M300CJ and M300RJ Control and Relay Modules With FlashScan®33
M300CJ and M300RJ Control and Relay Modules With FlashScan®33
GENERAL California
M300CJ Control Module — The M300CJ Address- MEA State Fire
Marshal
able Control Module provides Johnson Controls intelligent 457-99-E
control panels a circuit for Notification Appliances (horns, 7300-0554:131
Vol. VIII
strobes, speakers, etc.) or to monitor a telephone circuit.
Addressability allows the M300CJ to be activated, either
manually or through panel programming, on a select (zone S1570 MARYLAND
or area of coverage) basis. State Fire Marshal
M300RJ Relay Module — The M300RJ Addressable Permit #2029
Relay Module provides the system with a dry-contact output
for activating a variety of auxiliary devices, such as fans,
dampers, control equipment, etc. Addressability allows the
dry contact to be activated, either manually or through panel
programming, on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a new communi-
cation protocol developed by NOTIFIER Engineering that
greatly enhances the speed of communication between ana-
log intelligent devices. Intelligent devices communicate in a
grouped fashion. If one of the devices within the group has
new information, the panel CPU stops the group poll and
concentrates on single points. The net effect is response
speed greater than five times that of other designs.
FEATURES
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire SLC
loop. The M300CJ module requires power (for horns, strobes,
etc.), audio (for speakers), or a telephone riser (for hand-
6724mod2.tif
sets). Internal relay feature available on FlashScan® systems
only.
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red M300CJ Module
when activated. (See wiring diagram Fig. 5 for M300RJ)
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI). CONSTRUCTION
• The M300CJ may be used to switch 24-volt NAC power, • The face plate is made of off-white Noryl®.
audio (up to 70.7 VRMS) or telephone. • Controls include two rotary switches for direct-dial entry of
• Wide viewing angle of LED. address (01-159).
• SEMS screws with clamping plates for wiring ease. • The M300CJ is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
• Direct-dial entry of address 01 – 159 on FlashScan® sys-
tems (IFC-640, IFC-3030), or 01 – 99 on traditional systems • The M300RJ provides two Form-C dry contacts that switch
(IFC-400, IFC-640, IFC-1010/2020, IFC-3030, or FC-2000). together.
• Speaker, audible/visual, and telephone applications may OPERATION
be wired for Class B or A (Style Y or Z). Each M300CJ or M300RJ uses one of 159 possible module
APPLICATIONS addresses on a SLC loop. It responds to regular polls from
the control panel and reports its type and status, including
The M300CJ is used to switch 24 VDC audible/visual power, the open/normal/short status of its Notification Appliance
high-level audio (speakers), or control telephone devices. The
M300RJ may be programmed to operate dry contacts for door FlashScan® is a registered trademark of NOTIFIER. Noryl® is a
holders, Air Handling Unit shutdown, etc., and to reset four- registered trademark of GE Plastics, a subsidiary of General Elec-
wire smoke detector power. tric Company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact your
Johnson Controls Field Support Center.
507 East Michigan Street, Milwaukee, WI 53202
MOUNTING
DIAGRAMS
Note CB500 Module Barrier,
6724mt2.wmf
WIRING DIAGRAMS
The following wiring diagrams are provided:
1) M300CJ: Typical notification appliance circuit configuration,
NFPA Style Y.
2) M300CJ: Typical fault-tolerant notification appliance circuit con-
j6724fc.wmf, JCI01rev.tif
figuration, NFPA Style Z.
3) M300CJ: Typical wiring for speaker supervision and switch-
ing, NFPA Style Y.
4) M300CJ: Typical fault-tolerant wiring for speaker supervision
and switching, NFPA Style Z.
5) M300RJ: Relay module wiring diagram.
Fig. 2 M300CJ: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
• Connect modules to Listed compatible Johnson Controls control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
6827wir2.wmf
6724wir3.wmf
Fig. 4 M300CJ: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
• Connect modules to Listed compatible Johnson Controls control panels only.
• All wiring shown is supervised.
• Wires must be supervised per NFPA.
• Module polarities are shown in alarm.
6724wir4.wmf
Fig. 5
M300RJ: Relay module
wiring diagram.
• Connect modules to Listed
compatible Johnson Controls
control panels only.
• Module does NOT supervise
6724wir5.wmf controlled circuits.