May 24, 2004 JCI-6724

M300CJ and M300RJ


Control and Relay Modules
with FlashScan®

GENERAL California
M300CJ Control Module — The M300CJ Address- MEA State Fire
Marshal
able Control Module provides Johnson Controls intelligent 457-99-E
control panels a circuit for Notification Appliances (horns, 7300-0554:131
Vol. VIII
strobes, speakers, etc.) or to monitor a telephone circuit.
Addressability allows the M300CJ to be activated, either
manually or through panel programming, on a select (zone S1570 MARYLAND
or area of coverage) basis. State Fire Marshal
M300RJ Relay Module — The M300RJ Addressable Permit #2029
Relay Module provides the system with a dry-contact output
for activating a variety of auxiliary devices, such as fans,
dampers, control equipment, etc. Addressability allows the
dry contact to be activated, either manually or through panel
programming, on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a new communi-
cation protocol developed by NOTIFIER Engineering that
greatly enhances the speed of communication between ana-
log intelligent devices. Intelligent devices communicate in a
grouped fashion. If one of the devices within the group has
new information, the panel CPU stops the group poll and
concentrates on single points. The net effect is response
speed greater than five times that of other designs.

FEATURES
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire SLC
loop. The M300CJ module requires power (for horns, strobes,
etc.), audio (for speakers), or a telephone riser (for hand-

6724mod2.tif
sets). Internal relay feature available on FlashScan® systems
only.
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red M300CJ Module
when activated. (See wiring diagram Fig. 5 for M300RJ)
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI). CONSTRUCTION
• The M300CJ may be used to switch 24-volt NAC power, • The face plate is made of off-white Noryl®.
audio (up to 70.7 VRMS) or telephone. • Controls include two rotary switches for direct-dial entry of
• Wide viewing angle of LED. address (01-159).
• SEMS screws with clamping plates for wiring ease. • The M300CJ is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
• Direct-dial entry of address 01 – 159 on FlashScan® sys-
tems (IFC-640, IFC-3030), or 01 – 99 on traditional systems • The M300RJ provides two Form-C dry contacts that switch
(IFC-400, IFC-640, IFC-1010/2020, IFC-3030, or FC-2000). together.
• Speaker, audible/visual, and telephone applications may OPERATION
be wired for Class B or A (Style Y or Z). Each M300CJ or M300RJ uses one of 159 possible module
APPLICATIONS addresses on a SLC loop. It responds to regular polls from
the control panel and reports its type and status, including
The M300CJ is used to switch 24 VDC audible/visual power, the open/normal/short status of its Notification Appliance
high-level audio (speakers), or control telephone devices. The
M300RJ may be programmed to operate dry contacts for door FlashScan® is a registered trademark of NOTIFIER. Noryl® is a
holders, Air Handling Unit shutdown, etc., and to reset four- registered trademark of GE Plastics, a subsidiary of General Elec-
wire smoke detector power. tric Company.

This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact your
Johnson Controls Field Support Center.
507 East Michigan Street, Milwaukee, WI 53202

JCI-6724 • 05/24/04 — Page 1 of 4


Circuit (NAC). The LED blinks with each poll received. On RELAY CONTACT RATINGS
command, it activates its internal relay. The M300CJ super- for both M300CJ and M300RJ
vises Class B (Style Y) or Class A (Style Z) notification or
control circuits. Load Description Application MVaoxlitm um Current
age Rating
Upon code command from the panel, the M300CJ will dis-
connect the supervision and connect the external power sup- Resistive Non-Coded 30 VDC 3.0 A
ply in the proper polarity across the load device. The discon- Resistive C oded 30 V D C 2.0 A
nection of the supervision provides a positive indication to
Resistive Non-Coded 110 VDC 0.9 A
the panel that the control relay actually turned ON. The ex-
ternal power supply is always relay isolated from the com- Resistive Non-Coded 125 VAC 0.9 A
munication loop so that a trouble condition on the external Inductive (L/R = 5 ms) Coded 30 V D C 0.5 A
power supply will never interfere with the rest of the system.
Inductive (L/R = 2 ms) Coded 30 V D C 1.0 A
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in Inductive (PF = 0.35) Non-Coded 125 VAC 0.5 A
6724rate.tbl
TYPE CODE (not settable) will identify the module to the
control panel, so as to differentiate between a module and a PRODUCT LINE INFORMATION
sensor address. M300CJ Intelligent Addressable Control Module.
M300RJ Intelligent Addressable Relay Module.
SPECIFICATIONS for M300CJ
A2143-20 Capacitor, required for Class A (Style Z) opera-
Normal operating voltage: 15 to 32 VDC.
tion of speakers.
Maximum current draw: 6.5 mA (LED on).
SMB500 Optional Surface-Mount Backbox.
Average operating current: 350 µA direct poll (CLIP mode),
CB500 Control Module Barrier — required by UL for
375 µA group poll (FlashScan® mode) with LED flashing.
separating power-limited and non-power limited
External supply voltage (between Terminals T3 and T4): wiring in the same junction box as M300CJ.
maximum 80 volts (RMS or DC).
Drain on external supply: 2 mA maximum (using internal
EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.

SPECIFICATIONS for M300RJ


Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 230 µA direct poll (CLIP mode),
255 µA group poll (FlashScan® mode) with LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.

MOUNTING
DIAGRAMS
Note CB500 Module Barrier,
6724mt2.wmf

which creates isolated quadrant.


6724mt1.wmf

Page 2 of 4 — JCI-6724 • 05/24/04


The Face Plate

WIRING DIAGRAMS
The following wiring diagrams are provided:
1) M300CJ: Typical notification appliance circuit configuration,
NFPA Style Y.
2) M300CJ: Typical fault-tolerant notification appliance circuit con-

j6724fc.wmf, JCI01rev.tif
figuration, NFPA Style Z.
3) M300CJ: Typical wiring for speaker supervision and switch-
ing, NFPA Style Y.
4) M300CJ: Typical fault-tolerant wiring for speaker supervision
and switching, NFPA Style Z.
5) M300RJ: Relay module wiring diagram.

Fig. 1 M300CJ: Typical notification appliance circuit configuration, NFPA Style Y.


• Connect modules to Listed compatible Johnson Controls control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
6827wir1.wmf

Fig. 2 M300CJ: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
• Connect modules to Listed compatible Johnson Controls control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
6827wir2.wmf

JCI-6724 • 05/24/04 — Page 3 of 4


Fig. 3 M300CJ: Typical wiring for speaker supervision and switching, NFPA Style Y.
• Connect modules to Listed compatible
Johnson Controls control panels only.
• All wiring shown is supervised.
• Wires must be supervised per NFPA.
• Module polarities are shown in alarm.

6724wir3.wmf

Fig. 4 M300CJ: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
• Connect modules to Listed compatible Johnson Controls control panels only.
• All wiring shown is supervised.
• Wires must be supervised per NFPA.
• Module polarities are shown in alarm.

6724wir4.wmf

NOTE regarding AUDIO AMPLIFIER in Figures 3 & 4 above:


1) Audio circuit wiring must be twisted-pair as a minimum. See installation manual for detailed information.

Fig. 5
M300RJ: Relay module
wiring diagram.
• Connect modules to Listed
compatible Johnson Controls
control panels only.
• Module does NOT supervise
6724wir5.wmf controlled circuits.
Page 4 of 4 — JCI-6724 • 05/24/04