Date : LS Reference : 605331 1
29.mars.13 1
Customer : Turbomach 1
Project : GESCO BLACK START 1
Moteurs Leroy Somer +33 (0)2 38 60 48 46 Chargé d'Affaire : NCOURTEMANCHE 1
Div. EPG - Dept ORLEANS +33 (0)2 38 60 42 85
1 RUE DE LA BURELLE [email protected] 605331 1
45800 ST JEAN DE BRAYE NC A56B-085041H2LH35-xxxxxx
Subject: V3.31j - 03/2013
Site : Prime mover : Gas turbine 1
Application : Base Rating Manufacturer : Solar 1
Type : Taurus 60 1
Main data: Quantity
Generator type: LSA 56 BUL85 / 4p 1 1
Power: 6'750 kVA 5'400 kWe 5'562 kWm 1
Voltage: 11000V Star connection ± 5% Nominal current: 354 A 1
Power factor: 0,8 nominal 1
Frequency: 50 Hz Speed: 1500 rpm 1
Winding type : p5/6 Ambient: 40 °C 1
Insulation / Temperature rise : H/F Altitude: 1000 m 1
Electrical data: C
Efficiency: 110% 100% 75% 50% 25%
Power factor 0,8: 97.1 % 97.1 % 96.9 % 96.4 % 94.0 % 1
Power factor 1,0: 97.8 % 97.8 % 97.5 % 96.8 % 94.3 % 1
Reactances Unsaturated, (rated KVA): (%) time constants:
SCR: Xd Xq X'd X'q X"d X"q X2 Xo T'do T'd T''d Ta
0.55 201 102 29.5 102 19.2 24.0 21.6 12.1 3.827 0.562 0.027 0.120 1
Saturated, (rated KVA): (%) Seconds
Ra (%) Xds Xqs X'ds X'qs X"ds X"qs X2s Xo T''do T'q T"q T''qo
0.6 182 93 25.1 93 16.3 20.4 18.4 12.1 0.041 NA 0.024 0.104 1
Mounting : IM1101 1
Mounting : Two bearing Axis : horizontal 1
Rotation : Counter clockwise (seen when facing the D-end) 1
Bearing type: Sleeve - oil circulation with external lube oil set 1
Bearing insulation : 1 bearing insulated 1
Shaft end : Standard bare keywayed 1
Balancing : Full key / balancing class : G1 1
Flange : None / without 1
Shaft height : 710 mm / Width : 1500 mm 1
Axial clearance : Standard 1
Comments: REINFORCED INSULATION FOR AGGRESSIVE ATMOSPHERE - ISOLATION RENFORCEE POUR
ATMOSPHERE AGRESSIVE 1
-
Cooling : IC01 1
Protection : IP23 1
Cooler : Coolant : Air / Temperature : 40 °C 1
Air quality : Clean 1
1
Ventilation (internal) : Self vent. 1
Filter : without filter 1
Ducting (I / O) : No 1
Comments: 1
605331 rev. 1 Page 1
Date : LS Reference : 605331 1
29.mars.13 1
Customer : Turbomach 1
Project : GESCO BLACK START 1
-
Connection & regulation: Radio int. suppression: Class N 1
Parallel operation : With mains ( 3F ) 1
Type of excitation: AREP + PMI 1
Sustained three phase short circuit : > 3 x FLC for 10s. 1
AVR type: D610 (For panel mounting) 1
Voltage sensing : Terminal box mounted voltage sensing VTs / 1
Comments: 1
-
Protection and measurement accessories 1
With guide bearing sensor : = 1 x Pt100 per bearing 1
With Winding sensors : = 6 x Pt 100 1
With Anti-condensation heater : Voltage : 230 V / 1Ph / Power : 500 W 1
With Rotor earthing brush 1
Comments:
1
LS Supply 1
Set of measuring or protection CTs: I Primary (A) I Secondary (A) Power (VA) Class
Preliminary Neutral side S1 1
S2 1
Neutral side S3 1
Preliminary Line side S1 1
S2 1
Line side S3 1
Comments: X/5/5/5 - 1 x 20VA, 0,5FS5 - 2 x 20VA, 5P10 ou/or
X/1/1/1 - 1 x 10VA, 0,5FS5 - 2 x 10VA, 5P10
1
LS Supply 1
Set of Voltage measuring VTs: U Primary (V) U Secondary (V) Power (VA) Class
Preliminary Line side S1 6351 36.7 30 3P 1
S2 6351 63.5 30 1 1
Line side S3 1
Comments:
1
-
Terminal box :
Power connection : 4 connectors (brought out neutral) 1
Line side outlet : Back side 1
Extension on phase side : straight / length = 230 mm 1
Gland plate : Non magnetic 1
plate's drilling only 1
Comments: PLAQUE PERCEE SVT PP0296392 1
-
Various items :
Overspeed : 1800 rpm / Duration (min.) : 2 1
Requested noise level : 105 (dBA 1m) 1
Vibration level : 1,8 (mm/s RMS) 1
Comments: 1
specific text to mention in drawings : 1
Paint : C3H-E - Epoxy - RAL 7032 1
Documentation : PDF manual Language : anglais 1
Comments: PEINTURE RENFORCEE POUR AMBIANCE AGRESSIVE - 250 MICRONS - REINFORCED
PAINTING 1
605331 rev. 1 Page 2
Date : LS Reference : 605331 1
29.mars.13 1
Customer : Turbomach 1
Project : GESCO BLACK START 1
-
Controls :
Rules : CEI 1
QUAL/INES/006 001 Measurement of winding resistance 1
QUAL/INES/006 021 Insulation check on sensors (when fitted) 1
QUAL/INES/006 002 Voltage balance and phase order check 1
QUAL/INES/006 003 No load characteristics, no load losses 1
QUAL/INES/006 004 Three phase short circuit characteristic 1
QUAL/INES/006 005 On load test (subject to test bench capacity) 1
QUAL/INES/006 007 Overspeed test 1
QUAL/INES/006 008 Calculation of efficiency by summation of losses 1
QUAL/INES/006 009 High potential test 1
QUAL/INES/006 010 Insulation resistance measurement 1
QUAL/INES/006 019 Measurement of specified vibration level 1
1
-
Sleeve Bearing data: 1
Bearing cooling : oil circulation with external lube oil set / without cooler 1
external lub oil set :supplied by the client 1
oil type (viscosity) : mineral oil (Std) / / 1
Comments: 1
oil inlet connection : Left side (from DE) 1
oil outlet connection : Right side (from DE) 1
guide bearing sensor : 1 x Pt100 per bearing 1
Comments: 1
-
Performances :
Voltage accuracy : 0,25%
Maximum inrush current for a voltage dip of 15% : 4483 kVA
when starting an AC motor having a starting power factor between 0 and 0.4
605331 rev. 1 Page 3
Date : LS Reference : 605331 1
29.mars.13
Customer : Turbomach
Project : GESCO BLACK START
Chargé d'Affaire : NCOURTEMANCHE V3.31j - 03/2013
Main curves
ALTERNATOR 605331
LSA 56 BUL85 / 4p - 6750kVA - 11000V - 1500 rpm - 50 Hz
Capability Curve Un max
Un
Un min
kWe / rated kVA
PF -0,8 PF -0,9 PF 0,9 PF 0,8
PF -0,7 1 0,8 PF 0,7
0.8
PF -0,6 PF 0,6
PF -0,5
0.6 PF 0,5
PF -0,4 PF 0,4
0.4
PF -0,3 PF 0,3
PF -0,2 0.2 PF 0,2
PF -0,1 PF 0,1
0
-1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1
kVAr / rated kVA
Stator Current decrement curves
Isc (Per rated current - rms) Symetrical phase to neutral short circuit
Symetrical two phase short circuit
7 Symetrical three phase short circuit
Heat damage curve limit
6
short circuit at generator terminals
0
0.001 0.01 0.1 1 10 100
Time (second.)
605331 rev. 1 Page 1
Date : LS Reference : 605331 1
29.mars.13
Customer : Turbomach
Project : GESCO BLACK START
Chargé d'Affaire : NCOURTEMANCHE V3.31j - 03/2013
Main curves
ALTERNATOR 605331
LSA 56 BUL85 / 4p - 6750kVA - 11000V - 1500 rpm - 50 Hz
Efficiency Curves
PF 1 PF 0,8
99
98
Efficiency - Rendement en %
97
96
95
94
93
92
25% 50% 75% 100%
Load - Charge - % of rated electrical kWe
Transient Voltage Variation
Transient voltage dip curve Transient voltage rise curve
versus load impact versus load rejection
40% 30%
35%
Voltage rise - (% of rated voltage)
Voltage dip - (% of rated voltage)
25%
30%
25% 20%
20% 15%
15%
10%
10%
5% 5%
0% 0%
PF = 0 PF = 0,8
0.0 0.4 0.8 1.2 1.6 2.0 0.00 0.25 0.50 0.75 1.00 1.25 1.50
Load inrush - Appel de charge - % of rated kVA kVA shedding at P.F. Delestage de charge - % of ratedPF =kVA
0,8
605331 rev. 1 Page 2
Date : LS Reference : 605331 1
29.mars.13
Customer : Turbomach
Project : GESCO BLACK START
Chargé d'Affaire : NCOURTEMANCHE V3.31j - 03/2013
Main curves
ALTERNATOR 605331
LSA 56 BUL85 / 4p - 6750kVA - 11000V - 1500 rpm - 50 Hz
Thermal Damage Curve
Stator current
3 (per rated current)
2.5
1.5
1
10 100 1000 10000
Maximum duration (second.)
Unbalance Load Curve Stator Earth Fault Current
Negative phase sequence Current Fault Current (A)
C : Extensive damage
(per rated current) 75 B : Considerable damage
3
A : Acceptable damage
2 50 C
B
1 25
A
0 0
1 10 100 1000 10000 0 1 2 3 4 5 6 7 8 9 10 11 12
Maximum duration of fault (second.) Maximum duration of fault (second.)
605331 rev. 1 Page 3