Isolated Footing Design (ACI 318-11) - Metric: Elevation
Isolated Footing Design (ACI 318-11) - Metric: Elevation
Isolated Footing 1
0.3 m
Elevation
X 0.95 m
0.4 m
1.9 m
0.3 m
0.95 m
1.9 m
Plan
Input Values
Footing Geomtery
Column Dimensions
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 2 of 13
Pedestal
Include Pedestal : No
Pedestal Shape : N/A
Design Parameters
Soil Properties
Cohesion : 0.00kN/m2
Global Settings
Top Reinforcement Option : Calculate only when foundation is subjected to uplift forces
Concrete Design Option : Net Pressure(Gross Pressure - Self Weight Pressure)
Top Reinforcement Factor : 1.00
------------------------------------------------------
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 3 of 13
Design Calculations
Footing Size
Load Combinations
Moments are about the center of Column / Pedestal (does not include moments caused by lateral loads)
For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical axis.
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 4 of 13
2
Area from initial length and width, Ao = Lo X W o = 2.25 m
Note: Amin is an initial estimation considering self-weight, axial load and moment against factored bearing capacity.
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 5 of 13
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure will be set to zero and the pressure
will be redistributed to remaining corners.
Stability Check
OTM
Sliding Force
.
Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
301 43.85 37.64 28.56 1.50 81.61 111.92 1.50
302 47.48 36.29 28.83 1.50 78.69 122.27 1.50
303 9.29 35.45 8.99 1.50 78.17 7.33 1.50
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 6 of 13
Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X Direction
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z Direction
Area of
Load Case / Pressure at Pressure at Pressure at Pressure at
footing in
Load top left top right bottom right bottom left
Contact with
Combination corner corner corner corner
soil (Au)
ID (kN/m2) (kN/m2) (kN/m2) (kN/m2) 2
(m )
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 7 of 13
Actual Area in Contact for all ultimate load cases exceeds the minimum required. Hence Safe
Maximum Corner Pressure from all ultimate load cases is less than the allowable. Hence Safe
Shear Calculation
X 0.95 m
Z
0.105 m
0.95 m
Plan
Total Footing Depth, D = 0.30m
Calculated Effective Depth, d = D - Ccover - 1 * db = 0.21 m
For rectangular column, = Bcol / Dcol = 1.33
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 8 of 13
X 0.95 m
Z 0.6 m
0.95 m
0.6 m
Plan
From ACI Cl.11.2.1.1, Vc = = 297.51 kN
Check that 0.75 X Vc > Vux where Vux is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the X axis.
X 0.95 m
0.55 m 0.55 m
0.95 m
Plan
From ACI Cl.11.2.1.1, Vc = = 297.51 kN
Check that 0.75 X Vc > Vuz where Vuz is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the Z axis.
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 9 of 13
6 - 16 mm
Calculate the flexural reinforcement along the X direction of the footing. Find the area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.) by
Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in Mpa
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 10 of 13
16 mm @ 345mm o.c.
Because the number of bars is rounded up, make sure new reinforcement ratio < ρmax
Total reinforcement area, As_total = Nbar X (Area of one bar) = 1206.38 mm2
d= D - Ccover - 0.5 X (dia. of = 0.20 m
one bar)
6 - 16 mm
Calculate the flexural reinforcement along the Z direction of the footing. Find the area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.) by
Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in Mpa
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 11 of 13
16 mm @ 345mm o.c.
Because the number of bars is rounded up, make sure new reinforcement ratio < ρmax
Total reinforcement area, As_total = Nbar X (Area of one bar) = 1206.38 mm2
d= D - Ccover - 1.5 X (dia. of 0.20 m
=
one bar)
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 12 of 13
Along Z on Bottom
16 mm 6 10.50 16.58
Face
Along X on Bottom
16 mm 6 10.50 16.58
Face
Along Z on Top
N/A N/A N/A N/A
Face
Along X on Top
N/A N/A N/A N/A
Face
Concrete
3
- Length (m) Width (m) Thickness (m) Volume (m )
Formwork
Footing : 2.28 m2
Pedestal : 0.00 m2
Total : 2.28 m2
Soil Excavation
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
Page 13 of 13
file:///E:/Commercial%20Building/Staad/Admin%20Building_foundation/Footing/Report... 10/13/2020
X 0.95 m
Z
0.4 m
1.9 m
0.3 m
0.95 m
1.9 m 0.3 m
Plan
0.95 m
Elevation
BOTTOM 6 - 16 mm
Dimensions (m) Reinforcement
TOP N/A
L B D AstX(T) AstZ(T) AstX(B) AstZ(B)
Foundation
0.95 m