.3.1 Detection Principles ................................................................................72
4.3.2 Detection Reliability.................................................................................84
4.3.3 Networking Technologies........................................................................92
4.4 Selecting the Appropriate Fire Detector.............................................94
4.4.1 Consideration of the Type of Fire............................................................94
4.4.2 Considering the Room Height.................................................................97
4.4.3 Considering Ambient Conditions.............................................................97
4.4.4 Considering Prevailing Deceptive Phenomena ......................................98
4.4.5 Fire Detectors for Explosion-Hazard Areas ............................................98
4.4.6 Summary.................................................................................................99
4.5 Number and Positioning of Fire Detectors.......................................103
4.5.1 Basics....................................................................................................103
4.5.2 Manual Call Points ................................................................................105
4.5.3 Point-type Smoke Detectors .................................................................105
4.5.4 Point-type Heat Detectors.....................................................................107
4.5.5 Linear Smoke Detectors .......................................................................108
4.5.6 Aspirating Smoke Detectors .................................................................110
4.5.7 Flame Detectors....................................................................................116
61
62
4.1 Summary
The task of an automatic fire detection system is to detect fire as early as possible,
to alarm and activate the preprogrammed control functions. State-of-the-art fire
detection systems are capable of detecting fire extremely early and thus of mini-
mizing the damage that may be caused by fire. By an optimal product selection
and appropriate knowledge it is possible to set up systems that virtually rule out
false alarms.
A fire detection system consists of the control unit, the peripherals such as fire
detectors and contacts, as well as alarm and control devices activated by the
control unit.
When arranging the fire detectors, one must be sure that the fire phenomena
(smoke, heat, radiation, gas) reach the fire detectors, giving special consideration
to the ceiling’s construction (e.g. the ceiling joists, special roof or ceiling shapes),
and a possible room division by alcoves, furniture or fixtures and fittings.
In rooms where strong deceptive phenomena occur, the ideal arrangement of the
fire detectors is of central significance. Even small changes of the detector position
bring about massive improvements of the immunity to deception, without reducing
the detection reliability.
In selecting the fire detection control unit, user-friendliness, a high degree of flexi-
bility and a very high degree of fail-safe operation must be taken into consideration.
The control unit is the point of interaction between people and the system and must
thus make easy and intuitive alarm and fault processing possible.
High flexibility in networking and parameter setting facilitate extensions and the
adaptation of the system behavior to a change of customer requirements.
63
The availability of a fire detection system is crucial, which is why emergency power
supply and an integrated emergency operating function are mandatory, making fire
alarms possible in spite of a failure to a module or a power failure.
64
4.2 Basics
The knowledge of the outbreak of a fire and its development is decisive for fire
prevention and fire fighting. To ensure reliable, early detection in the case of fire, it
is equally important to be familiar with the different fire phenomena and the possi-
ble types of fire. The following four topics will be handled in detail hereinafter:
− outbreak of a fire
− development of a fire
− fire phenomena
− types of fire
Section 4.2.5 shows the setup of a fire detection system and the aspects to be
considered in its planning and implementation.
Oxygen Heat
Fuel
Fire thus occurs by the interaction of fuel, oxygen and heat (energy).
65
Flashover
As shown in Figure 4.2, most fires pass through the following phases and events:
• Early stage: The incipient fire can be extinguished with a few deciliters of water;
little visible smoke occurs, but especially invisible aerosols are generated.
• Smoldering phase: In this phase, the fire can be extinguished by means of a
fire extinguisher or a similar extinguishing agent. Visible, partly dense smoke
occurs. Usually, combustion is incomplete, which is why rather a lot of (toxic) CO
is produced in this phase.
• Flaming phase: We are faced with an open fire to be fought by the fire brigade.
As enough energy is available, the combustion process is rather complete, re-
sulting in a high production of CO2.
• Flashover: The transition between an open, flaming fire and a total fire is called
flashover. This is the explosive fire spread, taking place exactly at the point
when the gases and aerosols produced during the previous phases ignite and
carry the fire into all rooms already penetrated by the smoke gases.
• Total fire: In this phase, the fire has reached larger building parts. In most
cases, the building or fire sector can no longer be saved and the fire brigades
concentrate their efforts on the protection of neighboring buildings and fire sec-
tors.
66
Fire detection must occur as early as possible, so that intervention can start before
the flashover. Incipient fires should thus be detected in the early stage or in the
smoldering phase at the latest, so that there is enough intervention time left. The
problem is that the early stage and the smoldering phase can be of completely
different intensity and duration. Some smoldering fires may continue to smolder for
hours or even days before an open fire occurs.
With liquid fires, there is no smoldering phase at all; they directly develop flames.
With such fires, the intervention time is extremely short. Usually, damage can only
be limited by an automatic extinguishing system. Of course, there are other possi-
bilities, such as constructive measures, to slow down fire spread, thus prolonging
the intervention time – but this is usually very expensive.
Conclusion: The earlier a fire is detected, the more time there is for fire fighting,
and the less damage occurs. Earliest possible detection is thus the key to minimiz-
ing damage and winning precious intervention time.
The processes in material combustion can be principally viewed from the perspec-
tive of a conversion of energy and substances. The energetic conversion releases
energy into the environment. The substantial conversion produces – depending on
the substances present at the seat of fire – products in any physical state, ranging
from non-toxic to highly toxic.
The figure below indicates the concomitant phenomena of a fire with the associ-
ated fire phenomena (in parentheses).
67
Periodic Visible
(sound) Ultraviolet Infrared Liquid (smoke)
Ordered Colloid
Molecular
movement
After-effects Products
Energetic Substantial
conversion conversion
The energetic conversion releases energy by radiation and convection. The range
of radiation released during a fire can be divided, by wavelength, into ultraviolet
(UV), visible light and infrared (IR). Energy release by convection essentially takes
place through the ambient air. First, the kinetic energy of the air molecules is
increased, resulting in a temperature increase. The associated expansion leads to
an upward air flow. Due to this flow, cooler air and thus oxygen is guided to the fire
seat. These processes can also lead to periodic pressure fluctuations that are
perceived as sound in certain frequency ranges (e.g. the typical crackling of a fire).
68
Type of smoke Very light smoke Light smoke Dark smoke Very dark
(aerosol) smoke Depending on
the carbon
share of the
Optical Quickly Strongly Strongly gas, its
properties of Quickly spreading absorbing, absorbing, chemical
spreading
smoke spreading little spreading little properties and
High (except mixing with
Aerosol volume High High High pure alcohol: oxygen
none)
Combustion Much CO, Much CO, Little to much Little CO, Little CO,
gases little CO2 little CO2 CO, much CO2 much CO2 much CO2
The main property of the pyrolysis fire is that it does not go on independently but
requires the continuous supply of new energy. The fire can be extinguished by
stopping the energy supply. The propagation of that fire type is thus restricted to
the size of the heat source, which is why we can also speak of overheating accom-
panied by chemical decomposition. As soon as the ignition temperature is reached,
the fire develops to a glowing or even an open fire.
69
The glowing fire is an independent process. The glowing temperatures are high
and the particles produced are thus relatively small. The visible particles are only a
small part of the particle spectrum generated. Typical for a glowing fire are incipient
fires in hay or cotton bales.
Characteristic for open fires – with the exception of alcohol fires – is the production
of soot, i.e. black smoke. Although here, too, the major part of the particles gener-
ated is in the non-visible range. Studies have shown that in almost all cases,
including the early stage and smoldering phase, more invisible particles than
visible ones are generated.
Summarizing, we can state that large volumes of volatile fire aerosols are pro-
duced with almost all hostile fires. Smoke has thus become the most important fire
phenomenon for an early detection of fire. Depending on the size and concentra-
tion of the fire aerosols, they may be visible or invisible. In general, fire aerosols
are 10 to 10'000 times the size of gas molecules.
Viruses Bacteria
Pollen
Human
hair
Gases Fire aerosols
H2 Zinc oxide smoke
O2 Colophony smoke
CO/N2 Oil smoke
CO2 Ammonium chloride
Lamp soot
Tobacco smoke
Color pigments
Powdered milk
Insecticides
Carbon dust
Cement dust
70
Acoustic
alarm
Automatic
fire detectors
Optical alarming
Automatic
contacts
Fire brigade
Logging
The periphery comprises all field elements acquiring the actual state on site, which
is transmitted to the control unit in the form of hazard levels. The intelligent, auto-
matic fire detectors detect and analyze the different fire phenomena on site and
automatically report prevailing hazards to the control unit. Manual call points serve
for the direct alarm activation by people present in the danger zone. Automatic
contacts (e.g. from an activation of a sprinkler extinguishing system) report a fire
alarm indirectly.
The fire detection system is monitored, controlled and operated by the control unit,
which evaluates the hazard messages from the peripheral devices and activates
alarm and fire control installations. Additionally, it serves for operating the fire
detection system itself.
The measures initiated by the control unit serve for alarm and intervention. Optical
and acoustic alarm devices inform the people in the building and those responsible
for the building and call the fire brigade. Controls activate smoke extraction sys-
tems and stationary extinguishing systems. Optical escape route guidance and
voice alarm safely evacuate people from the building.
71
Of course, a smoke detector’s sensitivity does not only depend on the detection
principle but also on the specific detector design, the type of smoke and other
environmental factors, such as air humidity, etc. To be able to exactly determine
the sensitivity of a detector, a standardized procedure is used (see also section
4.4.1.1).
72
Based on the great significance of this fire detection principle, new and improved
point detectors have been continually developed in the past. The most important
principles are scattered light, extinction (light absorption) and ionization. Until about
1990, ionization was the most important principle. Today, however, most point
detectors work according to the scattered light principle. People speaking of optical
smoke detectors today usually refer to scattered light smoke detectors.
1 Light source
2 Lens
3 Photoelectric
cell
4 Signal
5 Smoke
particles
6 Labyrinth
The scattering capability of large, light smoke particles is extremely high. Soot
particles and black smoke scatter the light only faintly, which is why the scattered-
light smoke detector rather captures visible, light smoke particles and is especially
suited for the detection of such fire types whose smoke spectrum is marked by light
smoke. With a forward scatter detector, light smoke particles produce a much
stronger signal on the photoelectric cell than dark particles could. For this reason,
forward scatter detectors are best suited for the detection of smoldering fires with
light smoke particles. With the backscatter detector, the signal difference between
light and dark smoke particles is less distinct. Backscatter smoke detectors are
thus much more balanced in their detection behavior and are equally suited for the
detection of fires producing dark smoke particles.
73
If the distance between light source and receiver measures only a few centimeters,
as it is the case with a point detector, this signal reduction in case of smoke is very
low (0.05% to 0.2%). Although the evaluation of such a low signal change is meas-
urable with state-of-the-art electronics, the required long-time stability still consti-
tutes a great challenge.
The extinction smoke detector detects light and dark, large and small aerosols and
is characterized by its uniform response behavior. This detector is suited for the
early detection of all fires producing visible smoke.
74
The air between two electrodes, biased by a DC voltage, is ionized, i.e. made
conductive, by means of a slightly radioactive radiation source. Due to this ioniza-
tion, a weak electric current begins to flow in the sampling chamber. When smoke
particles penetrate the sampling chamber, ions attach to the smoke particles,
reducing the flow of electricity. This reduction is proportional to the number of
smoke particles in the measuring area.
The signal coming from the ionization smoke detector is proportional to the number
of smoke particles in the sampling chamber. Ionization smoke detectors are thus
particularly suited for the detection of open fires, as such fires produce a large
number of small, primarily invisible smoke particles. They are less suited for detect-
ing smoldering fires that produce only few, large smoke particles.
75
The emitter sends out a focused light beam. When there is no smoke, this light
beam reaches the receiver in its unattenuated intensity. However, if there is smoke
between the emitter and the receiver, the light is partly absorbed when impinging
the smoke particles and partly scattered by them, meaning that it changes direc-
tion. Only a part of the emitted light can reach the receiver. The signal reduction
indicates the average smoke density over the measuring section.
5 to 100m
Reflector
Receiver
Emitter
Linear smoke detectors are used for measuring sections between 5m and 100m.
Even a low smoke concentration causes a signal attenuation of several percent.
The stability problem, which must be considered with point-type extinction smoke
detectors, virtually does not exist with linear smoke detectors.
As the linear smoke detector reacts on absorption and scattering, it is suited for
light and dark, large and small aerosols. It is characterized by its uniform response
behavior and is suited for the early detection of all fires generating visible smoke.
76
Detection
chamber
Suction mechanism
Depending on the manufacturer and the desired sensitivity, the detection chamber
accommodates a smoke detector, employing one of the detection principles de-
scribed in the following.
Cloud Chamber
In a closed area, high air humidity is generated by means of a water bath. Then,
the smoke particles are guided through this zone. The high humidity condenses on
the smoke particles which act as condensation nuclei, resulting in fog. This fog is
illuminated with a pulsating LED to determine its density. The higher the density of
the fog, the higher the smoke density.
77
Xenon
Permanently aspirated air is guided through a detection chamber and is illuminated
by a xenon lamp over a distance of several centimeters. Smoke particles deflect
the beams and produce a correspondingly strong signal due to the relative length
of the detection chamber. This signal is evaluated and serves for triggering an
alarm. These aspiration smoke detectors require periodic calibration, which is
reflected in the expenditures for maintenance. Xenon detectors work according to
the scattered light smoke detector principle.
Particle Counter
A focused light beam illuminates aspirated air. Smoke particles deflect the beam,
which impinges on an optical mechanism and generates an electric pulse. The
number of pulses per unit of time is proportional to the smoke density. When the
number of particles exceeds a predefined value, an alarm is triggered. With this
measuring principle, the air flow must be regulated, as an inconstant air flow would
disturb the result.
Property Immunity to
Sensitivity deception Easy servicing
Detector type
Point-type
0 +++ ++
smoke detectors
Cloud chamber + 0 0
Optical smoke
++ ++ ++
detectors
Xenon ++ + 0
Particle counter +++ + +
+++ : Excellent
++ : Very good
+ : Good
0 : Moderate
Table 4.2: Comparison of ASD principles
78
As the reference value for alarm activation is the rate of rise, these detectors are
clearly superior to the maximum temperature detectors. However, they are still
restricted to low-risk applications and are only applied in situations where a smoke
detector would be subject to massive deceptive phenomena.
To rule out faults and deception by sunlight, reflected light, lamps and other light
sources as far as possible, the detection range of the detectors is shifted from the
visible to the invisible range. Most flame detectors therefore operate in the ultravio-
let or infrared range.
79
Intensity of
sunlight on
earth
Wavelength
UV IR
flame flame
detector detector
UV Flame Detector
UV flame detectors react on the electromagnetic radiation emitted by an open
flame in the short-wave range of UV radiation (at a wavelength of approximately
0.2µm).
High-voltage is applied between the cathode and the anode. As soon as UV rays
impinge on the cathode, its surface emits electrons. These electrons hit the gas
molecules in the tube, ionizing them and thus initiating a snowball-type electron
flow from the anode to the cathode. The result of this process is a striking increase
of the current flow that is proportional to the intensity of the UV radiation emitted by
the fire.
80
UV flame detectors are capable of detecting all types of open fires. With appropri-
ate sensitivity settings, they are also resistant to sunlight, special fluorescent lamps
and spark discharge. However, strong UV sources, such as welding flames, spe-
cial lamps, electric arc lamps and ionizing radiation (radioactivity or X-rays) may
cause false alarms. Any soiling of the detectors must be avoided as their sensitivity
will decrease. Especially an oil film on the sensor lid immediately renders a detec-
tor completely inoperable.
IR Flame Detector
IR flame detectors make use of the maximum intensity of the infrared-active flame
gases in a frequency range of 4.3µm, occurring during the combustion of carbona-
ceous materials (emission spectrum of hot CO2).
1 IR filter 4 Signal
2 Pyroelectric sensor (IR) 5 Flame radiation
3 Sampling chamber
The flame irradiation on the IR flame detector is filtered by the infrared filter in such
a way that only radiation with a wavelength between 4 and 5µm impinges on the
pyroelectric sensor. This sensor only responds on a change of the radiation inten-
sity (energy change) and generates an electric current proportional to that value.
Infrared flame detectors are suited for the detection of smokeless liquid and gas
fires as well as smoke-generating, open fires of carbonaceous materials. All or-
ganic, combustible materials such as wood, plastics, gases and oil products con-
tain carbon. Fires of purely inorganic materials such as hydrogen, phosphorus,
sodium, magnesium or sulfur cannot be detected by infrared detectors. As soon as
such materials are burned together with organic materials, like for example pack-
aging material, detection can be ensured.
81
CO Detectors
With smoldering and glowing fires, combustion is mostly incomplete due to the low
temperatures. For this reason, the aerosol particles agglutinate to larger and thus
more easily visible parts (strong smoke generation), and a lot of toxic CO gas is
produced.
CO sensors are suited for the early detection of smoldering fires but are only fit for
limited detection of open fires.
CO2 Detectors
In contrast to smoldering and glowing fires, open, flaming fires burn a considerable
load per unit of time. This is associated with a striking temperature increase and
high CO2 production.
CO2 is a very durable gas, which is why its chemical detection is rather difficult. To
detect CO2, opto-acoustic sensors and infrared absorption sensors are used today
(for measuring principles, see sections 3.4.4 and 3.4.5 starting on page 47).
CO2 sensors are suited for the detection of open fires but are only fit for limited
detection of smoldering fires.
CO2 is particularly produced by open fires generating a lot of fire gases. As thermal
sensor electronics are much more cost-efficient than CO2 measuring, and as the
two phenomena occur largely in parallel, gas measuring hardly has any additional
benefits.
82
Summary
CO fire detectors have serious problems in detecting open, flaming fires, while CO2
fire detectors reach their limits when it comes to detecting smoldering fires. In fire
detection, pure gas sensors are thus rarely used. For special applications, how-
ever, they are used together with other sensor types, mostly in combination with an
optical and / or a temperature sensor (multisensor fire detector).
Today, the most frequently used multisensor detectors identify smoke by means of
an optical sensor and heat with a heat sensor. Flame detectors also include multi-
ple sensor products. By intelligently interlinking the different sensor signals, the
response behavior and immunity to deception can be largely improved, resulting in
a much higher detection capability that it would be the case with separate sensors.
The crux of developing a multisensor fire detector is the selection of the best suited
sensor principles and combination of the sensors with optimum characteristics, so
that both the detection properties and the immunity to deception can be optimized.
1 Light source
2 Lens
3 Photoelectric
cell
4 Signal
5 Smoke
particles
6 Labyrinth
7 Temperature
sensor
83
The multisensor fire detector shown here is equipped with two scattered light
sensors (forward scatter and backscatter) and a heat sensor. The detection behav-
ior of such a detector is characterized by the following properties:
• Excellent detection of smoldering fires with light smoke particles by the forward
scatter sensor.
• Good detection of fires with black smoke particles by the backscatter sensor.
• Reliable detection of fires without visible smoke by the heat sensor.
• High reliability and immunity to deceptive phenomena such as vapor, exhaust
gases or heat sources due to the combination of the individual sensor signals.
The main advantage of multisensor fire detectors is that not only the strengths and
weaknesses of the different sensors can be balanced due to the combination of the
different measured quantities, but an interpretation of events becomes possible.
The result is an essential improvement of the response speed (early detection of
fires) and a considerably higher immunity to deceptive phenomena (no false
alarms).
Most false alarms are triggered by deceptive phenomena such as cigarette smoke,
water vapor from showers or aerosols produced during welding. Fire detectors
without automatic drift compensation frequently cause false alarms when the
detector is excessively soiled.
84
Basically, false alarms can never be completely ruled out. However, they can be
significantly reduced by taking appropriate measures:
• False alarms caused by fire-simulating events can be reduced by the correct
selection and arrangement of the fire detectors (detectors with intelligent signal
processing in locations with fewer deceptive phenomena).
• False alarms caused by faults can be reduced by paying attention to the quality
of the products applied in selecting the system.
• False alarms caused by erroneous operation can be reduced by user-friendly
control units and appropriate user training.
• Reducing willfully caused false alarms can usually be combated with additional
expenditures (e.g. access control, video monitoring).
Fire
development
Detection
reliability
False alarm
Time
At the beginning of a fire, the intensity of the fire phenomena is still very low. Pos-
sible deceptive phenomena at this stage may produce a signal many times higher
than the signal actually wanted. To reduce the risk of false alarms, it would thus
seem logical to simply give enough time to fire detection – which, however, contra-
dicts the desire of early fire detection and the associated damage mitigation.
85
Soiling of detectors cannot be generally ruled out or avoided. The detector must
thus be designed in a way that particle deposits inside or at the outside of the
detector do not impair the detection behavior. In designing a detector, correspond-
ing measures must be taken in addition to the intelligent signal processing with drift
compensation. The following aspects must be taken into account:
• The inlet openings must be designed in a way that the penetration of fibers, dust
and insects is aggravated, at the same time ensuring the unhindered penetration
of smoke.
• The distance between the detection volume and the labyrinth must be long
enough, so that fibers and other particles that have nevertheless penetrated the
detector cannot reach the detection area.
• The encapsulation of the optics must be designed in a way that particles can
neither settle on the emitter nor on the receiver.
In addition to soiling, especially the penetration of external light can cause faults or
malfunction. This can be avoided by the design and nature of the labyrinth. To
reduce malfunction due to the impact of electromagnetic fields, corresponding
measures must be taken regarding the detector electronics. A sophisticated layout
of mechanics, sensor unit and detector electronics is the prerequisite for reliable
signal processing.
The market offers fire detection systems in which the fire detectors transmit the
signals to the fire detection control unit, which is in turn responsible for signal
processing. Modern fire detection systems, however, almost exclusively work on
the principle of decentralized data processing. The sensor signals are directly
processed in the detector, and only the evaluated results are transmitted to the
control unit. The following paragraphs cover signal processing in the fire detector
used in systems with decentralized data processing.
86
Signal
Alarm threshold
Alarm
Time
ASIC Technology
Detectors employing ASIC technology are equipped with comprehensive electron-
ics featuring an ASIC (Application Specific Integrated Circuit). These highly inte-
grated modules enable fast and intelligent signal processing, making the detector
capable of detecting faults or soiling in addition to several hazard levels. In case of
minor soiling, the sensitivity is corrected automatically (drift compensation).
Signal Alarm
Alarm threshold 2
Alarm threshold 1
Fault
Time
87
Algorithm Technology
Fire detectors based on algorithm technology perform complex signal analyses at
short intervals and process large data volumes. They are therefore equipped with a
microprocessor. The sensor signals are broken down into mathematical compo-
nents and are offset against the defined and programmed algorithms (mathemati-
cal rules). The character of these algorithms is defined by their parameter setting.
The comparison of the calculated values with the default values stored in the
detector results in the corresponding hazard level.
88
Parameter set
Algorithms
Danger level
Diagnostic level
Default values
The figure shows the signal processing of a multisensor fire detector with smoke
and heat as fire phenomena. Intelligent signal processing is based on the data
provided by the smoke and heat sensors.
89
Algorithms
Danger level
Diagnostic level
Default values
Point-type fire detectors with the sensor combination smoke / heat or smoke / gas
are typical examples of such multisensor fire detectors. They are designed to
detect fires at an early stage and are at the same time highly immune to deceptive
phenomena. However, there are multisensor detectors in which only one sensor is
required for fire detection, as all other additional sensors merely have the task of
detecting possible deceptive phenomena in order to increase the detection reliabil-
ity.
90
Hot objects
Sun
Transmission [%]
Alcohol fire
Wavelength
Figure 4.20: Infrared spectrum of sunlight, hot objects and alcohol fire
The IR radiation spectrum of the sun differs from that of hot objects and organic
fires. Thanks to these different characteristics and the three sensors, the flame
detector can distinguish between real fires and deceptive phenomena. If sensor
signal A is stronger than sensor signal B, and if sensor signal A is significantly
stronger than sensor signal C, a real fire has occurred. Otherwise it is a deceptive
phenomenon. If sensor signal A more or less has the same intensity as sensor
signal B, the signal is emitted by a radiator. If sensor signal C is simultaneously
significantly stronger than the two other signals, solar irradiation is the cause.
91
4.3.2.5 Summary
Apart from the mechanical design and the sensor electronics applied, it is the
signal processing that determines the quality of fire detection. Early and absolutely
foolproof fire detection is the goal. When fire detectors are placed in a clean envi-
ronment, this is possible without any problems today. If, however, a detector shall
be able to detect a fire as early and safely as possible, even in environments
where different deceptive phenomena occur, we are still faced with a challenge.
Very fast fire detection combined with 100% detection reliability cannot be guaran-
teed. Fire detectors with intelligent signal processing and an appropriate detector
design, however, already come very close to this goal.
Intelligent
fire detection system A
Reliability of fire detection
Normal
fire
detection
system B
Fire development
92
To localize a hazard source in case of an alarm, the individual detector lines are
arranged in such a way that they can be easily traced; i.e. one detector line per
floor. In addition, external alarm indicators are often placed above the doors, so
that the alarm triggering detector and thus the seat of fire can be found within a
reasonable period of time.
When fire detectors with individual addressing are exclusively applied, external
alarm indicators become superfluous as the alarm triggering detector is directly
indicated on the fire detection control unit.
Modern fire detection systems in which the signal analysis is performed in the
detector itself come to a preliminary alarm decision and thus only need to transmit
the corresponding alarm level. Fire detectors without built-in signal analysis how-
ever depend on transmitting the measured values of the sensor signals to the
control unit, which can then decide on alarm in real time.
93
This document neither handles special detectors, such as pressure and spark
detectors applied for explosion protection which must respond within a few milli-
seconds, nor does it deal with gas sensors as they are used for the detection of
smoldering fires in carbonization plant, or for the detection of combustion gases.
In selecting the best suited fire detectors, the following aspects must be taken into
account:
− the type of fire to be expected
− the room height
− the ambient conditions
− possibly occurring deceptive phenomena
The use of point-type multisensor fire detectors that are capable of detecting both
smoke and heat increases constantly.
94
The measurements in the smoke channel are used for testing the detectors’ stabil-
ity and reproducibility and have little to do with the actual response behavior of the
detectors on real fires. It is thus absolutely thinkable that a smoke detector with
intelligent signal processing and a light obscuration module of 6%/m detects a real
fire earlier than a detector with normal signal processing and a light obscuration
module of 3%/m. The sensitivity required for approval conforming to EN 54 is
checked by means of the test fires described below.
95
EN 54
test fire
The figure above shows the qualitative, basic capability of the detectors to respond
to EN test fires. A heat detector cannot respond when a fire does not produce heat
(TF 2 and TF 3). The sensor design has an additional impact on the quantitative
response behavior of the sensors. The response of optical smoke detectors to
TF 1, for example, depends on the scattering angle.
96
When heat detectors are applied, it must be ensured that the minimum response
temperature is at least 10°C higher than the possible maximum ambient tempera-
ture.
Fire detectors are electric devices that can be damaged by water or by the impact
of solid objects. In selecting fire detectors, it must be tested whether the detector
type chosen has the IP protection category required for the respective environment
(see section “IP Protection Categories”, page 315).
97
Due to their setup and the sophisticated signal processing, state-of-the-art fire
detectors are largely capable of distinguishing between deceptive phenomena and
genuine fires. If, however, massive deceptive phenomena are to be expected
within the area to be monitored, the fire detectors’ position deserves special con-
sideration, in addition to the selection of modern fire detectors with intelligent signal
processing.
If deceptive alarms cannot be ruled out in spite of the optimum detector selection
and position, most fire detection systems offer technical measures by which decep-
tive alarms can be reduced. Among these, the most important ones are:
− verification of the alarm status with intermediate alarm storage
− multidetector or multizone logic
The term ignition protection sums up all measures taken in designing electrical
operating equipment in order to prevent the ignition of an explosive atmosphere.
Each type of ignition protection is advantageous for particular types of devices or
applications. This is based on the principle of isolating ignition sources. The most
important types of ignition protection for electrical operating equipment in explo-
sion-hazard areas are described in detail in the annex “Ignition Protection Classes”
on page 317.
98
4.4.6 Summary
A fire detector must be able to early and reliably detect at minimum one of the fire
phenomena to be expected. Room height, environmental conditions and possible
deceptive phenomena must be taken into account. The impact of deceptive phe-
nomena on the detection behavior can be reduced by measures such as correct
positioning, suitable detector settings or structural separation of fire sectors.
In selecting the best suited fire detector, risks and costs play an important role as
well. If an area with high fire risk shall be monitored, an area in which strong de-
ceptive phenomena may occur and operating interruptions must be avoided at any
rate, fire detection must be as early, reliable and immune to deception as possible.
This is the case with automatic welding facilities, for example. In such areas,
different fire detector types are often combined, for example multisensor fire detec-
tors and flame detectors. In an office building with smoking ban, the use of smoke
detectors will completely suffice.
For use in dirty environments or explosion-hazard areas, fire detectors must meet
special requirements set up for the respective area.
The following paragraphs describe some typical application areas for the different
types of fire detectors.
99
100
Flame Detectors
Flame detectors are used in areas where open fires may occur very rapidly and
where large open areas must be monitored.
Example: Workshop
The following example shows some considerations on the selection of the optimum
fire detector in a workshop.
A workshop with a room height of 7m shall be monitored with fire detectors. Weld-
ing work is frequently performed in this workshop. In addition, there are Diesel-
driven forklift trucks. These deceptive phenomena might cause false alarms with
smoke detectors. The use of heat detectors shall thus be discussed to reduce or
avoid the risk of deceptive alarms.
101
This example shows how complex the selection of the optimum fire detector can
be. In practice, of course, not each and every single fire detector can be planned in
this way, which is why highly experienced specialists are required to set up a fire
detection system.
Selecting the best suited detector type requires both profound technical knowledge
and a grasp for the application itself, its risk, the combustible load, the possible fire
progression and the probable and achievable fire size.
Selecting the optimum fire detector requires both knowledge and experience
In some cases, fire detection systems must be set up for objects in which one
cannot accurately predict how a fire will develop or the smoke will spread. In such
cases, the selection of the detector types, their settings and positioning must be
found out by means of simulation tools or optimized on site.
Development
Taking a closer look at automatic fire detectors applied today, more than 90% are
point-type fire detectors. Of these, approximately 75% are smoke detectors, 5%
are heat detectors and 20% are multisensor fire detectors. In many applications, a
clear shift from the “pure” smoke or heat detector to a multisensor fire detector can
be observed. The reason is that multisensor fire detectors make a more reliable
and nevertheless early detection of many different fire types possible. In addition,
the price difference to conventional, point-type smoke detectors has decreased
significantly over the past years. For special applications, ASD systems are applied
increasingly, as they can detect fires at a very early stage and may as well be
applied in rooms with strong deceptive phenomena, provided that additional meas-
ures are taken.
102
The number and positioning of fire detectors is frequently laid down in country-
specific directives, which always take priority.
4.5.1 Basics
The higher the room, the larger normally the distance between the seat of fire and
the detectors on the ceiling. This is why the intensity of the fire phenomenon to be
detected, i.e. smoke density, temperature increase or radiation intensity decreases
with increasing ceiling height. It must be taken into consideration that with an
increasing ceiling height an incipient fire may be larger due to the larger room
volume without increasing the danger of rapid fire propagation or flashover.
h3
h2
Heat
(convection)
Room height h1
Smoke
Radiation
Fire seat
103
Smoke
The thermal characteristics of open fires transport the smoke particles, which
become diluted in the larger air volume, even to very high ceilings. This smoke
dilution must be accommodated by the use of smoke detectors with sensitive
response behavior.
Smoldering fires largely lack the thermal conditions to transport smoke. Such fires
are thus only recognized by detectors mounted on high ceilings after they have
developed to open fires.
Heat
The warm air ascending from the fire cools down with increasing distance, which
means that heat detectors are of limited use with increasing room heights.
Radiation
Although the radiation energy is reduced the larger the distance between fire seat
and detector, flame detectors can be used in very high rooms thanks to their high
response sensitivity.
Each room to be monitored must be equipped with at least one automatic fire
detector.
The detector placement must comply with the prevailing room conditions (e.g. the
ceiling’s construction: ceiling with girders, special roof or ceiling shapes) or room
divisions (alcoves, furniture, equipment, etc.).
104
Manual call points must be generally installed at a height of 1.5 to 1.7m above the
floor, in order to avoid erroneous operation, for example by mistaking them for light
switches in the dark).
105
Room height
Figure 4.25: Coverage area per smoke detector depending on the room
height and the hazard potential
Area 1 with minor hazard potential should only be selected when the following
conditions are fulfilled:
− any danger to human life can be ruled out
− neither valuable property nor irreplaceable goods are stored in the area
− the fire risk is very low
− other fire protecting measures prevent possible fire propagation
− no hazard can be caused in adjacent areas, for example by corrosive decompo-
sition products
106
Area 2 with medium hazard potential can be selected for most applications.
107
The distances between detectors and walls, equipment or stored goods must not
fall below 0.5m, with the exception of corridors, channels, ducts or similar construc-
tions with a width below 1m. If there are any girders, beams, etc., or air condition-
ing ducts closer than 0.15m under the roof, the lateral distance of at least 0.5m
must be considered as well.
The detector must be secured in a way that it is fixed and inflexible. It must be
taken into account that flexible wall constructions are unsuited, as a too large
deviation of the monitoring ray makes reliable detection virtually impossible. Con-
crete and brick walls meet these prerequisites, whereas wood or steel construc-
tions are mostly unsuited, as they may be affected by temperature or moisture
changes, wind or snow pressure.
To make sure that smoldering fires or smaller fires with low fire thermals can be
detected in high rooms, a second and possibly third detector must be installed at
the assumed level of the smoke propagation of a smoldering fire. This differentia-
tion in levels becomes important in rooms higher than 6m.
108
Detectors Reflectors
The table below exemplarily shows the detector mounting height for three different
room heights.
109
Room
height
The values given here apply for rooms with a low fire risk. To cover larger risks, the
monitoring width should be half the value shown above.
4.5.6.1 Sensitivity
If a fire occurs in a room, the smoke ascending due to the thermal conditions is
gathered by the suction openings and is guided to the smoke detector via the pipe
system. The ASD triggers an alarm as soon as the average smoke concentration
of all suction openings exceeds the alarm threshold. It does not matter whether this
value is caused by very high smoke concentration at one suction opening or by a
slightly higher smoke concentration at several suction openings.
The required ASD sensitivity can be calculated by means of the following formula:
SDP
SASD = x NDPS
NDP
110
As a general rule, ASD systems are classified in the following sensitivity catego-
ries:
− normal sensitivity with a smoke sensitivity of 1.0 to 0.1%/m
− high / highest sensitivity with a smoke sensitivity of 0.1 to 0.005%/m
If a fire shall be detected as early as possible, the ASD system must trigger an
alarm as soon as there is smoke at one suction point. Such systems usually re-
quire a very high ASD sensitivity.
By applying the above formula, the required ASD sensitivity is calculated as (3/10)
x 3 = 0.9%/m.
111
Due to the large air volume, strong smoke dilution can be observed in large high
rooms such as storage rooms, atriums or hangars. If a fire in such a room shall be
detected at an early stage, a correspondingly sensitive system must be chosen. In
addition, in high rooms, heat cushions often occur below ceilings, caused by strong
solar radiation or by air warming due to fire. Such heat cushions partially or com-
pletely avoid that the smoke reaches the ceiling. This must be taken into account in
placing the ASD suction pipes (see Table 4.5 on page 106).
Heat cushion
ASD unit
In high storage rooms, the suction pipes are preferably mounted vertically. This
way, the heat cushion effect can be largely neutralized and, in addition, smaller
fires in the storage racks can be detected early thanks to this arrangement.
112
ASD unit
When planning ASD systems in special areas, additional points briefly mentioned
below must be taken into consideration.
113
Exhaust
collector
Ceiling collector
ASD unit
114
Ceiling
collector
Object
monitoring
ASD
unit
115
UV + IR IR
When placing the flame detectors, equipment or obstacles such as wings must be
taken into consideration. In a hangar, the area underneath the wings must be
monitored by flame detectors as well.
116
If several flame detectors are required in one room, they should be arranged so
that there is a high redundancy, that is, the monitoring areas of the individual flame
detectors should overlap.
117
d=a√3
45°
a
a
45°
Depending on the ratio of room surface and room height, it might make sense to
choose an inclination angle smaller than 45°. If, however, an angle > 45° is cho-
sen, the area directly underneath the detector with a visibility angle of 90° is no
longer within the visible range and thus not monitored.
118
The term “peripheral system” summarizes the networking of the fire detection
control unit with the peripheral devices, such as fire detectors, alarm devices and
fire control installations.
Commissioning reveals how easily and flexibly a fire detection control unit can be
parameterized according to customer needs. Some of these aspects should al-
ready be taken into account when evaluating the fire detection system.
Control
Line interface
interface
Fire detection
control unit
Commissioning Maintenance
119
The fire detection control unit is the core element of each fire detection system.
Compact and medium-sized systems usually have only one control unit, whereas
more complex systems often consist of several networked control units. This
makes it possible to act upon all control units by one single procedure. In such a
system, sensors and actuators can ideally be allocated to different control units,
and control can be performed so that it acts on several control units. In addition,
the transmission of fire alarms and faults to the receiving equipment can be ef-
fected centrally by a main control unit integrated into the network. This essentially
reduces the connection fees and dedicated line fees. How comprehensive the
functionality is in the specific case must be clarified in advance for each individual
system.
4.6.1.1 Setup
Each fire detection control unit comprises a minimum of five components:
• Main processor: The main processor is the heart of every fire detection control
unit. It coordinates and controls the entire fire detection system.
• Operating panel: This panel consists of indicating, acoustic and operating
elements. The indicating and acoustic elements inform the operator on the sys-
tem status (alarm, fault, operating mode, etc.). The operating elements make it
possible to operate the system by acknowledging messages, or switching from
unmanned to manned mode.
• Line interface: The line interface communicates with the peripherals and
transmits information to the main processor.
• Control interface: The control interface transmits the information received (e.g.
fire door open) to the main processor and activates the control outputs required
by the main processor (alarm devices, fire control installations, etc.).
• Power supply: The power supply unit provides the energy required for the fire
detection system.
Depending on the requirements and size of the fire detection system, the setup of
the fire detection control unit can largely vary. For a small hotel with 30 rooms, for
example, a control unit will suffice in which the main processor, operating unit, line
interface and control interface are combined on one board. Complex systems are
equipped with several line and control plug-in units. With such systems, remote
operation and the possibility to operate the system from different locations is fre-
quently required. Such operating terminals are connected to the control unit via a
control unit bus designed in compliance with the highest safety standards.
Alternatively, there is the possibility of visualizing the control unit’s user interface by
a mere software solution on a PC. The connection to the PC can be established by
a LAN, for example (see Glossary, starting on page 297). This solution also makes
it possible to indicate and operate several networked control units on the monitor of
a danger management system (see chapters 7.2ff starting on page 240).
120
Regarding the detection of fault signals and troubleshooting, the following emer-
gency operating times are recommended:
121
4.6.1.3 Functions
A state-of-the-art fire detection control unit must feature the following:
• Easy and safe system operation.
• Free adaptation of the control unit organization to changing customer require-
ments.
• Free programmable control outputs to use fire control installations.
• Manufacturer-specific battery charging characteristics and periodic endurance
testing of the batteries, in order to achieve optimum charging conditions and a
longer service life of the emergency power batteries.
• Real-time clock with date and automatic summer- / wintertime changeover.
• Event memory storing hundreds of events, sorted by information category, and
making them available on demand.
• Integrated emergency operating functions so that safe fire detection can still be
ensured in case of failure to a signal processing unit.
4.6.1.4 Operation
The user interface of a fire detection control unit must be set up so that the basic
functions such as alarm or reset alarm are easy to understand and to operate. This
makes sure that such operations can also be performed by persons who rarely
have to work on the system or who have received only elementary instructions.
Operation of a fire detection control unit not only comprises alarm processing.
Functions such as processing faults, switching from manned to unmanned, or
switching off detectors are other functions of a fire detection control unit. Since
functions like switching off detectors can impair safety, they must only be per-
formed by authorized and accordingly trained staff. State-of-the-art fire detection
control units thus offer the possibility of releasing commands in the menu structure
for some authorization levels only. The table below shows an example with 4
authorization levels.
122
4.6.1.5 Location
For the fire detection control unit, a location close to the main entrance or the fire
brigade access of the building to be monitored should be chosen. This location
must be agreed upon in advance with the organization (e.g. fire brigade) accepting
the fire detection control unit. It often suffices to place the fire department control
panel in the fire brigade’s main access, as in this case the fire detection control unit
can be placed in any room easily accessible for the wiring arrangement.
In larger building complexes where networked fire detection control units are used,
they are often installed in decentral locations, so that the lines to the detectors and
other peripheral devices can be kept as short as possible.
To keep influencing factors which might lead to false alarms or faults as low as
possible, only locations free from high electromagnetic interference (EMI) may be
selected for the fire detection control unit.
123
Topologies
The peripheral devices or line components of a fire detection system are con-
nected to the fire detection control unit via a stub or loop line. Additionally, modern
fire detection systems make it possible to use T-tabs without additional elements,
which increases the flexibility in wiring arrangement, at the same time reducing
system costs.
Stub line
Loop line
T-tab
Figure 4.38: Fire detection control unit with different detector lines
124
For reasons of safety, stub lines today are only used in systems where fire detec-
tors with conventional technology are applied or where existing lines are reused.
Individually addressed elements on a loop line ensure a considerably higher fail
safety of peripheral devices. In case of an open line, all elements remain fully
operable, as the control unit may communicate with the elements from both sides
of the loop. When all connected elements (fire detectors, input / output modules,
alarm elements) use a separator function, the entire system remains fully operable
even in case of a short-circuit, as the short-wired line segment is decoupled by the
separators. Otherwise, at least every 32nd element must be equipped with a
separator conforming to EN 54.
Collective Connection
With a collective connection, all detectors with conventional technology are con-
nected in parallel to the same stub line (see section 4.3.3.1 on page 93). To indi-
cate an alarm or a fault, a detector increases its power consumption. This change
is evaluated correspondingly in the control unit.
With a collective connection, the following aspects must be taken into account:
• Only one alarm message or fault signal can be evaluated per stub line,
as the detectors are not individually identifiable.
• Communication is unidirectional, from the detector to the control unit.
• In compliance with the EN 54 standard, a maximum of 32 devices may
be connected to one line.
• A mixture of automatic and non-automatic fire detectors on a stub is
not permitted.
• A line terminating element is installed at the end of a stub, with a monitoring
current flowing through this element. Based on this principle, the fire detection
control unit can monitor the line up to the line terminating element, but not the
connection to each individual detector.
Collective addressing gradually disappears from the market and is offered today
only as a standard connection for simple, compact fire detection control units.
When replacing existing systems in collective technology, however, it may still be
necessary to continue using the existing supply network. In this case, intelligent
detectors with complex signal processing can be applied, which are operated on
the stub line in collective mode. Due to the individual parameter setting possibili-
ties, such modern fire detectors can be set to optimum detection behavior. If com-
plete lines shall be retained in a modernization project due to cost reasons, the
new control unit must be equipped with the corresponding line modules (see chap-
ter 8.5 on page 275).
125
Addressable Connection
An addressable connection is a detector line system that can individually address
each detector (see section 4.3.3.2 on page 93). This makes it possible to individu-
ally indicate each detector that triggers an alarm and to assign a text indicated in
case of an event to this detector or detector zone. In addressable technology, the
topology types stub, loop or T-tab are principally possible. In some bus systems,
T-tabs can be implemented without additional modules, what considerably reduces
the costs for installing the supply network.
With an addressable connection, the following aspects must be taken into account:
• If the line is wired as a stub, a maximum of 32 detectors are permitted per stub
line, in compliance with the EN 54 standard.
• If the line is wired as a loop, a maximum of 128 detectors are permitted per loop
line, in compliance with the EN 54 standard.
• It must be ensured that, in case of a short-circuit, the relevant line segment is
isolated and that in case of an open line, access is possible from the opposite
side of the loop. The smaller the number of elements that fail in case of a short-
circuit, the better, which is why each bus element should contain separator ele-
ments.
• There must be a simple solution to localize detectors on the line. In this respect,
well-proven solutions are the addressing based on the physical sequence, or the
localization based on an unambiguous identification number.
Costs
The costs for installing a fire detection system are an integral part of the overall
costs. To keep wiring costs as low as possible, it is important that a fire detection
system allows for the connection of freely arranged detector lines, no matter
whether these are stub lines, loop lines or T-tabs. In addition, it must be taken into
account that as many elements as possible can be operated on the same bus and
that no extra lines for external power supply are required.
126
Alarm elements, such as flashing lights or horns, have limited information contents,
which is why voice alarm systems are increasingly used in buildings (see chapters
5.4ff starting on page 166). These systems enable step-by-step alarm and evacua-
tion depending on the situation.
The required systems are activated either decentralized via output modules on the
detector line or centralized, directly with monitored outputs such as relay contacts
or driver outputs in the fire detection control unit. Acknowledgement signals or the
execution of the fire control installations are monitored by allocated inputs.
127
4.6.3 Commissioning
By commissioning the plant, the fire detection system is configured so that it re-
sponds in accordance with the messages received from fire detectors and other
devices and acts on the relevant control systems. Short-circuits and open-circuits
prevent fast and correct commissioning, which is why the fire detection control unit
is commissioned only after a thorough check of the supply network.
In practice, the subdivision of the system structure into a logical and a physical tree
has proven worthwhile (see Figure 4.40). This allows for maximum flexibility,
completely independent from the effective hardware installation of the detector
network. For example, detectors connected to two different loop lines in the supply
network can be assigned to the same detector zone.
The logic structure reflects the geographic layout in a system. It may be flexibly
adapted to the room exploitation and is independent of the wiring arrangement in
the detector network.
The physical structure reflects the hardware. It is defined by the hardware installa-
tion and can be read in by means of a commissioning tool with modern fire detec-
tion control units.
128
The commissioning process of a fire detection system links the logic and the physi-
cal structures. In doing so, it is defined which device is located where, for example
“Smoke detector with ID 253A25 is in room 311“.
Area
Main building
Logical structure
Section 3rd floor 4th floor
Element 1 1 2 1 2
Free assignment
Device
Function unit
Physical structure
(e.g. line interface)
Station
129
In buildings with large rooms, such as production facilities or open-plan offices, all
detectors in the room are combined in a detector zone. In a building consisting of
several smaller rooms, such as an office building, the detectors in several
neighboring rooms are combined in a detector zone. The detectors in a staircase
are equally often combined in a detector zone.
The directives and limits in creating detector zones may differ from one country to
the next, which must be taken into account in project planning.
Outside normal operating hours, the detectors work with a parameter set that
already detects lowest aerosol concentrations and is thus capable of detecting a
smoldering fire. The parameters are set during commissioning by means of the
relevant tool. If the terms of use are changed, for example when the discotheque is
changed into a restaurant, the parameter sets of the respective detectors can be
adapted directly from the fire detection control unit.
130
Multidetector Logic
Multidetector logic is created wherever considerable deceptive phenomena may
occur, or where early fire detection is required for safety reasons, for example in a
Diesel engine depot. When only one detector within a detector zone transmits an
alarm message, only a prealarm is indicated on the fire detection control unit.
Alarm is only indicated when a predefined number of fire detectors transmit an
alarm message. In most cases, a two-detector logic is selected, meaning that two
alarm messages are required. Multidetector logic is possible as well, meaning that
three or four detectors must transmit alarm messages before an alarm is actually
indicated. Only now does the control unit actuate the optic and acoustic alarm
devices and / or a transmission unit and initiate the appropriate protective meas-
ures. As intelligent fire detectors are increasingly used, the significance of multide-
tector logic is continually decreasing.
131
Alarm initiation
Local alarm
Presence
Yes Yes No
When using delayed alarm transmission, the following aspects must be taken into
account in most countries:
• Delayed alarm transmission must only be active in system state “Manned”.
• An incoming alarm must be acknowledged within a maximum reaction time of 30
seconds. After that, the investigation delay begins.
• The maximum investigation delay must be 180 seconds.
• If another alarm is received during the acknowledging or investigation delay, an
external alarm must be transmitted immediately.
• Switching over to delayed alarm transmission (Manned) must be possible only
manually. Switching over to “Unmanned” must take place automatically, but
manual switchover must be possible as well.
• Alarms transmitted by manual call points must not be delayed.
132
4.6.3.5 Alarm
After detecting a hazard, the fire detection control unit must trigger an alarm ap-
propriate to the respective hazard and situation. Older or simpler control units
merely act upon the acoustic and optical signal transmitters. State-of-the-art control
units allow for programming specific, application-related alarms. Such systems
make the following settings possible:
• Several alarm devices are combined in a zone.
• Each alarm device can be actuated individually or in a zone.
• Each alarm device or each zone can be actuated depending on the respective
hazard (selection of the tonality, sound intensity or flashing frequency).
• Alarm activation and transmission to external intervention forces can be set up in
a way that it is only effected after verification of the alarm (delayed alarm trans-
mission).
• In larger building complexes, an acoustic evacuation alarm is initiated only for
the relevant fire sector. In all other fire sectors, an acoustic warning signal for the
fire alarm can be activated, alerting the people present in that sector without
asking them to leave the building.
133
The number and complexity of the control systems to be served by the fire detec-
tion control unit is essential in selecting the right control unit. It must have sufficient
memory capacity and processing speed for the number of control systems to be
processed, and it must allow for the necessary links.
When several individual buildings shall be monitored, or when the control unit shall
be operated by a superordinated system, a control unit must be chosen allowing
for easy networking.
When it can be anticipated that the existing building structure will be extended, it is
strongly recommended to opt for a modular control unit. These control units have
the advantage of facilitating a flexible and cost-efficient adaptation to the system
size due to their possible extension with additional control and line modules.
134
LAN
Controller n
Controller 1
Evaluation
Evaluation
analysis
analysis
Signal
Signal
Control Control
outputs outputs
135
By default, cables with activation temperatures between 60°C and 200°C are
available. The maximum sensor length is between 1 and 2km. By nature, the cable
is destroyed by such an event, which is why the cable needs to be replaced after
detection.
Alarm is activated as soon as the measured value falls below a defined resistance
value. The measured resistance, however, depends on the cable length and the
ambient temperature. The measured value is assumed to be the average value
over the complete cable length. One local hot spot has the same effect as a minor
temperature increase over a longer distance.
The cable is not capable of locating the fire position. By default, cables with activa-
tion thresholds between 50°C and 250°C are available. The maximum sensor
length is between 1 and 2km, depending on the system.
136
The fiber-optic cable is a doted quartz glass, i.e. a form of silicon oxide (SiO2). The
infrared electromagnetic laser radiation emitted is reflected in different ways by the
fiber-optic cable:
− Rayleigh scattering
− Stokes scattering
− Antistokes scattering
The Rayleigh scattering has the same wavelength as the laser beam, whereas the
stokes scattering has a slightly higher and the anti-stokes scattering a slightly lower
wavelength. The two stokes scattering types are also referred to as Raman scatter-
ing. While Stokes scattering is temperature-independent, Antistokes scattering is
affected by the thermal energy of the fiber-optic cable’s local temperature. The
intensity increases with the temperature. The temperature of the fiber-optic cable
thus results from the intensity ratio between Stokes and Antistokes scattering.
137
Controller
Optical waveguide
Laser
Laser beam
Backscatter
Evaluation
Laser beam
Intensity
Measured value
Antistokes Stokes
The sensor cable can be divided into sensor sections from 1 to x meters by using
appropriate electronic and software components. These sections are then handled
as individual sensors. This means that several sensors can be combined in groups,
or multisensor logic can be created. This measuring principle allows temperature
measuring and alarm triggering according to the differential and / or maximal
characteristics. Based on the accuracy of the sensor sections, it is possible to
localize the heat sources.
Depending on the fiber-optic cable type, systems available today make activation
temperatures up to 400°C possible. With a given sensor section length up to 4m,
current systems allow sensor lengths up to 16km.
138
The most suitable system has to be chosen depending on the field of application,
the risk and the price:
• If the operator wants to ensure with the simplest available means that a trans-
former will be switched off from the mains in case of overheating, it suffices to
use a cable triggering alarm when a predefined temperature is exceeded. When
such an event is expected rarely or not at all, no automatic resetting is required.
• To monitor the temperature of a reactor in the chemical industry, it is important
that the system reliably produces a prealarm and an alarm message. The possi-
bility of creating zones or localizing the heat spot is not normally necessary.
• To monitor a road tunnel with a linear heat detection system, it is mandatory to
create zones, compensate the ambient temperature and localize the heat spot,
i.e. the fire seat.
139
4.8 Planning
National standards and guidelines describe how fire detection systems must be
planned, installed and operated. Adhering to these regulations is a prerequisite for
the approval of an automatic fire detection system by the authorities, the fire bri-
gade and insurance companies. Protection-objective oriented fire detection sys-
tems can only be designed if the prevailing risk is clarified, the protection objective
is known and the resulting requirements on the fire detection system are specified.
Such systems are complex and costly and must be executed by experts.
The local requirements define which areas must be provided with what monitoring
extent. These requirements are limited to complete protection, selective protection
and escape route protection. Targeted monitoring and equipment protection are
not usually laid down in the specifications.
140
The threat plays a key role in the definition of the monitoring extent:
• If there is any threat to persons, as a general rule, all rooms frequented by
people, whether permanently or temporarily, as well as the adjacent rooms must
be included in the monitoring extent.
• If there is any threat to assets, as a general rule, all areas must be monitored.
This does not include areas that only contain a limited combustible load or that
do not facilitate fire spread.
For most buildings, the monitoring extent defined in the specification lists and
tables is sufficient. With certain types of buildings, however, the monitoring extent
must be determined for each area, based on the prevailing risks and the defined
protection objective. The following examples illustrate which deliberations are
required to define the monitoring extent of particular objects:
• A fire in a nuclear power station can have disastrous consequences. Therefore,
everything is done to prevent fire. The probability of occurrence is thus very low.
As the calculated risk is the product of the probability of occurrence and the ef-
fects, the effects of a fire must be minimized as well. In addition to a number of
structural measures such as fire compartments or the reduction of the combusti-
ble load, a fire must be detected as early as possible wherever it occurs, and
appropriate measures must be initiated. This means that complete protection is
required in all critical buildings.
• In a hospital, the protection of patients has top priority. This means that com-
plete protection is almost always required. All rooms, aisles and staircases must
be monitored by a fire detection system.
• Considering a metal-processing factory, the focus is on the protection of the
production facilities. A storage room with a low combustible load need not be
monitored by a fire detection system if fire spread is limited and possible dam-
age in this area is acceptable.
141
4.8.1.4 Fire Detection Control Unit, Supply Network and Energy Supply
The fire detection control unit serves for operating the fire detection system. In
addition, it evaluates the hazard messages received by the peripheral devices and
the fire alarm and control installations.
The supply networks must guarantee the reliable communication between the
control unit and the peripheral devices.
Detailed information on the topics of fire detection control unit, supply network and
energy supply can be found in chapter 4.6.
Depending on the type of fire detectors, room size and special areas, such as false
floors, particular restrictions apply for the creation of detector zones, referring to
the number of detectors or the size of the monitoring area, for example. It is impor-
tant that unambiguous identification of the fire location is always guaranteed.
The fire detection control unit must include at least one control device for an alarm
system to alert people. Depending on the alarm organization, alarm areas may be
defined, and additional acoustic and / or optical signal transmitters can be used for
the purpose of alerting people. The signals from these alarm devices must differ
from the usual operating signals.
To define the alarm organization and the measures in connection with it, the sys-
tem operator, fire brigade, planner and installer of a fire detection system must
work in close cooperation.
142
4.8.2.1 General
Authorities, insurance companies and fire brigades require automatic fire detection
systems for many buildings such as hospitals, hotels, museums or industrial facili-
ties. In most countries, there are also regulations specifying how such a system
must be set up, and what products are approved.
As in many other fields, economy calls for selecting the system technology in
accordance with the requirements and the risk situation:
• Collective systems are only used on the simplest application conditions, or for
low-risk applications. This system technology is exclusively distinguished by its
price.
• The addressable technology with threshold value technology is still very widely
spread, but is rarely used in new systems. Such systems are used only for low
or medium risk situations and with average degree of severity.
• Systems with individual addressing and algorithm technology are still character-
ized by their very good detection behavior. Their application is recommended
with medium risks or average requirements.
• For high risks and requirements on the detection behavior, the use of advanced
technology is indispensable. The savings resulting from early, reliable fire detec-
tion outbalance the high acquisition costs, as damage is minimized in the case
of fire and false alarms can be virtually ruled out.
143
Risk
A modern administrative building largely consists of office rooms, meeting rooms
and corridors. To minimize the combustible load and the risk of fire, only hardly
combustible materials are used wherever possible. Electric installations, electronic
devices and glowing cigarettes are possible ignition sources. Fire usually develops
within a few minutes and remains locally limited in case of early detection com-
bined with appropriate fire fighting.
The probability of a fire in such a building is rather low, due to the average com-
bustible load and the existing ignition sources. Damage is mostly locally limited; the
risk in such a building can be assessed as low to medium-sized.
If the administrative building has an EDP room, this area must be considered
separately due to its high risk.
Protection Objective
In an administrative building, the protection of people clearly has first priority. In the
event of fire, people must by no means be endangered and early alarm and
evacuation must be guaranteed. Containing and extinguishing the fire has second
priority, so that material damage can be limited. This means, for example, that
damage must at any rate be limited to one floor only. Any possible operational
interruption must be short-term and locally limited.
In a building of this type where smoking is prohibited, the operator has to expect
very weak deceptive phenomena. Monitoring is possible with individually ad-
dressed fire detectors with threshold value technology. Also, no preliminary clarifi-
cations are required. If the system is set up in compliance with the regulations, i.e.
the coverage area is taken into consideration and only approved fire detectors are
used, the required protection objective can be achieved.
Optical point detectors are installed in the offices and corridors. In rooms higher
than 3 meters and frequented by smokers, multisensor smoke detectors with
algorithm technology are recommended.
144
Risk
In a recycling facility for paper and synthetic materials, the combustible load is
extremely high. Electric installations, motors driving the production machines and
many rotating parts are potential ignition sources. A fire can cause machine failure
strongly impairing the production. Damage and resulting operational interruption
can cause enormous costs or even bankruptcy.
The risk in such a recycling facility must thus be assessed as very high. Although
damage is normally limited to property and operational interruption, it may be so
high that the company cannot survive.
Protection Objective
Protecting material assets and the production clearly have top priority. In the event
of a fire, the fire must be contained and extinguished as quickly as possible. The
production interruption must by no means exceed a certain defined value. For
example, a maximum of one production machine out of three may break down.
Danger to persons is rather low, as few people are present in such facilities, the
fire does not spread explosively, and there are sufficient escape routes.
Recycling halls are large, high rooms where rough environmental conditions pre-
vail. In addition to a high temperature and humidity fluctuation, the air usually
contains much dust depositing everywhere. Another aspect is solar radiation in
such halls, which is why deceptive alarms and holding time deserve special con-
sideration when it comes to selecting the fire detectors.
Intelligent flame detectors quickly respond to open fire and are completely immune
to the prevailing deceptive phenomena. However, they have the disadvantage that
they cannot detect smoldering fires. In addition, due to partitions, large machines,
etc., it is very difficult to monitor all areas with an acceptable number of flame
detectors.
145
Early and reliable fire detection in a recycling facility can only be ensured by com-
bining flame detectors and smoke detectors (e.g. aspirating smoke detectors or
linear smoke detectors)!
Risk
The semiconductor industry is one of the most advanced industrial sectors world-
wide. Chips are produced in clean rooms in expensive and complex processes and
with the finest microstructures. The processes must run in an extremely clean
atmosphere, which is why the quality requirements on the air in these clean rooms
are extremely high.
Typical fire hazards are the ignition of process solvents in electrically heated baths,
short-circuits or overload in technical equipment and installations, or hazards by
external fires.
Fires in clean rooms can have disastrous results. Even minor contamination by fire
aerosols or corrosive gases damages the products and intermediate products. If
the fire becomes larger, this may cause production to break down for many weeks.
The figures below show that the damage to be expected in clean rooms by far
extends the usual scope:
• In accordance with Factory Mutual, the average damage amount in the semi-
conductor industry exceeded the amount of USD 8'000'000 for each event in
1995.
• Also in 1995, one case of damage was registered for every tenth insured object.
• In comparison: In other industrial sectors, one damage case was registered for
every hundredth insured object, with an average damage amount of less than
USD 250'000 per event.
Protection Objective
In a clean room, the financial damage that can be caused by operational interrup-
tion clearly takes top priority. Everything must be done to guarantee a possibly
early, reliable detection of incipient fires. False alarms caused by environmental
influence also lead to operational interruptions and must be ruled out at any rate.
The protection of people is already ensured by early detection and alarm.
146
By selecting appropriate ventilation concepts, the desired pureness of the air can
be achieved. The ventilation delivers clean air to the room, supported by a more or
less strong air flow. Basically, we distinguish between systems with low-turbulence
displacement flow producing a laminar, i.e. uniform air flow, and systems with
turbulent mixed ventilation.
In areas with turbulent mixed ventilation, for example in service rooms, the ex-
pected air change is 10- to 50-fold. Here, point-type, intelligent smoke detectors on
the ceiling are suited for an early detection of incipient fire. A coverage area of
25m2 per detector and a maximum detector distance of 5m must be provided. In
addition, any possible perforation of the ceiling around the detector must be
avoided.
As clean rooms constitute a very high risk, the use of state-of-the-art technology is
indispensable. Application and placement of the fire detection systems listed below
are to be understood as a basic concept.
• High-sensitive ASD systems for early fire detection by monitoring the exhaust air
from the clean room. The pipe system is usually placed in the false floor and
must be planned depending on the ventilation systems. For maintenance rea-
sons, the ASD must be placed in the servicing area and thus outside the clean
room.
• By installing sensitive point detectors in the pipe system, a second alarm level is
generated, with the purpose of automatically alerting the fire brigade.
• Intelligent, point-type detectors with a high sensitivity level are applied to monitor
false ceilings and ventilation floors in large facilities.
• The servicing area is monitored by point-type smoke detectors; the coverage
area should not exceed 25m2 per smoke detector.
• Manual call points are used for manually alerting intervention forces.
147
Zone Allocation
In compliance with the IEC definition, explosion-hazard areas are classified in three
danger zones 0, 1 and 2, with the temporal and local probability of the occurrence
of an explosive atmosphere being relevant (see Annex: “Zone Division of Explosion
Areas” on page 316).
Each industrial facility must be individually divided into such zones. In doing so, it
must be taken into account that the authority in charge may as well divide one
explosion-hazard room into different zones, for example up to 1.5m room height in
zone 1, the part above 1.5m in zone 2.
Ex-zone 0 includes all areas where processes run. These hazards must thus be
controlled by processing technology. Safety technology only handles ex-zones 1
and 2.
Zone 1
Office
spaces
Autoclaves:
Zone 0
Zone 2
148
Installation
While installing fire detection systems in explosion-hazard areas, it is important that
country-specific regulations are always adhered to!
The following list reveals some points to be taken into account for the installation a
fire detection system in explosion-hazard areas:
• Whether rooms are considered explosion-hazard areas and the degree of dan-
ger are defined by the local authorities in charge. Prior to implementation, a
zone plan must be demanded from the relevant authorities, indicating zones 0,
1 and 2 as well as all zones that are not endangered.
• The passageways for detection lines and other lines from ex-rooms to non-ex-
rooms must be gastight.
• Electric decoupling of the detection line is ensured with specially developed
safety barriers that may not be mounted in the danger zone.
• In explosion-hazard rooms, only such products and installation materials may be
used that comply with the national directives.
• In explosion-hazard zones, plants and pieces of equipment made of metal must
be connected to the equipotential bonding rail.
• In explosion-hazard zones, only such wires may be placed that are used by the
equipment in these rooms. Concealed wiring, completely embedded in concrete,
may be run through the ex-zone.
• The protection distances of electrical equipment to door and ventilation openings
in explosion-hazard rooms must be taken from the national regulations.
The above list only shows the most important aspects but is by no means exhaus-
tive. In addition to products specially developed for such areas, the expert setup of
a fire detection system in explosion-hazard areas requires a lot of knowledge and
experience.
149
4.9.1 Installation
The following aspects must be taken into account for the installation of a fire detec-
tion system:
• Deviations from the system documentation can only be accepted after consulting
the responsible parties and upon adhering to the protection objectives defined in
the fire protection concept.
• Each deviation must be laid down and justified in the system documentation.
• When fitting the components of the fire detection system, the installation instruc-
tions provided by the manufacturer must be observed.
• All system parts must be secured to a solid, level surface. They must be
mounted in such a way that the risk of mechanical damage is as low as possible.
When installing the fire detection control unit, the following aspects must be taken
into account:
• The mounting location of the control unit must be close to the area where the fire
brigade arrives in the event of fire. The control unit must be directly accessible.
• The control unit must be installed in a clean room with sufficient room illumina-
tion. It must be protected against damaging environmental influences, such as
direct solar radiation, operational vibrations, dust or humidity.
• A separate electric circuit with a specially marked fuse must be used for the
mains supply.
When setting up the supply network, the following aspects must be taken into
account:
• The supply network must be installed according to approved rules and the local
regulations.
• The lines must be routed in a way that they are sufficiently mechanically pro-
tected and fixed and must comply with the requirements for room usage.
• Only the cable types approved by the supplier for use with the respective fire
detection system may be installed.
• Energy or signal cables must be laid in such a way that damaging influence on
the system will be avoided. In so doing, electromagnetic influence impairing the
correct function must be avoided as well.
150
4.9.2 Commissioning
The commissioning of a fire detection system is preceded by a detailed mounting
check of all components. Commissioning itself is performed by an authorized
installer.
4.9.3 Acceptance
The prerequisite for acceptance is a successful commissioning test. During the
acceptance test, the test positions listed in the acceptance testing list must be
checked for their compliance with the system setup and the parameter settings.
• As with commissioning, it must be ensured during the acceptance test work that
the transmission facility to the public intervention forces and the actuation of fire
protection equipment are disabled, in order to avoid erroneous activation. The
reactivation of these transmission facilities after the acceptance deserves spe-
cial consideration.
• The operating panel indicators, and especially the customizable texts, must be
checked during the test sequence for their compliance with the parameter set-
ting documentation or the system documentation.
• After a successful acceptance test, the system must be handed over to the
operator by the accepting party. The acceptance protocol must be completed,
signed and also handed over to the operator / customer.
151
Ideally, these cost blocks should be recorded and compared for each system.
However, usually this exceeds the scope by far, and most points are difficult to
elicit. The following section covers some aspects that are of significance.
152
Based on two extremes, it shall be illustrated below that service lives between 6
and 15 years are possible.
Example A
• The manufacturer launches a new generation every 4 years.
• The current system was first sold 3 years ago.
• The quality of the products and detection behavior is fairly good, but it cannot be
improved.
• The system is not designed for a seamless integration of modules of an older
system.
• The manufacturer guarantees for the delivery of system parts up to 5 years after
announcing the system’s phase-out.
The system will thus probably be replaced in a year, and the guaranteed delivery of
system parts will end in 6 years from now. Since an adaptation to changed re-
quirements and a step-by-step modernization are not possible with this system, the
realistic service life is 6 years.
153
Example B
• The manufacturer launches a new generation every 8 years.
• The current system was first sold 2 years ago.
• The quality of the products and detection behavior is sufficient and can be
improved without problems, for example by compatible fire detectors with im-
proved properties.
• The system is designed so that modules of an older system can be integrated,
for example by means of an interface to older modules.
• The manufacturer guarantees for the delivery of system parts up to 5 years after
announcing the system’s phase-out.
The system will thus probably be replaced in 6 years, and the guaranteed delivery
of system parts will end in 11 years from now. Since an adaptation to changed
requirements and a step-by-step modernization are possible with this system, the
realistic service life is 15 years for most system elements.
These two examples show that a fire detection system’s service life strongly de-
pends on the possibilities for system extension and modernization – features that
have not been sufficiently taken into account in the scope of system evaluation.
Sooner or later, a fire detection system begins to age, and the question for re-
placement arises. As it rarely happens that the complete system requires the same
degree of renovation, the system parts that are still operable should continue to be
used for several years for economic reasons. By means of well thought-out mod-
ernization concepts, a step-by-step replacement is made possible, so that the
system parts that most urgently require replacement can indeed be replaced first,
while others that are in better condition can continue to be used. Smart moderniza-
tion thus has a positive influence on the profitability of a fire detection system.
154
In large cities, it has been a rule for many years to partially pass on the cost of fire
brigade expenditures in case of false alarms. If it happens repeatedly, it may
exceed 1'000 € per case. Based on a conservative calculation of 1'000 € internal
costs (due to the interruption of productive work), the internal and external costs of
each false alarm amount to a total of 2'000 €. A fire detection system with a service
life of 10 years and two false alarms per year generates extra costs of 40'000 €.
This amount shows that an investment in a fire detection system with intelligent fire
detectors that ensure reliable detection quickly pays for itself.
4.10.5 Conclusion
To evaluate a fire detection system, the required quality regarding the detection
behavior and detection reliability must clearly take top priority. Only this way can
the defined protection objective be achieved, defining the required degree of per-
sonal safety, damage mitigation regarding buildings and assets, as well as the
limitation of operational interruptions and environmental damage.
During the planning phase, it is virtually impossible to exactly determine the overall
costs of a fire detection system. The result may be more or less accurate, depend-
ing on how thoroughly the different aspects are considered. It is important that the
determination of the overall costs, in addition to the mere acquisition costs, takes
into account maintenance, extendibility and extension costs as well as moderniza-
tion possibilities. Longer service life has already led to an excellent profitability for
many fire detection systems, although their acquisition costs were initially higher.
155