Controls Programing Guide PGD1

This document provides a programming manual for a microprocessor controller. It describes the controller's display interface and menus, including sections for manufacturers, users, maintenance, inputs/outputs, and alarms. The manufacturer section allows configuration of installed options and settings for unit operation, networking, timing, and initialization.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
585 views

Controls Programing Guide PGD1

This document provides a programming manual for a microprocessor controller. It describes the controller's display interface and menus, including sections for manufacturers, users, maintenance, inputs/outputs, and alarms. The manufacturer section allows configuration of installed options and settings for unit operation, networking, timing, and initialization.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 39

DELTA2 Microprocessor Controller. System Programming Manual.

D
RANGE.ELTA 2

MICROPROCESSOR CONTROLLER
SYSTEM PROGRAMMING MANUAL

UNITS WITH PGD DISPLAY

1
DELTA2 Microprocessor Controller. System Programming Manual.

CONTENTS

PGD Display ____________________________________________________________ 3


Description of Menus _____________________________________________________ 4
Manufacturers Section ___________________________________________________ 5
Unit Configuration ________________________________________________ 5
Humidifier ________________________________________________________ 8
I/O Config. _______________________________________________________ 9
Parameters ______________________________________________________ 11
pLAN (Handshake) _______________________________________________ 14
EVD Driver ______________________________________________________ 14
EC Net __________________________________________________________ 18
Timing __________________________________________________________ 20
Initialization _____________________________________________________ 21
User Section ___________________________________________________________ 22
Unit On/Off Control _______________________________________________ 22
Temperature Control ______________________________________________ 22
Humidity Control _________________________________________________ 24
EC Fan _________________________________________________________ 25
Alarms __________________________________________________________ 26
B.M.S (Supervisor) ________________________________________________ 27
Force Aout _______________________________________________________ 27
Maintenance Section ____________________________________________________ 28
Run Hours _______________________________________________________ 28
Alarm Log _______________________________________________________ 28
Reset Run Hours _________________________________________________ 29
Sensor Calibration ________________________________________________ 29
Manual Procedure ________________________________________________ 31
Humidifier _______________________________________________________ 32
Inputs/Outputs Section __________________________________________________ 33
Clock Section __________________________________________________________ 36
Alarms ________________________________________________________________ 37

Document Reference: E 4.19-03-01-03

2
DELTA2 Microprocessor Controller. System Programming Manual.

PGD DISPLAY

Turning the unit On/Off: Pressing the “ESC” & the “Enter / Return” arrow
buttons together turns on and off the unit at the display. Pressing the up arrow button
+ followed by the “Enter / Return” arrow button also turns unit on/off. Follow on
screen instruction.
+
Alarm button: By pressing this button you can display the alarm that has occurred & reset it manually.
When the red led indicator lights up, at least one alarm condition has occurred. If there are multiple
alarms then using the arrow “up” & “down” buttons lets you scroll through them.

Up arrow button: Displays the program windows and allows the user to set the value of the control
parameter

Down arrow button: Displays the program windows and allows the user to set the value of the control
parameter. In default menu, pressing down arrow button displays unit operating mode.

Enter / Return arrow button: Confirms the set data.

Escape button: By pressing this button, you go back one level from where you are.

Program button: By pressing this button, you get a range of sub-menus.

3
DELTA2 Microprocessor Controller. System Programming Manual.

PROGRAM BUTTON
Pressing the “Prg” button brings up a screen with various sub-menu’s some which are password
protected.
Sub-menus are as follows:

DESCRIPTION OF THE MENUS

Menu Level 1 Sub Menu Level Description


Maintenance Run Hours View of component operational hours
Alarm Log View alarm history log
Adjust Run Hours  Reset run hours and adjust run hours maintenance alarm thresholds
 Sensor Calibration  Adjust calibration of sensors.
Manual Procedure  Manual operation of components. Unit must be Off.
Humidifier  Auto drain setup, change cylinder, disable hum.
Values of inputs and outputs, humidifier status, EVD status, controller
Input / Output
info
Clock Set date and time and enable time zones
Setpoints Adjust Humidity and Temperature setpoints
User Unit OnOff Control Unit On Off by remote, keyboard and auto restart options
Temperature Control Setpoint limits, control bands, cooling \ heating outputs limits
Setpoint limits, control bands, valve dehum. limits, humidifier output
Humidity Control
limit
EC Fan Speed \ pressure \ airflow setpoints, fan operational limits.
 Alarms Temperature and humidity alarms. Adjust serious and non-serious alarms
B.M.S (Supervisor) Protocol, address and Baud Rate settings
Force AOUT Force minimum voltage on Y4 and Y2 analog outputs
Password Change service password
Manufacturer Unit Configuration Enable and disable of installed options. Normally set at factory
Humidifier Sensor config. Humidifier size, type, drain options, conductivity options
IO Config. Configuration of controller inputs and outputs
Parameters On / Off points for installed heating / cooling devices. Erase alarm history
pLAN (Handshake) Local area network (handshake) setup and operation parameters

EVD Driver Electronic expansion valve driver setup menu. See additional prog. guide
EC Net Fan network setting and addresses
Timing Adjustment of time delays for components & alarms. PID timing
Initialization Restore default values, change manufacturer passwords
Version Software and BIOS version. Required for querying software with factory
Board Switch Select controller for display to view. View network status

Notes
1. Maintenance sub-menus with symbol are protected by the service password.
2. Menu User is protected by service password
3. Menu Manufacturer is protected by manufacturer password
4. Some submenus and options may not be available depending on installed and enabled options in
Manufacturer menu.

There is also an Alarm list included at the end of this manual.


4
DELTA2 Microprocessor Controller. System Programming Manual.

MANUFACTURER SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down
buttons until you get to MANUFACTURER. This section is password protected and the relevant
password is required for access to some screens. To enter the password the “up” and “down” &
“enter” arrow keys are used.

The manufacturer’s part of the program is subdivided into 6 distinct sections as outlined below. Each
section will be examined separately. Sections are:

UNIT CONFIGURATION
HUMIDIFIER
I/O CONFIG.
PARAMETERS
PLAN (HANDSHAKE)
EVD DRIVER
EC NET
TIMING
INITIALIZATION

UNIT CONFIGURATION – SUBSECTION

TABLE NO. 1
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Supervisor Y/N See Note If a Supervisor is connected to the unit
Select Temp C/F °C/°F °C Degrees Fahrenheit or Celsius
Regulation Type P / P+I P Can be set as P+I to add an Integration Time
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Elec Heating Stages 0/1/2/B See Note If unit has heaters & number of stages
EN 0-10V Cool Y/N See Note If unit has proportional cooling \ cooling valve
EN 0-10V Heat Y/N See Note If unit has proportional heating \ heating valve
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Number Compressors 0/1/2 See Note If unit has compressors & number of compressors
En. VSD Control Y/N N If unit has compressors with VSD capacity control
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
En. Head Pressure Control Y/N See Note To enable head pressure control from pCO
Number Outputs 1/2 See Note Depends on number of condensers
Regulate Type P/PID/P+I P Select regulation for fan speed control
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Select Type Refrigerant See Note See Note Type refrigerant used

5
DELTA2 Microprocessor Controller. System Programming Manual.

TABLE NO. 1 CONTINUED


Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Enable Sensors
B01 See Note See Note Return Humidity / External Air Temp.
B02 See Note See Note Conductivity / Ext. Humidity / Airflow / Air Pressure
B03 Hum Current Hum Current Not adjustable
B04 Return Air / No Return Air Enable return air probe
B05 See Note See Note Water Inlet / Supply Air
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
B06 See Note See Note Head Press. 1 / Water Inlet
B07 See Note See Note Air Pressure / Water Outlet
B08 See Note See Note Head Press. 2 / External Air
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Select Probe for Temp Regulation RA\SA RA Select for temperature control on return air or supply air
Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Configuration
Enable EC Fan Y/N See Note For units with EC Fan fitted
Strategy 1/2/3/4/5 See Note See Note 1 below
En De-Hum Speed Y/N See Note Enables a set fan speed for when unit is in De-Hum
Screen Ref – 10
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 3
Volt Step 00.0V – 10.0V 0.2V Sets the voltage change after each time delay
Action Delay 000s 10s Time unit must be outside set pressure before voltage to
fan is adjusted
Screen Ref – 11
TEXT OPTION FACTORY SET DESCRIPTION
Airflow Measurement
K-value of inlet ring 000 See Note K-value of inlet ring. Used for airflow calculation
Number of Fans 1/2/3/4 See Note Number of fans in unit. Used for airflow calculation
Screen Ref – 12
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 5
Volt Step 00.0V – 10.0V 0.2V Sets the voltage change after each time delay
Action Delay 000s 10s Time unit must be outside set pressure before voltage to
fan is adjusted
Screen Ref – 13
TEXT OPTION FACTORY SET DESCRIPTION
En Dryer Y/N See Note For units that are to control an external dryer
Dryer Type See Note See Note Depends on dryer type – On/Off or Proportional
En Dryer Alarm Y/N See Note Enable alarm input for dryer

Notes
1. Strategy 1 - Gives a user selectable 0-10V value to have a fixed speed for the EC Fan.
Strategy 2 - Fan speed varies tracking temperature setpoint with user selectable start and stop points.
Strategy 3 - Fan speed varies tracking a pressure setpoint with user selectable start and stop points. If
pressure read is outside the pressure setpoint plus differential for the set Time Delay the voltage to the
fan is increased or decreased by the set Voltage Step. The controller will then check pressure for the set
Time Delay and repeat process if necessary.
Strategy 4 – Fan speed can be controlled from a BMS within user selectable limits.
Strategy 5 – Fan speed varies to maintain a constant airflow.

6
DELTA2 Microprocessor Controller. System Programming Manual.

TABLE NO. 1 CONTINUED


Screen Ref – 14
TEXT OPTION FACTORY SET DESCRIPTION
Freecooling Config.
Enable Freecooling Y/N See Note For units with freecooling
Freecooling by Analog Output Y/N See Note For units with freecooling. Activates analog output
Freecooling With W/A See Note Water or external air
Screen Ref – 15
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Config.
Alarm Input ID13 See Note See Note Cond. Pump / EC Fan AL
Select Config. Of Alarm Input N/C / N/O See Note
Screen Ref – 16
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Config.
ID7 Flow Alarm Select Unit Type See Note See Note Dual Cooling or Glycol depending on unit type
Valve Ports Num. 2/3 See Note Number of ports on cooling valve
Screen Ref – 17
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Config.
Enable Refrigerant Leak Alarm Y/N See Note Enable refrigerant leak alarm
Enable Phase Rotation Alarm Y/N See Note Enable phase rotation alarm
Screen Ref – 18 (pCO Small Board Only)
Condensate Pump Alarm OPTION FACTORY SET
Select Config. of Alarm Input N/C / N/O See Note Depends on condensate pump type & alarm output
Alarm Input ID13 See Note See Note Sets alarm input ID13 cond. pump / EC fan AL
Screen Ref – 19
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Config.
ID3 Configuration See Note See Note Reheat Stat / Condensate Pump / EC Fan Alarm
ID7 Configuration See Note See Note Condensate Pump Alarm / Phase Rotation Alarm / Water
Flow Switch
Valve Ports Num. 2/3 See Note Number of ports on cooling valve
Screen Ref – 20
Output Config. OPTION FACTORY SET
Configuration of Output NO08 See Note See Note Serious Alarm / Common Alarm
Configuration of Output NO07 See Note See Note Serious Alarm / Non-Serious Alarm
Screen Ref – 21
Configuration of Output NO13 See Note See Note Slave Fan / Damper / On/Off Dryer
Screen Ref – 22
AOUT Config. OPTION FACTORY SET
Y1 See Note See Note Configuration of analog output Y1
Y2 See Note See Note Configuration of analog output Y2
Y3 See Note See Note Configuration of analog output Y3
Y4 See Note See Note Configuration of analog output Y4
Y5 See Note See Note Configuration of analog output Y5

Notes
1. Loss of Water Flow alarm can be configured for Glycol or dual cooling depending on unit type. If set for
glycol then when controller detects a loss of water flow alarm all water valves are closed and the
compressor is stopped to prevent a high pressure alarm. When set for dual cooling the valves are closed but
the compressor is left running.

7
DELTA2 Microprocessor Controller. System Programming Manual.

HUMIDIFIER – SUBSECTION

TABLE NO. 2
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Enable Humidifier Y/N See Note If unit has humidifier
“ST” & “LT” Line / “KUE” Line Same as Text See Note Humidifier type
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Cylinder Config.
Humidifier Type See Note See Note Size and voltage of humidifier installed
Custom Humidifier See Note See Note Special code of non-standard humidifier. Special case only
Screen Ref – 3 (KUE Type Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Drainage Options
Drain if Steam Request Drops Y/N Y Humidifier drains water if steam request drops
Power-off Electrodes When Draining N Allow humidifier to drain with electrodes powered
Drain After Inactivity Y/N Y Drains bottle if humidifier inactive for x days
Screen Ref – 4 (KUE Type Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Dilution drain time 50-200% 100% Percentage adjustment of drain time threshold
Dilution drain frequency 50-200% 100% Percentage adjustment of drain frequency threshold
Screen Ref – 5 (KUE Type Humidifier Only)
Water Conductivity
Override conductivity 0–2000us/cm 0 Manual conductivity reading (0 = not enabled)
Conductivity Alarm
Pre-Alarm (warning) 0-2000 1000 Threshold value for conductivity warning alarm
Alarm 0-2000 1250 Threshold value for high conductivity alarm. Shuts down
humidifier
Screen Ref – 6 (ST and LT Type Humidifier Only)
Humidifier Setup
Humidifier See Note See Note Humidifier size. xx kg/hr depending on unit
Voltage See Note See Note Based on unit voltage
Phases Number 3 3 Always 3 Phase Power
Tam Model 100 100 Always a Tam 100 transformer
Screen Ref – 7 (ST and LT Type Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Enable drain with voltage Y/N N Humidifier cannot drain when live
Parameter C0 See Note See Note Set at factory, do not adjust
Parameter C1 See Note See Note Set at factory, do not adjust

8
DELTA2 Microprocessor Controller. System Programming Manual.

I/O CONFIG. SUBSECTION

TABLE NO. 3
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B04 Return Air
Probe Type See Note NTC NTC / ON/OFF / PT1000
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B05 Supply Air
Probe Type See Note NTC NTC / ON/OFF / PT1000
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 Humidity
Probe Type See Note 0-1V 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0% RH 10.0% Minimum relative humidity value
Max Value 0000.0% RH 90.0% Maximum relative humidity value
Alarm Delay 00000s 30s Defines operation point of compressor 2 in freecooling
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 Air Pressure
Probe Type See Note 4-20mA 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B06 Head Press. Circuit 1
Probe Type See Note 4-20mA 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0barg 0barg Minimum pressure sensor value
Max Value 0000.0barg 44.8barg Maximum pressure sensor value
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B08 Head Press. Circuit 2
Probe Type See Note 4-20mA 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0barg 0barg Minimum pressure sensor value
Max Value 0000.0barg 44.8barg Maximum pressure sensor value
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 Water Inlet
Probe Type See Note NTC NTC / ON/OFF / PT1000
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B07 Water Outlet
Probe Type See Note NTC 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA

9
DELTA2 Microprocessor Controller. System Programming Manual.

Table No. 3 continued


Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
Analog Input B00 External Air
Probe Type See Note NTC 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Alarm Delay 00000s 30s Alarm delay time
Screen Ref – 10
TEXT OPTION FACTORY SET DESCRIPTION
External Humidity Analog Input B00
Probe Type See Note 0-1V 0-10V / 0-1V / NTC / NTC HT / 0.5-4.5V / 0-5V / 4-
20mA / 0-20mA
Min Value 0000.0% RH 10.0% RH Minimum relative humidity value
Max Value 0000.0% RH 90.0% RH Maximum relative humidity value
Alarm Delay 00000s 30s Alarm delay time

10
DELTA2 Microprocessor Controller. System Programming Manual.

PARAMETERS – SUBSECTION
Table No. 4
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Parameters
Compressors with Freecooling Y/N See Note For units with freecooling. Can be with or without.
Rotation of Compressors Y/N Y Compressor operation is rotated for equal wear
Compressors for Dehumidification. 0/1/2 1 Normally only 1 compressor set for dehumidification
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Compressor 1 Step without
Freecooling
Set 000.0% 25.0% Defines operation point of compressor 1
Hysteresis 000.0% 25.0% Defines operation point of compressor 1
Compressor 1 Step with Freecooling
Set 000.0% 50.0% Defines operation point of compressor 1 in freecooling
Hysteresis 000.0% 16.0% Defines operation point of compressor 1 in freecooling
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Compressor 2 Step without
Freecooling
Set 000.0% 75.0% Defines operation point of compressor 2
Hysteresis 000.0% 25.0% Defines operation point of compressor 2
Compressor 2 Step with Freecooling
Set 000.0% 83.3% Defines operation point of compressor 2 in freecooling
Hysteresis 000.0% 16.6% Defines operation point of compressor 2 in freecooling
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Output
Without Freecooling 0-100% 0-100% Defines operation point of compressor VSD
With Freecooling 0-100% 40-100% Defines operation point of compressor VSD in freecooling
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Output Voltage Limits
Min Vout 00.0V 0V Minimum output voltage to compressor VSD
Max Vout 00.0V 10.0V Maximum output voltage to compressor VSD
Dehum Vout 00.0V 10.0V Compressor VSD output during Dehum
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Ramp Enable Y/N N Enable compressor ramp times
Ramp up/down time 33-100% 000s 60s Ramp time
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Step Heater 1 Set 000.0% 25.0% Defines operation point of heater 1
Step Heater 1 Hysteresis 000.0% 25.0% Defines operation point of heater 1
Step Heater 2 Set 000.0% 50.0% Defines operation point of heater 2
Step Heater 2 Hysteresis 000.0% 25.0% Defines operation point of heater 2
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Step heater in binary control
Set 000.0% 62.5% Defines operation point of heater 3
Hysteresis 000.0% 12.5% Defines operation point of heater 3
Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
Cool Valve 0-10V
Dehum with Chilled Water Y/N See Note Enables dehum unsing chilled water valve
Chilled Water with Freecooling Y/N See Note For units with freecooling. Can be with or without.

11
DELTA2 Microprocessor Controller. System Programming Manual.

Table No. 4 continued


Screen Ref – 10
TEXT OPTION FACTORY SET DESCRIPTION
Cool Valve 0-10V
Without Freecooling Valve 000-100% See Note Cooling valve operational points
With Freecooling Valve 000-100% 50-100% Cooling valve operational points with freecooling
Screen Ref –11
TEXT OPTION FACTORY SET DESCRIPTION
Prop. Heat 0-10V
Start 0.00% 0.00% If proportional 0-10V heating installed
Stop 100.00% 100.00% If proportional 0-10V heating installed
Screen Ref – 12
TEXT OPTION FACTORY SET DESCRIPTION
ECX Valve 0-10V
Start 0.00% 0.00% If freecooling valve installed
Stop 100.00% 100.00% If freecooling valve installed
Dehum ECX Valve Y/N See Note Enables dehum using freecooling valve
Dryer 0-10V
Start 0.00% 0.00% If proportional 0-10V dryer control is installed
Stop 100.00% 100.00% If proportional 0-10V dryer control is installed
Screen Ref – 13
TEXT OPTION FACTORY SET DESCRIPTION
EC FAN
Cooling
Start 000.0% 000.0% Defines operational point of main fan when tracking
temperature. Strategy 2 must be enabled.
Stop 000.0% 100.0% Defines operational point of main fan when tracking
temperature. Strategy 2 must be enabled.
Freecooling
Start 000.0% 000.0% Defines operational point of main fan when tracking
temperature. Strategy 2 must be enabled.
Stop 000.0% 100.0% Defines operational point of main fan when tracking
temperature. Strategy 2 must be enabled.
Screen Ref – 14
TEXT OPTION FACTORY SET DESCRIPTION
Step Humidity
Set 000.0% 50% Defines operation point of external humidifier
Hysteresis 000.0% 50% Defines operation point of external humidifier
Screen Ref – 15
TEXT OPTION FACTORY SET DESCRIPTION
Step Dehumidity
Set 000.0% 70.0% Defines operation point of dehumidification
Hysteresis 000.0% 30.0% Defines operation point of dehumidification
Low Temp Limit Stop Dehum
Set 000.0% 60.0% Low temp point where dehum is enabled / disabled
Hysteresis 000.0% 35.0% Low temp point where dehum is enabled / disabled
Screen Ref – 16
TEXT OPTION FACTORY SET DESCRIPTION
Set Minimum Water Valve Voltage 00.0V See Note Minimum valve voltage before unit can alarm on loss of
water flow.
Screen Ref – 17
TEXT OPTION FACTORY SET DESCRIPTION
Head Pressure Control
Fan Speed Controller
Low Voltage 00.0V 1.8V Low output voltage to fan speed control module 1
Upper Voltage 00.0V 6.5V High output voltage to fan speed control module 1
HP Control Circuit 1
Setpoint 00.0bar 17.0bar Head pressure setpoint. Pressure at which fans start to
ramp from min speed.
Differential 00.0bar 6.0bar Head pressure control band.
Cut-Out (PID) 00.0bar 16.5bar Pressure at which the fans cut out.

12
DELTA2 Microprocessor Controller. System Programming Manual.

Table No. 4 continued


Screen Ref – 18
TEXT OPTION FACTORY SET DESCRIPTION
HP Control Circuit 2
Setpoint 00.0bar 17.0bar Head pressure setpoint. Pressure at which fans start to
ramp from min speed.
Differential 00.0bar 6.0bar Head pressure control band.
Cut-Off (PID) 00.0bar 16.5bar Pressure at which the fans cut out.
Screen Ref – 19
TEXT OPTION FACTORY SET DESCRIPTION
High Pressure Limit
High Limit 00.0 34.0bar High pressure limit set point for VSD ramp back
Control Band 00.0bar 4.0bar Control band.
Min Output 00.0V 02.6V Minimum value VSD will ramp to.
Screen Ref –20
TEXT OPTION FACTORY SET DESCRIPTION
Enable Alarm Y/N Yes Enable high pressure limit alarm
Delay 000s 120s Alarm delay
Screen Ref – 21
TEXT OPTION FACTORY SET DESCRIPTION
Alarm History
Erase Alarm History Y/N N Erases alarm history

13
DELTA2 Microprocessor Controller. System Programming Manual.

PLAN (HANDSHAKE) – SUBSECTION

TABLE NO. 5
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
No. of Units in Local Network 000 See Note For local network of up to 16 Units
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Local Network Setup See Note See Note Master control / rotate by time or alarms /
rotate by alarm only
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Units in Standby 000 See Note Assign no. of units in standby
Hours/Minutes Hour/Min See Note Select hours or minutes
Rotation Time 000 See Note Can be set up to 500
Reset Sequence Y/N See Note Resets the rotation sequence
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Units in Standby 0 See Note Assigns no. of units in standby (rotate by alarm only)
Set standby unit 00 See Note Choice of unit to enter standby (rotate by alarm only)
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Force Unit in Standby Mode Y/N See Note Makes Standby Units Available
Delay Low Temperature 000m 3m Time delay to start standby units low temperature
Delay High Temperature 000m 3m Time delay to start standby units high temperature
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Low Temperature Offset 00.0 C 4.0 C Starts standby units 4 C below setpoint
Low Temperature Differential 00.0 C 3.0 C Stops standby units 1 C below setpoint
High Temperature Offset 00.0 C 4.0 C Starts standby units 4 C above setpoint
High Temperature Differential 00.0 C 3.0 C Stops standby units 1 C above setpoint

EVD DRIVER – SUBSECTION


a. CONFIGURATION

TABLE NO. 6. A.
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Enable EEVs Y/N Y
EVD1 Address 000 005 Valve driver 1 address
EVD2 Address 000 006 Valve driver 2 address
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
EVD Driver Only DEFAULT
INSTALLATION
Erase user settings and install Y/N N Set all valve driver setting back to factory default.
global default value
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Valve See Note Carel ExV Electronic valve type
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Main Regulation See Note See Note Sets main regulation for valve
Auxiliary Regulation See Note See Note Sets auxiliary regulation for valve

14
DELTA2 Microprocessor Controller. System Programming Manual.

TABLE NO. 6. A. CONTINUED


19m0

TEXT OPTION FACTORY SET DESCRIPTION


Probe S1 Alarm EN/DIS EN Enable/disable alarm
Type See Note RAZ. 0-5V Type of sensor connected
Min. 0000.0barg 0000.0barg Minimum range of sensor
Max. 0000.0barg 34.5barg Maximum range of sensor
Alarm Min. 0000.0barg 0000.0barg Low alarm threshold
Alarm Max. 0000.0barg 34.5barg High alarm threshold
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Probe S2 Alarm EN/DIS EN Enable/disable alarm
Type See Note NTC Carel NTC Carel /0-10V ext. signal / NTC SPKP**T0 / Carel
NTC-HT
Alarm Min. 000.0°C -50.0°C
Alarm Max. 000.0°C 105.0°C
Screen Ref -7
TEXT OPTION FACTORY SET DESCRIPTION
Probe S3 Alarm EN/DIS EN Enable/disable alarm
Type See Note RAZ. 0-5V RAZ. 0-5V / 4-20mA external / 4-20mA remote / 4-20mA
Min. 0000.0barg 0000.0barg Minimum range of sensor
Max. 0000.0barg 34.5barg Maximum range of sensor
Alarm Min. 0000.0barg 0000.0barg Low alarm threshold
Alarm Max. 0000.0barg 34.5barg High alarm threshold
Screen Ref -8
TEXT OPTION FACTORY SET DESCRIPTION
Probe S4 Alarm EN/DIS EN Enable/disable alarm
Type See Note NTC Carel NTC Carel /0-10V ext. signal / NTC SPKP**T0 / Carel
NTC-HT
Alarm Min. 000.0°C -50.0°C Range of -60°C - 200°C
Alarm Max. 000.0°C 105.0°C Range of -60°C - 200°C
Screen Ref -9
TEXT OPTION FACTORY SET DESCRIPTION
Relay Configuration See Note Disabled Valve position relay / Reversed alarm relay / Valve +
alarm relay / Solenoid valve ready / Alarm relay
Screen Ref -10
TEXT OPTION FACTORY SET DESCRIPTION
ID1 Configuration See Note Reg. Backup Set configuration of driver digital input 1
ID2 Configuration See Note Reg. Backup Set configuration of driver digital input 1
Screen Ref -11
TEXT OPTION FACTORY SET DESCRIPTION
Backup Digital Input Valve A Y/N N
Screen Ref -12
TEXT OPTION FACTORY SET DESCRIPTION
S1 Probe Alarm Manag. See Note No Action / Use backup S3 / Valve at fixed pos. / Valve forced closed
S2 Probe Alarm Manag. See Note No Action / Use backup S4 / Valve at fixed pos. / Valve forced closed
Screen Ref -13
TEXT OPTION FACTORY SET DESCRIPTION
S3 Probe Alarm Manag. See Note No Action / Use backup S3 / Valve at fixed pos. / Valve forced closed
S4 Probe Alarm Manag. See Note No Action / Use backup S3 / Valve at fixed pos. / Valve forced closed
Screen Ref -14
TEXT OPTION FACTORY SET DESCRIPTION
DC Power Supply Y/N N Whether DC power supply is being used.
Screen Ref -15
TEXT OPTION FACTORY SET DESCRIPTION
S3 Probe Alarm Manag. See Note No Action / Valve at fixed pos. / Valve forced closed
S4 Probe Alarm Manag. See Note No Action / Valve at fixed pos. / Valve forced closed

15
DELTA2 Microprocessor Controller. System Programming Manual.

b. REGULATION
TABLE NO. 6. B.
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Valve Opening at Start-Up 000% 80% Open percentage of valve on start up
Delay Comp. Start 00s 00s Delays compressor start until valve opened
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Valve Opened in Stand-By Y/N N Valve open or closed when compressor off
Start-Up Delay after Defrost 00min 10min N/A
Valve Preposition Delay 00000s 6s Time valve remains at preposition before starting
regulation
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
PID Parameters
Prop. Gain 000.0 15.0 Proportional gain for superheat control
Integral Time 0000s 150s Integral time for superheat control
Derivative Time 000.0s 5.0s Derivative time for superheat control
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Integral Time
LowSH Protection 000.0s 10.0s Integral time for low superheat protection
LOP Protection 000.0s 10.0s Integral time for low evaporating pressure protection
MOP Protection 000.0s 20.0s Integral time for high evaporating pressure protection
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Delay
LowSH 00000s 180s Alarm delay low superheat
LOP 00000s 180s Alarm delay low evaporating pressure
MOP 00000 180s Alarm delay high evaporating pressure
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Low Suction Temperature
Threshold 000.0°C -5.0°C Low suction temperature alarm setpoint
Timeout 00000s 180s Alarm delay
Screen Ref -7
TEXT OPTION FACTORY SET DESCRIPTION
Thermoregulation
Setpoint SH 000.0K 10.0K Superheat setpoint
LowSH Threshold 000.0K 2.0K Low superheat threshold
LOP Threshold 000.0°C -5.0°C Minimum evaporating pressure setpoint
MOP Threshold 000.0°C 26.0°C Maximum evaporating pressure setpoint

16
DELTA2 Microprocessor Controller. System Programming Manual.

c. CUSTOM

TABLE NO. 6. C.
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Valve Custom
Min. Steps 00000 50 Minimum valve steps for custom valve
Max. Steps 00000 480 Maximum valve steps for custom valve
Closing Steps 00000 500 Closing steps for custom valve
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Nom. Step Rate 0000Hz 50Hz Nominal step rate
Closing Rate 0000Hz 150Hz Closing step rate
Move Current 000mA 450mA Valve moving current
Holding Current 000mA 100mA Valve holding current
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Duty Cycle 000% 30% Duty cycle of custom valve
Opening Synchr. Y/N Y Opening synchronisation of custom valve
Closing Synchr. Y/N Y Closing synchronisation of custom valve

17
DELTA2 Microprocessor Controller. System Programming Manual.

EC NET –SUBSECTION

TABLE NO. 7
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Fieldbus Config.
Parity See Note None Parity type for fan fieldbus
Stop Bits 1/1.5/2 2 Number of stop bits
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Enable EC Net Y/N Y Enable EC Fan fieldbus
Fan Type Ebm / Ziehl Ziehl Fan manufacturer
Number fans 1/2/3/4 3 Number of fans in unit
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 01
Fan Address 000 001 Address of fan 1
New Parity See Note 8 None 1 New parity of fan 1
New Address 000 000 New address of fan 1
Start Change Y/N N Write new parity and new address to fan 1
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 02
Fan Address 000 002 Address of fan 2
New Parity See Note 8 None 1 New parity of fan 2
New Address 000 000 New address of fan 2
Start Change Y/N N Write new parity and new address to fan 2
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 03
Fan Address 000 003 Address of fan 3
New Parity See Note 8 None 1 New parity of fan 3
New Address 000 000 New address of fan 3
Start Change Y/N N Write new parity and new address to fan 3
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl Fan 04
Fan Address 000 004 Address of fan 4
New Parity See Note 8 None 1 New parity of fan 4
New Address 000 000 New address of fan 4
Start Change Y/N N Write new parity and new address to fan 4
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Ziehl-Abegg
Dir. See Note Clockwise Set fan rotation direction
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Fan Config.
Ebmpapst Fan No.01
Current Address 000 001 Address of fan 1
New Address 000 001 New address of fan 1
Confirm changes Y/N N Write new address to fan

18
DELTA2 Microprocessor Controller. System Programming Manual.

TABLE NO. 7 CONTINUED


Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
Ebmpapst Fan No.01
Communication Param.
Baudrate 00000bps 19200bps New baudrate for fan 1
Parity See Note 8 Even 1 New parity for fan 1
Confirm Y/N See Note Write new communication parameters to fan
Screen Ref – 10
TEXT OPTION FACTORY SET DESCRIPTION
Ebmpapst Fan No.02
Current Address 000 002 Address of fan 2
New Address 000 002 New address of fan 2
Status Offline Offline Write new address to fan
Screen Ref – 11
TEXT OPTION FACTORY SET DESCRIPTION
Ebmpapst Fan No.02
Communication Param.
Baudrate 00000bps 19200bps New baudrate for fan 2
Parity See Note 8 Even 1 New parity for fan 2
Confirm Y/N See Note Write new communication parameters to fan
Screen Ref – 12
TEXT OPTION FACTORY SET DESCRIPTION
Ebmpapst Fan No.03
Current Address 000 003 Address of fan 3
New Address 000 003 New address of fan 3
Status Offline Offline Write new address to fan
Screen Ref – 13
TEXT OPTION FACTORY SET DESCRIPTION
Ebmpapst Fan No.03
Communication Param.
Baudrate 00000bps 19200bps New baudrate for fan 3
Parity See Note 8 Even 1 New parity for fan 3
Confirm Y/N See Note Write new communication parameters to fan
Screen Ref – 14
TEXT OPTION FACTORY SET DESCRIPTION
Ebmpapst Fan No.04
Communication Param.
Baudrate 00000bps 19200bps New baudrate for fan 4
Parity See Note 8 Even 1 New parity for fan 4
Confirm Y/N See Note Write new communication parameters to fan
Screen Ref – 15
TEXT OPTION FACTORY SET DESCRIPTION
Fan Ramps
Ramp-up Time 0000s 30s Ramp up time of fans
Ramp-down time 0000s 30s Ramp down time of fans

19
DELTA2 Microprocessor Controller. System Programming Manual.

TIMING – SUBSECTION
Table No. 8
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Time Delay
Fan Start 000 Sec 1 Sec Main fan start up delay time.
Fan Stop 000 Sec 20 Sec Main fan off delay time.
Device 000 Sec 20 Sec Settle Timer - delays all components on start except fan
EC Fan (Y3) 0000 Sec 0 Sec Delays activation of EC Fan output
Screen Ref –2
TEXT OPTION FACTORY SET DESCRIPTION
PID Timing – Temp. PID timing setup for temperature control
Integral Time 0000 Sec 600 Sec Integration time for P+I \ PID control.
Derivative Time 0000 Sec 0 Sec Derivative time for PID control. Must be set for proper
operation.
PID Timing – H. Pressure PID timing setup for head pressure control
Integral Time 0000 Sec 60 Sec Integration time for P+I \ PID control.
Derivative Time 0000 Sec 25 Sec Derivative time for PID control. Must be set for proper
operation.
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Delay Loss of Airflow Alarm
On Start 0000s 50s Alarm delay on unit start
Running 00s 10s Alarm delay during operation
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Delay Alarm Low/High Temp/Hum 0000 Sec 600 Sec Temperature & humidity alarm time delays
Delay Loss of Water Flow Alarm 000 Sec 10 Sec Loss of water flow alarm delay
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Delay Serious Alarm Output 000 Sec 0 Sec Serious alarm time delay
Delay Non-Serious Alarm Output 000 Sec 0 Sec Non serious alarm time delay
Heater Inter Stage Delay 0000 Sec 3 Sec Heater inter stage delay
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Compressor Timing
Min Off Time 0000 Sec 180 Sec Defines minimum compressor on time
Min On Time 0000 Sec 60 Sec Defines minimum compressor off time
Start Delay Same Compressor 0000 Sec 360 Sec Defines start delay of the same compressor
Compressor Inter Stage Delay 0000 Sec 10 Sec Defines an inter stage delay for twin compressors
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Winter Start Over-ride LP Alarm 000s 180s LP switch time delay for winter start
Delay
Running LP Delay 00s 00s Alarm delay during compressor operation

20
DELTA2 Microprocessor Controller. System Programming Manual.

INITIALIZATION – SUBSECTION
Table No. 9
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Default Installation
Erase User Settings & Install Global Y/N N Reset all setting to factory default
Default Value
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
New Manufacturers Password 0000 N/A Allows manufacturers password to be changed

Notes
1. Great care must be exercised in this section as using this will reload the factory settings but the unit must then
be re-configured to reflect the installed options. Default DX unit is a single circuit DX unit with 2 stage heating
& Default CW unit is a CW unit with 0-10V valve with 2 stage heating .

21
DELTA2 Microprocessor Controller. System Programming Manual.

USER SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to USER. This section is password protected and the relevant password is required for access to some
screens. To enter the password the “up” and “down” & “enter” arrow keys are used.

The user’s part of the program is subdivided into 8 distinct sections as outlined below. Each section
will be examined separately. Sections are:

UNIT ON/OFF CONTROL


TEMPERATURE CONTROL
HUMIDITY CONTROL
EC FAN
ALARMS
B.M.S (SUPERVISOR)
FORCE AOUT

UNIT ON/OFF CONTROL – SUBSECTION

TABLE NO. 10
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Enable On/Off Keyboard Y/N Y Enables or disables on/off at display
Enable On/Off by Remote Input Y/N Y Enable on/off by remote digital input
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Auto Restart After Power Failure Y/N Y Enables auto restart of unit after power failure
Auto Restart After Fire Alarm Y/N N Enables auto restart after fire alarm

TEMPERATURE CONTROL – SUBSECTION


Table No. 11
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Temp. Setpoint Limits
Min. 00.0°C 16.0 C Minimum allowable temperature setpoint value entered.
Max. 00.0°C 26.0 C Maximum allowable temperature setpoint value entered.
Temp. Control Bands
Cooling Band 00.0°C See Note 02.0 C DX Units & 01.7 C CW & Freecooling Units
Heating Band 00.0°C See Note 02.0 C DX Units & 01.7 C CW & Freecooling Units
Neutral Zone 00.0°C See Note 00.0 C DX Units & 00.3 C CW & Freecooling Units

22
DELTA2 Microprocessor Controller. System Programming Manual.

Table No. 11 continued


Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
0-10V Output Limits
Y1 (Cooling Output)
Min Output 00.0-10.0V 00.0V Minimum cooling output voltage
Max Output 00.0-10.0V 10.0V Maximum cooling output voltage
Y2 (Heating Output)
Min Output 00.0-10.0V 00.0V Minimum heating output voltage
Max Output 00.0-10.0V 10.0V Maximum heating output voltage
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
ECXV Output Limits (Freecooling)
Min Output 00.0-10.0V 00.0V Minimum freecooling output voltage
Max Output 00.0-10.0V 10.0V Maximum freecooling output voltage
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Freecooling Control
Diff Air/Water Start Freecooling 00.0°C 5.0 or 14.0 C See notes 2 – 4 at end of this table
Diff Air/Water Stop Freecooling 00.0°C 4.5 or 13.5 C See notes 2 – 4 at end of this table
Diff RA above Setpoint to Start 00.0 C 0.5 C Sets the temperature above setpoint that the return air has to
Freecooling be before freecooling can take place
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Enable Adaptive Control Y/N N Enable adaptive freecooling control
Req. Delta for Nominal Capacity 00.0°C 12.0°C Require temperature difference to meet nominal unit
capacity
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
High Temp. Disable
Enable Y/N See Note Enable disable of freecooling on high temperature
Offset 00.0°C 3.0°C High temperature offset
Differential 00.0°C 2.0°C High temperature differential
Delay 000min 002min Delay before disable of freecooling
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Enable Enthalpy Limit Y/N See Note Enable disable of freecooling based on external air enthalpy
Low Limit 00.0g/kg 6.9g/kg Low limit on external enthalpy
High Limit 00.0g/kg 7.8g/kg High limit on external enthalpy
Diff 0.0g/kg 0.2g/kg Deferential
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Supply Air Temperature Limit
Enable Y/N See Note Enable supply air low temperature limit
Setpoint 00.0°C 12.0°C Low temperature limit setpoint
Offset 00.0°C 05.0°C Low temperature limit offset

Notes
1. If Freecooling unit is selected as Freecooling with Compressors (Parameters Screen 1) then Freecooling will
be enabled when the water is 5.0 C below the Return Air Temperature and will stop again when water rises to
4.5 C below Return Air Temperature
2. If Freecooling unit is selected as Freecooling without Compressors (Parameters Screen 1) then Freecooling
will be enabled when the water is 14.0 C below the Return Air Temperature and will stop again when water
rises to 13.5 C below Return Air Temperature
3. Values noted in notes 1 & 2 are user adjustable.

23
DELTA2 Microprocessor Controller. System Programming Manual.

HUMIDITY CONTROL – SUBSECTION

Table No. 12
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Humid Setpoint Limits
Min 000.0% 35.0% Minimum allowable humidity setpoint value entered.
Max 000.0% 65.0% Maximum allowable humidity setpoint value entered.
Humid Control Bands
Control Band 00.0% 5.0% Control humidity band
Neutral Zone 00.0% 1.0% Control humidity neutral zone
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Humidifier Output Limit 00.0kg/hr See Note Depends on size of unit. (ST & LT humidifiers only)
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Limit Humidifier Production 000% See Note Depends on size of unit. (KUE humidifiers only)
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Dehumidification Valve Limit CW Chill water value dehumidification settings
Value
Low Limit 0.00V 10.00V Minimum chill water valve output during dehum
High Limit 0.00V 10.00V Maximum chill water valve output during dehum
Dehumidification Valve Limit ECX Freecooling water valve dehumidification settings
Value
Low Limit 0.00V 10.00V Minimum ECXV output during dehum
High Limit 0.00V 10.00V Maximum ECXV output during dehum
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Dryer Output Limits
Min Output 0.00V 00.00V Minimum dryer output voltage (Proportional dryer only)
Max Output 0.00V 10.00V Maximum dryer output voltage (Proportional dryer only)

24
DELTA2 Microprocessor Controller. System Programming Manual.

EC FAN – SUBSECTION
Table No. 13
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 1 Fixed Fan Speed
Voltage 00.0V See Note Sets the fixed speed of the EC Fan
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 2 Select Probe for
RA/SA RA Select for temperature control on return air or supply air
Temperature Regulation
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Operational Range Voltage
Cooling Min 00.0V 5.0V Minimum fan speed in cooling
Cooling Max 00.0V 10.0V Maximum fan speed in cooling
Heating Max 00.0V 5.0V Minimum fan speed in heating
Heating Min 00.0V 10.0V Maximum fan speed in heating
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Setpoint 00.0°C 22.0°C Temperature setpoint for control (only if control sensor is
different to normal regulation)
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 3 Air Pressure
Setpoint 0000Pa 50Pa Air pressure setpoint
Deadband 000Pa 10Pa Range plus or minus from setpoint where fan speed
remains constant
Operational Range
Voltage Min 00.0V 5.0V Minimum fan output voltage
Voltage Max 00.0V 10.0V Maximum fan output voltage
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 4 Operational Range
Voltage Min 00.0V 5.0V Minimum fan output voltage
Voltage Max 00.0V 10.0V Maximum fan output voltage
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Strategy 5 Unit Airflow
Setpoint 000000m3/hr 0m3/hr Airflow setpoint
Deadband 0000m3/hr 400m3/hr Range plus or minus from setpoint where fan speed
remains constant
Operational Range
Voltage Min 00.0V 5.0V Minimum fan output voltage
Voltage Max 00.0V 10.0V Maximum fan output voltage
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan De-Hum Fan Speed
Voltage 00.0V 6.0V Fan output voltage in dehum (must be enabled in
manufacturer first)

25
DELTA2 Microprocessor Controller. System Programming Manual.

ALARMS – SUBSECTION
Table No. 14
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Temperature Alarm - Low Offset 00.0 C 6.0 C Room low temperature alarm offset from setpoint.
Temperature Alarm - High Offset 00.0 C 6.0 C Room high temperature alarm offset from setpoint.
Humidity Alarm - Low Offset 000.0 % 20.0 % Room low humidity alarm offset from setpoint.
Humidity Alarm - High Offset 000.0 % 20.0 % Room high humidity alarm offset from setpoint.
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Entering Water
Temp Alarm Low 00.0 C -5.0 C Entering water low temp alarm threshold
Temp Alarm High 00.0 C 45.0 C Entering water high temp alarm threshold
Outlet Water
Temp Alarm Low 00.0 C -5.0 C Outlet water low temp alarm threshold
Temp Alarm High 00.0 C 45.0 C Outlet water high temp alarm threshold
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Low Press. Set 00.0bar 2.5bar Low pressure alarm setpoint
Hysteresis 00.0bar 1.0bar Low pressure alarm hysteresis for cut-in
Max Restarts 0-9 4 Number of attempted compressor restarts
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 01-18
Screen Ref – 5
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 19-36
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 37-54
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 55-72
Screen Ref – 8
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 73-91
Screen Ref – 9
TEXT OPTION FACTORY SET DESCRIPTION
Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 92-102

26
DELTA2 Microprocessor Controller. System Programming Manual.

B.M.S (SUPERVISOR) – SUBSECTION

Table No. 15
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
BMS1 Plug-In Card
Address 000 001 Address of unit in BMS 1 communication network
Protocol See Note BACnet Protocol type of BMS 1 connection
MSTP
Comm. Speed 00000bps 19200bps Baud rate of BMS 1 connection
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Parity See Note None Parity of BMS 1 connection
Stop Bits 1/2 2 Number of stop bits for BMS 1 connection
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
BMS2 Built-In RS485
Address 000 001 Addresses of unit in BMS 2 communication network
Protocol Modbus RTU Modbus RTU Protocol (Modbus RTU only0
Comm. Speed 00000bps 19200bps Baud rate of BMS 2 connection
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
BMS2 Built-In RS485
Parity See Note None Parity of BMS 2 connection
Stop Bits 1/2 2 Number of stop bits for BMS 2 connection

FORCE AOUT – SUBSECTION

Table No. 16
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Force Analogue Output Y4 Fresh Air /
Freecool
Y4 Enable Y/N N To Force Analogue Output Y4
Output Voltage 00.0V 10.0V Can be set from 00.0V to 10.0V
Force Analogue Output Y2 0-10V Prop
Heat
Y2 Enable Y/N N To Force Analogue Output Y2 Prop Heat
Output Voltage 00.0V 10.0V Can be set from 00.0V to 10.0V

27
DELTA2 Microprocessor Controller. System Programming Manual.

MAINTENANCE SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to MAINTENANCE. This section is password protected and the relevant password is required for
access to some screens. To enter the password the “up” and “down” & “enter” arrow keys are used.
The maintenance part of the program is subdivided into 6 distinct sections as outlined below. Each
section will be examined separately. Sections are:

RUN HOURS
ALARM LOG
RESET RUN HOURS
SENSOR CALIBRATION
MANUAL PROCEDURE
HUMIDIFIER

RUN HOURS – SUBSECTION

TABLE NO. 17
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Run Hours
Fan 0000 N/A Gives Fan Run Hours
Compressor 1 0000 N/A Gives Compressor 1 Run Hours
Compressor 2 0000 N/A Gives Compressor 2 Run Hours
Freecooling 0000 N/A Gives Freecooling Run Hours
0-10V Cooling 0000 N/A Gives 0-10V Cooling Run Hours
0-10V Heating 0000 N/A Gives 0-10V Heating Run Hours
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Run Hours
Heater 1 0000 N/A Gives Humidifier Run Hours
Heater 2 0000 N/A Gives Dehumidification Run Hours
Humidifier 0000 N/A Gives Heater 1 Run Hours
Dehumidify 0000 N/A Gives Heater 2 Run Hours

ALARM LOG – SUBSECTION


Table No. 18
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Alarm History N/A N/A Press Alarm Button to view Alarm History

28
DELTA2 Microprocessor Controller. System Programming Manual.

ADJUST RUN HOURS – SUBSECTION


Table No. 19
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Fan Hours Alarm Threshold 000 x 000 200 x 1000 Fan Run Hours Alarm Threshold
Reset 000000 N/A Reset of Run Hours Fan
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Comp 1 Hours Alarm Threshold 00 x 000 100 x 1000 Compressor 1 Run Hours Alarm Threshold
Reset 000000 N/A Reset of Run Hours Compressor 1
Comp 2 Hours Alarm Threshold 00 x 000 100 x 1000 Compressor 2 Run Hours Alarm Threshold
Reset 000000 N/A Reset of Run Hours Compressor 1
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Reset Hours
Heater 1 Y/N N Heater 1 Run Hours Reset
Heater 2 Y/N N Heater 2 Run Hours Reset
Humidify Y/N N Humidifier Run Hours Reset
Dehum. Y/N N Dehumidification Run Hours Reset
Freecool Y/N N Freecooling Run Hours Reset
0-10V Cool Y/N N 0-10V Cooling Run Hours Reset
0-10V Heat Y/N N 0-10V Heating Run Hours Reset

SENSOR CALIBRATION – SUBSECTION


Table No. 20
Screen Ref –1
TEXT OPTION FACTORY SET DESCRIPTION
Offset
Return Air +/-9.9°C 00.0°C Allows Sensor Recalibration. +/- 9.9°C Available
Humidity +/-9.9 % 0.0% Allows Sensor Recalibration. +/- 9.9 % Available
Supply Air +/-9.9°C 00.0°C Allows Sensor Recalibration. +/- 9.9°C Available
Water Inlet +/-9.9°C 00.0°C Allows Sensor Recalibration. +/- 9.9°C Available
Screen Ref – 2
TEXT OPTION FACTORY SET DESCRIPTION
Offset
External Air +/-9.9°C 00.0°C Allows Sensor Recalibration. +/- 9.9°C Available
Water Outlet +/-9.9°C 00.0°C Allows Sensor Recalibration. +/- 9.9°C Available
Air Pressure +/-9.9 Pa 00.0 Pa Allows Sensor Recalibration. +/- 9.9 Pa Available
Head Press. C1 +/-9.9 bar 0.0bar Allows Sensor Recalibration. +/- 9.9 bar Available
Head Press. C2 +/-9.9 bar 0.0bar Allows Sensor Recalibration. +/- 9.9 bar Available
Screen Ref – 3
TEXT OPTION FACTORY SET DESCRIPTION
Probe Adjust. EVO No.01
S1 Offset 000.0barg 000.0barg Allows Sensor Recalibration. EVD Driver 1
S1 Probe 0000.0barg See note Active readout of sensor value. EVD Driver 1
S2 Offset 00.0°C 00.0°C Allows Sensor Recalibration. EVD Driver 1
S2 Probe 0000.0°C See note Active readout of sensor value. EVD Driver 1
Screen Ref – 4
TEXT OPTION FACTORY SET DESCRIPTION
Probe Adjust. EVO No.01
S3 Offset 000.0barg 000.0barg Allows Sensor Recalibration. EVD Driver 1
S3 Probe 0000.0barg See note Active readout of sensor value. EVD Driver 1
S4 Offset 00.0°C 00.0°C Allows Sensor Recalibration. EVD Driver 1
S4 Probe 0000.0°C See note Active readout of sensor value. EVD Driver 1

29
DELTA2 Microprocessor Controller. System Programming Manual.

Table No. 20 continued


Screen Ref –5
TEXT OPTION FACTORY SET DESCRIPTION
Probe Adjust. EVO No.02
S1 Offset 000.0barg 000.0barg Allows Sensor Recalibration. EVD Driver 2
S1 Probe 0000.0barg See note Active readout of sensor value. EVD Driver 2
S2 Offset 00.0°C 00.0°C Allows Sensor Recalibration. EVD Driver 2
S2 Probe 0000.0°C See note Active readout of sensor value. EVD Driver 2
Screen Ref – 6
TEXT OPTION FACTORY SET DESCRIPTION
Probe Adjust. EVO No.02
S3 Offset 000.0barg 000.0barg Allows Sensor Recalibration. EVD Driver 2
S3 Probe 0000.0barg See note Active readout of sensor value. EVD Driver 2
S4 Offset 00.0°C 00.0°C Allows Sensor Recalibration. EVD Driver 2
S4 Probe 0000.0°C See note Active readout of sensor value. EVD Driver 2

30
DELTA2 Microprocessor Controller. System Programming Manual.

MANUAL PROCEDURE – SUBSECTION


Table No. 21
Screen Ref –1
TEXT OPTION FACTORY SET DESCRIPTION
Fan (Master) Y/N N Allows Manual Running of Fan ( Master Fan)
Fan (Slave) Y/N N Allows Manual Running of Fan ( Slave Fan )
Compressor 1 Y/N N Allows Manual Running of Compressor 1
Compressor 2 Y/N N Allows Manual Running of Compressor 2
Heater 1 Y/N N Allows Manual Running of Heater 1
Heater 2 Y/N N Allows Manual Running of Heater 2
Dryer - - Allows Manual Running of Dryer
Screen Ref –2
TEXT OPTION FACTORY SET DESCRIPTION
Condenser 1 0.00V 00.0V Gives manual signal to fan speed controller 1
Condenser 2 0.00V 00.0V Gives manual signal to fan speed controller 2
Screen Ref –3
TEXT OPTION FACTORY SET DESCRIPTION
Alarm Outputs
Non Serious Y/N N Allows proving of Non Serious Alarm Output
Serious Y/N N Allows proving of Serious Alarm Output
Screen Ref –4
TEXT OPTION FACTORY SET DESCRIPTION
Compressor VSD Output
Enable Y/N N Enable manual compressor VSD output voltage
Output 00.0V 00.0V Gives manual signal to compressor VSD
Screen Ref –5
TEXT OPTION FACTORY SET DESCRIPTION
Cool 00.0V See Note Gives manual signal to cooling valve
Heat 00.0V See Note Gives manual signal to heating valve
EC Fan 00.0V See Note Gives manual signal to EC fan
ECXV 00.0V See Note Gives manual signal to freecooling valve/damper
Screen Ref –6
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.01
Enable Manual Valve Position Y/N N Enable manual position of electronic valve 1
Manual Valve Position 00000stp See Note Set manual valve position
Screen Ref –7
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.02
Enable Manual Valve Position Y/N N Enable manual position of electronic valve 2
Manual Valve Position 00000stp See Note Set manual valve position

31
DELTA2 Microprocessor Controller. System Programming Manual.

HUMIDIFIER – SUBSECTION

Table No. 22
Screen Ref – 1
TEXT OPTION FACTORY SET DESCRIPTION
Auto Drain Enable Y/N N To enable additional automatic humidifier drain
Drain Interval 00Hr 05Hr From 00 to 99Hr
Drain Length 000Sec 120Sec From 000 to 240Sec
Disable Humidifier Y/N N Allows Disabling of Humidifier
Manual Drain Y/N N Allows Manual Humidifier Drain of 120 Seconds
Screen Ref –2 (KUE Humidifier Only)
TEXT OPTION FACTORY SET DESCRIPTION
Change Cylinder
Empty Cylinder Y/N N Manually drains the humidifier cylinder
Flush new Cylinder Y/N N Performs 15min wash cycle on new cylinder

32
DELTA2 Microprocessor Controller. System Programming Manual.

INPUTS / OUTPUTS SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to INPUTS / OUTPUTS. This section is not password protected.

TABLE NO. 23
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Return Air Temperature N/A N/A Active Readout of I/O
Return Air Humidity N/A N/A Active Readout of I/O
Supply Air Temperature N/A N/A Active Readout of I/O
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Analog Inputs
Water Inlet N/A N/A Active Readout of I/O
Water Outlet N/A N/A Active Readout of I/O
External Air N/A N/A Active Readout of I/O
Air Pressure N/A N/A Active Readout of I/O
Airflow N/A N/A Active Readout of I/O
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
External humid. N/A N/A Active Readout of I/O
External Air Absolute Humidity N/A N/A Active Readout of I/O
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Head Pressure Control
Circuit 1 HP N/A N/A Active Readout of I/O
Circuit 2 HP N/A N/A Active Readout of I/O
Condenser 1 N/A N/A Active Readout of I/O
Condenser 2 N/A N/A Active Readout of I/O
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Digital Inputs N/A N/A Active Readout of I/O
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Digital Inputs N/A N/A Active Readout of I/O
Digital Outputs N/A N/A Active Readout of I/O
Screen Ref -7
TEXT OPTION FACTORY SET DESCRIPTION
Analog Outputs
Y1: Heat N/A N/A Active Readout of I/O
Y2: Heat N/A N/A Active Readout of I/O
Y3: EC Fan N/A N/A Active Readout of I/O
Y4: Freecooling N/A N/A Active Readout of I/O
Y5: SPARE N/A N/A Active Readout of I/O
Screen Ref -8
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Status
Speed Request N/A N/A Active Readout of I/O
Motor 1 Speed N/A N/A Active Readout of I/O
Screen Ref -9
TEXT OPTION FACTORY SET DESCRIPTION
EC Fan Status
Speed Request N/A N/A Active Readout of I/O
Motor 1 Speed N/A N/A Active Readout of I/O
Motor 2 Speed N/A N/A Active Readout of I/O
Motor 3 Speed N/A N/A Active Readout of I/O

33
DELTA2 Microprocessor Controller. System Programming Manual.

TABLE NO. 23 CONTINUED


Screen Ref -10
TEXT OPTION FACTORY SET DESCRIPTION
Digital Outputs N/A N/A Active Readout of I/O
Screen Ref -11
TEXT OPTION FACTORY SET DESCRIPTION
Humidifier
Hum Contactor N/A N/A Active Readout of I/O
Fill Valve N/A N/A Active Readout of I/O
Drain Valve N/A N/A Active Readout of I/O
Water Level N/A N/A Active Readout of I/O
Elec. Cond. N/A N/A Active Readout of I/O
Production N/A N/A Active Readout of I/O
Screen Ref -12
TEXT OPTION FACTORY SET DESCRIPTION
Humidifier - Current
Measured N/A N/A Active Readout of Current
Target N/A N/A Active Readout of Current
Nominal N/A N/A Active Readout of Current
Humidifier Cylinder Worn N/A N/A Yes or No
Humidifier Cylinder Mode N/A N/A Start, Run, Full, Foam, Low Current & High Current
Humidifier Cylinder Status N/A N/A Evaporating, Draining, Filling
Screen Ref -13 (KUE Type Only)
TEXT OPTION FACTORY SET DESCRIPTION
Humidifier Measured Current N/A N/A Active Readout of Current
Humidifier Rated Current N/A N/A Active Readout of Current
TAM Full Scale Reading N/A N/A Active Readout of Current
Humidifier Status N/A N/A Status of humidifier
Humidifier Activity N/A N/A Current humidifier function
Screen Ref -13
TEXT OPTION FACTORY SET DESCRIPTION
Software Info
Perm Memory Write Cycles (00) N/A N/A Active Readout of I/O
Application Cycle Time N/A N/A Active Readout of I/O
Screen Ref -14
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.01 N/A N/A Active Readout of I/O
Valve Status N/A N/A Active Readout of I/O
Valve Opening N/A N/A Active Readout of I/O
Valve Positions N/A N/A Active Readout of I/O
Cool Capacity N/A N/A Active Readout of I/O
Superheat N/A N/A Active Readout of I/O
Screen Ref -15
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.01 N/A N/A Active Readout of I/O
Discharge SH N/A N/A Active Readout of I/O
Disch. SH Set N/A N/A Active Readout of I/O
Disch. Temp N/A N/A Active Readout of I/O
Disch. Temp Set N/A N/A Active Readout of I/O
Screen Ref -16
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.01 Digital Input Status
DI1 N/A N/A Active Readout of I/O
DI2 N/A N/A Active Readout of I/O

34
DELTA2 Microprocessor Controller. System Programming Manual.

TABLE NO. 23 CONTINUED


Screen Ref -17
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.02 N/A N/A Active Readout of I/O
Valve Status N/A N/A Active Readout of I/O
Valve Opening N/A N/A Active Readout of I/O
Valve Positions N/A N/A Active Readout of I/O
Cool Capacity N/A N/A Active Readout of I/O
Superheat N/A N/A Active Readout of I/O
Screen Ref -18
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.02 N/A N/A Active Readout of I/O
Discharge SH N/A N/A Active Readout of I/O
Disch. SH Set N/A N/A Active Readout of I/O
Disch. Temp N/A N/A Active Readout of I/O
Disch. Temp Set N/A N/A Active Readout of I/O
Screen Ref -19
TEXT OPTION FACTORY SET DESCRIPTION
EVO No.02 Digital Input Status
DI1 N/A N/A Active Readout of I/O
DI2 N/A N/A Active Readout of I/O

35
DELTA2 Microprocessor Controller. System Programming Manual.

CLOCK SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until
you get to CLOCK. This section is password protected and the relevant password is required for access to
some screens. To enter the password the “up” and “down” & “enter” arrow keys are used.

TABLE NO.24
Screen Ref -1
TEXT OPTION FACTORY SET DESCRIPTION
Regulation Clock
Hour See Note See Note Sets Clock Hours & Minutes
Date See Note See Note Sets Clock Date in format MM/DD/YY
Day See Note See Note Mo, Tu, We, Th, Fr, Sa, Su
Screen Ref -2
TEXT OPTION FACTORY SET DESCRIPTION
Clock Password 0000 0000 Password Required
Screen Ref -3
TEXT OPTION FACTORY SET DESCRIPTION
Enable Auto Temp Set Point Variation Y/N N Enables Automatic Temperature Set Point Variation
Screen Ref -4
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 1 – Start Hour 00.00 00.00 Time Zone No. 1 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 1 Temperature Set Point
Screen Ref -5
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 2 – Start Hour 00.00 00.00 Time Zone No. 2 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 2 Temperature Set Point
Screen Ref -6
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 3 – Start Hour 00.00 00.00 Time Zone No. 3 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 3 Temperature Set Point
Screen Ref – 7
TEXT OPTION FACTORY SET DESCRIPTION
Time Zone N. 4 – Start Hour 00.00 00.00 Time Zone No. 4 Temperature Set Point Start Hour
Temperature Set Point 00.0 C 00.0 C Time Zone No. 4 Temperature Set Point

36
DELTA2 Microprocessor Controller. System Programming Manual.

ALARMS SECTION
Notes:
1. All alarms can be set as serious or non-serious in the user section of the controller. All serious alarms will
shut down the unit
2. A05 & A09 are deemed serious alarms by default. A05 can be changed by the user.
3. A06 is deemed non-serious by default to keep a slave module of a duplex unit running in the event of a master
air flow alarm. This is only when A05 is set as a non-serious alarm.
4. A35 & A08 will always disable the Humidifier whether set as serious or non-serious.
5. A36, if set in unit configuration as glycol will stop compressors and close all water valves. If set as dual
cooling will close water valves and leave compressors running.
6. A39 indicates a fault detected in the controllers permanent memory during start up. Should this alarm occur
please refer to factory for further support.
7. There may also be some additional alarms which are order specific.

ALARM LIST
AL 01 Compressor 1 HP / Thermal Overload
AL 02 Compressor 2 HP / Thermal Overload
AL 03 Compressor 1 LP
AL 04 Compressor 2 LP
AL 05 Air Flow Alarm (Serious Alarm)
AL 06 Air Flow Alarm – Slave
AL 07 Alarm Electric Reheat High Temp Trip
AL 08 Condensate Pump / High Water Level
AL 09 Smoke/Fire (Serious Alarm)
AL 10 Alarm Air Filter
AL 11 High Temperature Alarm
AL 12 Low Temperature Alarm
AL 13 High Humidity Alarm
AL 14 Low Humidity Alarm
AL 15 High Entering Water Temperature
AL 16 Low Entering Water Temperature
AL 17 Compressor 1 Run Hours
AL 18 Compressor 2 Run Hours
AL 19 Fan Run Hours
AL 20 Return Air Temperature Probe Fault Or Offline
AL 21 Entering Water Temperature Probe Fault Or Offline
AL 22 External Air Temperature Probe Fault Or Offline
AL 23 Supply Air Temperature Probe Fault Or Offline
AL 24 Return Air Humidity Probe Fault Or Offline
AL 25 Leaving Water Temperature Probe Fault Or Offline
AL 26 High Leaving Water Temperature
AL 27 Low Leaving Water Temperature
AL 28 High Current Into Humidifier
AL 29 Lack Of Water Into Humidifier
AL 30 Lack Of Current Into Humidifier
AL 31 Humidifier Low Production
AL 32 Humidifier Drain Alarm
AL 33 Humidifier Water Conductivity High - Warning
AL 34 Humidifier Water Conductivity High – Alarm
AL 35 Water Under Floor
AL 36 Loss of Water Flow Alarm
AL 37 Air Pressure Probe Fault or Offline
AL 38 Circuit 1 High Pressure Sensor Fault / Offline
AL 39 Circuit 2 High Pressure Sensor Fault / Offline

37
DELTA2 Microprocessor Controller. System Programming Manual.

ALARM LIST CONTINUED


AL 40 Alarm Dryer
AL 41 Clock Alarm
AL 42 Permanent Memory Read/Write Error (Contact Factory)
AL 43 EC Fan Fault or Offline
AL 44 Alarms EVO n1 - EEV Motor Error
AL 45 Alarms EVO n1 - MOP (high temperature of evaporation)
AL 46 Alarms EVO n1 - LOP (low temperature of evaporation)
AL 47 Alarms EVO n1 - Low superheat alarm
AL 48 Alarms EVO n1 - Low suction temperature
AL 49 Alarms EVO n1 - High condensing temperature
AL 50 Alarms EVO n1 - EEPROM error alarm
AL 51 Alarms EVO n1 - EEV probe S1 fault
AL 52 Alarms EVO n1 - EEV probe S2 fault
AL 53 Alarms EVO n1 - EEV probe S3 fault
AL 54 Alarms EVO n1 - EEV probe S4 fault
AL 55 Alarms EVO n1 - EEV driver offline
AL 56 Alarms EVO n1 - EEV driver battery discharged
AL 57 Alarms EVO n2 - EEV Motor Error
AL 58 Alarms EVO n2 - MOP (high temperature of evaporation)
AL 59 Alarms EVO n2 - LOP (low temperature of evaporation)
AL60 Alarms EVO n2 - Low superheat alarm
AL 61 Alarms EVO n2 - Low suction temperature
AL 62 Alarms EVO n2 - High condensing temperature
AL 63 Alarms EVO n2 - EEPROM error alarm
AL 64 Alarms EVO n2 - EEV probe S1 fault
AL 65 Alarms EVO n2 - EEV probe S2 fault
AL 66 Alarms EVO n2 - EEV probe S3 fault
AL 67 Alarms EVO n2 - EEV probe S4 fault
AL 68 Alarms EVO n2 - EEV driver offline
AL 69 Alarms EVO n2 - EEV driver battery discharged
AL 70 Alarm Compressor 1 VSD
AL 71 Alarm Compressor 2 VSD
AL 72 Alarms Probe B00 External humidity fault
AL 73 Alarm External smoke alarm (Freecooling disabled)
AL 74 Alarm Ziehl-Abegg fan n1
AL 75 Warning Ziehl-Abegg fan n1
AL 76 Alarm Ziehl-Abegg fan n1 Offline
AL 77 Alarm Ziehl-Abegg fan n2
AL 78 Warning Ziehl-Abegg fan n2
AL 79 Alarm Ziehl-Abegg fan n2 Offline
AL 80 Alarm Ziehl-Abegg fan n3
AL 81 Warning Ziehl-Abegg fan n3
AL 82 Alarm Ziehl-Abegg fan n3 Offline
AL 83 Alarm Ziehl-Abegg fan n4
AL 84 Warning Ziehl-Abegg fan n4
AL 85 Alarm Ziehl-Abegg fan n4 Offline
AL 86 Alarm Ebmpapst fan n1
AL 87 Warning Ebmpapst fan n1
AL 88 Alarm Ebmpapst fan n1 Offline
AL 89 Alarm Ebmpapst fan n2
AL 90 Warning Ebmpapst fan n2
AL 91 Alarm Ebmpapst fan n2 Offline
AL 92 Alarm Ebmpapst fan n3
AL 93 Warning Ebmpapst fan n3

38
DELTA2 Microprocessor Controller. System Programming Manual.

ALARM LIST CONTINUED


AL 94 Alarm Ebmpapst fan n3 Offline
AL 95 Alarm Ebmpapst fan n4
AL 96 Warning Ebmpapst fan n4
AL 97 Alarm Ebmpapst fan n4 Offline
AL 98 Analog outputs incorrectly configured check unit config.
AL 99 Alarm Refrigerant leak
AL 100 Low pressure circuit 1 (transducer)
AL 101 Low pressure circuit 2 (transducer)
AL 102 Phase rotation alarm
AL 103 High pressure prevent active. Compressor capacity reduced
Notes:

39