PGD DISPLAY
Turning the unit On/Off: Pressing the “ESC” & the “Enter / Return” arrow
buttons together turns on and off the unit at the display. Pressing the up arrow button
+ followed by the “Enter / Return” arrow button also turns unit on/off. Follow on
screen instruction.
+
Alarm button: By pressing this button you can display the alarm that has occurred & reset it manually.
When the red led indicator lights up, at least one alarm condition has occurred. If there are multiple
alarms then using the arrow “up” & “down” buttons lets you scroll through them.
Up arrow button: Displays the program windows and allows the user to set the value of the control
parameter
Down arrow button: Displays the program windows and allows the user to set the value of the control
parameter. In default menu, pressing down arrow button displays unit operating mode.
Escape button: By pressing this button, you go back one level from where you are.
3
DELTA2 Microprocessor Controller. System Programming Manual.
PROGRAM BUTTON
Pressing the “Prg” button brings up a screen with various sub-menu’s some which are password
protected.
Sub-menus are as follows:
Notes
1. Maintenance sub-menus with symbol are protected by the service password.
2. Menu User is protected by service password
3. Menu Manufacturer is protected by manufacturer password
4. Some submenus and options may not be available depending on installed and enabled options in
Manufacturer menu.
MANUFACTURER SECTION
The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down
buttons until you get to MANUFACTURER. This section is password protected and the relevant
password is required for access to some screens. To enter the password the “up” and “down” &
“enter” arrow keys are used.
The manufacturer’s part of the program is subdivided into 6 distinct sections as outlined below. Each
section will be examined separately. Sections are:
UNIT CONFIGURATION
HUMIDIFIER
I/O CONFIG.
PARAMETERS
PLAN (HANDSHAKE)
EVD DRIVER
EC NET
TIMING
INITIALIZATION
TABLE NO. 1
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Supervisor Y/N See Note If a Supervisor is connected to the unit
Select Temp C/F °C/°F °C Degrees Fahrenheit or Celsius
Regulation Type P / P+I P Can be set as P+I to add an Integration Time
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Elec Heating Stages 0/1/2/B See Note If unit has heaters & number of stages
EN 0-10V Cool Y/N See Note If unit has proportional cooling \ cooling valve
EN 0-10V Heat Y/N See Note If unit has proportional heating \ heating valve
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Number Compressors 0/1/2 See Note If unit has compressors & number of compressors
En. VSD Control Y/N N If unit has compressors with VSD capacity control
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
En. Head Pressure Control Y/N See Note To enable head pressure control from pCO
Number Outputs 1/2 See Note Depends on number of condensers
Regulate Type P/PID/P+I P Select regulation for fan speed control
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Select Type Refrigerant See Note See Note Type refrigerant used
5
DELTA2 Microprocessor Controller. System Programming Manual.
Notes
1. Strategy 1 - Gives a user selectable 0-10V value to have a fixed speed for the EC Fan.
Strategy 2 - Fan speed varies tracking temperature setpoint with user selectable start and stop points.
Strategy 3 - Fan speed varies tracking a pressure setpoint with user selectable start and stop points. If
pressure read is outside the pressure setpoint plus differential for the set Time Delay the voltage to the
fan is increased or decreased by the set Voltage Step. The controller will then check pressure for the set
Time Delay and repeat process if necessary.
Strategy 4 – Fan speed can be controlled from a BMS within user selectable limits.
Strategy 5 – Fan speed varies to maintain a constant airflow.
6
DELTA2 Microprocessor Controller. System Programming Manual.
Notes
1. Loss of Water Flow alarm can be configured for Glycol or dual cooling depending on unit type. If set for
glycol then when controller detects a loss of water flow alarm all water valves are closed and the
compressor is stopped to prevent a high pressure alarm. When set for dual cooling the valves are closed but
the compressor is left running.
7
DELTA2 Microprocessor Controller. System Programming Manual.
HUMIDIFIER – SUBSECTION
TABLE NO. 2
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Enable Humidifier Y/N See Note If unit has humidifier
“ST” & “LT” Line / “KUE” Line Same as Text See Note Humidifier type
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Cylinder Config.
Humidifier Type See Note See Note Size and voltage of humidifier installed
Custom Humidifier See Note See Note Special code of non-standard humidifier. Special case only
Screen Ref – 3 (KUE Type Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Drainage Options
Drain if Steam Request Drops Y/N Y Humidifier drains water if steam request drops
Power-off Electrodes When Draining N Allow humidifier to drain with electrodes powered
Drain After Inactivity Y/N Y Drains bottle if humidifier inactive for x days
Screen Ref – 4 (KUE Type Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Dilution drain time 50-200% 100% Percentage adjustment of drain time threshold
Dilution drain frequency 50-200% 100% Percentage adjustment of drain frequency threshold
Screen Ref – 5 (KUE Type Humidifier Only)
Water Conductivity
Override conductivity 0–2000us/cm 0 Manual conductivity reading (0 = not enabled)
Conductivity Alarm
Pre-Alarm (warning) 0-2000 1000 Threshold value for conductivity warning alarm
Alarm 0-2000 1250 Threshold value for high conductivity alarm. Shuts down
humidifier
Screen Ref – 6 (ST and LT Type Humidifier Only)
Humidifier Setup
Humidifier See Note See Note Humidifier size. xx kg/hr depending on unit
Voltage See Note See Note Based on unit voltage
Phases Number 3 3 Always 3 Phase Power
Tam Model 100 100 Always a Tam 100 transformer
Screen Ref – 7 (ST and LT Type Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Enable drain with voltage Y/N N Humidifier cannot drain when live
Parameter C0 See Note See Note Set at factory, do not adjust
Parameter C1 See Note See Note Set at factory, do not adjust
8
DELTA2 Microprocessor Controller. System Programming Manual.
TABLE NO. 3
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B04 Return Air
Probe Type See Note NTC NTC / ON/OFF / PT1000
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B05 Supply Air
Probe Type See Note NTC NTC / ON/OFF / PT1000
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 Humidity
Probe Type See Note 0-1V 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0% RH 10.0% Minimum relative humidity value
Max Value 0000.0% RH 90.0% Maximum relative humidity value
Alarm Delay 00000s 30s Defines operation point of compressor 2 in freecooling
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 Air Pressure
Probe Type See Note 4-20mA 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B06 Head Press. Circuit 1
Probe Type See Note 4-20mA 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0barg 0barg Minimum pressure sensor value
Max Value 0000.0barg 44.8barg Maximum pressure sensor value
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B08 Head Press. Circuit 2
Probe Type See Note 4-20mA 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0barg 0barg Minimum pressure sensor value
Max Value 0000.0barg 44.8barg Maximum pressure sensor value
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 Water Inlet
Probe Type See Note NTC NTC / ON/OFF / PT1000
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B07 Water Outlet
Probe Type See Note NTC 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
9
DELTA2 Microprocessor Controller. System Programming Manual.
10
DELTA2 Microprocessor Controller. System Programming Manual.
PARAMETERS – SUBSECTION
Table No. 4
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Parameters
Compressors with Freecooling Y/N See Note For units with freecooling. Can be with or without.
Rotation of Compressors Y/N Y Compressor operation is rotated for equal wear
Compressors for Dehumidification. 0/1/2 1 Normally only 1 compressor set for dehumidification
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Compressor 1 Step without
Freecooling
Set 000.0% 25.0% Defines operation point of compressor 1
Hysteresis 000.0% 25.0% Defines operation point of compressor 1
Compressor 1 Step with Freecooling
Set 000.0% 50.0% Defines operation point of compressor 1 in freecooling
Hysteresis 000.0% 16.0% Defines operation point of compressor 1 in freecooling
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Compressor 2 Step without
Freecooling
Set 000.0% 75.0% Defines operation point of compressor 2
Hysteresis 000.0% 25.0% Defines operation point of compressor 2
Compressor 2 Step with Freecooling
Set 000.0% 83.3% Defines operation point of compressor 2 in freecooling
Hysteresis 000.0% 16.6% Defines operation point of compressor 2 in freecooling
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Output
Without Freecooling 0-100% 0-100% Defines operation point of compressor VSD
With Freecooling 0-100% 40-100% Defines operation point of compressor VSD in freecooling
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Output Voltage Limits
Min Vout 00.0V 0V Minimum output voltage to compressor VSD
Max Vout 00.0V 10.0V Maximum output voltage to compressor VSD
Dehum Vout 00.0V 10.0V Compressor VSD output during Dehum
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Ramp Enable Y/N N Enable compressor ramp times
Ramp up/down time 33-100% 000s 60s Ramp time
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Step Heater 1 Set 000.0% 25.0% Defines operation point of heater 1
Step Heater 1 Hysteresis 000.0% 25.0% Defines operation point of heater 1
Step Heater 2 Set 000.0% 50.0% Defines operation point of heater 2
Step Heater 2 Hysteresis 000.0% 25.0% Defines operation point of heater 2
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Step heater in binary control
Set 000.0% 62.5% Defines operation point of heater 3
Hysteresis 000.0% 12.5% Defines operation point of heater 3
Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
Cool Valve 0-10V
Dehum with Chilled Water Y/N See Note Enables dehum unsing chilled water valve
Chilled Water with Freecooling Y/N See Note For units with freecooling. Can be with or without.
11
DELTA2 Microprocessor Controller. System Programming Manual.
12
DELTA2 Microprocessor Controller. System Programming Manual.
13
DELTA2 Microprocessor Controller. System Programming Manual.
TABLE NO. 5
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
No. of Units in Local Network 000 See Note For local network of up to 16 Units
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Local Network Setup See Note See Note Master control / rotate by time or alarms /
rotate by alarm only
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Units in Standby 000 See Note Assign no. of units in standby
Hours/Minutes Hour/Min See Note Select hours or minutes
Rotation Time 000 See Note Can be set up to 500
Reset Sequence Y/N See Note Resets the rotation sequence
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Units in Standby 0 See Note Assigns no. of units in standby (rotate by alarm only)
Set standby unit 00 See Note Choice of unit to enter standby (rotate by alarm only)
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Force Unit in Standby Mode Y/N See Note Makes Standby Units Available
Delay Low Temperature 000m 3m Time delay to start standby units low temperature
Delay High Temperature 000m 3m Time delay to start standby units high temperature
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Low Temperature Offset 00.0 C 4.0 C Starts standby units 4 C below setpoint
Low Temperature Differential 00.0 C 3.0 C Stops standby units 1 C below setpoint
High Temperature Offset 00.0 C 4.0 C Starts standby units 4 C above setpoint
High Temperature Differential 00.0 C 3.0 C Stops standby units 1 C above setpoint
TABLE NO. 6. A.
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Enable EEVs Y/N Y
EVD1 Address 000 005 Valve driver 1 address
EVD2 Address 000 006 Valve driver 2 address
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
EVD Driver Only DEFAULT
INSTALLATION
Erase user settings and install Y/N N Set all valve driver setting back to factory default.
global default value
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Valve See Note Carel ExV Electronic valve type
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Main Regulation See Note See Note Sets main regulation for valve
Auxiliary Regulation See Note See Note Sets auxiliary regulation for valve
14
DELTA2 Microprocessor Controller. System Programming Manual.
15
DELTA2 Microprocessor Controller. System Programming Manual.
b. REGULATION
TABLE NO. 6. B.
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Valve Opening at Start-Up 000% 80% Open percentage of valve on start up
Delay Comp. Start 00s 00s Delays compressor start until valve opened
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Valve Opened in Stand-By Y/N N Valve open or closed when compressor off
Start-Up Delay after Defrost 00min 10min N/A
Valve Preposition Delay 00000s 6s Time valve remains at preposition before starting
regulation
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
PID Parameters
Prop. Gain 000.0 15.0 Proportional gain for superheat control
Integral Time 0000s 150s Integral time for superheat control
Derivative Time 000.0s 5.0s Derivative time for superheat control
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Integral Time
LowSH Protection 000.0s 10.0s Integral time for low superheat protection
LOP Protection 000.0s 10.0s Integral time for low evaporating pressure protection
MOP Protection 000.0s 20.0s Integral time for high evaporating pressure protection
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Delay
LowSH 00000s 180s Alarm delay low superheat
LOP 00000s 180s Alarm delay low evaporating pressure
MOP 00000 180s Alarm delay high evaporating pressure
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Low Suction Temperature
Threshold 000.0°C -5.0°C Low suction temperature alarm setpoint
Timeout 00000s 180s Alarm delay
Screen Ref -7
TEXT OPTION FACTORY SET DESCRIPTION
Thermoregulation
Setpoint SH 000.0K 10.0K Superheat setpoint
LowSH Threshold 000.0K 2.0K Low superheat threshold
LOP Threshold 000.0°C -5.0°C Minimum evaporating pressure setpoint
MOP Threshold 000.0°C 26.0°C Maximum evaporating pressure setpoint
16
DELTA2 Microprocessor Controller. System Programming Manual.
c. CUSTOM
TABLE NO. 6. C.
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Valve Custom
Min. Steps 00000 50 Minimum valve steps for custom valve
Max. Steps 00000 480 Maximum valve steps for custom valve
Closing Steps 00000 500 Closing steps for custom valve
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Nom. Step Rate 0000Hz 50Hz Nominal step rate
Closing Rate 0000Hz 150Hz Closing step rate
Move Current 000mA 450mA Valve moving current
Holding Current 000mA 100mA Valve holding current
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Duty Cycle 000% 30% Duty cycle of custom valve
Opening Synchr. Y/N Y Opening synchronisation of custom valve
Closing Synchr. Y/N Y Closing synchronisation of custom valve
17
DELTA2 Microprocessor Controller. System Programming Manual.
EC NET –SUBSECTION
TABLE NO. 7
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Fieldbus Config.
Parity See Note None Parity type for fan fieldbus
Stop Bits 1/1.5/2 2 Number of stop bits
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Enable EC Net Y/N Y Enable EC Fan fieldbus
Fan Type Ebm / Ziehl Ziehl Fan manufacturer
Number fans 1/2/3/4 3 Number of fans in unit
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 01
Fan Address 000 001 Address of fan 1
New Parity See Note 8 None 1 New parity of fan 1
New Address 000 000 New address of fan 1
Start Change Y/N N Write new parity and new address to fan 1
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 02
Fan Address 000 002 Address of fan 2
New Parity See Note 8 None 1 New parity of fan 2
New Address 000 000 New address of fan 2
Start Change Y/N N Write new parity and new address to fan 2
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 03
Fan Address 000 003 Address of fan 3
New Parity See Note 8 None 1 New parity of fan 3
New Address 000 000 New address of fan 3
Start Change Y/N N Write new parity and new address to fan 3
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 04
Fan Address 000 004 Address of fan 4
New Parity See Note 8 None 1 New parity of fan 4
New Address 000 000 New address of fan 4
Start Change Y/N N Write new parity and new address to fan 4
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl-Abegg
Dir. See Note Clockwise Set fan rotation direction
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Fan Config.
Ebmpapst Fan No.01
Current Address 000 001 Address of fan 1
New Address 000 001 New address of fan 1
Confirm changes Y/N N Write new address to fan
18
DELTA2 Microprocessor Controller. System Programming Manual.
19
DELTA2 Microprocessor Controller. System Programming Manual.
TIMING – SUBSECTION
Table No. 8
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Time Delay
Fan Start 000 Sec 1 Sec Main fan start up delay time.
Fan Stop 000 Sec 20 Sec Main fan off delay time.
Device 000 Sec 20 Sec Settle Timer - delays all components on start except fan
EC Fan (Y3) 0000 Sec 0 Sec Delays activation of EC Fan output
Screen Ref –2
TEXT OPTION FACTORY SET DESCRIPTION
PID Timing – Temp. PID timing setup for temperature control
Integral Time 0000 Sec 600 Sec Integration time for P+I \ PID control.
Derivative Time 0000 Sec 0 Sec Derivative time for PID control. Must be set for proper
operation.
PID Timing – H. Pressure PID timing setup for head pressure control
Integral Time 0000 Sec 60 Sec Integration time for P+I \ PID control.
Derivative Time 0000 Sec 25 Sec Derivative time for PID control. Must be set for proper
operation.
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Delay Loss of Airflow Alarm
On Start 0000s 50s Alarm delay on unit start
Running 00s 10s Alarm delay during operation
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Delay Alarm Low/High Temp/Hum 0000 Sec 600 Sec Temperature & humidity alarm time delays
Delay Loss of Water Flow Alarm 000 Sec 10 Sec Loss of water flow alarm delay
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Delay Serious Alarm Output 000 Sec 0 Sec Serious alarm time delay
Delay Non-Serious Alarm Output 000 Sec 0 Sec Non serious alarm time delay
Heater Inter Stage Delay 0000 Sec 3 Sec Heater inter stage delay
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Timing
Min Off Time 0000 Sec 180 Sec Defines minimum compressor on time
Min On Time 0000 Sec 60 Sec Defines minimum compressor off time
Start Delay Same Compressor 0000 Sec 360 Sec Defines start delay of the same compressor
Compressor Inter Stage Delay 0000 Sec 10 Sec Defines an inter stage delay for twin compressors
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Winter Start Over-ride LP Alarm 000s 180s LP switch time delay for winter start
Delay
Running LP Delay 00s 00s Alarm delay during compressor operation
20
DELTA2 Microprocessor Controller. System Programming Manual.
INITIALIZATION – SUBSECTION
Table No. 9
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Default Installation
Erase User Settings & Install Global Y/N N Reset all setting to factory default
Default Value
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
New Manufacturers Password 0000 N/A Allows manufacturers password to be changed
Notes
1. Great care must be exercised in this section as using this will reload the factory settings but the unit must then
be re-configured to reflect the installed options. Default DX unit is a single circuit DX unit with 2 stage heating
& Default CW unit is a CW unit with 0-10V valve with 2 stage heating .
21
DELTA2 Microprocessor Controller. System Programming Manual.
USER SECTION
The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to USER. This section is password protected and the relevant password is required for access to some
screens. To enter the password the “up” and “down” & “enter” arrow keys are used.
The user’s part of the program is subdivided into 8 distinct sections as outlined below. Each section
will be examined separately. Sections are:
TABLE NO. 10
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Enable On/Off Keyboard Y/N Y Enables or disables on/off at display
Enable On/Off by Remote Input Y/N Y Enable on/off by remote digital input
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Auto Restart After Power Failure Y/N Y Enables auto restart of unit after power failure
Auto Restart After Fire Alarm Y/N N Enables auto restart after fire alarm
22
DELTA2 Microprocessor Controller. System Programming Manual.
Notes
1. If Freecooling unit is selected as Freecooling with Compressors (Parameters Screen 1) then Freecooling will
be enabled when the water is 5.0 C below the Return Air Temperature and will stop again when water rises to
4.5 C below Return Air Temperature
2. If Freecooling unit is selected as Freecooling without Compressors (Parameters Screen 1) then Freecooling
will be enabled when the water is 14.0 C below the Return Air Temperature and will stop again when water
rises to 13.5 C below Return Air Temperature
3. Values noted in notes 1 & 2 are user adjustable.
23
DELTA2 Microprocessor Controller. System Programming Manual.
Table No. 12
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Humid Setpoint Limits
Min 000.0% 35.0% Minimum allowable humidity setpoint value entered.
Max 000.0% 65.0% Maximum allowable humidity setpoint value entered.
Humid Control Bands
Control Band 00.0% 5.0% Control humidity band
Neutral Zone 00.0% 1.0% Control humidity neutral zone
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Humidifier Output Limit 00.0kg/hr See Note Depends on size of unit. (ST & LT humidifiers only)
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Limit Humidifier Production 000% See Note Depends on size of unit. (KUE humidifiers only)
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Dehumidification Valve Limit CW Chill water value dehumidification settings
Value
Low Limit 0.00V 10.00V Minimum chill water valve output during dehum
High Limit 0.00V 10.00V Maximum chill water valve output during dehum
Dehumidification Valve Limit ECX Freecooling water valve dehumidification settings
Value
Low Limit 0.00V 10.00V Minimum ECXV output during dehum
High Limit 0.00V 10.00V Maximum ECXV output during dehum
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Dryer Output Limits
Min Output 0.00V 00.00V Minimum dryer output voltage (Proportional dryer only)
Max Output 0.00V 10.00V Maximum dryer output voltage (Proportional dryer only)
24
DELTA2 Microprocessor Controller. System Programming Manual.
EC FAN – SUBSECTION
Table No. 13
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 1 Fixed Fan Speed
Voltage 00.0V See Note Sets the fixed speed of the EC Fan
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 2 Select Probe for
RA/SA RA Select for temperature control on return air or supply air
Temperature Regulation
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Operational Range Voltage
Cooling Min 00.0V 5.0V Minimum fan speed in cooling
Cooling Max 00.0V 10.0V Maximum fan speed in cooling
Heating Max 00.0V 5.0V Minimum fan speed in heating
Heating Min 00.0V 10.0V Maximum fan speed in heating
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Setpoint 00.0°C 22.0°C Temperature setpoint for control (only if control sensor is
different to normal regulation)
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 3 Air Pressure
Setpoint 0000Pa 50Pa Air pressure setpoint
Deadband 000Pa 10Pa Range plus or minus from setpoint where fan speed
remains constant
Operational Range
Voltage Min 00.0V 5.0V Minimum fan output voltage
Voltage Max 00.0V 10.0V Maximum fan output voltage
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 4 Operational Range
Voltage Min 00.0V 5.0V Minimum fan output voltage
Voltage Max 00.0V 10.0V Maximum fan output voltage
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 5 Unit Airflow
Setpoint 000000m3/hr 0m3/hr Airflow setpoint
Deadband 0000m3/hr 400m3/hr Range plus or minus from setpoint where fan speed
remains constant
Operational Range
Voltage Min 00.0V 5.0V Minimum fan output voltage
Voltage Max 00.0V 10.0V Maximum fan output voltage
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan De-Hum Fan Speed
Voltage 00.0V 6.0V Fan output voltage in dehum (must be enabled in
manufacturer first)
25
DELTA2 Microprocessor Controller. System Programming Manual.
ALARMS – SUBSECTION
Table No. 14
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Temperature Alarm - Low Offset 00.0 C 6.0 C Room low temperature alarm offset from setpoint.
Temperature Alarm - High Offset 00.0 C 6.0 C Room high temperature alarm offset from setpoint.
Humidity Alarm - Low Offset 000.0 % 20.0 % Room low humidity alarm offset from setpoint.
Humidity Alarm - High Offset 000.0 % 20.0 % Room high humidity alarm offset from setpoint.
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Entering Water
Temp Alarm Low 00.0 C -5.0 C Entering water low temp alarm threshold
Temp Alarm High 00.0 C 45.0 C Entering water high temp alarm threshold
Outlet Water
Temp Alarm Low 00.0 C -5.0 C Outlet water low temp alarm threshold
Temp Alarm High 00.0 C 45.0 C Outlet water high temp alarm threshold
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Low Press. Set 00.0bar 2.5bar Low pressure alarm setpoint
Hysteresis 00.0bar 1.0bar Low pressure alarm hysteresis for cut-in
Max Restarts 0-9 4 Number of attempted compressor restarts
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 01-18
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 19-36
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 37-54
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 55-72
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 73-91
Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 92-102
26
DELTA2 Microprocessor Controller. System Programming Manual.
Table No. 15
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
BMS1 Plug-In Card
Address 000 001 Address of unit in BMS 1 communication network
Protocol See Note BACnet Protocol type of BMS 1 connection
MSTP
Comm. Speed 00000bps 19200bps Baud rate of BMS 1 connection
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Parity See Note None Parity of BMS 1 connection
Stop Bits 1/2 2 Number of stop bits for BMS 1 connection
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
BMS2 Built-In RS485
Address 000 001 Addresses of unit in BMS 2 communication network
Protocol Modbus RTU Modbus RTU Protocol (Modbus RTU only0
Comm. Speed 00000bps 19200bps Baud rate of BMS 2 connection
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
BMS2 Built-In RS485
Parity See Note None Parity of BMS 2 connection
Stop Bits 1/2 2 Number of stop bits for BMS 2 connection
Table No. 16
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Force Analogue Output Y4 Fresh Air /
Freecool
Y4 Enable Y/N N To Force Analogue Output Y4
Output Voltage 00.0V 10.0V Can be set from 00.0V to 10.0V
Force Analogue Output Y2 0-10V Prop
Heat
Y2 Enable Y/N N To Force Analogue Output Y2 Prop Heat
Output Voltage 00.0V 10.0V Can be set from 00.0V to 10.0V
27
DELTA2 Microprocessor Controller. System Programming Manual.
MAINTENANCE SECTION
The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to MAINTENANCE. This section is password protected and the relevant password is required for
access to some screens. To enter the password the “up” and “down” & “enter” arrow keys are used.
The maintenance part of the program is subdivided into 6 distinct sections as outlined below. Each
section will be examined separately. Sections are:
RUN HOURS
ALARM LOG
RESET RUN HOURS
SENSOR CALIBRATION
MANUAL PROCEDURE
HUMIDIFIER
TABLE NO. 17
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Run Hours
Fan 0000 N/A Gives Fan Run Hours
Compressor 1 0000 N/A Gives Compressor 1 Run Hours
Compressor 2 0000 N/A Gives Compressor 2 Run Hours
Freecooling 0000 N/A Gives Freecooling Run Hours
0-10V Cooling 0000 N/A Gives 0-10V Cooling Run Hours
0-10V Heating 0000 N/A Gives 0-10V Heating Run Hours
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Run Hours
Heater 1 0000 N/A Gives Humidifier Run Hours
Heater 2 0000 N/A Gives Dehumidification Run Hours
Humidifier 0000 N/A Gives Heater 1 Run Hours
Dehumidify 0000 N/A Gives Heater 2 Run Hours
28
DELTA2 Microprocessor Controller. System Programming Manual.
29
DELTA2 Microprocessor Controller. System Programming Manual.
30
DELTA2 Microprocessor Controller. System Programming Manual.
31
DELTA2 Microprocessor Controller. System Programming Manual.
HUMIDIFIER – SUBSECTION
Table No. 22
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Auto Drain Enable Y/N N To enable additional automatic humidifier drain
Drain Interval 00Hr 05Hr From 00 to 99Hr
Drain Length 000Sec 120Sec From 000 to 240Sec
Disable Humidifier Y/N N Allows Disabling of Humidifier
Manual Drain Y/N N Allows Manual Humidifier Drain of 120 Seconds
Screen Ref –2 (KUE Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Change Cylinder
Empty Cylinder Y/N N Manually drains the humidifier cylinder
Flush new Cylinder Y/N N Performs 15min wash cycle on new cylinder
32
DELTA2 Microprocessor Controller. System Programming Manual.
The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to INPUTS / OUTPUTS. This section is not password protected.
TABLE NO. 23
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Return Air Temperature N/A N/A Active Readout of I/O
Return Air Humidity N/A N/A Active Readout of I/O
Supply Air Temperature N/A N/A Active Readout of I/O
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Analog Inputs
Water Inlet N/A N/A Active Readout of I/O
Water Outlet N/A N/A Active Readout of I/O
External Air N/A N/A Active Readout of I/O
Air Pressure N/A N/A Active Readout of I/O
Airflow N/A N/A Active Readout of I/O
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
External humid. N/A N/A Active Readout of I/O
External Air Absolute Humidity N/A N/A Active Readout of I/O
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Head Pressure Control
Circuit 1 HP N/A N/A Active Readout of I/O
Circuit 2 HP N/A N/A Active Readout of I/O
Condenser 1 N/A N/A Active Readout of I/O
Condenser 2 N/A N/A Active Readout of I/O
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Digital Inputs N/A N/A Active Readout of I/O
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Digital Inputs N/A N/A Active Readout of I/O
Digital Outputs N/A N/A Active Readout of I/O
Screen Ref -7
TEXT OPTION FACTORY SET DESCRIPTION
Analog Outputs
Y1: Heat N/A N/A Active Readout of I/O
Y2: Heat N/A N/A Active Readout of I/O
Y3: EC Fan N/A N/A Active Readout of I/O
Y4: Freecooling N/A N/A Active Readout of I/O
Y5: SPARE N/A N/A Active Readout of I/O
Screen Ref -8
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Status
Speed Request N/A N/A Active Readout of I/O
Motor 1 Speed N/A N/A Active Readout of I/O
Screen Ref -9
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Status
Speed Request N/A N/A Active Readout of I/O
Motor 1 Speed N/A N/A Active Readout of I/O
Motor 2 Speed N/A N/A Active Readout of I/O
Motor 3 Speed N/A N/A Active Readout of I/O
33
DELTA2 Microprocessor Controller. System Programming Manual.
34
DELTA2 Microprocessor Controller. System Programming Manual.
35
DELTA2 Microprocessor Controller. System Programming Manual.
CLOCK SECTION
The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to CLOCK. This section is password protected and the relevant password is required for access to
some screens. To enter the password the “up” and “down” & “enter” arrow keys are used.
TABLE NO.24
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Regulation Clock
Hour See Note See Note Sets Clock Hours & Minutes
Date See Note See Note Sets Clock Date in format MM/DD/YY
Day See Note See Note Mo, Tu, We, Th, Fr, Sa, Su
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Clock Password 0000 0000 Password Required
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Enable Auto Temp Set Point Variation Y/N N Enables Automatic Temperature Set Point Variation
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 1 – Start Hour 00.00 00.00 Time Zone No. 1 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 1 Temperature Set Point
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 2 – Start Hour 00.00 00.00 Time Zone No. 2 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 2 Temperature Set Point
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 3 – Start Hour 00.00 00.00 Time Zone No. 3 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 3 Temperature Set Point
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 4 – Start Hour 00.00 00.00 Time Zone No. 4 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 4 Temperature Set Point
36
DELTA2 Microprocessor Controller. System Programming Manual.
ALARMS SECTION
Notes:
1. All alarms can be set as serious or non-serious in the user section of the controller. All serious alarms will
shut down the unit
2. A05 & A09 are deemed serious alarms by default. A05 can be changed by the user.
3. A06 is deemed non-serious by default to keep a slave module of a duplex unit running in the event of a master
air flow alarm. This is only when A05 is set as a non-serious alarm.
4. A35 & A08 will always disable the Humidifier whether set as serious or non-serious.
5. A36, if set in unit configuration as glycol will stop compressors and close all water valves. If set as dual
cooling will close water valves and leave compressors running.
6. A39 indicates a fault detected in the controllers permanent memory during start up. Should this alarm occur
please refer to factory for further support.
7. There may also be some additional alarms which are order specific.
ALARM LIST
AL 01 Compressor 1 HP / Thermal Overload
AL 02 Compressor 2 HP / Thermal Overload
AL 03 Compressor 1 LP
AL 04 Compressor 2 LP
AL 05 Air Flow Alarm (Serious Alarm)
AL 06 Air Flow Alarm – Slave
AL 07 Alarm Electric Reheat High Temp Trip
AL 08 Condensate Pump / High Water Level
AL 09 Smoke/Fire (Serious Alarm)
AL 10 Alarm Air Filter
AL 11 High Temperature Alarm
AL 12 Low Temperature Alarm
AL 13 High Humidity Alarm
AL 14 Low Humidity Alarm
AL 15 High Entering Water Temperature
AL 16 Low Entering Water Temperature
AL 17 Compressor 1 Run Hours
AL 18 Compressor 2 Run Hours
AL 19 Fan Run Hours
AL 20 Return Air Temperature Probe Fault Or Offline
AL 21 Entering Water Temperature Probe Fault Or Offline
AL 22 External Air Temperature Probe Fault Or Offline
AL 23 Supply Air Temperature Probe Fault Or Offline
AL 24 Return Air Humidity Probe Fault Or Offline
AL 25 Leaving Water Temperature Probe Fault Or Offline
AL 26 High Leaving Water Temperature
AL 27 Low Leaving Water Temperature
AL 28 High Current Into Humidifier
AL 29 Lack Of Water Into Humidifier
AL 30 Lack Of Current Into Humidifier
AL 31 Humidifier Low Production
AL 32 Humidifier Drain Alarm
AL 33 Humidifier Water Conductivity High - Warning
AL 34 Humidifier Water Conductivity High – Alarm
AL 35 Water Under Floor
AL 36 Loss of Water Flow Alarm
AL 37 Air Pressure Probe Fault or Offline
AL 38 Circuit 1 High Pressure Sensor Fault / Offline
AL 39 Circuit 2 High Pressure Sensor Fault / Offline