Data Sheet: Diesel Generator 26Kw 50HZ/1500RPM PERKINS MODEL: 1103A-33G
Data Sheet: Diesel Generator 26Kw 50HZ/1500RPM PERKINS MODEL: 1103A-33G
, LTD
GUANGZHOU SANQ DIESEL GENERATOR SET CO., LTD
Tel:86-13729889887 Fax:86-20-84550026
Web: www.fdkenergy.com Email: [email protected]
DATA SHEET
DIESEL GENERATOR 26KW
MODEL#FDK-P26/H1
50HZ/1500RPM
PERKINS MODEL: 1103A-33G
General Features:
All qualified generator sets are subjected to a comprehensive performance test which includes 50% load, 70% load, 100%
load, 110% load and to check, verify that all control systems, alarm and shut-down protection.
Equipped with battery charger and 24V high performance maintenance-free lead-acid starting batteries and connecting
cables.
Stainless galvanized zinc plates with strong corrosion-proof.
Vibration isolators between the engine/alternator and base frame.
Equipped with industrial silencer and flexible exhaust hose.
Designed to comply with ISO8528/GB2820.
Powered by Perkins engine and coupled with Stamford alternator.
Water jacket preheater, oil heater and double air cleaner, etc. are available.
(1) Prime power: The rating is available for an unlimited of annual operating hours in variable load applications, in accordance with
ISO8528-1.A 10% overload is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1.
(2) Standby power: The rating is applicable for supplying emergency power in variable load applications for up to 200 hours per year in
ISO9001:2008 FDK reserves the right to change the specifications and designs without noice.
www.fdkenergy.com
SHENZHEN FUDIANKANG ENERGY CO., LTD
GUANGZHOU SANQ DIESEL GENERATOR SET CO., LTD
Tel:86-13729889887 Fax:86-20-84550026
Web: www.fdkenergy.com Email: [email protected]
Piston Speed 6.35m/s Fuel Consumption at 100% load 7.1 L
Typical genset electrical output (0,8 pf 24kw (L/HOUR)
25°C) Starter motor 12V
Alternator Specifications
Alternator model PI124F Number of phase 3
Alternator manufacturer STAMFORD Rated voltage 400V (Available with
Exciter type Single bearing, Brushless, custom requirements)
Self-excited Power factor 0.8
ISO9001:2008 FDK reserves the right to change the specifications and designs without noice.
www.fdkenergy.com
SHENZHEN FUDIANKANG ENERGY CO., LTD
GUANGZHOU SANQ DIESEL GENERATOR SET CO., LTD
Tel:86-13729889887 Fax:86-20-84550026
Web: www.fdkenergy.com Email: [email protected]
Optional
Generator set Alternator Low environment Temp ATS
Open generator set Stamford Water heater CHINT
Silent generator set Marathon Oil heater SCHNEIDER
Trailer generator set Mecc Alte Battery heater ABB
ABB MCCB circuit breaker Leroy Somer
Farady
Engga
Sales Promises
FDK provides a full line of brand new and high quality products. Each and every unit is strictly factory tested before
shipment.
Quality warranty is according to our standard conditions: 12 months from BL date or 1000 running hours, whichever comes
first.
Service and parts are available from FDK or distributors in your location.
ISO9001:2008 FDK reserves the right to change the specifications and designs without noice.
www.fdkenergy.com
@Perkins ®
Technical Data
1100 Series 1103A-33G
Gen Set 30,4 kWm @ 1500 rev/min
35,4 kWm @ 1800 rev/min
Basic technical data Performance
Number of cylinders . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 3 Steady state speed stability at constant load:
Cylinder arrangement ... ... ... ... ... ... ... ... ... ... ... ... Vertical in-line - G2 ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ± 0.75%
Cycle. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... Four stroke Note: All data based on operation to ISO 3046/1, BS 5514 and
Induction system... ... ... ... ... ... ... ... ... ... ... ... Naturally Aspriated DIN 6271 standard reference conditions.
Compression ratio. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 19.25 : 1 Test conditions
Bore .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 105 mm (4.13 in)
Air temperature. . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 25 °C
Stroke .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 127 mm (4.99 in)
Cubic capacity .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 3.3 litres Barometric pressure... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 100 kPa
Relative humidity ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 30%
Direction of rotation... ... ... ... ... ... ... ... .Clockwise view from front
Firing order ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1,2,3 Sound level
Total weight (engine only) Overall sound pressure level (cooling pack and air cleaner fitted):
-dry ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...412 kg - at 1500 rev/min ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 88.1dBA
-wet ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...430 kg - at 1800 rev/min ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 90.7dBA
Overall dimensions
Sound pressure level from the mean of 4 microphones at the front,
-height... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 951 mm (37.44 in)
left, right and above the engine. Exhaust was piped away out of the
-length... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 1029 mm (40.51 in)
-width (including mounting brackets) ... ... ... ... 629 mm (24.76 in) test cell.
Moment of inertia (mk²) If the engine is to operate in ambient conditions other than those of
Engine: the test conditions, suitable adjustments must be made for these
- longitudinal . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 23.3 kgm² changes. For full details, contact Perkins Technical Service
- horizontal ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 38.1 kgm² Department.
- axial ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 24.4 kgm²
Flywheel (polar) ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1.14 kgm²
Centre of gravity (wet)
- forward from rear of block... ... ... ... ... ... ... ... .. 210 mm (8.26 in)
- above centre line of block... ... ... ... ... ... ... ... .. 120 mm (4.72 in)
- offset of RHS of centre line. ... ... ... ... ... ... ... ... 40 mm (1.57 in)
www.fdkenergy.com
General installation
Type of Operation and Application
Designation Units Prime Stand-by Prime Stand-by
50 Hz 50 Hz 60 Hz 60 Hz
Gross engine power kWm 28,2 31,0 33,2 36,5
Brake mean effective pressure kPa (lbf/in²) 684 (99.2) 752 (109.0) 669 (97.0) 736 (106.7)
Mean piston speed m/s (ft/s) 6,35 (20.8) 6,35 (20.8) 7,62 (25.0) 7,62 (25.0)
ElectropaK net engine power kWm 27,7 30,4 32,2 35.4
125,5 125,5 151,0 151,0
Engine coolant flow 35 kPa restriction I/min (UK gal/min)
(27.6) (27.6) (33.2) (33.2)
Combustion air flow m³/min (ft³/min) 2,16 (76.2) 2,15 (75.9) 2,6 (91.8) 2,57 (90.7)
Exhaust gas flow (max) m³/min (ft³/min) 5,7 (201.2) 5,8 (204.8) 6,4 (226.0) 6,6 (233.0)
Exhaust gas temperature (max) in manifold °C (°F) 500 (932) 520 (968) 520 (968) 530 (986)
Cooling fan air flow m³/min (ft³/min) 53,0 (1871.6) 53,0 (1871.6) 70,0 (2472.0) 70,0 (2472.0)
Overall thermal efficiency % 39,2 39,2 40,0 37.3
kWe 24,0 26,4 27,9 30,6
Typical genset electrical unit (0.8 pf 25° C
kVA 30,0 33,0 34,9 38,2
Assumed alternator effiency % 87
Energy balance
Power in fuel (Fuel heat of combustion) kW (Btu/min) 72,0 (4098.2) 79,0 (4496.6) 83,0 (4724.3) 98,0 (5578.1)
Power output (gross) kW (Btu/min) 28,2 (1605.1) 31,0 (1764.5) 33,2 (1889.7) 36,5 (2077.5)
Power to cooling fan kW (Btu/min) 0,5 (28.4) 0,6 (34.1) 1,0 (56.9) 1,1 (62.6)
Power output (net) kW (Btu/min) 27,7 (1576.6) 30,4 (1730.3) 32,2 (1832.8) 35,4 (2014.9)
Power to coolant and lubricating oil kW (Btu/min) 16,0 (910.7) 18,0 (1024.5) 18,0 (1024.5) 22,0 (1252.2)
Power to exhaust kW (Btu/min) 22,0 (1252.2) 25,0 (1422.9) 27,0 (1536.8) 34,0 (1935.2)
Power to radiation kW (Btu/min) 5,0 (284.5) 6,0 (341.5) 5,0 (284.5) 6,0 (341.5)
Caution: The airflows shown in this table will provide acceptable cooling for an open power unit operating in ambient temperatures of up
to 53 °C (127 °F) or 46 °C (114.8 °F) if a canopy is fitted. If the power unit is to be enclosed totally, a cooling test should be done to check
that the engine cooling is acceptable. If there is insufficient cooling, contact Perkins Technical Service Department.
www.fdkenergy.com
Cooling system
Radiator
Exhaust system
- face area . ... ... ... ... ... ... ... ... ... ... ... ... ... ... 0.276 m² (2.97 ft²)
Maximum back pressure
- rows and materials.. ... ... ... ... ... ... ... ... ... single row aluminium
- 1500 rev/min ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...8 kPa
- matrix density and material . ... ... ... ... .. Aluminium 12,5 fins/inch
- 1800 rev/min ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .10 kPa
- width of matrix. ... ... ... ... ... ... ... ... ... ... ... ... .. 526 mm (20.7 in)
Exhaust outlet size . ... ... ... ... ... ... ... ... ... ... ... ... .56 mm (2.2 in)
- height of matrix ... ... ... ... ... ... ... ... ... ... ... ... .. 524 mm (20.6 in)
- pressure cap setting ... ... ... ... ... ... ... ... ... ... ... ... ... ... 107 kPa Fuel System
Fan Type of injection . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. Direct
- diameter .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 457mm (18 in) Fuel injection pump ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . Rotary
- drive ratio ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 0.85 : 1 Fuel atomiser.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... Multi-hole
- number of blades ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 7 Nozzel opening pressure ... ... ... ... ... ... ... ... .29,0 MPa (290 bar)
- material ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... Composite Fuel lift pump
- type . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..Pusher
Type ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . Electrical
Coolant -flow/hour ... ... ... ... ... ... ... ... ... ... . 120 - 150 l/h (211 - 264 pt/m)
Recommended coolant: 50 % ethylene glycol with a corrosion -pressure ... ... ... ... ... ... ... ... ... ... ... . 30 - 75 kPa (4.4 - 10.9 psi)
inhibitor (BS 658 : 1992 or MOD AL39) and 50% clean fresh water. Maximum suction head:
Total system capacity - 1500 rev/min ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 17 kPa
- with radiator ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 10.2 l (21.5 pt) Governor type
- without radiator ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 4.4 l (9.2 pt)
Electronic governor (optional) ... ... ... ... ... ... ... ... ... Woodward LCG2
Maximum top tank temperature ... ... ... ... ... ... ... 110 °C (230 °F)
Mechnical and electronic governor speed control to .. ISO 8528, G2
Thermostat operating range.. ... ... ... ... ..82 - 93 °C (180 - 199 °F)
Fuel specification
Electrical system
European RF75-T-96 / DIN
Fuel Specification
Type .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...Negative ground EN590 / BS2869 class A2
Alternator voltage .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..12 V Density (kg/l @ 15 °C) 0,835 - 0,845
Alternator output ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 65 amps Viscosity (mm²/s @ 40 °C) 2,5 - 3,5
Starter motor voltage. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..12 V
Sulphur content (%) 0,1 - 0,2
Starter motor power .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 3 kW
Number of teeth on flywheel . ... ... ... ... ... ... ... ... ... ... ... ... ... 126 Cetane number 45 - 50
Pull in current of starter motor solenoid ... ... ... ... ... ... .. 60 amps Fuel consumption litres/hour (UK gals/hr)
Hold in current of starter motor solenoid ... ... ... ... ... ... .. 15 amps
Power rating
Engine stop solenoid. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..12 V
Stop solenoid (minimum) Speed 110% 100% 75% 50% 25%
- pull in current .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 10 amps 1500 7,9 (1.73) 7,1 (1.56) 5,4 (1.18) 3,9 (0.85) 2,5 (0.54)
- hold in current . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 10 amps 1800 9,5 (2.08) 8,6 (1.89) 6,6 (1.45) 4,9 (1.07) 3,1 (0.68)
Cold start recommendations
Induction system
Minimum cranking speed .. ... ... ... ... ... ... ... ... ... ... . 120 rev/min
Maximum air intake restriction
Starter specification
-clean filter.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 3,0 kPa
Starter Min. - dirty filter... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 6,5 kPa
Lubricating oil viscosity SAE / battery
motor starting
type - values in CCA - air filter type.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . Dry
type temp.
°C (°F) 15W/40 15W/40 10W/40 5W/40 5W/30 Lubrication system
-7 (19.4) 1 x 770 Lubricating oil capacity
12 volt -10 (14) * 1 x 770 Total system ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...8,3 l (17.5 pt)
3.0 kW -15 (5) * 1 x 770 Sump minimum .. ... ... ... ... ... ... ... ... ... ... ... ... ... ...6,2 l (13.1 pt)
-20 (-4) * 1 x 900 Sump maximum . ... ... ... ... ... ... ... ... ... ... ... ... ... .. 7.8 l (16.4 pt)
Maximum engine operating angles:
-25 (-13) * 2 x 570
- front up, front down, right side or left side ... ... ... ... ... ... ... .. 25°
* - Glow plug start aid fitted.
Lubricating oil pressure
Note: CCA - Cold Cracking Amps to SAEJ537. - relief valve opens . ... ... ... ... ... ... ... ... ... ... ... ... . 415 - 470 kPa
- at maximum no-load speed .. ... ... ... ... ... ... ... ... . 276 - 414 kPa
Max continuous oil temperature (in rail) . ... ... ... ...125 °C (257 °F)
Notes:
Oil consumption at full load as a % of fuel consumption ... ..0.15%
! Battery capacity is defined by the 20 hour rate
! If a change to a low viscosity oil is made, the cranking torque
necessary at lower ambient temperatures is much reduced.
The starting equipment has been selected to take advantage
of this. It is important to change the appropriate multigrade oil
in anticipation of operating in low ambient temperatures.
! Breakaway current is dependent on battery capacity available.
Cables should be capable of handling the transient current
which may be up to double the steady cranking current.
www.fdkenergy.com
1103A-33G ElectropaK - left view
X
LHS FAN GUARD
REMOVED FOR
CLARITY 346
254,6
37[
GOVERNOR
25 REMOVAL
441
FAN HEIGHT
350
285
241,8
355,9
Ø
69
Y Y
172 MAX
15
225
20 REMOVAL
130,1 156,4
247,9
16 A/F
262
Ø 94
X
www.fdkenergy.com
1103A-33G ElectropaK - front view
629
185,5
6 - M8 X 1,25
THREAD INSERT
135,5
Ø 8
298
526,2 OVERCORE
BETWEEN HEADER PLATES
691
674,5
951,3
285
524,2
Y Y
13
260,3
16
118,6
272 272
www.fdkenergy.com
1103A-33G ElectropaK - right view
257,1
97,6
604,1
486,8
Y Y
239,4
771,7
X
1028,8
1500
www.fdkenergy.com
1103A-33G ElectropaK - rear view
211,1 A
54°
573,1
516,7
1 Y Y
RE 7
MO
VA
L
8 - M8 X 1,25 X 14,3
EQUISPACED ON
203,2 P.C.DIA
12 - M10 X 1,5 X 20
Z DRILL PATTERN, FLANGE
AND SPIGOT TO NO. 3 SAE
www.fdkenergy.com
1100 Series 1103A-33G
0W
5W20
10W30
15W40
20W50
20
30
40
-30 -20 -10 0 10 20 30 40 50oC
-22 -4 14 32 50 68 86 104 122oF
Ambient temperarture
W1355
Mountings
Maximum static bending moment
at rear face of block ... ... ... ... ... ... ... ... ... ... ... 791 Nm (583 lb/ft)
Load Acceptance
Inital load acceptance when engine reaches rated speed
(15 seconds max after engine starts to crank)
1500 1800
Units
rev/min rev/min
Prime Power % 90 90
kWm 25,7 29,4
Load
(kWe) (21.8) (24.7)
Transient Frequency Deviation % < -10% < -10%
Frequency Recovery Second <1 <1
@Perkins ® Distributed by